HomeMy WebLinkAboutCarmel South Garage - Combined Set 6-1-2017PROJECT LOCATIONPROJECT LOCATIONDANDRIDGEDREWW H IT E HITAR-19400087ARCTECSTATE OFNo.DNDINAAAIIREGISTEREDNDINAAIHITARCTECDANDRIDGEDREWW H IT EREVISIONS:DRAWN BYDATE ISSUEDCHECKED BYScope DrawingsThese drawings indicate the general scope of the project interms of architectural design concept, the dimensions of thebuilding, the major architectural elements and the type ofstructural, mechanical and electrical systems. The drawingsdo not necessarily indicate or describe all work required forfull performance and completion of the requirements of thecontract. On the basis of the general scope indicated ordescribed, the trade contractors shall furnish all itemsrequired for the proper execution and completion of work.PROJECT NUMBER:618 East Market StreetIndianapolis, Indiana 46202phone 317/264.8162a x i s a r c h . c o mConstruction Manager:Civil Engineer:Structural Engineer:MEP Engineer:Owner:Carmel Redevelopment Commission30 West Main Street, Suite 200Carmel, Indiana 46032317.571.2492Garmong Construction Services5988 North Michigan RoadIndianapolis, Indiana 46228317.682.1001Corrie Meyer, Executive DirectorCHCH03/28/2017G001COVER SHEET17003Civil & Environmental Consultants, Inc.530 East Ohio Street, Suite G317.655.7777Vector Consulting1005 North Senate Avenue317.632.4444Fink Roberts & Petrie9449 Priority Way West Drive, Suite 200317.872.8400Indianapolis, IN 46204Indianapolis, IN 46202Indianapolis, IN 46240MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032MARCH 28, 2017 - ISSUED FOR BID AND PERMITBUILDING INFORMATIONPROJECT CONTACTSDESIGN TEAM CONTACTSSITE LOCATIONARCHITECTCIVIL ENGINEERChris Hagan, Project ManagerKevin Cooper, Partner in ChargePH 317 264-8162Indianapolis, Indiana 46202618 East Market StreetAxis Architecture + InteriorsDRAWING INDEXBUILDING LOCATIONSTRUCTURAL ENGINEERMEP ENGINEEROWNERCONSTRUCTION MANAGERCarmel Redevelopment CommissionCorrie Meyer, Executive Director30 West Main Street, Suite 200Carmel, IN 46032317.571.2492Garmong Construction ManagementDustin Frye, Project Manager5988 North Michigan RoadIndianapolis, IN 46228317.682.1001MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032Civil & Environmental Consultants, Inc.530 East Ohio Street, Suite GGreg Rasmussen317.655.7777-Vector Consulting1005 North Senate AvenueTim Luley, PE317.632.4444-Fink Roberts & Petrie9449 Priority Way West Drive, Suite 200Joe Petrolia, PE317.872.8400-Indianapolis, IN 46204Indianapolis, IN 46202Indianapolis, IN 46240First FloorCONSTRUCTION TYPEUSE GROUPBUILDING GROSS AREAThird FloorS-2 & B or MType IBGROSS AREA TOTALMARCH 28, 2017 - BID AND PERMIT SETAPRIL 13, 2017 - ADDENDUM No. 1MAY 11, 2017 ADLS COMMENTS.........DWG # DRAWING NAME ISSUE DATEMECHANICAL●H001 SYMBOLS, NOTES, ABBREVEATIONS 03/28/2017●H201 FIRST FLOOR HVAC PLAN 03/28/2017●H202 OFFICE TENANT HVAC PLAN 03/28/2017●H601 DETAILS AND SCHEDULES 03/28/2017PLUMBING●P001 SYMBOLS AND ABBREVIATIONS 03/28/2017●●P200 OFFICE TENANT PLUMBING PLAN 03/28/2017●P201 FIRST FLOOR PLUMBING PLAN 03/28/2017●P202 SECOND FLOOR PLUMBING PLAN 03/28/2017●P203 THIRD FLOOR PLUMBING PLAN 03/28/2017●P204 FOURTH FLOOR PLUMBING PLAN 03/28/2017●P205 PARTIAL FOURTH FLOOR PLUMBING PLAN 03/28/2017●P206 OFFICE TENANT PLUMBING PLAN 03/28/2017●P601 PLUMBING SCHEDULES AND DETAILS 03/28/2017ELECTRICAL●E001 ELECTRICAL SYMBOLS AND ABBREVIATIONS 03/28/2017●●E201 FIRST FLOOR LIGHTING PLAN 03/28/2017●E202 SECOND FLOOR LIGHTING PLAN 03/28/2017●E203 THIRD FLOOR LIGHTING PLAN 03/28/2017●E204 FOURTH FLOOR LIGHTING PLAN 03/28/2017●E205 PARTIAL FOURTH FLOOR LIGHTING PLAN 03/28/2017●E206 OFFICE TENANT ELECTRICAL PLAN 03/28/2017●E301 FIRST FLOOR POWER AND SYSTEMS PLAN 03/28/2017●E302 SECOND FLOOR POWER AND SYSTEMS PLAN 03/28/2017●E303 THIRD FLOOR POWER AND SYSTEMS PLAN 03/28/2017●E304 FOURTH FLOOR POWER AND SYSTEMS PLAN 03/28/2017●E305 PARTIAL FOURTH FLOOR POWER ANDSYSTEMS PLAN03/28/17●E306 OFFICE TENANT POWER AND SYSTEMS PLAN 03/28/2017●E501 ELECTRICAL DETAILS 03/28/2017●E502 ELECTRICAL DETAILS 03/28/2017●E503 ELECTRICAL DETAILS 03/28/2017●E601 ELECTRICAL SCHEDULES 03/28/2017●E602 LIGHT FIXTURE SCHEDULE 03/28/2017MARCH 28, 2017 - BID AND PERMIT SETAPRIL 13, 2017 - ADDENDUM No. 1MAY 11, 2017 ADLS COMMENTS.........DWG # DRAWING NAME ISSUE DATEGENERAL●●●G001 COVER SHEET 03/28/2017●●G002 CODE REVIEW AND LIFE SAFETY PLAN 03/28/2017●G003 LIFE SAFETY PLANS 03/28/2017CIVIL●●C000 COVER SHEET 03/28/17●●C200 SITE LAYOUT PLAN 03/28/2017●●C300 GRADING PLAN 03/28/2017●●C400 DRAINAGE PLAN 03/28/2017●●C500 SITE UTILITY PLAN 03/28/2017●C800 SITE DETAILS 03/28/2017●●C801 SITE DETAILS 03/28/2017●C802 SITE DETAILS 03/28/2017●C803 SITE DETAILS 03/28/2017●C804 SITE DETAILS 03/28/2017●C805 SITE DETAILS 03/28/2017●C806 PARCEL INFORMATION 03/28/2017●●C900 EROSION CONTROL PLAN 03/28/2017●●C901 STORM WATER POLLUTION PREVENTIONPLAN03/28/2017●C902 EROSION CONTROL DETAILS 03/28/2017STRUCTURAL●S001 GENERAL NOTES 03/28/2017●●S100S FOUNDATION PLAN 03/28/2017●●S101 SLAB ON GRADE PLAN 03/28/2017●S102 SECOND LEVEL PLAN 04/14/17●S103 THIRD LEVEL PLAN 04/14/17●S104 FOURTH LEVEL PLAN 04/14/17●S105 FIFTH LEVEL PLAN 04/14/17●S300 TYPICAL FOUNDATION DETAILS 03/28/2017●●S301 FOUNDATION DETAILS 03/28/2017●●S302 FOUNDATION DETAILS 03/28/2017●●S303 FOUNDATION DETAILS 03/28/2017●●S310 TYPICAL SLAB ON GRADE DETAILS 03/28/2017●S370 PRECAST FRAMING SECTIONS AND DETAILS 04/14/17●S400 TYPICAL MASONRY DETAILS 04/14/17●S500 TYPICAL STEEL DETAILS 04/14/17ARCHITECTURAL●A001 GENERAL NOTES, SYMBOLS AND LEGENDS 03/28/2017●●A002 INTERIOR WALL TYPES AND DETAILS 03/28/2017●●●A101 FIRST FLOOR CONSTRUCTION PLAN 03/28/2017●A102 SECOND FLOOR CONSTRUCTION PLAN 03/28/2017●A103 THIRD FLOOR PLAN CONSTRUCTION PLAN 03/28/2017●●A104 FOURTH FLOOR PLAN CONSTRUCTION PLAN 03/28/2017●●A105 FIFTH FLOOR PLAN CONSTRUCTION PLAN 03/28/2017●●A106 ROOF PLAN 03/28/2017●A110 OFFICE BUILDOUT PLANS 04/13/2017●●A120 STAIR 1 PLANS AND SECTIONS 03/28/2017●●A121 STAIR 2 AND 4 PLANS AND SECTIONS 03/28/2017●●A122 STAIR 3 PLANS AND SECTIONS 03/28/2017●A125 STAIR DETAILS 03/28/2017●A130 PARKING LAYOUT PLANS 04/13/2017●A131 PARKING LAYOUT PLANS 04/13/2017●●A201 EXTERIOR ELEVATIONS NORTH AND SOUTH 03/28/2017●●A202 EXTERIOR ELEVATIONS EAST AND WEST 03/28/2017●●A203 PANEL THICKNESS NORTH AND SOUTH 03/28/2017●●A204 PANEL THICKNESS EAST AND WEST 03/28/2017●●A205 MOCKUP PANEL DETAILS 03/28/2017●●A301 BUILDING SECTIONS 03/28/2017●A302 WALL SECTIONS 04/13/2017●A310 SECTION DETAILS 03/28/2017●●A401 REFLECTED CEILING PLANS 03/28/2017●●A501 DOOR SCHEDULE 03/28/2017●A502 DOOR AND STOREFRONT DETAILS 03/28/2017●●A503 GLAZING ELEVATIONS 03/28/201726,708Second FloorFourth FloorFifth Floor112,701 SF26,70826,70826,708 5,880# DESCRIPTION DATE1 ADDENDUM No 1 4/17/20172 ADLS COMMENTS 5/11/2017
UPUPUPUPUPINDICATES ONE-HOURRATED CONSTRUCTIONINDICATES TWO-HOURRATED CONSTRUCTIONINDICATES EGRESS PATHINDICATES FIREEXTINGUISHER LOCATIONFECEGRESS CAPACITY TAGOCCUPANT LOADOCCUPANT CAPACITY24126B3224,000 SFOCCUPANCY TAGNUMBER OF OCCUPANTSSPACE FUNCTION FROM TABLE1004.1.1AREA OF SPACE(net or gross)P = Parking Garage 200 sf/occM = Mercantile 30 sf/occME = Mechanical 300 sf/occS = Storage 300 sf/occB = Business/OfficeS = StorageM = MechanicalLIFE SAFETY PLAN LEGENDAPPLICABLE CODESIndiana General Administrative Rules2014 Indiana Building Code (2012 International Building Code with IndianaAmmendments)2014 Indiana Fire Code (2012 International Fire Code with IndianaAmmendments)2012 Indiana Plumbing Code (2006 International Plumbing Code with IndianaAmmendments)2008 National Electrical Code (2008 NFPA 70)2014 Indiana Mechanical Code (2012 International Mechanical Code withIndiana Ammendments)2010 Indiana Energy Code (ASHRAE 90.1 2007)Americans with Disabilities Act Accessible Guidelines (ADAAG) for Buildings andFacilitiesAmerican National Standards Institute Accessible and Usable Buildings and FacilitiesStandard (CABO/ANSI A117.1-2009)EGRESS TRAVEL DISTANCETable 1016. 1, IBC limits the maximum travel distance in a non-sprinklered S-2occupancy to 200 feet.NUMBER OF EXITS2 means of egress are required from rooms or areas with an occupant loadexceeding 50 or a common path of travel exceeding 100 feet. (1015.1)Each floor requires 2 exits.BUILDING HEIGHT AND AREAOCCUPANT LOADFirst Floor Occupant Load:24,575 s.f. / 200 sf = 123 occupantsTotal Occupant Load =574 OccupantsParking GarageSecond Floor Occupant Load:Third Floor Occupant Load:26,708First Floor = gsfSecond Floor = gsfThird Floor = gsf112,701Total = gsfFourth Floor = gsfFourth Floor Occupant Load:26,708 s.f. / 200 sf = 133 occupantsParking GarageParking GarageParking GarageActual Height and Area112,701 s.f.51 ft 26,708 26,708 26,7082,132 s.f. / 100 s.f. gross = 22 occupantsBusiness / Office26,708 s.f. / 200 sf = 133 occupants26,708 s.f. / 200 sf = 133 occupantsTop of Ramp = gsf 5,880Top of Ramp Occupant Load:Parking Garage 5,880 s.f. / 200 sf = 30 occupantsCODE SUMMARYPLUMBING FIXTURE REQUIRED (PLUMBING OCCUPANT LOAD)Parking Garages are not required to have restroom facilities per2902.1.1 exception C.Separate facilities are not required in occupancies in which 15 or fewerpeople per shift are employeed per 2902.2 exception 4.Office lease areas are limited to 1,100 sf max. This is 11 occupantsmaximum per occupancy load factors.STAIR 2ST2-1STAIR 1ST1-1ELEV.EL1-1STAIR 3ST3-1ELECTRICAL101RISER RM.102OPEN BELOW RAMPTO STORM DETENTIONAREAOFFICEBUILDOUTSPACE103IT ROOM104NOTE:OFFICE BUILDING IS NOT INPROJECT SCOPE.GARAGEFIRST FLOOR100R 75' - 0"36" WIDE DOOR(34" USABLE)2-HOURELEVATOR SHAFTNO RATING REQUIREDAT STAIR SHAFTS2-HOUR RATED WALLPRECAST CONCRETE WITH8" CMU ABOVEP12324,575 SFB222,132 SF36" WIDE DOOR(34" USABLE)81707170717036" WIDE DOOR(34" USABLE)45170FECFECFEC20/8017036" WIDE DOOR(34" USABLE)20/8017036" WIDE DOOR(34" USABLE)NO RATING REQUIREDAT STAIR SHAFTSNO RATING REQUIREDAT STAIR SHAFTSPEDESTRIAN ACCESS TOBICYCLE PARKING AREARAMP UPSTAIR 1ST1-3ELEV.EL1-3STAIR 2ST2-3STAIR 3ST3-32-HOURELEVATOR SHAFTNO RATING REQUIREDAT STAIR SHAFTSFECFECFEC20/8017036" WIDE DOOR(34" USABLE)NO RATING REQUIREDAT STAIR SHAFTS4516036" WIDE DOOR(34" USABLE)48" WIDE STAIRSTAIRS CONTROL0.3"/occNO RATING REQUIREDAT STAIR SHAFTS36" WIDE DOOR(34" USABLE)4516048" WIDE STAIRSTAIRS CONTROL0.3"/occ4516048" WIDE STAIRSTAIRS CONTROL0.3"/occP13326,708 SFRAMP DNRAMP UPRAMP DOWNR 75' - 0"DANDRIDGEDREWW H IT E HITAR-19400087ARCTECSTATE OFNo.DNDINAAAIIREGISTEREDNDINAAIHITARCTECDANDRIDGEDREWW H IT EREVISIONS:DRAWN BYDATE ISSUEDCHECKED BYScope DrawingsThese drawings indicate the general scope of the project interms of architectural design concept, the dimensions of thebuilding, the major architectural elements and the type ofstructural, mechanical and electrical systems. The drawingsdo not necessarily indicate or describe all work required forfull performance and completion of the requirements of thecontract. On the basis of the general scope indicated ordescribed, the trade contractors shall furnish all itemsrequired for the proper execution and completion of work.PROJECT NUMBER:618 East Market StreetIndianapolis, Indiana 46202phone 317/264.8162a x i s a r c h . c o mConstruction Manager:Civil Engineer:Structural Engineer:MEP Engineer:Owner:Carmel Redevelopment Commission30 West Main Street, Suite 200Carmel, Indiana 46032317.571.2492Garmong Construction Services5988 North Michigan RoadIndianapolis, Indiana 46228317.682.1001Corrie Meyer, Executive DirectorCHCH03/28/2017G002CODE REVIEWAND LIFE SAFETYPLAN17003Civil & Environmental Consultants, Inc.530 East Ohio Street, Suite G317.655.7777Vector Consulting1005 North Senate Avenue317.632.4444Fink Roberts & Petrie9449 Priority Way West Drive, Suite 200317.872.8400Indianapolis, IN 46204Indianapolis, IN 46202Indianapolis, IN 46240MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032VARIANCE INFORMATION CODE SUMMARYSCALE: 1/16" = 1'-0"01FIRST FLOOR LIFE SAFETY PLANSCALE: 1/16" = 1'-0"02THIRD FLOOR LIFE SAFETY PLANOPEN GARAGE CALCULATIONSVARIANCE 17-05-49 WAS APPROVED FOR THE ITEMS BELOW ON 5/04/2017.(SECOND FLOOR SIMILAR)# DESCRIPTION DATE1 ADLS COMMENTS 5/11/20171
UP
UP
RAMP DN
FEC
FEC
FEC
NO RATING REQUIRED
AT STAIR SHAFTS
15
160
48" WIDE STAIR
STAIRS CONTROL
0.3"/occ
TOP OF RAMP
P 30
5,880 SF
EGRESS DOWN TO NE STAIR
EGRESS DOWN TO 4TH
FLOOR SW STAIR
NOTE:
OFFICE BUILDING IS NOT IN
PROJECT SCOPE.
INDICATES ONE-HOUR
RATED CONSTRUCTION
INDICATES TWO-HOUR
RATED CONSTRUCTION
INDICATES EGRESS PATH
INDICATES FIRE
EXTINGUISHER LOCATIONFEC
EGRESS CAPACITY TAG
OCCUPANT LOAD
OCCUPANT CAPACITY
24
126
B 32
24,000 SF
OCCUPANCY TAGNUMBER OF OCCUPANTS
SPACE FUNCTION FROM TABLE
1004.1.1
AREA OF SPACE
(net or gross)
P = Parking Garage 200 sf/occ
M = Mercantile 30 sf/occ
ME = Mechanical 300 sf/occ
S = Storage 300 sf/occ
B = Business/Office
S = Storage
M = Mechanical
LIFE SAFETY PLAN LEGEND
RAMP DN RAMP UP
STAIR 1
ST1-4
ELEVATOR
LOBBY
401
ELEV.
EL1-4
RAMP DOWN
STAIR 2
ST2-4
STAIR 3
ST3-4
GARAGE
FOURTH
FLOOR
400
NOTE:
OFFICE BUILDING IS NOT IN
PROJECT SCOPE.
2-HOUR
ELEVATOR SHAFT
NO RATING REQUIRED
AT STAIR SHAFTS
FEC
FEC
FEC
36" WIDE DOOR
(34" USABLE)
NO RATING REQUIRED
AT STAIR SHAFTS
45
160
36" WIDE DOOR
(34" USABLE)48" WIDE STAIR
STAIRS CONTROL
0.3"/occ
NO RATING REQUIRED
AT STAIR SHAFTS
36" WIDE DOOR
(34" USABLE)
45
160
48" WIDE STAIR
STAIRS CONTROL
0.3"/occ
45
160
48" WIDE STAIR
STAIRS CONTROL
0.3"/occ
R 75' - 0"
STAIR DOWN FROM TOP OF RAMP
216' - 0"123' - 10"FI
RE TRUCKFIRE TRUCK12' WIDE ACCESS DRIVE
MIN WIDTH
20' - 2"
PARKING LOT
BOLLARDSFIRE TRUCK CAN ACCESS AS
FAR AS THIS POINT 230' - 0". MAX LENGTH
PARKING
GARAGE
OFFICE
BUILDINGAPARTMENT
BUILDING
VETERANS WAY
FDC
STANDPIPE IN STAIR
STANDPIPE IN STAIRSTANDPIPE IN STAIR
STANDPIPE AT
TOP OF RAMP
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
G003
LIFE SAFETY PLANS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 1/16" = 1'-0"02 LIFE SAFETY 05 - TOP OF RAMP
SCALE: 1/16" = 1'-0"01 FOURTH FLOOR CONSTRUCTION
PLAN
# DESCRIPTION DATE
SCALE: 1" = 40'-0"03 CODE SITE PLAN
JCTGLRACHNACOVER SHEETC000
01
BLOCK 3 PARKING GARAGE
CARMEL MIDTOWN
CARMEL, INDIANA 46032
BID DOCUMENTS
March 28, 2017
LOCATION MAP
CONSULTANT TEAM:
CIVIL ENGINEER
CIVIL & ENVIRONMENTAL
CONSULTANTS, INC.
530 E. OHIO STREET
SUITE G
INDIANAPOLIS, IN 46204
PH: (317) 655-7777
CONTACT: GREG RASMUSSEN
DRAWING INDEX
Sheet
Number Sheet Title Drawing
No.
COVER SHEET
SITE LAYOUT PLAN
DRAINAGE PLAN
C000
C800SITE DETAILS
1ST AVENUE SWPROJECT
LOCATION
C801SITE DETAILS
GAS
TELEPHONE
NOTE:MONON TRAILC400
SITE UTILITY PLAN C500
UTILITIES:
C802SITE DETAILS
S RANGELINE RD6TH STREET SW
C300GRADING PLAN
C200
ADDITIONAL CITY OF CARMEL NOTES:
REFERENCE:
UTILITY NOTE:
FLOOD INFORMATION NOTE:
STORM SEWER
OWNER/OPERATING AUTHORITY
STREET DESIGN SPEED
C900STORMWATER POLLUTION PREVENTION PLAN
C901STORMWATER POLLUTION PREVENTION PLAN NOTES
C902STORMWATER POLLUTION PREVENTION PLAN DETAILS
OFFICE
BUILDING
PARKING
GARAGE
APARTMENTS
WATER
ELECTRIC
SANITARY SEWER
STREETS
SITE DETAILS
SITE DETAILS
SITE DETAILS
PARCEL INFORMATION
C803
C804
C806
C805
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
VICINITY MAP
STORM SEWER
ARCHITECT
AXIS ARCHITECTURE &
INTERIORS
618 E. MARKET STREET
INDIANAPOLIS, INDIANA 46202
PH: (317) 264-8162
CONTACT: KEVIN COOPER
(BY OTHERS)
(BY OTHERS)
SITE
DEVELOPER
CARMEL REDEVELOPMENT
COMMISSION
30 WEST MAIN STREET
CARMEL, INDIANA 46032
PH: (317) 571-2787
CONTACT: CORRIE MEYER
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
DNOT TO SCALE
NOT TO SCALE
16
17
STORM SEWER PROFILES
STORM SEWER PROFILES
C401
C4021
1 s t A V E N U E S W℄MONON TRAILTTTTTTM O N O N T R A I LOFFICE
BUILDING
(BY OTHERS)
APARTMENTS
(BY OTHERS)
DRIVE
A
A
A A
A
PARKING
GARAGE
FFE = 828.50
A
A
B
B
A
A
C
C
C
B
A
A
KEYNOTE LEGEND
B
C
NORTH JCTGLRACH1" = 20'SITE PLANC200
02
GENERAL LAYOUT NOTES:
REFERENCE:
NOTE
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
D1
1
M O N O N T R A I L1 s t A V E N U E S WFUTURE
OFFICE
BUILDING
APARTMENTSTTTTTT℄MONON TRAILPARKING
GARAGE
FFE = 828.50
NORTH JCTGLRACH1" = 20'GRADING PLANC300
04
UTILITY NOTE:
PROPOSED GRADING AND DRAINAGE LEGEND:
BENCHMARKS:
”
NOTES:
GENERAL GRADING NOTES:
ADDITIONAL CITY OF CARMEL NOTES:
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1(2KLR6WUHHWÃ6XLWH*,QGLDQDSROLV,1Ãwww.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
D1
1
1
1
1
1
1
1
1
1 1
1
1
FUTURE
OFFICE
BUILDING
APARTMENTS℄MONON TRAILTTTTTTPARKING
GARAGE
FFE = 828.50
JCTGLRACH1" = 20'DRAINAGE PLANC400
05
GENERAL LAYOUT NOTES:
REFERENCE:
UTILITY NOTE:
PROPOSED GRADING AND DRAINAGE LEGEND:
BENCHMARKS:
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
DNORTH
DRAINAGE SUMMARY
1
1
1
1
1
1 1
1
1
TTTTTTM O N O N T R A I L FORMER INDIANA RAILROAD (66)'1 s t A V E N U E S WFUTURE
OFFICE
BUILDING
APARTMENTS
(BY OTHERS)
PARKING
GARAGE
FFE = 828.50
NORTH JCTGLRACH1" = 20'UTILITY PLANC500
06
REFERENCE:
UTILITY NOTE:
GENERAL UTILITY NOTES:
GAS
TELEPHONE
STREETS
UTILITY CONTACTS:
ADDITIONAL CITY OF CARMEL NOTES:
ELECTRIC
SANITARY SEWER
STORM SEWER
WATER
PROPOSED UTILITY LEGEND:
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G INEERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
D1
1
1
1
1
SITE DETAILSC800
14
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G INEERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
DJCTGLRACHAS NOTED
SECTION A-A
A A
DETAIL #5 - AS-8 AND STR. 104 DETAILS
PLAN VIEW
SECTION A-A
A A
DETAIL #4 - STRUCTURE #101
NTS
PLAN VIEW
ELEVATION VIEW
AS NOTEDSITE DETAILSC801
21
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
D8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
DJCTGLRACHCROSS SECTION
DETAIL 10 - CURB INLET TYPE "M"
PLAN VIEW
PLAN VIEW
CROSS SECTION
DETAIL # - PAVEMENT INLET TYPE "A"
1
SITE DETAILSC802
22
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
DJCTGLRACHNTS
SITE DETAILSC803
23
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
DJCTGLRACHAS NOTED
SITE DETAILSC804
24
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
DJCTGLRACHAS NOTED
SITE DETAILSC805
25
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
DJCTGLRACHNA
PARCEL INFORMATIONC806
25
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
DJCTGLRACHNA
PROPOSED LEGEND:TTTTTTFUTURE OFFICE BUILDING
(BY OTHERS)
APARTMENTS
(BY OTHERS)
SILT FENCEMONON AVENUE & CORRIDOR(DESIGN BY OTHERS)SITE DISCHARGE
LOCATION
1st AVENUE SW(DESIGN BY OTHERS)PROPOSED CONCRETE
WASHOUT
PROPOSED CONSTRUCTION ENTRANCE
SILT FENCE
PARKING
GARAGE
FFE = 828.50
NORTH JCTGLRACH1" = 20'STORMWATER POLLUTIONPREVENTION PLANC900
21
GENERAL NOTES:
(6) SOILS MAP
SOILS MAP LEGEND
PROJECT BOUNDARY
(14) CONTACT INFORMATION
8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
D1 N.I.C.1 N.I.C.1 N.I.C.
1 N.I.C.
1 N.I.C.1 N.I.C.
JCTGLRACHNONEC901
(13) MATERIAL HANDLING AND SPILL PREVENTION
(5) POST CONSTRUCTION MAINTENANCE GUIDELINES(4) POST CONSTRUCTION STORMWATER QUALITY
(3) STORMWATER QUALITY IMPLEMENTATION
(1) POTENTIAL LANDUSE POLLUTANTS
EROSION CONTROL MAINTENANCE REQUIREMENTS
K. MONITORING AND MAINTENANCE GUIDELINES
(2) LOCATION, DIMENSIONS, SPECIFICATIONS, AND CONSTRUCTION
DETAILS OF EACH STORMWATER QUALITY MEASURE
(10) LOCATION OF PROPOSED SOIL STOCKPILES
(12) EROSION CONTROL MEASURES FOR INDIVIDUAL BUILDING LOTS
SWPPP FOR POST CONSTRUCTION- CITY OF CARMEL
(7) POTENTIAL CONSTRUCTION POLLUTANTS
(6) SOIL MAP
(8) TEMPORARY & PERMANENT STORMWATER QUALITY MEASURES
C. CONCENTRATED FLOW SEDIMENT CONTROL
B. SHEET FLOW SEDIMENT CONTROL
A. CONSTRUCTION ENTRANCE INFORMATION
(11-B) PERMANENT SURFACE STABILIZATION
(11-A) TEMPORARY SURFACE STABILIZATION
DESCRIPTION MEASURES:
D. INLET PROTECTION LOCATIONS AND SPECS.
E. RUNOFF CONTROL MEASURES
F. OUTLET PROTECTION SPECIFICATIONS
G. GRADE STABILIZATION MEASURES
H. STORMWATER QUALITY DETAILS
I. TEMPORARY SURFACE STABILIZATION
J. PERMANENT SURFACE STABILIZATION
(9) GENERAL CONSTRUCTION SEQUENCE
(3) ESTIMATED PEAK DISCHARGE
(2) RECEIVING WATERS
(1) HYDROLOGIC UNIT CODE
SWPPP FOR CONSTRUCTION SITES- CITY OF CARMEL
(5) LOCATION WHERE STORMWATER MAY BE DIRECTLY
DISCHARGED INTO GROUNDWATER
(4) LOCATION WHERE SPECIFIC POINTS OF STORMWATER
DISCHARGE LEAVING THE SITE
STORMWATER POLLUTIONPREVENTION PLAN NOTES8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G INEERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
D1 1
JCTGLRACHAS NOTEDC902
23
PERMANENT SEEDING DATES
TEMPORARY SEEDING DATES
LAWNS AND HIGH MAINTENANCE AREAS
LEVEL AND SLOPING, OPEN AREAS
TEMPORARY SEEDING
PERMANENT SEEDING
DETAIL 1 - 48" TREE PROTECTION DETAIL
5'
DETAIL 2 - 48" TREE PROTECTION FENCE
DETAIL 5 - SILT FENCE
PLAN
SECTION B-B
NOT TO SCALE
DETAIL 4- CONCRETE WASHOUT BMP
NOT TO SCALE
DETAIL 3- STRAW BALE SEDIMENT TRAP FOR CONCRETE WASHOUT
DETAIL 7 - TEMPORARY CONSTRUSTION ENTRANCE
(SITES 2 ACRES OR LARGER)
INSTALLATION DETAIL
DETAIL 8 - EROSION CONTROL INLET PROTECTION
FOR CURB INLET AND CATCH BASINS
DETAIL 9 - NON-PAVED AREA CATCH BASIN
INLET PROTECTION DETAIL STORMWATER POLLUTION PREVENTIONPLAN DETAILS8
A
B
34567 12
C
D
E
F
G
H
8 34567 12
A
B
C
D
E
F
G
H
DESCRIPTIONDATENOREVISION RECORD02/17/2017SUBMITTAL TO CARMEL03/27/2017BID SET - NOT FOR CONSTRUCTION04/13/2017ADDENDUM NO. 1530 E. Ohio Street · Suite G - Indianapolis, IN 46204317-655-7777 · 877-746-0749 www.cecinc.comDATE:DWG SCALE:DRAWN BY:CHECKED BY:APPROVED BY:PROJECT NO:SHEET OF
DRAWING NO.:170-386FEBRUARY 28, 2017BLOCK 3PARKING GARAGECARMEL MIDTOWNCARMEL, INDIANAPROF
E
SSIONA L E N G IN EERINDIA N AAARON C. H
U
RTPE10300058
STATE OF
-oNREGIS TER
E
D
ALL REINFORCING STEEL BARS SHALL BE ASTM A-615 GRADE 60. SEE MASONRY
SERIES DRAWINGS FOR REINFORCING DETAILS. SEE ARCHITECTURAL DRAWINGS FOR EXTENT
AND LAYOUT OF NON-STRUCTURAL CMU WALLS.
ALL LAP SPLICES SHALL BE IN ACCORDANCE WITH THE MASONRY REINFORCEMENT
DEVELOPMENT AND LAP LENGTH TABLE.
ALL HORIZONTAL JOINT REINFORCEMENT FOR ALL WALLS SHALL BE LAPPED A MINIMUM OF 75
DIAMETERS OF THE SIDE ROD (13” FOR 9 GAGE).
PROVIDE REINFORCING STEEL IN VERTICAL CORES AS INDICATED ON THE DRAWINGS. PROVIDE
ADDITIONAL REINFORCEMENT AROUND OPENINGS, DOORS AND WINDOWS AS INDICATED ON
MASONRY SERIES DRAWINGS.
ALL VERTICAL REINFORCING SHALL BE HELD IN PLACE AT 8'-0” O.C. MAXIMUM AND AT EACH END.
MINIMUM CLEARANCE SHALL BE ¾” FROM MASONRY AND 1” BETWEEN BARS. PROVIDE REBAR
POSITIONING ACCESSORIES TO SUPPORT REINFORCING AS REQUIRED. SEE SPECIFICATIONS FOR
PRODUCTS.
ALL CELLS WHICH RECEIVE REINFORCING SHALL BE GROUTED SOLID.
ALL HORIZONTAL REINFORCING STEEL SHALL BE PLACED IN CONTINUOUSLY GROUTED BOND
BEAMS. PROVIDE HORIZONTAL BOND BEAM WITH 2 #5'S CONTINUOUS IN THE TOP OF ALL CMU
WALLS AND AT ALL POINTS OF STRUCTURAL ATTACHMENTS AND MISCELLANEOUS STEEL
ANCHORAGE.
DOWELS FOR CMU WALLS SHALL BE DRILLED AND GROUTED BY THE CMU CONTRACTOR.
SEE SPECIFICATIONS AND ARCHITECTURAL DRAWINGS FOR INTERIOR PARTITION CONTROL JOINT
REQUIREMENTS.
TOP OF ALL CMU WALLS SHALL BE BRACED TO THE STRUCTURE ABOVE UNLESS NOTED
OTHERWISE. SEE MASONRY SERIES DRAWINGS FOR TYPICAL ATTACHMENT DETAILS. SEE
ARCHITECTURAL DRAWINGS FOR CONDITIONS AND ELEVATIONS OF WALLS.
SEE DRAWINGS MASONRY SERIES DRAWINGS FOR LINTEL REINFORCING REQUIRED AT OPENINGS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
DESIGN INFORMATIONGENERAL NOTES
#3
#4
#5
#6
#7
#8
#9
#10
#11 75
63
52
42
33
26
20
18
16 16
18
26
33
43
54
67
82
97126
105
86
70
55
40
34
24
1816
18
26
33
43
54
67
82
99
BAR
SIZE
UNCOATED
TYPE I TYPE IITYPE IITYPE I
UNCOATED
NOTES:
1. LAP SPLICE LENGTHS ARE IN INCHES.
2. TYPE I: HORIZONTAL BOTTOM BAR AND VERTICAL BAR SPLICES.
3. TYPE II: HORIZONTAL TOP BAR SPLICES.
TABLE 1:
TENSION LAP SPLICES
CONCRETE REINFORCEMENT
84
70
58
47
37
28
23
18
16 16
20
29
35
48
61
75
91
109
UNCOATED
TYPE I TYPE II
131
110
89
73
58
40
35
24
1816
18
27
32
44
56
69
84
101
TYPE IITYPE I
f 'c = 3 ksi
EPOXY COATED
f 'c = 4 ksi f 'c = 4 ksi f 'c = 5 ksi
AND COLUMN BASE PLATES:...................................
SHEAR CONNECTORS:............................
STRUCTURAL TUBING:...............................................
W-SHAPES
ANGLES, CHANNELS, PLATES & BARS:........................................
3/4" INCH DIAMETER, ASTM A108
ASTM A500, GRADE B,
ASTM A992, GRADE 50
ASTM A36
Fy = 46 KSI
Fy = 35 KSI OR ASTM A501, Fy = 36 KSI
ASTM A53, TYPE E OR S, GRADE B,STRUCTURAL PIPE:...............................
28 DAY
STRENGTH
COMPRESSIVE
ADMIXTURE REQUIRED
WATER REDUCING3000 PSIA
REMARKSCONCRETE PLACEMENTCLASS
CONCRETE SCHEDULE
FOOTINGS
B 4000 PSI
6 1 1/2% SLABS ON GRADE
+-
OPTIONAL
AIR CONTENT
6000 PSIPCA PRECAST CONCRETE
4000 PSIC
WALLS AND PIERS0 - 3%
7000 PSIPCB PRECAST COLUMNS AS REQUIRED
HIGH RANGE WATER REDUCING
ADMIXTURE AND SYNTHETIC
FIBERS REQUIRED
MID OR HIGH RANGE WATER
REDUCING ADMIXTURE
REQUIRED
HIGH RANGE WATER REDUCING
ADMIXTURE REQUIRED
FOR INFORMATION REGARDING SUBSURFACE CONDITIONS REFER TO REPORT OF GEOTECHNICAL
ENGINEERING INVESTIGATION PREPARED BY ALT & WITZIG ENGINEERING, DATED MAY 31, 2016
(A&W NO. 15IN0457-0516).
WELDED WIRE FABRIC: ASTM A185
REINFORCING BARS: ASTM A615, GRADE 60
SEE CONCRETE SCHEDULE FOR 28 DAY COMPRESSIVE STRENGTHS.
LATERAL EARTH PRESSURE:
UNIT WEIGHT OF BACKFILL = 125 PCF
AT-REST COEFFICIENT, Ko = 0.45
COLUMNS AND WALL FOOTINGS BEARING :
ALLOWABLE NET BEARING PRESSURE, ANBP = 4000 PSF
EXPOSURE B
TABLE 1609)
BASIC WIND SPEED = 115 MPH (2014 INDIANA BUILDING CODE:
IMPORTANCE FACTOR, Iw = 1.00
ACTIVE COEFFICIENT, Ka = 0.30
EPOXY-COATED REINFORCING BARS: ASTM A775, GRADE 60
PARKING SURFACES:FLOOR ROOF
SLABS 40 PSF 60 PSF
BEAMS 40 PSF 60 PSF
COLUMNS 40 PSF 60 PSF
STAIR/ELEVATOR TOWERS:100 PSF 25 PSF
WALL BUMPER LOAD: 10,000 POUNDS (ULTIMATE) APPLIED AT 2'-0"
ABOVE THE PARKING SURFACE OVER ONE FOOT
SQUARE (AT ANY POINT ALONG WALL, ACTING
OUTWARD)
CONCENTRATED WHEEL LOAD:2,000 POUNDS ON 20 SQUARE
INCHES.
1.
FOR CONCRETE MIX PROPORTIONING AND SUBMITTAL REQUIREMENTS.
SEE SECTION 0330000, CAST-IN-PLACE CONCRETE, OF THE PROJECT MANUAL
E.MINIMUM SHEAR REINFORCEMENT ACCORDING TO ACI 318-89 IS REQUIRED IN ALL
PRECAST MEMBERS.
F.MAXIMUM ALLOWABLE TENSILE STRESSES UNDER FULL DESIGN SERVICE LOADS IN
ALL PRECAST PRESTRESSED MEMBERS SHALL BE
G.AN ADDITIONAL 1.33 LOAD FACTOR WILL BE REQUIRED FOR ALL PRECAST
CONNECTION DESIGN.
SEISMIC USE GROUP I
SEISMIC DESIGN CATEGORY
SEISMIC SITE CLASS
Ss = 0.146
Sl = 0.081
IMPORTANCE FACTOR
R = 4.0
B
C
IE = 1.0
AGGREGATES:
AS SPECIFIED UNDER CAST-IN-PLACE CONCRETE AND HEREIN.
PRECOATED REINFORCING. IN AREAS OF DISPUTE, THE FOLLOWING
COLUMNS
PROVIDE ADEQUATE SHORING AND BRACING DURING CONSTRUCTION
DO NOT EMBED CONDUITS IN CONCRETE FLOOR TOPPING.
1. ALL DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH ACI 318-05,
PCI MNL-120, AND PCI MNL-116, MOST CURRENT EDTIONS. REFER TO SPECIFICATIONS SECTION
034133, "PRECAST CONCRETE", FOR DESIGN REQUIREMENTS FOR PRECAST MEMBERS
PRECAST CONCRETE:
DESCRIPTION
COLUMNS
BEAMS
SHEAR/LIGHT WALLS
DOUBLE TEES
WALLS
STAIRS
ARCHITECTURE
F'c PSI MAX. W/C TOTAL AIR
CONTENTRATIO
28 DAYS
7000 PSI
6000 PSI
6000 PSI
6000 PSI
6000 PSI
6000 PSI
6000 PSI
0.39
0.39
0.39
0.39
0.39
0.39
0.39
0.39
6 1/2%
6 1/2%
6 1/2%
6 1/2%
6 1/2%
6 1/2%
6 1/2%
6 1/2%
TOLERANCE ON TOTAL AIR CONTENT IS 1 1/2%.
CEMENT:
MILD REINFORCEMENT:
AS SPECIFIED UNDER CAST-IN-PLACE CONCRETE.
AS SPECIFIED UNDER CAST-IN-PLACE CONCRETE.
THE MINIMUM CONCRETE PROTECTION SHALL BE PER ACI 318-05, EXCEPT
AS NOTED ON THE DRAWINGS AND SPECIFIED HEREIN. SPECIFIC PLANS,
SECTIONS AND DETAILS MAY OR MAY NOT INDICATE EPOXY COATING OR
SCHEDULE SHALL GOVERN IN ALL CASES.
PROTECTIONCOVER
BEAMS
LIGHT WALLS
WALLS
STAIRS
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
UNCOATED
UNCOATED
UNCOATED
UNCOATED
UNCOATED
PRESTRESSING TENDON END COVER SHALL ALSO BE AS SPECIFIED HEREIN
INDICATED UNDER "COVER".
3.
4.
5.
6.
7. PRESTRESSING TENDONS:
SEVEN-WIRE, LOW-RELAXATION TYPE STRAND (LRS) ASTM A416, GRADE
A, 270 KSI.
AS SPECIFIED UNDER CAST-IN-PLACE CONCRETE AND HEREIN.
COIL RODS TO BE HIGH STRENGTH, ELECTRO GALVANIZED ASTM B633.
DOUBLE TEE FLANGE EDGE CONNECTION, STAINLESS STEEL ASTM A666,
TYPE 304L.
CONCRETE ACCESSORIES:
BEARING PADS:
DOUBLE TEES: RANDOM ORIENTED FIBER, 3/8" THICK.
BEAMS PREFORMED FABRIC PADS: 1/2" THICK.
SHIM PADS: AASHTO GRADE NEOPRENE, SHORE HARDNESS 50.
SHIM STOCK: "KOROLATH".
GROUT:
GENERAL PRECAST CONCRETE:
AS SPECIFIED UNDER CAST-IN-PLACE CONCRETE.
ALL WELDS SHALL USE E70XX LOW HYDROGEN ELECTRODES, 1/4"
MINIMUM, STAINLESS STEEL ELECTRODES TO BE TYPE 347.
HIGH-STRENGTH BOLTS TO BE ASTM A325 TYPE 1, HOT-DIP GALVANIZED
3/4" DIAMETER UNLESS OTHERWISE NOTED ON THE DRAWINGS.
FOR LEDGER SPANDREL BEAMS AND INVERTED TEE BEAMS WHICH SUPPORT
TEE STEMS, PROVIDE EMBEDDED BEARING PLATE (OR ANGLE) IN THE BEAM
LEDGE UNDER ANY TEE STEM WITH ULTIMATE LOAD REACTIONS EQUAL TO
OR GREATER THAN 35 KIPS.
AT ALL INVERTED TEE AND SPANDREL BEAM MEMBER END BEARINGS,
PROVIDE BEARING PLATES IN THE BOTTOM OF THE BEAM MEMBER AND
AFTER MEMBER IS ERECTED. SUCH OPENINGS SHALL BE COORDINATED
BY THE CONTRACTOR AND RECEIVE PRIOR APPROVAL BY THE PRECAST
MANUFACTURER AND THE ENGINEER.
WHERE UNBALANCED LOADING CONDITIONS ARE POSSIBLE.
DO NOT USE DRILLED-IN ANCHORS OR POWER DRIVEN FASTENERS IN
PRESTRESSED CONCRETE.
8.
9.
10.
11.
PROVIDE ONE INCH CLEARANCE FOR DOUBLE TEE FLANGE AROUND
IN THE TOP OF THE SUPPORTING HAUNCH (3/8" MINIMUM THICK).
OPENINGS LESS THAN 10" ROUND OR SQUARE SHALL BE LOCATED AND
FIELD DRILLED OR SAW CUT BY THE TRADE REQUIRING THE OPENING
COLUMNS.
1 1/2" UNCOATEDDOUBLE TEES
A.
B.
C.
D.
E.
F.
G.
I.
J.
AND ALL OTHER INFORMATION NOT SPECIFIED HEREIN.
CONCRETE: ACI 362, 1R-97 TABLE 3.3.A.
A.
A.
A.
B.
C.
A.
A.
B.
C.
A.
B.
C.
D.
A.
(MIN)
DESCRIPTION
D.ALL BARS IN PRECAST CAST-IN-PLACE WASHES AND SLAB IN-FILLS SHALL BE
EPOXY COATED.
2.THE DESIGN OF ALL PRECAST COMPONENTS SHALL BE THE RESPONSIBILITY OF THE
PRECAST CONTRACTOR. CALCULATIONS PREPARED BY AN ENGINEER REGISTERED IN
THE STATE OF INDIANA MUST BE SUBMITTED. DRAWINGS INCLUDED HEREIN SHOW
DESIGN INTENT.
THERMAL AND MOISTURE PROTECTION:
CONCRETE SEALER
A.A 100% SILANE CONCRETE SEALER SHALL BE APPLIED TO ALL SLAB ON
GRADE AND SUPPORTED SLAB SURFACES (INCLUDING STAIRS, LANDINGS
AND LOBBIES).
JOINT SEALANTS
A.ALL JOINTS BETWEEN STRUCTURAL (AND ARCHITECTURAL) MEMBERS
SHALL BE PROPERLY PREPARED AND FILLED WITH JOINT SEALANT UNLESS
NOTED OTHERWISE. ALL JOINT EDGES, INCLUDING TOP AND BOTTOM
SURFACES AND VERTICAL AND HORIZONTAL SURFACES, SHALL BE
FORMED OR TOOLED AS REQUIRED. JOINT SEALANT SHALL BE APPLIED
ONLY TO THE TOP, VERTICAL AND HORIZONTAL SURFACES UNLESS NOTED
OTHERWISE.
B.JOINTS TO BE PROPERLY PREPARED AND FILLED WITH JOINT SEALANT
SHALL INCLUDE, BUT ARE NOT LIMITED TO, CONSTRUCTION JOINTS,
CONTROL JOINTS, ISOLATION JOINTS AND ALL INTERFACE JOINTS
BETWEEN SIMILAR AND DISSIMILAR MEMBERS. SPECIFIC LOCATIONS MAY
BE INDICATED ON THE DRAWINGS, OR MAY BE REQUIRED BY THE SHOP
DRAWINGS, OR MAY OCCUR DUE TO THE CONSTRUCTION SEQUENCE
SLECTED BY THE CONTRACTOR.
H.
INTERMEDIATE PRECAST CONCRETE SHEAR WALLS
1.
2.
3.
4.
5.
6.
7.
9.
PREPARE AREAS OF THE SITE SUPPORTING STRUCTURE BY REMOVING TOPSOIL,
EXISTING FILL, ORGANIC MATERIAL, OR FROZEN, WET, SOFT, LOOSE OR OTHERWISE
UNSUITABLE MATERIALS.
FIELD BENDING OF REINFORCING STEEL IS PROHIBITED.
13.
12.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
THE MIXING, HANDLING, PLACING AND CURING OF CONCRETE SHALL BE1.
h.
g.
a.
b.
c.
f.
a.
b.
WALLS.
AND DETAILS OF REVEALS (3/4" MAXIMUM DEPTH) IN EXPOSED CONCRETE
ARCHITECTURAL REVEALS: SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS11.
ROUGH FORM FINISH
FOR FORM REMOVAL AND RESHORING REQUIREMENTS.
SEE SECTION 031000, CONCRETE FORMWORK, OF THE PROJECT MANUAL
MANUAL, FOR CONCRETE MIX PROPORTIONING REQUIREMENTS.
SEE SECTION 033000, CAST-IN-PLACE CONCRETE, OF THE PROJECT
EXCEPT THOSE ABUTTING MASONRY.
PROVIDE 3/4 INCH CHAMFERS ON EXPOSED CORNERS OF CONCRETE
STRUCTURAL CONCRETE" (ACI 318-99).
IN ACCORDANCE WITH THE ACI "BUILDING CODE REQUIREMENTS FOR
SEE SECTION 033000, CAST-IN-PLACE CONCRETE, OF THE PROJECT MANUAL
FOR HOT WEATHER CONCRETING REQUIREMENTS.
MANUAL FOR COLD WEATHER CONCRETING REQUIREMENTS.
SEE SECTION 033000, CAST-IN-PLACE CONCRETE, OF THE PROJECT
FINISHING OF FORMED SURFACES: FINISH FORMED SURFACES AS
INDICATED BELOW, AND AS DESCRIBED IN SECTION 033000, CAST-IN-PLACE
CONCRETE, OF THE PROJECT MANUAL.
SIDES OF FOOTINGS
WALLS NOT EXPOSED TO PUBLIC VIEW
WALLS EXPOSED TO PUBLIC VIEW
COLUMNS & PIERS
BOTTOMS OF SLABS
BOTTOMS & SIDES OF BEAMS
NONE
ROUGH FORM FINISH
SMOOTH FORM FINISH
ROUGH FORM FINISH
ROUGH FORM FINISH
CURING OF SLABS: CURE SLABS WITH CURING COMPOUNDS OR MOISTURE
RETENTION COVERS AS DESCRIBED IN SECTION 033000, CAST-IN-PLACE
CONCRETE, OF THE PROJECT MANUAL.
FINISHING OF SLABS: AFTER SCREEDING, BULL FLOATING AND FLOATING
OPERATIONS HAVE BEEN COMPLETED, APPLY FINAL FINISH AS INDICATED
BELOW, AND AS DESCRIBED IN SECTION 033000, CAST-IN-PLACE CONCRETE,
OF THE PROJECT MANUAL.
STAIR/ELEVATOR TOWER FLOOR SLABS HARD TROWEL FINISH
FINISH CONCRETE SLABS ON COMPOSITE STEEL FLOOR DECK TO THE
TOLERANCE SPECIFIED IN SECTION 033000, CAST-IN-PLACE CONCRETE,
OF THE PROJECT MANUAL. MAINTAIN AT LEAST THE REQUIRED SLAB
THICKNESS AT ALL LOCATIONS, INCREASING THE THICKNESS AS REQUIRED,
TO COMPENSATE FOR DECK AND BEAM DEFLECTIONS, AND RESIDUAL BEAM
CAMBER.
2.
3.
4.
5.
8.
9.
10.
6.
7.
PARKING SURFACES ROUGH SWIRL FINISH
SMOOTH FORM FINISH
OTHER SURFACES NOT EXPOSED
TO PUBLIC VIEW
OTHER SURFACES EXPOSED TO
PUBLIC VIEW
ROUGH FORM FINISH
7.
6.6.
5.
4.
1.
2.
3.
11.
10.
9.
8.
INDICATED ON THE DRAWINGS.
SHALL BE DOUBLE WEB ANGLES, 5/16 INCH MINIMUM THICKNESS.
MANUAL FOR STRUCTURAL STEEL SHOP PAINTING REQUIREMENTS.
SEE SECTION 051200, STRUCTURAL STEEL OF THE PROJECT
MANUAL FOR STRUCTURAL STEEL TESTING REQUIREMENTS.
SEE SECTION 051200, STRUCTURAL STEEL OF THE PROJECT
HOLES, UNLESS OTHERWISE NOTED OR DETAILED ON THE DRAWINGS, OR
INCH DIAMETER ASTM A325 BOLTS WITH STANDARD 13/16 INCH DIAMETER
BOLTED CONNECTIONS SHALL BE BEARING-TYPE CONNECTIONS USING 3/4
DETAILED ON THE DRAWINGS.
OR WELDED. FIELD CONNECTIONS SHALL BE BOLTED UNLESS OTHERWISE
SHOP CONNECTIONS, UNLESS OTHERWISE SHOWN, MAY BE EITHER BOLTED
BUILDINGS, ALLOWABLE STRESS DESIGN AND PLASTIC DESIGN".
INSTITUTE OF STEEL CONSTRUCTION "SPECIFICATION FOR STRUCTURAL STEEL
STRUCTURAL STEEL CONSTRUCTION SHALL CONFORM TO THE AMERICAN
CONNECTIONS NOT DETAILED ON THE DRAWINGS SHALL BE DESIGNED BY
THE STEEL FABRICATOR IN ACCORDANCE WITH THE AISC "MANUAL OF
STEEL CONSTRUCTION". BEAM END CONNECTIONS SHALL BE DESIGNED
FOR ONE-HALF THE BEAM LOAD CAPACITY AS GIVEN IN THE
AISC "ALLOWABLE LOADS ON BEAMS" TABLES. CONNECTION ANGLES
FABRICATE SIMPLE SPAN BEAMS WITHOUT SPECIFIED CAMBERS SO THAT,
AFTER ERECTION, ANY MINOR CAMBER DUE TO ROLLING OR SHOP
ASSEMBLY SHALL BE UPWARD.
SLIP CRITICAL (S.C.) AND PRETENSIONED BOLTS SHALL BE USED WHERE
APPROVED BY THE ARCHITECT/ENGINEER.
TENSION SLIP CRITICAL AND PRETENSIONED BOLTS IN ACCORDANCE
USING ASTM A325 OR A490 BOLTS.
3.
2.
1.
4.
OF SPAN WITH SELF TAPPING SCREWS NOT SMALLER THAN #10.
INCH DIAMETER OR EQUIVALENT. CONNECT SIDELAPS AT ONE-THIRD POINTS
INSTRUCTIONS AND THE SHOP DRAWINGS. WELDS SHALL BE AT LEAST 5/8
12 INCH CENTERS AND IN STRICT COMPLIANCE WITH THE DECK MANUFACTURER'S
WELD 1 1/2", WIDE RIB STEEL ROOF DECK TO EACH SUPPORT AT NOT MORE THAN
AT ONE-THIRD POINTS OF SPANS.
BE AT LEAST 3/4 INCH DIAMETER OR EQUIVALENT. CONNECT SIDELAPS
MANUFACTURER'S INSTRUCTIONS AND THE SHOP DRAWINGS. WELDS SHALL
THAN 12 INCH CENTERS AND IN STRICT COMPLIANCE WITH THE DECK
WELD COMPOSITE STEEL FLOOR DECK TO EACH SUPPORT AT NOT MORE
STEEL DECK CONSTRUCTION SHALL CONFORM TO THE STEEL DECK
INSTITUTE'S "DESIGN MANUAL FOR COMPOSITE DECKS, FORM DECKS AND
ROOF DECKS".
DECK SHALL BE THREE OR MORE SPANS CONTINUOUS WHERE POSSIBLE.
PROCEEDING WITH WORK IN THE AREA UNDER QUESTION.
ETC. NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES BEFORE
RELATING TO ARCHITECTURAL FINISHES, MECHANICAL OPENINGS, EQUIIPMENT,
1.
2.
3.
THERE SHALL BE NO VERTICAL OR HORIZONTAL SLEEVES SET, OR HOLES
CUT OR DRILLED IN ANY BEAM OR COLUMN UNLESS IT IS SHOWN ON THE
STRUCTURAL DRAWINGS OR APPROVED BY THE ARCHITECT/ENGINEER.
MECHANICAL AND ELECTRICAL OPENINGS THROUGH CONCRETE SLABS AND
WALLS LARGER THAN 8 INCHES IN DIAMETER, NOT SHOWN ON THE
STRUCTURAL DRAWINGS, MUST BE APPROVED BY THE ARCHITECT/ENGINEER.
OPENINGS 8 INCHES IN DIAMETER OR LESS SHALL HAVE AT LEAST 1'-0"
CLEAR BETWEEN OPENINGS UNLESS APPROVED BY THE ARCHITECT/ENGINEER.
THE CONTRACTOR SHALL COORDINATE AND CHECK ALL DIMENSIONS
4.VERIFY DIMENSIONS AND LOCATIONS OF MECHANICAL AND ELECTRICAL
OPENINGS THROUGH CONCRETE SLABS, SHOWN ON THE STRUCTURAL
DRAWINGS, WITH THE MECHANICAL AND ELECTRICAL CONTRACTORS.
1.
UNDER QUESTION.
OF ANY DISCREPANCIES BEFORE PROCEEDING WITH WORK IN THE AREA
PROCEEDING WITH NEW CONSTRUCTION. NOTIFY THE ARCHITECT/ENGINEER
VERIFY ALL EXISTING DIMENSIONS, ELEVATIONS AND CONDITIONS BEFORE
14. EPOXY-COATED REINFORCING STEEL
5.MECHANICAL AND ELECTRICAL CONDUIT SHALL NOT BE EMBEDDED IN
POST-TENSIONED SLABS.
d.
1.
2.
3.
4.
5.
ACCORDANCE WITH THE PRODUCT MANUFACTURER'S INSTRUCTIONS.
DRILLED HOLE SIZE AND INSTALLATION PROCEDURE SHALL BE IN
CLEAN DRILLED HOLES BEFORE INSTALLING DOWELS.
USE CARBIDE BIT DRILL TO PREVENT DAMAGE TO REINFORCING STEEL.
OF THE PROJECT MANUAL FOR PRODUCT STANDARDS.
ANCHOR SYSTEM. SEE SECTION 033000, CAST-IN-PLACE CONCRETE
ANCHOR DRILLED-IN DOWELS TO EXISTING CONCRETE WITH AN ADHESIVE
SPACING AS INDICATED ON THE DRAWINGS.
PROVIDE DRILLED-IN DOWELS WITH SIZE, LENGTH, EMBEDMENT AND
e.
c.SLIP RESISTANT SURFACES
(STAIR TREADS AND RAMPS)
BROOM FINISH
ONLY A WELL-GRADED, FREE-DRAINING GRANULAR MATERIAL SHALL BE USED
FOR BACKFULL BEHIND ALL CONCRETE BASEMENT AND FREE-STANDING,
CANTILEVERED RETAINING WALLS AND SHALL BE PLACED WITHIN A ZONE
DEFINED BY A LINE EXTENDING UPWARD AND OUTWARD ON A 1 TO 1 (OR FLATTER)
SLOPE FROM THE BASE OF THE WALL.
11.CENTER ALL COLUMN AND WALL FOOTINGS UNDER THE COLUMN OR WALL ABOVE UNLESS
OTHERWISE INDICATED.
10.
SHOP GALVANIZE STEEL AS INDICATED ON THE DRAWINGS. SEE SPECIFICATION
SECTION S51200, FOR WELDING PROCEDURE FOR GALVANIZED STEEL.
12.
1.
FOUNDATIONS
A GEOTECHNICAL TESTING AGENCY SHALL INSPECT FOOTING EXCAVATIONS TO [1] VERIFY
THAT THE SOIL AT THE BEARING ELEVATION IS OF THE TYPE DEFINED IN THE GEOTECHNICAL
STUDY TO ENSURE THAT CONDITIONS ARE SIMILAR TO THOSE UPON WHICH THE FOUNDATION
RECOMMENDATIONS ARE BASED AND [2] VERIFY THE ALLOWABLE BEARING CAPACITY AT EACH
SPREAD FOOTING AND EVERY 8 FEET ON CENTER FOR STRIP FOOTINGS PRIOR TO
PLACEMENT OF CONCRETE. INSPECTION OF THE BASE OF THE FOOTING EXCAVATIONS
SHALL BE DONE IN ACCORDANCE WITH THE PROJECT'S GEOTECHNICAL ENGINEERING
INVESTIGATION REPORT PER NOTE 12. SEE "DESIGN INFORMATION" ON THIS DRAWING FOR
ALLOWABLE NET BEARING PRESSURES.
PROOFROLL THE EXPOSED SUBGRADE WITH A MEDIUM-WEIGHT ROLLER TO DETERMINE
IF ANY POCKETS OF SOFT, UNSUITABLE MATERIAL EXIST BENEATH THE EXPOSED
SUBGRADE. REMOVE ANY UNSUITABLE MATERIAL ENCOUNTERED AND REPLACE WITH A
WELL COMPACTED GRANULAR MATERIAL.
PLACEMENT AND COMPACTION OF ENGINEERED FILL SHALL BE OVERSEEN BY THE
ENGINEERING TESTING FIRM. PLACE FILL MATERIAL IN LAYERS NOT EXCEEDING 8 INCHES
IN LOOSE THICKNESS. MECHANICALLY COMPACT EACH LAYER TO THE FOLLOWING
PERCENTAGE OF MAXIMUM DRY DENSITY PER MODIFIED PROCTOR (ASTM D-1557): BELOW
FOOTINGS - 95%, BELOW SLABS ON GRADE - 93%, BEHIND EARTH RETAINING WALLS - 90%.
REFER TO THE GEOTECHINICAL REPORT FOR ADDITIONAL REQUIREMENTS FOR
MATERIALS, COMPACTION METHODS AND FIELD QUALITY CONTROL.
REINFORCING STEEL
PROVIDE MINIMUM CONCRETE COVER FOR REINFORCING STEEL IN ACCORDANCE
WITH THE ACI "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" (ACI
318-05), UNLESS OTHERWISE INDICATED.
REINFORCING STEEL SHALL BE SUPPORTED AND SECURED AGAINST DISPLACEMENT
IN ACCORDANCE WITH THE CONCRETE REINFORCING STEEL INSTITUTE'S "MANUAL OF
STANDARD PRACTICE". SEE SECTION 032000, CONCRETE REINFORCEMENT, OF THE
PROJECT MANUAL FOR ADDITIONAL REQUIREMENTS.
DETAILS OF REINFORCING STEEL FABRICATION AND PLACEMENT SHALL CONFORM TO
ACI "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT" (ACI 315) AND "MANUAL
OF ENGINEERING AND PLACING DRAWINGS FOR REINFORCED CONCRETE STRUCTURES"
(ACI 315R) UNLESS OTHERWISE INDICATED.
SPREAD REINFORCING STEEL AROUND SMALL OPENINGS AND SLEEVES IN SLABS AND
WALLS, WHERE POSSIBLE, AND WHERE BAR SPACING WILL NOT EXCEED 1.5 TIMES THE
NORMAL SPACING. DISCONTINUE BARS AT LARGE OPENINGS, WHERE NECESSARY, AND
PROVIDE AN AREA OF REINFORCEMENT, EQUAL TO THE INTERRUPTED
REINFORCEMENT, IN FULL LENGTH BARS, DISTRIBUTING ONE-HALF EACH SIDE OF THE
OPENING. WHERE SHRINKAGE AND TEMPERATURE REINFORCEMENT IS INTERRUPTED,
ADD 2-#5 x OPENING DIMENSION +4'-0" ON EACH SIDE OF THE OPENING. PROVIDE #5 x
4'-0" DIAGONAL BARS IN BOTH FACES, AT EACH CORNER OF OPENINGS LARGER THAN 12
INCHES IN ANY DIRECTION.
PROVIDE INDIVIDUAL HIGH CHAIRS WITH SUPPORT BARS, AS REQUIRED, FOR THE SUPPORT
OF TOP REINFORCEMENT FOR SUPPORTED SLABS. DO NOT PROVIDE STANDEES.
PROVIDE PLASTIC, SNAP-ON SPACE WHEELS TO MAINTAIN REQUIRED CONCRETE COVER FOR
VERTICAL WALL REINFORCEMENT.
PROVIDE FOOTING DOWELS FOR VERTICAL WALL REINFORCEMENT. DOWELS SHALL BE THE
SAME SIZE AND SPACING AS THE VERTICAL WALL REINFORCEMENT, UNLESS NOTED
OTHERWISE, WITH LAP SPLICES AS INDICATED IN TABLE 1 ON THIS DRAWING. INSTALL DOWELS
IN THE FOOTING FORMS BEFORE CONCRETE IS PLACED, SUPPORTING AND TIEING THEM
SECURELY IN POSITION. DO NOT STICK DOWELS INTO FOOTINGS AFTER CONCRETE IS PLACED.
POSITION DOWELS FOR VERTICAL WALL REINFORCEMENT IN COLUMN FOOTINGS AND WALL
FOOTING STEPS WITH 6 INCHES MAXIMUM BOTTOM COVER.
PROVIDE TENSION LAP SPLICES, AS INDICATED IN THE LAP SPLICE SCHEDULE ON THIS
DRAWING, FOR HORIZONTAL WALL REINFORCEMENT AND LONGITUDINAL GRADE BEAM
REINFORCEMENT, UNLESS OTHERWISE INDICATED.
CAST-IN-PLACE CONCRETE STRUCTURAL STEEL
SUB-BASE (LEVELING) PLATES WILL NOT BE ALLOWED UNDER
COLUMN BASE PLATES.
BURNING OF HOLES IN STRUCTURAL STEEL SHALL NOT BE ALLOWED WITHOUT
APPROVAL OF THE ARCHITECT/ENGINEER.
STEEL DECK
DRILLED-IN DOWELS
COORDINATION WITH OTHER TRADES
OTHER NOTES
EXISTING CONSTRUCTION
ALL WELDED STUDS AND ALL WELDED DEFORMED BAR ANCHORS ( dba )
SHALL BE AUTOMATICALLY WELDED ( NOT STICK WELDED ) .
BACKFILL EACH SIDE OF CONCRETE WALLS, WITH EARTH ON BOTH SIDES, SIMULTANEOUSLY.
FOOTINGS SUPPORTED ON NATURAL SOILS IMPROVED BY USING A RAMMED AGGREGATE PIER
(RAP) FOUNDATION SYSTEM.
CONCRETE WALLS RETAINING EARTH MUST HAVE REACHED 100 PERCENT OF THEIR
REQUIRED 28 DAY COMPRESSIVE STRENGTH BEFORE BACKFILLING OPERATIONS BEGIN.
STRUCTURAL SLABS AND SLABS ON GRADE, PROVIDING TOP AND BOTTOM SUPPORT
FOR CONCRETE WALLS RETAINING EARTH, MUST BE IN PLACE AND HAVE REACHED 70
PERCENT OF THEIR REQUIRED 28 DAY COMPRESSIVE STRENGTH BEFORE
BACKFILLING OPERATIONS BEGIN.
PLACE FOOTINGS THE SAME DAY EXCAVATIONS ARE OPENED. IF THIS IS NOT
POSSIBLE, ADEQUATELY PROTECT THE EXPOSED MATERIAL IN THE BASES OF THE
FOOTING EXCAVATIONS FROM ANY DETRIMENTAL CHANGE IN CONDITION SUCH AS
FROM DISTURBANCE, RAIN OR FREEZING. SURFACE RUNOFF SHALL NOT BE ALLOWED
TO ENTER THE EXCAVATIONS.
REINFORCING STEEL BENDS, HOOKS AND LAP SPLICES SHALL CONFORM TO THE ACI
"BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" (ACI 318-05) UNLESS
OTHERWISE INDICATED.
PROVIDE STANDEES FOR THE SUPPORT OF TOP REINFORCEMENT FOR FOOTINGS AND MATS.
SEE SECTION 032000, CONCRETE REINFORCEMENT, OF THE PROJECT MANUAL FOR SHOP
DRAWING PREPARATION REQUIREMENTS.
PRECAST CONCRETE
DESIGN SEISMIC LOADS
DESIGN WIND LOADS
CONCRETE
REINFORCING STEEL
GEOTECHNICAL DESIGN LIVE LOADS
NOTES:
PRECAST CONTRACTOR:1.
PRECAST DOUBLE TEESA.
PRECAST SPANDRELS
PRECAST LIGHTWALLS
PRECAST COLUMNS
PRECAST WALL PANELS
SUPPLY PRECAST COLUMN ANCHOR BOLTS AND EMBEDDED PLATES
FOOTINGS
CAST-IN-PLACE RETAINING WALLS
CAST-IN-PLACE COLUMNS
SLABS ON GRADE
CAST-IN-PLACE CONCRETE WASHES AS DETAILED ON
DRAWINGS, INCLUDING ANY NECESSARY FORMWORK
INSTALLATION OF COIL RODS AND DOWELS FOR CONNECTION
TO CAST-IN-PLACE COMPONENTS
INSTALLATION OF PRECAST COLUMN AND WALLS, ANCHOR BOLTS AND EMBEDDED PLATES
B.
C.
D.
E.
F.
G.
H.
A.
B.
C.
E.
F.
G.
CAST-IN-PLACE CONCRETE CONTRACTOR:2.
SCOPE BREAKDOWN
D.
12.
STRUCTURAL STEEL
WITH TABLE 4 OF THE "SPECIFICATION FOR STRUCTURAL JOINTS
8.THE QUANTITY AND SIZE OF THE RAMMED AGGREGATE PIERS (RAP) UNDER EACH FOOTING OR
MAT SHALL BE DETERMINED NY THE RAP FOUNDATION DESIGNER AND INSTALLED BY A
CERTIFIED RAP CONTRACTOR. RAP FOUNDATION SYSTEM SHALL MEET A MINIMUM ALLOWABLE
SOIL BEARING PRESSURE OF 6000 PSF.
NON-STRUCTURAL CONCRETE MASONRY WALLS (EXTERIOR CLADDING)
ALL CONNECTIONS FOR PRECAST COMPONENTS INCLUDING
TEMPORARY CONNECTIONS (INCLUDES ALL CONNECTION
HARDWARE, BEARING PADS, BOLTS AND WELDS AS REQUIRED)
SUPPLY COIL RODS FOR CONNECTION FROM PRECAST TO
CAST-IN-PLACE WASHES
SPECIFIED COMPRESSIVE STRENGTH OF MASONRY, f'm = 2000 PSI
CONCRETE MASONRY
UNITS:...........................
MORTAR:.................
GROUT:..................
NORMAL WEIGHT, ASTM C90, TYPE 1.
MINIMUM COMPRESSIVE STRENGTH OF UNITS
= 2800 PSI
TYPE 'S' IN ACCORDANCE WITH ASTM C270 SHALL
BE USED ON ALL MASONRY WALLS.
PROPORTIONED IN ACCORDANCE WITH ASTM
C476. GROUT SHALL ATTAIN A MINIMUM
COMPRESSIVE STRENGTH OF 2500 PSI AT 28 DAYS.
ALL BARS IN SLAB ON GRADE AND FIELD WASH/TOPPING SLABS ON
PRECAST SHALL BE EPOXY COATED.
ALL FOUNDATIONS HAVE BEEN DESIGNED FOR AN ALLOWABLE NET
BEARING PRESSURE (A.N.B.P.) OF 4000 PSF. SEE GEOTECHNICAL
REPORT FOR ADDITIONAL INFORMATION.
CONCRETE TOPPING SLABS
AND WASHES5000 PSID 6 1 1/2%+-
6 1 1/2%+-
6 1 1/2%+-
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S001
GENERAL NOTES
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA1
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
F.S.
PLAN NOTES:
TOP OF FIRST LEVEL SLAB ELEVATION = 100'-0". USGS ELEVATION 828.50 = 100'-0"
DENOTES COLUMN FOOTING MARK. SEE S300 FOR COLUMN
FOOTING SCHEDULE, NOTES AND TYPICAL FOUNDATION DETAILS.
FOOTINGS BASED ON 4000 PSF ALLOWABLE BEARING CAPACITY.
DENOTES FOOTING STEP. SEE DETAIL 1/S300 (TYPICAL WALL FOOTING
STEPS).
1.
2.
3.
4.
FX
A
B
1 2
C
3 4 5 6 7
10 1/2"48' - 0"24' - 0"36' - 0"36' - 0"24' - 0"48' - 0"1' - 1 1/2"
218' - 0"2' - 3 1/2"61' - 9"61' - 9"3' - 1 1/2"128' - 11"WF7WF7
F17F17
F40 F16
PRECAST WALL
PANEL, TYP
1
S303
WF7WF2.5WF12
WF6
WF7 WF6WF7WF6L.E. 97' - 3 1/8"
T.W. 99' - 0"
L.E. 97' - 4 1/8"
T.W. 99' - 0"
L.E. 97' - 1 7/8"
BASE MAT
12" THICK CONCRETE MAT
WITH #7 AT 12" TOP AND
BOTTOM, EACH WAY
T.W. 100' - 3"
T/MAT
EL 92' - 6"
1
S301
2
S301
3
S301
T.W. 99' - 0"
T.W. 99' - 0"
L.E. 97' - 3 1/8"
T.W. 99' - 4"
L.E. 97' - 2 1/8"
T.W. 99' - 0"
T.W. 99' - 0"
T.W. 99' - 0"
T.W. 99' - 0"
L.E. 97' - 4 1/8"
T.W. 99' - 0"
4
S301
5
S301
5
S301
6
S301
1
S303
2
S303
T.F. 92' - 6"
T.F. 95' - 9"F.S.F.S.2' - 0"6' - 0"
T.F. 99' - 0"F.S.F.S.6' - 0"
2' - 6 3/8"
T.F. 95' - 9"
3
S301
6
S301
2
S301
6
S301
7
S301
8
S301
2' - 9"11"1' - 2"1' - 2"2' - 3"1' - 11"1' - 5"8"20' - 8 1/2"26' - 0"6' - 8 1/2"8' - 0"
1' - 6"7' - 0"7' - 0"
28' - 2"4' - 3"5' - 3"5' - 5 1/2"6' - 7"8"10"9' - 5"4"7 5/8"
11' - 10"10"20' - 1"1"1' - 2"5"1"9' - 9"10"8"1"10"19' - 3"10"10"19' - 2"10"1"1"9' - 9"10"8' - 8"9"8"7 5/8"8' - 0 3/8"10"8"HATCHED AREA INDICATES
AREA OF SLAB LEFT OUT
FOR CRANE PATH
3' - 0"T.W. 99' - 0"WF3SIM
WF4WF3WF320' - 0"20' - 0"7' - 0"7' - 0"
12' - 2 1/4"
L.E. 97' - 0 3/8"
T.W. 100' - 0"
L.E. 97' - 0 3/8"L.E. 99' - 0"
LEDGE
SLOPED
2' - 8 3/4"
WF5WF4 T.P. 96' - 4"
10
S301
9
S301
T.W. 99' - 4"
WF7WF2.5REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S100S
FOUNDATION
PLAN
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 1/8" = 1'-0"
FOUNDATION PLAN NORTH
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
PLAN NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
FOR GENERAL NOTES DESIGN INFORMATION AND CONCRETE
SCHEDULE, SEE DRAWING S001.
INDICATES TOP OF WALL ELEVATION.
INDICATES TOP OF LEDGE ELEVATION.
EXISTING CONSTRUCTION: VERIFY ALL EXISTING DIMENSIONS,
ELEVATIONS, AND CONDITIONS BEFORE PROCEEDING WITH NEW
CONSTRUCTION TO PREVENT UNDERMINING OF EXISTING
CONSTRUCTION. NOTIFY THE ARCHITECT/ENGINEER OF ANY ISSUES
WITH EXISTING CONSTRUCTION/NEW CONSTRUCTION INTERFACE
BEFORE PROCEEDING WITH WORK IN THE AREA UNDER QUESTION. SEE
DRAWING S100 EXISTING CONDITIONS NOTES FOR ADDITIONAL
INFORMATION.
TOP OF FIRST LEVEL SLAB ELEVATION = 100'-0". USGS ELEVATION 828.50'
= 100' - 0"
SEE ARCHITECTURAL AND PLUMBING DRAWINGS FOR LOCATIONS OF
FLOOR DRAINS CAST IN CONCRETE SLAB AND FOR FLOOR SLAB
DRAINAGE REQUIREMENTS.
SEE ARCH DRAWINGS FOR LOCATIONS OF CMU WALLS. SEE DETAILS ON
DRAWING S400 FOR INFORMATION.
SLAB ON GRADE: 5" THICK CONCRETE UNLESS NOTED OTHERWISE. SEE
DETAILS ON DRAWING S310 FOR TYPICAL SLAB CONSTRUCTION.
INDICATES CONSTRUCTION JOINT IN SLAB ON GRADE. SEE
DETAIL 2/S310.
C.J.
A
B
1 2
C
3 4 5 6 7
48' - 0"24' - 0"36' - 0"36' - 0"24' - 0"48' - 0"
216' - 0"61' - 9"61' - 9"123' - 6"F.S.PRECAST WALL
PANEL, TYP
1
S303
1
S301
2
S301
3
S301
4
S301
5
S301
6
S301
2
S303
7
S301
TOP OF 5" SLAB
ON GRADE
TOP OF 5" SLAB
ON GRADE
TOP OF 5" SLAB
ON GRADE
TOP OF 5" SLAB
ON GRADE C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.C.J.RAMP UP
28" PRECAST DOUBLE TEEWITH 3" FIELD TOPPING SLAB28" PRECAST DOUBLE TEEWITH 3" FIELD TOPPING SLABPRECAST DOUBLE
LEDGER BEAM
12" PRECAST
SHEAR WALL
PRECAST DOUBLE
LEDGER BEAM
12" PRECAST
LITE WALL
12' - 0"11' - 0 7/8"13 SPA AT 12'-0" = 156' - 0"11' - 4 1/8"11' - 8 3/4"12' - 0"
24" x 24" PRECAST
COLUMN
24" x 24" PRECAST
COLUMN9 SPA AT 6' - 3" = 56' - 3"P/C SHEAR CONNECTOR,
SEE NOTE 5
10" PRECAST WALL/SPANDREL
LOAD BEARING
8" PRECAST WALL
9" PRECAST WALL
9" PRECAST WALL
10" PRECAST
WALL/SPANDREL
8" PRECAST WALL
9" PRECAST WALL
8" PRECAST WALL
9" PRECAST WALL
10" PRECAST WALL/SPANDREL
LOAD BEARING
10" PRECAST
WALL/SPANDREL
SIM
10
S301
9
S301
EL 100' - 0"
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S101
SLAB ON GRADE
PLAN
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 1/8" = 1'-0"
SLAB ON GRADE PLAN NORTH
T.W.
T.L.
ADDED PRECAST TEES AND
ASSOCIATED INFORMATION.
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
A
B
1 2
C
3 4 5 6 7
216' - 0"
48' - 0"24' - 0"36' - 0"36' - 0"24' - 0"48' - 0"123' - 6"61' - 9"61' - 9"RAMP DOWN RAMP UP
RAMP UP RAMP DOWN
28" PRECAST DOUBLE TEEWITH 3" FIELD TOPPING SLAB28" PRECAST DOUBLE TEEWITH 3" FIELD TOPPING SLABPRECAST DOUBLE
LEDGER BEAM
12" PRECAST
SHEAR WALL
PRECAST DOUBLE
LEDGER BEAM
12" PRECAST
LITE WALL
12' - 0"11' - 0 7/8"13 SPA AT 12'-0" = 156' - 0"11' - 4 1/8"11' - 8 3/4"12' - 0"
24" x 24" PRECAST
COLUMN
24" x 24" PRECAST
COLUMN2' - 0"9 SPA AT 6' - 3" = 56' - 3"2' - 0"P/C SHEAR CONNECTOR,
SEE NOTE 5
10" PRECAST WALL/SPANDREL
LOAD BEARING
8" PRECAST WALL
9" PRECAST WALL
9" PRECAST WALL
10" PRECAST
WALL/SPANDREL
8" PRECAST WALL
9" PRECAST WALL
8" PRECAST WALL
9" PRECAST WALL
10" PRECAST WALL/SPANDREL
LOAD BEARING
10" PRECAST
WALL/SPANDREL
3' - 10" x 1' - 4""
PRECAST COLUMN
2
S500
154' - 0 7/8"
8' - 0"8' - 0"3
S500 9' - 8 1/4"3' - 9 3/8"3' - 9 3/8"3' - 9"3' - 9"3' - 11 1/2"3' - 11 1/2"6' - 0 5/8"6' - 0 5/8"8' - 0"1' - 6 3/8"3' - 0 3/8"5' - 10 3/8"5' - 10 3/8"6' - 0"6' - 0"6' - 0"6' - 0"6' - 0"6' - 0"6' - 3 1/8"5' - 10 1/2"6' - 3 1/4"6' - 0"6' - 0"6' - 0"6' - 0"6' - 0"6' - 0"6' - 10 1/4"5' - 1 7/8"4' - 8 3/4"6' - 5 1/4"6' - 5 1/4"6' - 0 1/8"6' - 0 1/8"
3' - 7 3/8"
3' - 7 3/8"9' - 11 1/8"HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4HSS8x4x1/4C15x33.9C15x33.9
HSS8x4x1/4
HSS8x4x1/4
HSS8x4x1/4
HSS8x4x1/4
HSS8x4x1/4
HSS8x4x1/4
HSS8x4x1/4
HSS8x4x1/4
HSS8x4x1/4
HSS8x4x1/4
HSS8x4x1/4
C15x33.9
C15x33.9HSS8x4x1/4
HSS8x4x1/4
2
S500
3
S500
A A8' - 0"2
S500
SIM
3
S500
SIM
S500
4
S500
4
S500
4
REFER TO S10X SERIES DRAWINGS FOR DESIGN INFORMATION, CONCRETE
SCHEDULE, AND GENERAL NOTES PERTAINING TO FOUNDATIONS,
CONCRETE, REINFORCING STEEL, AND STRUCTURAL STEEL.
PRECAST CONTRACTOR SHALL PROVIDE AND INSTALL SHEAR CONNECTORS
AT SPACING SHOWN AT ALL DOUBLE TEE JOINTS. CONNECTORS SHALL HAVE
AN ALLOWABLE SHEAR CAPACITY (WITH TENSION) OF AT LEAST 8k EACH.
STANDARD: JVI VECTOR CONNECTOR.
PRECAST DOUBLE TEES SHALL HAVE FULL FIELD PLACED TOPPING SLAB, 3"
MINIMUM THICKNESS WITH 6x6 - W4.0 x W4.0 WELDED WIRE FABRIC. ALL
WALLS AND EDGES SHALL HAVE 3'-0" WIDE x 3" HIGH WASH WITH (4) #5 BARS,
CONTINUOUS. SEE TYPICAL PRECAST DOUBLE TEE PROFILE ON S350.
INDICATES OPENING IN SLAB. VERIFY SIZE AND LOCATIONS
WITH M.E.P. CONTRACTOR.
INDICATES 8" C.M.U. WALL FROM BELOW TO UNDERSIDE
OF PRECAST. SEE TYPICAL DETAILS ON S400.
PLAN NOTES:
1.
INDICATES TOP OF TOPPING SLAB SPOT ELEVATION, EXCLUSIVE
OF PERIMETER WASH.
INDICATES TOP ELEVATION OF LEVEL SLAB.
2.xxx'-xx"
3.F.D.INDICATES FLOOR DRAIN.
4.PROJECT REFERENCE ELEVATION 100'-0" = 815.10' U.S.G.S.
5.
6.
7.
8.
INDICATES SPAN OF 1 1/2", 20 GAGE ROOF DECK.9.
INDICATES TRAFFIC BEARING MEMBRANE. SEE ARCHITECTURAL
DRAWINGS AND DECK WATERPROOFING SPECIFICATIONS.
10.
A
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S102
SECOND LEVEL
PLAN
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 1/8" = 1'-0"
SECOND LEVEL PLAN NORTH
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
A
B
1 2
C
3 4 5 6 7
48' - 0"24' - 0"36' - 0"36' - 0"24' - 0"48' - 0"
216' - 0"61' - 9"61' - 9"123' - 6"RAMP DOWN RAMP UP
RAMP UP RAMP DOWN
28" PRECAST DOUBLE TEEWITH 3" FIELD TOPPING SLAB28" PRECAST DOUBLE TEEWITH 3" FIELD TOPPING SLABPRECAST DOUBLE
LEDGER BEAM
12" PRECAST
SHEAR WALL
PRECAST DOUBLE
LEDGER BEAM
12" PRECAST
LITE WALL
12' - 0"11' - 0 7/8"13 SPA AT 12'-0" = 156' - 0"11' - 4 1/8"11' - 8 3/4"12' - 0"
24" x 24" PRECAST
COLUMN
24" x 24" PRECAST
COLUMN2' - 0"9 SPA AT 6' - 3" = 56' - 3"2' - 0"P/C SHEAR CONNECTOR,
SEE NOTE 5
10" PRECAST WALL/SPANDREL
LOAD BEARING
8" PRECAST WALL
9" PRECAST WALL
9" PRECAST WALL
10" PRECAST
WALL/SPANDREL
8" PRECAST WALL
9" PRECAST WALL
8" PRECAST WALL
9" PRECAST WALL
10" PRECAST WALL/SPANDREL
LOAD BEARING
10" PRECAST
WALL/SPANDREL
2
S500
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S103
THIRD LEVEL PLAN
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANANORTH
1/8" = 1'-0"
THIRD LEVEL PLAN
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
A
B
1 2
C
3 4 5 6 7
48' - 0"24' - 0"36' - 0"36' - 0"24' - 0"48' - 0"
216' - 0"61' - 9"61' - 9"123' - 6"RAMP DOWN
TO LEVEL 2
RAMP UP
RAMP UP
TO LEVEL 4
RAMP DOWN
28" PRECAST DOUBLE TEEWITH 3" FIELD TOPPING SLAB28" PRECAST DOUBLE TEEWITH 3" FIELD TOPPING SLABPRECAST DOUBLE
LEDGER BEAM
12" PRECAST
SHEAR WALL
PRECAST DOUBLE
LEDGER BEAM
12" PRECAST
LITE WALL
24" x 24" PRECAST
COLUMN
24" x 24" PRECAST
COLUMN
P/C SHEAR CONNECTOR,
SEE NOTE 5
10" PRECAST WALL/SPANDREL
LOAD BEARING
8" PRECAST WALL
9" PRECAST WALL
9" PRECAST WALL
10" PRECAST
WALL/SPANDREL
8" PRECAST WALL
9" PRECAST WALL
8" PRECAST WALL
9" PRECAST WALL 2' - 0"9 SPA AT 6' - 3" = 56' - 3"2' - 0"12' - 0"11' - 0 7/8"13 SPA AT 12'-0" = 156' - 0"11' - 4 1/8"11' - 8 3/4"12' - 0"
10" PRECAST WALL/SPANDREL
LOAD BEARING
10" PRECAST
WALL/SPANDREL
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S104
FOURTH LEVEL
PLAN
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANANORTH
1/8" = 1'-0"
FOURTH LEVEL PLAN
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
A
B
1 2
C
3 4 5 6 7
48' - 0"24' - 0"36' - 0"36' - 0"24' - 0"48' - 0"
216' - 0"61' - 9"61' - 9"123' - 6"RAMP DOWN
TO LEVEL 2
28" PRECAST DOUBLE TEEWITH 3" FIELD TOPPING SLAB10" PRECAST
SPANDREL/WALL
12" PRECAST
SHEAR WALL
12" PRECAST
LITE WALL
24" x 24" PRECAST
COLUMN
24" x 24" PRECAST
COLUMN
P/C SHEAR CONNECTOR,
SEE NOTE 5
10" PRECAST WALL/SPANDREL
LOAD BEARING
8" PRECAST WALL
9" PRECAST WALL
9" PRECAST WALL
10" PRECAST
WALL/SPANDREL
8" PRECAST WALL
9" PRECAST WALL
8" PRECAST WALL
9" PRECAST WALL
9 SPA AT 6' - 3" = 56' - 3"REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S105
FIFTH LEVEL PLAN
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANANORTH
1/8" = 1'-0"
FIFTH LEVEL PLAN
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
TYPICAL WALL
REINFORCEMENT
SEE WALL SECTIONS
TYPICAL WALL
REINFORCEMENT
SEE WALL SECTIONS
CORNER
BARS
CLASS B
SPLICE
WALL REINFORCEMENT
(BOTH FACES)
CORNER
BARS
CLASS B
SPLICE
CORNER
BARS
CLASS B
SPLICE
WALL REINFORCEMENT
(MIDDLE)
WALL REINFORCEMENT
(INSIDE FACE)
TYPICAL WALL
REINFORCEMENT
SEE WALL SECTIONS
TYPICAL WALL
REINFORCEMENT
SEE WALL SECTIONS
#4
#4
#4
#4
#4#4
TYPICAL WALL
REINFORCEMENT
SEE WALL SECTIONS
TYPICAL WALL
REINFORCEMENT
SEE WALL SECTIONS
PROVIDE CORNER BARS AS SHOWN. MATCH HORIZONTAL WALL REINFORCEMENT IN BAR SIZE AND SPACING.
SEE APPLICABLE SECTIONS FOR REINFORCING STEEL CLEARANCES.
TERMINATE HORIZONTAL WALL REINFORCEMENT 2" CLEAR FROM END WALL
GRADE BEAMS: PROVIDE CORNER BARS FOR LONGITUDINAL REINFORCEMENT IN GRADE BEAMS AT CORNERS
(WHERE THERE IS NO CONCRETE PIER) AS SHOWN IN THE ABOVE DETAIL "WALL REINFORCEMENT BOTH FACES".
NOTES:
1.
2.
3.
4.O"IF OPTIONAL JOINT IS
NOT USED, OMIT DOWELS,
AND PROVIDE STANDARD
90˚ END HOOKS ON
THESE BARS
LAP SPLICE AS
INDICATED IN THE
SCHEDULE (AS
REQUIRED)
DOWELS TO MATCH
HORIZONTAL WALL
REINFORCEMENT IN
SIZE AND SPACING
(TYPICAL)
OPTIONAL JOINT OPTIONAL JOINT
2" CLR STANDARD HOOK
HORIZONTAL
REINFORCEMENTSTANDARD HOOK
WALL REINFORCEMENT
(MIDDLE)
WALL REINFORCEMENT
(BOTH FACES)
SEE APPLICABLE SECTIONS FOR WALL REINFORCEMENT AND REINFORCING STEEL CLEARANCES.1.
NOTES:
CONSTRUCTION JOINT
HORIZONTAL WALL
REINFORCEMENT
CONTINUOUS THROUGH
CONSTRUCTION JOINT
THIS DETAIL APPLIES ONLY TO WALLS WITHOUT VERTICAL
CONTROL JOINTS. SEE TYPICAL VERTICAL WALL CONTROL
JOINT DETAIL FOR CONSTRUCTION JOINTS IN WALLS WITH
VERTICAL CONTROL JOINTS.
1.
NOTES:
PLAN VIEW
PLAN VIEW
1" AT FACE OF WALL
1 1/2" CLR
SEE NOTE 1
CUT EVERY OTHER
HORIZONTAL BAR
(EACH FACE AT
CONTROL JOINT)
HORIZONTAL
REINFORCING
VERTICAL
REINFORCING
PROVIDE VERTICAL CONTROL JOINTS IN WALLS (W.C.J.) W HERE INDICATED ON
PLANS, WITH UNIFORM SPACING ALONG THE LENGTH OF WALL.
LOCATE VERTICAL CONSTRUCTION JOINTS IN WALLS WITH VERTICAL CONTROL
JOINTS AT CONTROL JOINT LOCATIONS.
FORM FOR CONTROL JOINT MAY BE LEFT IN PLACE ON SIDE WITH BACKFILL.
EXTEND CONTROL JOINT FROM TOP OF FOOTING TO TOP OF WALL UNLESS
OTHERWISE INDICATED.
1.
2.
3.
4.
NOTES:
1 1/2" CLR
1/2" AT BACK OF STRIP
REMOVABLE BEVELLED
FORM
EXPOSED
FACE
SEE NOTE 3
2" CLR STANDARD 90 DEG HOOK
2'-0" TYPICAL OR PROVIDE
(2) #5
1 EACH FACE
(2) #5 x 4'-0"
1 EACH FACE
(2) #5 x 4'-0"
1 EACH FACE
(2) #5
1 EACH FACE
(2) #5
1 EACH FACE
AT BOTTOM OF
OPENING
(2) #5 x 4'-0"
1 EACH FACE
(2) #6
1 EACH FACE
AT TOP OF
OPENING
(2) #5 x 4'-0"
1 EACH FACEOPENINGOPENING
WHERE VERTICAL REINFORCEMENT IS INTERRUPTED BY THE OPENING, PROVIDE ONE-HALF
OF THE INTERRUPTED BARS (FULL LENGTH( ON EACH SIDE OF THE UPENING IN PLACE
OF THE (2) #5 INDICATED.
CIRCULAR OPENINGS: PROVIDE ONLY THE REINFORCEMENT DETAILED ELSEWHERE.
THIS DETAIL APPLIES TO OPENINGS IN CONCRETE WALLS, UNLESS DETAILED OTHERWISE.
1.
2.
3.
NOTES:
ELEVATION
SEE FOUNDATIONS SECTION OF THE GENERAL NOTES FOR
PREPARATION REQUIREMENTS FOR EARTH BEARING MATERIALS.
1.
NOTES:2" CLR3"
CLRT2"
CLR(1) #5 x 4'-0" ADDITIONAL IN
CONCRETE WALL FOR EACH
MAT OF REINFORCING STEEL
WALL FOOTING
REINFORCEMENT,
SEE SECTIONS
2
1 T3" CLRFOOTING STEP (F.S.), SEE FOUNDATION PLAN FOR
TOP OF FOOTING ELEVATIONS AND LOCATIONSF.S.F.S.F.S.CONCRETE WALL CONCRETE FOOTING
PLAN
TIES (TYP.)
1 1/2" CLR. TO
3" CLR.4"8"PLACEMENT TIES
(SEE NOTES 2 AND 3)
1/2 TYPICAL TIE SPACING
(MAXIMUM)
SEE NOTE 1
PROVIDE STANDARD 90° HOOK
ON DOWELS OR 3" CLEAR WHERE
HOOK LENGTH IS LIMITED BY
FOOTING SIZE.
SEE FOUNDATION PLAN
FOR TOP OF FOOTING
ELEVATION
SEE CONCRETE COLUMN DETAILS
OR SCHEDULE ON DRAWING S340
FOR COLUMN INFORMATION
SEE COLUMN FOOTING
SCHEDULE FOR FOOTING
INFORMATION
1.PROVIDE FOOTING DOWELS THE SAME SIZE AND SPACING AS VERTICAL
COLUMN REINFORCEMENT.
2.PROVIDE ADDITIONAL PLACEMENT TIES SPACED AT 12" IN FOOTINGS
3'-0" OR MORE IN THICKNESS.
3.PROVIDE INTERMEDIATE CROSS TIES WITH PLACEMENT TIES TO MATCH
COLUMN DETAIL TIE ARRANGEMENT WITHIN FOOTING.
NOTES:
MECHANICAL TENSION BUTT SPLICE
SEE CONCRETE COLUMN DETAILS
OR SCHEDULE (SEE NOTE 5)
TYPICAL TIE SPACING
SEE CONCRETE COLUMN
SCHEDULE
TYP.
3" CLR.
4.A = 2'-0" FOR 1/2 OF VERTICAL BARS
A = 4'-0" FOR 1/2 OF VERTICAL BARS
5.SEE DIVISION 3 OF THE SPECIFICATIONS FOR MECHANICAL TENSION BUTT
SPLICE STANDARDS.SEE NOTE 4ASEE COLUMN SCHEDULE
COLUMN FOOTING
1' - 6"1' - 6"8"3" CLR3" CLR(3) #5 x 3'-0"
WALL FOOTING
REINFORCEMENT,
SEE SECTIONS
SEE FOUNDATION PLAN
FOR TOP OF FOOTING
WALL FOOTING,
SEE SECTIONS
COLUMN & WALL FOOTINGS PLACED SEPARATELY 3" CLR3" CLRWALL FOOTING
REINFORCEMENT,
SEE SECTIONS
SEE FOUNDATION PLAN
FOR TOP OF FOOTING
WALL FOOTING,
SEE SECTIONS
COLUMN & WALL FOOTINGS PLACED MONOLITHICALLY
2' - 0"
1' - 0"
SEE FOOTING SCHEDULE
COLUMN FOOTING 1' - 0"
2' - 0"
(CONTRACTORS OPTION)
FOOTING NOTES:
1.COMPACT ENGINEERED FILL SUPPORTING FOOTINGS TO 98 PERCENT MODIFIED MAXIMUM DRY DENSITY
(ASTM D 1557)
2.COLUMN AND WALL FOOTINGS HAVE BEEN DESIGNED FOR AN ALLOWABLE NET BEARING PRESSURE OF
6000 PSF AND 5000 PSF RESPECTIVELY. THE GEOTECHNICAL ENGINEERING TESTING FIRM SHALL VERIFY THAT
THE SOIL BEARING CAPACITY IS ACCEPTABLE AT EACH COLUMN FOOTING AND AT 8'-0" INTERVALS ALONG
WALL FOOTINGS AT THE INDICATED BEARING ELEVATIONS. SOIL MODIFICATION WITH AGGREGATE PIERS HAS
BEEN ASSUMED TO ACHIEVE 6000PSF BEARING.
3.CENTER COLUMN AND WALL FOOTINGS UNDER THE COLUMN OR WALL ABOVE UNLESS OTHERWISE INDICATED.
4.PLACE FOOTINGS IN WOOD FORMS. UNLESS IT CAN BE SHOWN THAT FOOTING EXCAVATIONS ARE ADEQUATELY
STABLE.
5.SEE GENERAL NOTES FOR CONCRETE 28 DAY COMPRESSIVE STRENGTH.
6.SEE GENERAL NOTES FOR REINFORCING STEEL GRADE.
7.PROVIDE CLASS B LAP SPLICES FOR LONGITUDINAL WALL REINFORCEMENT.
8.PROVIDE #4 TRANSVERSE BARS AT 6'-0" ON CENTER FOR WALL FOOTINGS, TO BE POSITIONED ON TOP OF THE
LONGITUDINAL BARS, TO HOLD THEM SECURELY IN PLACE.
9.SEE TYPICAL COLUMN FOOTING DETAILS AND CONCRETE COVER REQUIREMENTS FOR REINFORCEMENT
AND FOR INFORMATION REGARDING COLUMN AND PIER DOWELS, AND PLACEMENT TIES.
10.SEE TYPICAL COLUMN FOOTING DETAILS AND ANCHOR ROD PLACEMENT DETAILS FOR CONCRETE COVER
REQUIREMENTS FOR PLACEMENT AND FOR INFORMATION REGARDING EMBEDMENT OF ANCHOR RODS.
11.SEE CONCRETE SCHEDULE AND GENERAL NOTES PERTAINING TO FOUNDATIONS, CONCRETE AND
REINFORCING STEEL.
MARK
COLUMN FOOTING SCHEDULE
SIZE BOTTOM
REINFORCEMENT REMARKS
F16
F17
(16) - #9 E.W.
(17) - #10 E.W.
16'-0" x 16'-0" x 4'-0"
17'-0" x 17'-0" x 4'-0"
F40 (40) - #10 x13'-6"
(16) - #8x39'-6"40'-0" x 14'-0" x 3'-6"
MARK
WALL FOOTING SCHEDULE
WIDTH x DEPTH BOTTOM
REINFORCEMENT REMARKS
WF2.5
WF3
2'-6" x 1'-6"
3'-0" x 1'-6"
(4) - #5 LONGITUDINAL
#5 AT 12" TRANSVERSE
(4) - #5 LONGITUDINAL
#5 AT 12" TRANSVERSE
WF6 6'-0" x 2'-0"(6) - #5 LONGITUDINAL
#7 AT 12" TRANSVERSE
WF7 7'-0" x 2'-0"(7) - #5 LONGITUDINAL
#7 AT 12" TRANSVERSE
WF8 8'-0" x 2'-3"(7) - #5 LONGITUDINAL
#8 AT 12" TRANSVERSE
WF12 12'-0" x 3'-3"(15) - #6 LONGITUDINAL
#9 AT 12" TRANSVERSE
WF5 5'-0" x 1'-6"(5) - #5 LONGITUDINAL
#6 AT 12" TRANSVERSE
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S300
TYPICAL
FOUNDATION
DETAILS
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 1/2" = 1'-0"
TYPICAL CORNER REINFORCEMENT FOR WALLS2 1/8" = 1'-0"
TYPICAL CONCRETE WALL INTERSECTIONS3 1" = 1'-0"
TYPICAL VERTICAL WALL CONSTRUCTION JOINT4
1" = 1'-0"
TYPICAL VERTICAL WALL CONTROL JOINT5 1/8" = 1'-0"
TYPICAL REINFORCING AT WALL OPENING6
1" = 1'-0"
TYPICAL WALL FOOTING STEP DETAIL1
3/8" = 1'-0"
TYPICAL CONCRETE COLUMN AT FOOTING7
1/4" = 1'-0"
TYPICAL COLUMN / WALL FOOTING INTERSECTION9 1/4" = 1'-0"
TYPICAL COLUMN / WALL FOOTING INTERSECTION10
# DESCRIPTION DATE
T.F. 99' - 0"
T.F. 92' - 6"1' - 0"T.W. 99' - 0"
#4 AT 12"
#5 AT 9"3" CLR2" CLR5" SLAB ON GRADE
PRECAST
CONCRETE WALL
#3 TIES AT 48"
EACH WAY
16' - 7"11"
T.W. 99' - 0"
T.F. 92' - 6"
PRECAST WALL
2' - 7"#4 AT 12"
#5 AT 9"
#3 TIES AT 48"
EACH WAY
10"1"
T.F. 99' - 0"
PRECAST WALL
2' - 7"1' - 7"
#4 AT 12"
#5 AT 9"
#3 TIES AT 48"
EACH WAY
11"8"2' - 0"1"10"
T/MAT 92' - 6"
7 5/8"
CMU WALL
EMBED PLATE,
COORDINATE WITH
PRECAST SUPPLIER 5"T/MAT 92' - 6"
T.W. 100' - 3"
SLAB ON GRADE
#5 AT 6"
#5 AT 12"2' - 0"SEE S400 FOR CMU
WALL REINFORCING
2" CLR
PRECAST WALL
10"
T.W. 99' - 0"
T/SLAB 100' - 0"
SLAB ON GRADE
T/FTG SEE PLAN
PRECAST WALL
3"2' - 7"10"8"
1' - 6"
1"9"1"10"
T/SLAB 99' - 0"
SLAB ON GRADE
#4 AT 12"
#5 AT 9"
#3 TIES AT 48"
EACH WAY
#4 AT 12"
#5 AT 9"
#3 TIES AT 48"
EACH WAY
T/MAT 92' - 6"
1"1' - 4"8"
T.W. 99' - 0"
T.P. 96' - 4"
T/MAT 92' - 6"
LEAVE OUT SLAB
RX WATERSTOP, TYPDBR, TYP
#5 AT 6"
#5 AT 12"
SLAB ON GRADE
T.W. 99' - 4"
JOINT FILLLER,
AND SEALANT
TOPPING SLAB
ON PRECAST
3"2' - 7"5"3"7 5/8"
2" CLR
7
1"10"2' - 9"
T.P. 96' - 4"
T.W. 99' - 0"
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S301
FOUNDATION
DETAILS
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 3/4" = 1'-0"
SECTION1 3/4" = 1'-0"
SECTION2 3/4" = 1'-0"
SECTION3 3/4" = 1'-0"
SECTION4
3/4" = 1'-0"
SECTION5
3/4" = 1'-0"
SECTION6
3/4" = 1'-0"
SECTION7
3/4" = 1'-0"
SECTION8 3/4" = 1'-0"
SECTION10
3/4" = 1'-0"
SECTION9
1
1
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
2 1/4" MIN. EMBEDMENT
2' - 0"1' - 4"1/2" DIA. DRILLED-IN
ANCHORS (3 PER SIDE)
GALVANIZED GRATING:
1/8" x 1 1/4" BEARING BARS AT 1 3/16"
4" CROSS BAR SPACING (PROVIDE
UNDER SECTION 055000 METAL
FABRICATIONS, OF THE PROJECT
MANUAL)
L3x2x1/4 LLV (GALV)
ANCHORED TO 2 SIDES
OF SUMP PIT TO
SUPPORT GRATING
(2) 3/4" DIA. EXPANSION
ANCHORS AT 12"
REINFORCEMENT
NOT SHOWN
2"2"L4x4x5/16 ELEVATOR
SILL ANGLE
(CONTINUOUS FULL
LENGTH OF HOISTWAY)
T/SLAB EL. VARIES
(SEE PLAN)
NON-SHRINK GROUT
AND ERECTION SHIMS
BY PRECAST SUPPLIER
EMBEDDED WELD
PLATES BY
PRECAST SUPPLIER
PRECAST WALL
GRADE
TOP/FOOTING
EL PER PLAN
(4) #5, CONTINUOUS
10"
3' - 0"VARIES2" WASHSEE PLAN
#4 AT 12"SEE SCHEDULE3" CLRC
SEE PLAN SEE SCHEDULE2" WASHVARIES1'-0"
6" 6"2'-2" 3" 3"
8"1'-1"1"1/2"VARIES2" CLR3" CLR2" WASH3'-0"SEE PLAN1"2"TOP/SLAB EL
VARIES, SEE PLAN
EQUAL
(4) - #5 AT 3",
WALL
PRECAST LIGHT
DOWELS TO MATCH WALL VERTICALS,
#5 AT 12"
#7 AT 12"
#4 AT 12" HORIZONTAL, EACH FACE
#3 TIES AT 48" O.C.
EACH DIRECTION
DOUBLE TEE
EQUAL
EMBEDDED PLATE AND WELD
PLATE CONNECTION BY
PRECAST SUPPLIER
CONTINUOUS TOP OF P/C AT
RAMP PER PLAN
TOP/FOOTING
EL PER PLAN
BACKFILL WITH FREE
DRAINING GRANULAR
MATERIAL DOWN TO
FOOTING PER RECOMMENDATIONS
OF GEOTECHNICAL REPORT
6"(MAX.)(MAX.)
T/WALL EL
PER PLAN
T/SLAB EL
PER PLAN
LAP PER TABLE 1, SEE S100
1 1/2" CLR 1 1/2" CLR
3'-0"
(TYP, U.N.O.)(TYP, U.N.O.)EMBEDDED WELD PLATES, SHIMS
AND GROUT BY PRECAST SUPPLIER
3'-0" WASH
1" CLR.BOND BREAKER
3'-0"
L
#6 AT 12"
(7)-4 TOP
SEE FOOTING SCHEDULE FOR
BOTTOM REINFORCEMENT
SEE FOOTING SCHEDULE FOR
BOTTOM REINFORCEMENT
1' - 2"
BENTONITE
WATERSTOP
(4 SIDES)
#6 AT 8" TOP
AND BOTTOM
(SHORT DIRECTION)#5 AT 12"
TOP AND BOTTOM
(LONG DIRECTION)
#5 AT 12"
VERT.
#5 AT 12"
HORIZ., TYP
NOTE:
2.* VERIFY PIT SIZE AND DEPTH AND SUMP PIT SIZE AND LOCATION WITH
ELEVATOR SUPPLIER.
SEE PLAN FOR
SLAB ON GRADE
THICKNESS
1.WALL REINFORCEMENT INDICATED IS TYPICAL FOR ALL 4 SIDES OF ELEVATOR PIT.
2'-0" x 2'-0" x 1'-6"
SUMP PIT BEYOND;
PROVIDE 1 1/2" x 1
1/2" NOTCH FOR
GRATING
(2) #4, TYP
#4 AT 12"
3'-6"
TOP/CAST-IN-PLACE
WALL PER PLAN
AND PRECAST WALL LOCATIONS
9" PRECAST WALL
EMBEDDED PLATES, SHIMS
AND GROUT BY PRECAST SUPPLIER
BOND BREAKER
SEE FOUNDATIONPLAN FOR TOP OF MATSEE FOUNDATION PLAN
FOR ELEVATOR PIT LAYOUT DIMENSIONS*
2'-0".11/2"
2" CLR.2" CLR.1 1/2" CLR.3" CLR2" CLRSEE PLANSEE PLAN7
10"8' - 8"1' - 5"7 5/8"7' - 2 3/8"10"1"
SUMP PIT,
SEE 1/S302
2' - 0"2' - 0"5
S302
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S302
FOUNDATION
DETAILS
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 3/4" = 1'-0"
ELEVATOR SUMP PIT DETAIL1 1 1/2" = 1'-0"
ELEVATOR SILL ANGLE2 3/4" = 1'-0"
SECTION3
3/4" = 1'-0"
SECTION6 3/8" = 1'-0"
SECTION5
1/4" = 1'-0"
PLAN - ELEVATOR PIT4
1 1
11
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
7
5" SLAB ON GRADE
PRECAST CONCRETE, TYP
10"1"
1"9"
T.W. 99' - 0"T.W. 99' - 0"
T/SLAB 100' - 0"2' - 7"T/SLAB 100' - 0"
#4 AT 12"
#5 AT 9"
#3 TIES AT 48"
EACH WAY
#4 AT 12"
#5 AT 9"
#3 TIES AT 48"
EACH WAY
S303
3
AT SIM
CONDITION
7
5" SLAB ON GRADE
PRECAST CONCRETE, TYP
T.W. 99' - 0"T.W. 99' - 0"
T/SLAB 100' - 0"T/SLAB 100' - 0"
1"10"1"9"
T/MAT 92' - 6"
SLAB ON GRADE
#4 AT 12"
#5 AT 9"
#3 TIES AT 48"
EACH WAY
#4 AT 12"
#5 AT 9"
#3 TIES AT 48"
EACH WAY
SLAB ON GRADE
JOINT FILLLER,
AND SEALANT
TOPPING SLAB
ON PRECAST
3"5"T.W. 99' - 4"
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S303
FOUNDATION
DETAILS
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 3/4" = 1'-0"
SECTION1
3/4" = 1'-0"
SECTION2
3/4" = 1'-0"
SECTION3
1
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
SLAB ON GRADE:
SEE GENERAL NOTES
SHEET FOR CONCRETE
MIX REQUIREMENTS
SEE CONCRETE GENERAL NOTES AND DIVISION 3 OF THE
SPECIFICATIONS FOR SLAB FINISHING AND CURING REQUIREMENTS.
REFER TO GEOTECHNICAL REPORT FOR FILL MATERIALS, COMPACTION
REQUIREMENTS, METHODS, AND FIELD QUALITY CONTROL.
1.
2.
NOTES:5"PROVIDE MINIMUM OF 6" LAYER
OF FREE DRAINING GRANULAR
FILL MATERIAL, SEE NOTE 2
SLAB ON GRADE:
SEE GENERAL NOTES
SHEET FOR CONCRETE
MIX REQUIREMENTS
2"SEE NOTE 2
LOCATE CONSTRUCTION JOINTS AT CONTROL JOINT LOCATIONS.
APPLY LIQUID BONDBREAKER TO FULL DEPTH OF CONSTRUCTION JOINT.
1.
2.
NOTES:5"4"JOINT TO BE TOOLED
AND SEALED
CONTINUOUS 2x4
SHEAR KEY
SEE 1/S310 FOR
ADDITIONAL
INFORMATION
SLAB ON GRADE:
SEE GENERAL NOTES
SHEET FOR CONCRETE
MIX REQUIREMENTS
COORDINATE TOOLING OF JOINT WITH SEALANT MANUFACTURER.
(1/2" MAXIMUM RADIUS)
1.
NOTES:5"1 1/4" MINIMUM1/4" MAXIMUM
TOOLED AND SEALED
CONTROL JOINT
T4 (3/4" MIN)SLAB ON GRADE PRECAST TOPPING SLAB
WELDED WIRE
FABRIC CONTINUOUS
ACROSS JOINT PRECAST DOUBLE
TEE SLAB 2"T (3" MIN)1 1/2" CLRTOOLED AND SEALED
CONTROL JOINT CENTERED
OVER ALL PRECAST JOINTS
FELT STRIP
MASONRY WALL, SEE ARCHITECTURAL
DRAWINGS FOR LOCATION AND EXTENT
6" COMPACTED FREE DRAINING
GRANULAR MATERIAL
SLAB ON GRADE
PROVIDE THICKENED SLAB UNDER MASONRY WALLS NOT SUPPORTED
BY A FOOTING.
1.
NOTES:
6"
THICKNESS
WALL 6"6"1
2
EDGE OF SLAB WHERE
MASONRY WALL OCCURS
AT EDGE OF SLAB
3/4"TOP OF SLAB
ELEVATION
AT DRAIN
6" FREE DRAINING
GRANULAR MATERIAL
DRAIN, SET PRIOR
TO CONCRETE POUR
PIPE
COLUMN ISOLATION SECTION. MINIMUM THICKNESS TO MATCH THICKNESS OF ADJACENT
SLAB ON GRADE.
PROVIDE JOINT FILLER BETWEEN COLUMN ISOLATION SECTIONS AND SLAB ON GRADE PER
SECTIONS. PREPARE AND SEAL JOINT AS SPECIFIED IN DIVISION 7 OF THE PROJECT
MANUAL.
PROVIDE JOINT FILLER BETWEEN WALL AND SLAB ON GRADE. PREPARE AND SEAL JOINT AS
SPECIFIED IN DIVISION 7 OF THE PROJECT MANUAL.
"C.J." DENOTES CONTROL JOINT IN SLAB ON GRADE. SEE DETAIL 3/S310 (TYPICAL SLAB ON
GRADE CONTROL JOINT).
1.
2.
3.
4.
NOTES:
NOTE 1
SLAB ON GRADE
C.J.C.J.C.J.CONTROL OR
CONSTRUCTION
JOINT ON COLUMN
CENTERLINES, TYP
NOTE 3
NOTE 1
NOTE 1
NOTE 1 2" CLR, TYPNOTE 2 NOTE 2
NOTE 3 NOTE 22" CLR, TYPNOTE 2
8"8"1' - 0"3' - 6"SEE PLAN4"1 1/2" CLR3/16
3"GALVANIZED STEEL
PIPE SLEEVE
(HSS7.5x0.375)
(1) - #4 x 3'-0" EACH
SIDE OF PIPE
(1) - #4 x 3'-0" EACH
SIDE OF PIPE
1
2
(4) - 3/4" DIA x 6" LONG
HEADED STUDS
SEAL JOINT
FILL PIPE WITH
CONCRETE
6" DIA STANDARD WEIGHT
STEEL PIPE (ASTM A53)
PAINTED YELLOW
WASH
STRUCTURAL SLAB OR SLAB
ON GRADE PER PLAN
SEAL JOINT
EPOXY COATED #4 DOWELS AT
CORNERS AND AT 2'-0" MAX. ENTIRE
PERIMETER. DRILLED IN DOWELS
WITH 3" EMBEDMENT ALLOWED AT
CONTRACTOR'S OPTION
2" CLR. AT SLAB ON GRADE
1 1/2" RADIUS
PLANSEEPLANSEE.1' - 0"2D
BONDBREAKER
EITHER OF TWO CONSTRUCTION METHODS SHOWN IS ACCEPTABLE.
SEE SLAB ON GRADE PLAN AND ARCHITECTURAL PLAN AND ELEVATIONS
EXTENT AND LOCATION OF DEPRESSED SLAB AREAS
1.
2.
NOTES:
6" FREE DRAINING
GRANULAR FILL
1' - 0"2D
6" FREE DRAINING
GRANULAR FILL
SLAB DEPRESSION D
(12" MAXIMUM).SLAB DEPRESSION D
(12" MAXIMUM).CONNECTION BY
PRECASTER
PRECAST STAIR
5"7"2' - 0"
(4)-#6 CONTINUOUS
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
03/28/17
S310
TYPICAL SLAB ON
GRADE DETAILS
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 1 1/2" = 1'-0"
TYPICAL SLAB ON GRADE CONSTRUCTION1 1 1/2" = 1'-0"
TYPICAL SLAB ON GRADE CONSTRUCTION JOINT2 1 1/2" = 1'-0"
TYPICAL SLAB ON GRADE CONTROL JOINT DETAIL3 1 1/2" = 1'-0"
TYPICAL THICKENED SLAB AT MASONRY WALL4
1 1/2" = 1'-0"
TYPICAL FLOOR DRAIN5 3/8" = 1'-0"
TYPICAL ISOLATION JOINT DETAIL AT COLUMNS6 1" = 1'-0"
TYPICAL BOLLARD DETAIL AT SLAB ON GRADE7 1" = 1'-0"
TYPICAL CONCRETE CURB / ISLAND DETAIL8
1" = 1'-0"
TYPICAL FLOOR RECESS9 1" = 1'-0"
THICKENED SLAB AT PRECAST STAIR BASE10
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
AA3/4"1' - 8"1' - 8"3/4"1/2"1/2"6"6"6"1 1/2" CLR1 1/2" CLR5"1' - 4 7/16"11 9/16"3"3"1 1/2" CLR1 1/2" CLR1"1' - 0"1' - 0"1"
2' - 6" (TYP)
BEARING PAD BY
PRECAST SUPPLIER
PRECAST DOUBLE
LEDGER BEAM
#4 BAR x 6'-6"
AT 2'-0" O.C.
EMBEDDED BARS AND/OR
EMBEDDED WELD PLATE,
CONNECTIONS BY PRECAST
SUPPLIER
WELDED WIRE FABRIC
PER PLAN, TYP
(INCLUDES JOINT)
3' - 0" NOMINAL 6' - 0"
(INCLUDES JOINT)
3' - 0" NOMINAL
12' - 0" (INCLUDES JOINT)2' - 7"3" TOPPING SLAB2" SLAB2' - 2" STEMSEE PLAN
SECTION A - A
2' - 7"5"2' - 2" STEM2" SLAB3" TOPPING SLAB3" WASH.18' - 0".18' - 0"
DAPPED
BEARING
UNDAPPED
BEARING
6" WIDE x 4" HIGH
BLOCKOUT. ALIGN WITH
TOP OF STEM (TYP)
CAST-IN-PLACE
CONCRETE
WASH (TYP)
3" MINIMUM THICKNESS
FIELD TOPPING SLAB
SIDE ELEVATION
EMBEDDED PLATE
AND WELD PLATE
CONNECTION BY
PRECAST SUPPLIER
WELDED WIRE FABRIC
PER PLAN, TYP
3' - 0" WASH
6"1 1/2" CLR1 1/2" CLRSEAL JOINT
PRECAST
WALL
CAST-IN-PLACE
WASH/TOPPING SLAB
(4) #5 BARS
AT 3" CONTINUOUS
PRECAST
DOUBLE TEE
3' - 0" WASH
10"
PRECAST
WALL/SPANDREL
EMBEDDED PLATE AND
WELD PLATE CONNECTION
BY PRECAST SUPPLIER
1/2"
PRECAST DOUBLE TEE
BEARING PAD BY
PRECAST SUPPLIER1" CLRSEAL
JOINT
1 1/2" CLRWELDED WIRE FABRIC
PER PLAN, TYP
#5 CONTINUOUS
PAST COLUMNS
REINFORCING STEEL BETWEEN
COLUMNS LAP WITH COIL ROD INSERTS
#5 BARS CONTINOUS AT 3", SEE PLAN
CAST-IN-PLACE
WASH/TOPPING SLAB
2' - 7"5"SEE PLAN SEAL JOINT
BARS PER PLAN
CAST-IN-PLACE
WASH/TOPPING SLAB
WELDED WIRE FABRIC
PER PLAN, TYP
EMBEDDED PLATE
AND WELD PLATE
CONNECTION BY
PRECAST SUPPLIER
1/2"PRECAST DOUBLE
LEDGER BEAM
10"
BEARING PAD BY
PRECAST SUPPLIER
PRECAST WALL
6"
3' - 0" WASH
TOOL AND SEAL JOINTDOOR JAMB
BEYOND
ELEVATION OF
ADJACENT FLOOR
OR STAIR
BARS AT 3" CONTINUOUS DIRECTLY ON TEE SLAB FOR
WIDTH OF DOOR OPENING ONLY. RAISE BACK UP TO 1"
CLR EITHER SIDE AS SOON AS WASH IS DEEP ENOUGH
FOR 1 1/2" TOP CLR (BARS SHALL NOT BE LAPPED
WITHIN 2'-0" OF FLAT AREA)
WASH BEYOND
CAST-IN-PLACE WASH/TOPPING
SLAB, WARP AT DOOR OPENING
TO MATCH ADJACENT FLOOR
ELEVATIONS
PRECAST DOUBLE TEEDOOR OPENINGDOOR JAMB
BEYOND
ELEVATION OF
ADJACENT FLOOR
OR STAIR
DOOR OPENING3' - 0" WASH
6"1/2" CLRWARP WASH AS NECESSARY
TO MEET ADJACENT FLOOR
ELEVATION AT DOOR
BARS AT 3" CONT
SEE PLAN
WASH BEYOND
CAST-IN-PLACE
WASH/TOPPING SLAB1 1/2" CLRPRECAST
DOUBLE TEE
#4 x 2'-6" AT 12"
2" CLR
WELDED WIRE FABRIC
PER PLAN, TYP
1' - 0"3' - 0" WASH
P/C SPANDREL
EMBEDDED PLATE AND
WELD PLATE CONNECTION
BY PRECAST SUPPLIER
BEARING PAD BY
PRECAST SUPPLIER 3"3"2"10"1"
9"3' - 0" WASH
P/C SPANDREL
EMBEDDED PLATE AND
WELD PLATE CONNECTION
BY PRECAST SUPPLIER
BEARING PAD BY
PRECAST SUPPLIER 3"3"2"10"9"3' - 0" WASH
7' - 0"3"3"TOPPING SLAB
#5 x 5'-0" AT 6" O.C.
(3)-#5 HORIZONTAL
PRECAST TEE
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
10/13/16
S370
PRECAST
FRAMING
SECTIONS &
DETAILS
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 3/4" = 1'-0"
SECTION3
1/2" = 1'-0"
TYPICAL PRECAST DOUBLE TEE PROFILE7
3/4" = 1'-0"
SECTION5
3/4" = 1'-0"
SECTION1
3/4" = 1'-0"
SECTION6
3/4" = 1'-0"
SECTION8 3/4" = 1'-0"
SECTION9
3/4" = 1'-0"
SECTION2
3/4" = 1'-0"
SECTION4
1" = 1'-0"
SECTION10
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
FOR ALL OPENINGS AND RECESSES IN BOTH INTERIOR AND EXTERIOR NON-LOAD BEARING WALLS
NOT SHOWN ON STRUCTURAL DRAWINGS. PROVIDE THE FOLLOWING LINTELS:
LINTEL SCHEDULE NOTES:
SEE ARCHITECTURAL PLANS, ELEVATIONS AND DETAILS, ETC, FOR LINTEL ELEVATIONS AND CLEAR
OPENINGS, ETC.
PROVIDE STEEL LINTELS WHERE SPECIFICALLY INDICATED AND FOR OPENINGS LARGER THAN
COVERED BY THE LINTEL SCHEDULE.
ALL MASONRY BEARING STEEL LINTELS SHALL BE ANCHORED WITH (1) 3/4" x 0'-4" HOOKED ANCHOR
BOLT AT EACH END INTO GROUT. PROVIDE SLOTTED HOLES IN LINTEL.
LINTELS WITH CLEAR SPAN OPENING OF 6'-0" OR LARGER, PROVIDE 100 PERCENT GROUT FILL FROM
FOOTING (OR FLOOR BELOW) TO LINTEL BEARING.
LINTELS WITH CLEAR SPAN OPENING LESS THAN 6'-0", PROVIDE SOLID OR GROUTED MASONRY TO A
MINIMUM DEPTH OF 2'-8" BELOW THE LINTEL BEARING.
ALL LINTELS SHALL BE CENTERED ON WALL THICKNESS, UNLESS OTHERWISE NOTED. BOTTOM LINTEL
PLATE SHALL BE SHOP WELDED TO BEAM.
ANCHOR MASONRY, ENCASING STEEL LINTEL BEAMS, WITH CHANNEL SLOTS AND ANCHORS, WELD CHANNEL
SLOTS TO EACH SIDE OF BEAM WEB AT 32" O.C. PROVIDE ONE LONGITUDINAL ROW FOR BEAMS UP TO 18"
IN DEPTH AND 2 ROWS FOR DEEPER BEAMS.
ALL LINTELS EXPOSED TO WEATHER SHALL BE GALVANIZED.
CONTINUOUS PLATE CONNECTED TO LINTEL BOTTOM FLANGE SHALL BE PROVIDED FOR THE FULL LENGTH
OF THE LINTEL, UNLESS NOTED OTHERWISE.
A.
B.
C.
D.
E.
F.
G.
H.
I.
1.STEEL LINTELS:
2.CMU BLOCK LINTEL:
REINFORCE LINTEL BLOCK AS INDICATED IN THE "CONCRETE BLOCK LINTEL SCHEDULE" FOR THE WALL
THICKNESS AND CLEAR SPAN.
FILL WITH CONCRETE OR GROUT ( NOT MORTAR).
JOINTING SHALL BE AS ADJACENT WALL.
MINIMUM BEARING ON MASONRY WALL IS 8" EACH END, BUT NOT LESS THAN 1" OF BEARING PER FOOT WIDTH
OF OPENING SPAN.
LINTEL SHALL BE SHORED FOR 28 DAYS.
PROVIDE 100 PERCENT GROUT FILL FROM FOOTING (OR FLOOR BELOW) TO LINTEL BEARING.
CONTRACTOR HAS THE OPTION TO PROVIDE PRECAST CONCRETE LINTELS WITH SAME DIMENSIONS AND
REINFORCING GIVEN IN LINTEL SCHEDULE FOR CONDITIONS CONCEALED BY ARCHITECTURAL FINISHES.
A.
B.
C.
D.
E.
F.
G.
USE WHERE MASONRY WALL IS EXPOSED IN A FINISHED ROOM.
3.OPENING IN BRICK (NEW AND EXISTING)
PROVIDE LOOSE LINTEL LXxXxX FOR OPENINGS UP TO 6'-0" WIDE. AT OPENINGS GREATER THAN 6'-0" PROVIDE
SHELF ANGLE WITH 8" BEARING EACH END BOLTED TO CMU BACKUP. SEE DETAIL BELOW.
SEE ARCHITECTURAL AND MEP DRAWINGS FOR SIZE AND LOCATIONS OF PENETRATIONS IN NEW AND
EXISTING BRICK. PROVIDE LINTELS FOR ALL PENETRATIONS LARGER THAN 1'-4".
A.
B.
CMU LINTEL
GROUT SOLID
SEE SCHEDULE
1/2" DIAMETER GALVANIZED
ADHESIVE ANCHOR AT 2'-0"
O.C. 4 1/2" EMBEDMENT
LXxXxX GALVANIZED SHELF ANGLE
BEARING LENGTH = 8" AT EACH END
LINTEL SCHEDULE
LIGHT WEIGHT BLOCK NON-BEARING WALLS
*NOMINAL BLOCK DIMENSION
MARK
WALL*
THICK
LINTEL*
HEIGHT
BOTTOM
REINF.
MAXIMUM
CLEAR SPAN SECTION
L1 6 8
L2 8 8
L3 8 16
(1) #5
(1) #6
(2) #4
(2) #6
(2) #4
(2) #6
4'-8"
4'-8"
5'-4"
5'-4"
9'-0"
10'-8"
TYPE A
TYPE A
TYPE B
REINFORCE
PER SCHEDULE
TYPE "A"1' - 4"FILL BOTH UNITS
WITH GROUT AT
THE SAME TIME
BREAK WEBS
OUT TO ALLOW
PLACEMENT
OF (2) #33"REINFORCE
PER SCHEDULE
USE SUPPORTS TO HOLD BARS
IN PROPER POSTION
TYPE "B"
USE LINTEL SECTION THAT COINCIDES WITH OPENING CLEAR SPAN UNLESS OTHERWISE NOTED ON THE
BUILDING ELEVATIONS.
THE SCHEDULE ABOVE APPLIES ONLY TO LINTELS SUPPORTING MASONRY IN RUNNING BOND.
PROVIDE LINTELS FOR ANY OPENING GREATER THAN 1'-4" TO BE CUT INTO EXISTING CMU WALL IN
ACCORDANCE WITH THE SHCEDULE ABOVE. SHORE WALL ABOVE AS REQUIRED UNTIL NEW LINTEL IS
INSTALLED. SEE ARCHITECTURAL AND MEP DRAWINGS FOR SIZE AND LOCATIONS OF PENETRATIONS.
SEE 500 SERIES DRAWINGS FOR ADDTIONAL MISCELLANEOUS STEEL REQUIRED FOR LARGE OPENINGS.
1.
2.
3.
4.
NOTES:7 5/8"3"1 1/2"(2) #3
VERTICAL REINF:
TYPE I: #5 AT 24"
TYPE II: #5 AT 48"
(1) #5
(1) #5
(2) # 5
C.J.
(1) # 5
(1) #5
ATTACH WALL TO STRUCTURE FRAMING ABOVE SEE TYPICAL
ATTACHMENT DETAILS. (2) #5 AT NEXT TO TOP COURSE WALLS
AND AT LEVEL OF ANY STRUCTURAL ATTACHMENTS.
FILL TOP COURSE WITH GROUT
PROVIDE 9 GAGE HORIZONTAL JOINT REINFORCEMENT AT 16" O.C.
REINFORCING SHOWN IS TYPICAL AT ALL WALLS UNLESS NOTED OTHERWISE
ON INDIVIDUAL BUILDING PLANS OR ELEVATIONS ON S54X SERIES DRAWINGS. SEE LINTEL
SCHEDULE FOR GROUT AND REINFORCING ABOVE OPENINGS.
LAP SPLICE HORIZONTAL JOINT REINFORCEMENT 12 INCHES.
DOWEL INTO FOUNDATIONS WITH SAME BAR SIZE AND SPACING. CONTRACTOR HAS OPTION
TO EMBED DOWELS DURING POUR.
C.J. INDICATES CONTROL JOINT. SEE TYPICAL CONTROL JOINT DETAIL. SEE PLANS AND
SPECIFICATIONS FOR ADDITIONAL CONTROL JOINT LAYOUT INFORMATION.
TYPE I WALLS ARE WALLS EXPOSED TO VEHICULAR TRAFFIC.
TYPE II WALLS ARE WALLS NOT DEFINED AS TYPE I WALLS.
1.
2.
3.
4.
5.
6.
7.
NOTES:
2' - 0"
(1) #5 AT ALL
ENDS OF WALL
AND EACH SIDE
OF CONTROL
JOINT
SEE SCHEDULESEE SCHEDULE
C.J.
#5 AT 8" DOWELS
AT TYPE I WALLS,
SEE 11/S400
VERTICAL BAR AT
ALL INTERSECTIONS
PREFABRICATED WIRE JOINT
REINFORCING AT 16" O.C.
LAP WITH TYPICAL CONTINUOUS
JOINT REINFORCING
PREFABRICATED WIRE JOINT
REINFORCING AT 16" O.C.
LAP WITH TYPICAL CONTINUOUS
JOINT REINFORCING
CONTRACTOR HAS THE OPTION TO USE LADDER
TYPE JOINT REINFORCEMENT
1 1/2" CLR3/4" CLRPROVIDE VERTICAL
REINFORCING AT ALL
CORNERS AND
INTERSECTIONS
USE REBAR POSITIONER
HAREWARE AT 8'-0" O.C.LAP SPLICECORNER BARS TO MATCH
SIZE OF HORIZONTAL
WALL REINFORCING
SEE INDIVIDUAL BUILDING PLANS FOR HORIZONTAL AND VERTICAL
REINFORCING STEEL REQUIREMENTS.
SEE GENERAL NOTES FOR REINFORCING STEEL CLEARANCES.
1.
2.
NOTES:
SINGLE HORIZONTAL BAR CONDITION LAP SPLICEBOND BEAM REINFORCING
DOUBLE HORIZONTAL BAR CONDITION
DOWELS TO MATCH AND
LAP WITH BOND BEAM
REINFORCING
WALL THICKNESSS WALL THICKNESS
USE REBAR POSITIONER
HAREWARE AT 8'-0" O.C.
LAP SPLICE STD. HOOK STD. HOOK LAP SPLICEGROUT CORE
FULL HEIGHT
INTERIOR OR
EXTERIOR CMU
INTERIOR
NON-LOAD
BEARING CMU
EXTERIOR
WALL
JOINT STABLIZATION
ANCHORS SEE
SPECIFICATIONS
VERTICAL BAR EACH SIDE OF
CONTROL JOINT (TYPICAL)GROUT SOLID
BUILDING PAPER BONDBREAKER
OPTION 1
OPTION 2
OPTION 3
CONTROL JOINT MATERIAL
SPECIAL CONTROL JOINT UNITS
DISCONTINUE HORIZONTAL JOINT REINFORCEMENT AND
BOND BEAM REINFORCEMENT AT CONTROL JOINTS
1.
NOTES:LAP SPLICE SCHEDULESEE MASONRY WALL1"L8x4x1/2 x 1'-0" (GALV) AT 48"
WITH (2) - 3/4" DIA. HILTI HY-150
(GALV), 3" MAX. DIA. OVERSIZE
HOLES IN ANGLE AND
OVERSIZED PLATE WASHER
BOND BEAM WITH (2) - #4 CONT,
SECOND BLOCK FROM TOP
PRECAST SLAB OR BEAM
(REINFORCING NOT SHOWN)
EMBED PLATE (GALV)
1/2"x12"x1'-0" @ 48"
WITH (4) - 3/4" DIA. HAS
AT CMU EXPOSED TO VEHICULAR
TRAFFIC PROVIDE #5 DOWELS AT
8", GROUT FIRST SIX COURSES
SOLID, CONTINUOUS. VERTICAL
DOWEL HEIGHT TO EXTEND TO
TOP OF 6TH COURSE.
#5 IN FULLY GROUTED CORES,
LAP WITH DOWELS. SEE
DETAIL 3/S400 FOR SPACING
GROUT SOLID OR PROVIDE
SOLID BLOCK AT EACH
ANCHOR LOCATION
HOOKED DOWEL OR DRILLED-
IN DOWELS.
MASONRY WALL
REINFORCING LAP
SPLICE SCHEDULE
#3
#4
#5
#6
#7
18"
24"
30"
36"
48"
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
TWL
JMP
10/13/16
S400
TYPICAL
MASONRY
DETAILS
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 1" = 1'-0"
LINTEL SCHEDULE NOTES1
1" = 1'-0"
LINTEL SCHEDULE2 1/4" = 1'-0"
TYPICAL CMU WALL REINFORCING3 1" = 1'-0"
TYPICAL HORIZONTAL JOINT REINFORCING DETAIL4
1" = 1'-0"
TYPICAL CMU WALL REINFORCEMENT5 1" = 1'-0"
TYPICAL CMU WALL REINFORCEMENT6 1" = 1'-0"
TYPICAL CONTROL JOINT DETAIL7
1" = 1'-0"
TYPICAL CONTROL JOINT DETAIL8 3/4" = 1'-0"
TYPICAL TOP AND BOTTOM CONNECTIONS9
1
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
36/7 PATTERN AT ALL
INTERMEDIATE SUPPORTS
5/8" DIAMETER
PUDDLE WELD
AT 6" O.C. (TYP)
S HE E T W ID TH
36" M A X IM U M
W E LD R E Q 'D A T
A LL S ID E LA P
S U P P O R T P O IN T S
(6) SIDELAP
CONNECTIONS
(#10 TEK SCREWS)
BETWEEN EACH
BEAM, TYPICAL
36/7 PATTER AT
ALL END LAP SUPPORT
POINTS AND BUILDING
PERIMETER (ONE WELD
PER 6" PARALLEL TO
DECK SPAN)
END LAPS SHALL OCCUR ONLY AT SUPPORT POINTS.
WELD THRU MULTIPLE SHEETS AT ALL ENDS AND SIDE LAPS.
DECK UNITS SHALL BE CONTINUOUS OVER AS MANY SPANS
AS THE STRUCTURAL STEEL LAYOUT WILL PERMIT.
1.
2.
3.
NOTES:
C
1" Ø ROD WITH NO. 3
CLEVIS AND TURNBUCKLES
3/4" PLATE
WOOD BLOCKING
1 1/2" ROOF DECK
PRECAST
CONCRETE
PANEL
SLOPE 1/4" / FT
HSS8x4x1/4C15x33.9,
SEE 10/S500
FOR SPLICE
1/4
TYP
3/4" PLATE
1/4
NOTE: SEE 3/S500 FOR TOP
CANOPY SUPPORT AT STEEL
COLUMN
6.6K
3.3K
6.6K
6.6K
(7' - 8" AT SIM)
8' - 0"
EL. 118' - 3 1/2"
T.B. 111' - 3"
(117' - 11 1/2 AT SIM)
45.00°
C
3/4" PLATE
WOOD BLOCKING
1 1/2" ROOF DECK
PRECAST
CONCRETE
PANEL
SLOPE 1/4" / FT
HSS8x4x1/4C15x33.9,
SEE 10/S500
FOR SPLICE
1/4
TYP
6.6K
3.3K
7
T.B. 111' - 3"
(7'-8" AT SIM)
8' - 0"
WELD ALL
SIDES
REVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
Author
Checker
04/13/17
S500
TYPICAL STEEL
DETAILS
Project
NumberSOUTH GARAGECARMEL REDEVELOPMENT COMMISSIONCARMEL, INDIANA 1" = 1'-0"
TYPICAL ROOF DECK FASTENING REQUIREMENTS1 3/4" = 1'-0"
SECTION2 3/4" = 1'-0"
SECTION3
1
1" = 1'-0"
DETAIL4
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
BASE MATERIAL
CONCRETE OR
CONCRETE BLOCK
GYPSUM
CONCRETE OR
CONCRETE BLOCK
GYPSUM
BASIS OF DESIGN: HILTI CONSTRUCTION CHEMICALS, INC.
PENETRATING ITEM
METAL PIPE
STEEL, COPPER, CONDUIT OR EMT
(SLEEVED OR UNSLEEVED)
STEEL, COPPER, CONDUIT OR EMT
STEEL, COPPER, CONDUIT OR EMT
STEEL, COPPER, CONDUIT OR EMT
STEEL, COPPER, CONDUIT OR EMT
(SLEEVED)
STEEL, COPPER, CONDUIT OR EMT
INSULATED METAL PIPES
STEEL, COPPER, CONDUIT OR EMT
W/ GLASSFIBER INSULATION
(SLEEVED OR UNSLEEVED)
STEEL, COPPER, CONDUIT OR EMT
W/ AB/PVC INSULATION
(SLEEVED OR UNSLEEVED)
STEEL, COPPER, CONDUIT OR EMT
PIPE W/ GLASSFIBER INSULATION
IN A SLEEVE
STEEL, COPPER, CONDUIT OR EMT
W/ GLASSFIBER INSULATION
STEEL, COPPER, CONDUIT OR EMT
W/ AB/PVC INSULATION
STEEL, COPPER, CONDUIT OR EMT
W/ GLASSFIBER INSULATION
(SLEEVED OR UNSLEEVED)
STEEL, COPPER, CONDUIT OR EMT
PIPE W/ GLASSFIBER INSULATION
IN A SLEEVE
FIRE RATING
3 HR
4 HR
1 OR 2 HR
1 OR 2 HR
2 HR
4 HR
2 HR
3HR
4 HR
1 OR 2 HR
1 OR 2 HR
1 OR 2 HR
4 HR
UL SYSTEM
NO.
CAJ 1155
CAJ 1226
WJ 1042
WL 1054
WL 1085
WL 1058
WL 1110
CAJ 5091
CAJ 5090
WJ 5029
WL 5029
WL 5028
WL 5025
WL 5073
APPROVED EQUALS: PRODUCT OF EQUIVALENT CHARACTERISTICS UL COMPLIANT WITH UL 1479 AND UL 2079, ASTM E1339.
BASIS OF DESIGN
HILTI PRODUCT
FS-ONE
FS ONE
FS ONE
FS ONE
FS ONE
FS ONE
FS ONE
FS ONE
FS ONE
FS ONE
FS ONE
FS ONE
FS ONE
W/ COLLAR
FS ONE
CONCRETE OR
CONCRETE
BLOCK
GYPSUM
CONCRETE OR
CONCRETE BLOCK
GYPSUM
JOINTS
CONCRETE BLOCK WALL TO METAL
DECK (TOP OF WALL)
GYPSUM WALL TO METAL DECK
(TOP OF WALL TO ROOF) D13/A601
(TOP OF WALL TO FLOOR)
PLASTIC & GLASS PIPE
PVC, CPVC (CLOSED SYSTEM ONLY)
PVC, CPVC , ABS, FRPP
GLASS PIPE
MAX 6" PVC, CPVC, ABS, FRPP
(IN A SLEEVE)
PVC, CPVC (CLOSED SYSTEM ONLY)
PVC, CPVC, ABS, FRPP
(CLOSED SYSTEM ONLY)
2 HR
1 OR 2 HR
1 OR 2 HR
3 HR
3 HR
3 HR
3 HR
1 OR 2 HR
1 OR 2 HR
HWD-0008
HWD-1011
HWD-1003/-1011
CAJ 2141
CAJ 2109
CAJ 2118
CAJ 2110
WL 2098
WL 2078
WL 2075
FS ONE
CP 601 OR
FS ONE
FS ONE
CP 642
FS ONE
CP 642
FS ONE
CP 642
FS ONE
GENERAL PROJECT NOTES
SCOPE DRAWINGS AND SPECIFICATIONS, AS DEFINED BY THE
INDIANA CONSTRUCTION INDUSTRY COUNCIL’S GUIDELINES,
A. THE CONTRACTOR SHALL OBSERVE THE FOLLOWING:
NOTHING SET FORTH IN THESE DRAWINGS SHALL RELEASE ANY
CONTRACTOR FROM RESPONSIBILITY TO PROVIDE APPROPRIATE
QUANTITIES, FIELD MEASUREMENTS, DIMENSIONAL STABILITY,
INSTALLATION, ANCHORAGE AND COORDINATION WITH OTHER
TRADES, OR WAIVE THE CONTRACTOR'S RESPONSIBILITY TO IDENTIFY
AND RESOLVE DEVIATIONS FROM THE REQUIREMENTS OF THE
CONTRACT DOCUMENTS, OR WAIVE THE CONTRACTOR'S
RESPONSIBILITY TO ALERT THE ARCHITECT TO ERRORS OR OMISSIONS
CONTAINED THEREIN.
CONTRACTOR SHALL VERIFY IN THE FIELD ALL EXISTING APPLICABLE
CONDITIONS AND DIMENSIONS SHOWN ON THE DRAWINGS AND
AS PERTINENT TO THE INTENT OF THESE DRAWINGS. ANY
DISCREPANCY DISCOVERED SHALL BE BROUGHT TO THE ATTENTION
OF THE ARCHITECT PRIOR TO THE COMMENCEMENT OF ANY WORK
AFFECTED BY, OR RELATED TO, SUCH DISCREPANCY.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS ASSOCIATED
WITH, OR CAUSED BY FAILURE TO COMPLY WITH REQUIREMENT.
CONTRACTOR SHALL REVIEW IN ADVANCE ALL PORTIONS OF THE
WORK TO VERIFY THAT THE WORK WILL NOT PROHIBIT COMPLETION
OF THE PROJECT AS INTENDED IN THESE CONTRACT DOCUMENTS.
ANY QUESTIONS SHALL BE PROMPTLY REFERRED TO THE ARCHITECT
FOR RESOLUTION.
CONTRACTOR SHALL REFER TO THE PROJECT MANUAL FOR CLEANING
AND DISPOSAL REQUIREMENTS.
CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL
SURFACES AND FINISHES AT INTERIOR AND EXTERIOR OF BUILDING.
DAMAGED SURFACES AND FINISHES RESULTING FROM THE
PERFORMANCE OF THE WORK SHALL BE REPAIRED AT NO COST TO THE
OWNER BY THE RESPONSIBLE CONTRACTOR TO MATCH EXISTING TO
THE SATISFACTION OF THE OWNER.
CONTRACTOR SHALL BECOME COMPLETELY FAMILIAR WITH ALL ASPECTS
OF THE WORK, EVEN THOSE AREAS DESIGNATED TO BE PROVIDED BY
OTHERS. THIS FAMILIARIZATION INCLUDES FULL AND COMPLETE
UNDERSTANDING OF THE WORK DESCRIBED ON ALL SHEETS OF THE
DRAWINGS AND IN ALL SECTIONS OF THE PROJECT MANUAL. FAILURE BY
THE CONTRACTOR TO BECOME COMPLETELY FAMILIAR AND COGNIZANT
OF ALL ASPECTS OF THE WORK SHALL NOT RELIEVE THE CONTRACTOR OF
THE RESPONSIBILITY TO PROVIDE MATERIALS, ASSEMBLIES, OR SERVICES
INDICATED IN THE CONTRACT DOCUMENTS.
B. THE CONTRACTOR SHALL PROVIDE THE FOLLOWING:
ALL MATERIAL AND EQUIPMENT OF INDUSTRY STANDARD QUALITY,
SPECIFIED OR NOT, AND WITH THE LIMITATION OF THE CONTRACT
DOCUMENTS TO CAUSE THE INSTALLATION TO FUNCTION IN
ACCORDANCE WITH THE INTENTION AND OBJECTIVE OF THE FINISHED
PROJECT.
ALL MATERIAL NECESSARY FOR EQUIPMENT TO FUNCTION IN A NORMAL
AND ACCEPTABLE MANNER.
ALL WORK REQUIRED TO CAUSE CONSTRACTOR’S OPERATIONS TO FIT
AND COORDINATE WITH OTHER TRADES.
ALL WORK REQUIRED TO COMPLY WITH GOVERNING CODES WITH
RESPECT TO CONSTRACTOR’S ACTIVITY, EXCEPT FOR DESIGN CRITERIA
INVOLOVING CAPACITIES AND BASIC DESIGN.
WHEN NOT INDICATED IN THE CONTRACT DOCUMENTS, THE SIZING OF
INTERCONNECT FACILITIES, SUCH AS DUCTS AND WIRING IN PIECES OF
EQUIPMENT IN ORDER TO UTILIZE THE SPECIFIED CAPACITIES OF THE
EQUIPMENT.
WHEN NOT INDICATED IN THE CONTRACT DOCUMENTS, THE
STANDARDS ESTABLISHED BY THE RECOGNIZED TRADE ASSOCIATION
HAVING JURISDICTION FOR THE PRODUCT INCLUDED IN THE PROJECT
SHALL GOVERN THE WORK.
ALL UNSPECIFIED FIXTURES, ACCESSORIES AND / OR EQUIPMENT
PROVIDED BY THE CONTRACTOR SHALL HAVE CUT SHEETS / DRAWINGS
SUBMITTED TO THE ARCHITECT FOR APPROVAL.
A. DO NOT SCALE THE DRAWINGS. REFER DISCREPANCIES TO
ARCHITECT FOR FINAL DECISIONS.
B. ALL DIMENSIONS SHOWN ARE TO FINISHED FACE OF WALL
UNLESS NOTED OTHERWISE. DIMENSIONS DESIGNATED AS
"CLR OR "CLEAR" INDICATE A CLEAR DIMENSION FROM FACE
OF FINISH TO FACE OF FINISH.
C. PROVIDE BRACING AND WOOD BLOCKING AS REQUIRED
IN WALLS SUPPORTING CASEWORK, DISPLAY BOARDS,
EQUIPMENT, RESTROOM ACCESSORIES, ETC.
D. SEAL ALL JOINTS BETWEEN DISSIMILAR MATERIALS.
E. ALL GYPSUM WALLBOARD IS 5/8" TYPE "X" UNLESS NOTED
OTHERWISE. PROVIDE MOISTURE AND MOLD RESISTANT
GYPSUM WALLBOARD IN WET AREAS AND EXTERIOR EXPOSURE
AREAS.
F. WHERE MOUNTING HEIGHTS ARE NOT INDICATED, MOUNT
INDIVIDUAL UNITS OF WORK AT INDUSTRY RECOGNIZED
STANDARD MOUNTING HEIGHTS, ADA AND ANSI A117.1 FOR
THE PARTICULAR APPLICATION AND REFER QUESTIONABLE
MOUNTING HEIGHT CHOICES TO ARCHITECT FOR FINAL
DECISIONS.
G. COORDINATE ENGINEERING DRAWINGS WITH ARCHITECTURAL
DRAWINGS AND FIELD CONDITIONS, AND REPORT
DISCREPANCIES IMMEDIATELY TO ARCHITECT.
H. CONFLICTS BETWEEN SPECIFICATIONS AND DRAWINGS SHALL BE
COMMUNICATED TO THE ARCHITECT FOR RESOLUTION PRIOR TO
COMMENCEMENT OF THE WORK.
I. SUPPLY, COORDINATE, AND INSTALL ACCESS DOORS, PANELS
AND HATCHES IN CEILINGS, WALLS, AND FLOORS; AND NOTIFY
ARCHITECT OF ANY CONFLICTS WITH FEATURES SHOWN ON
DRAWINGS.
J. PROVIDE WATER ROUGH-IN AND ELECTRICAL CONNECTIONS
FOR OWNER-PROVIDED EQUIPMENT IN COMPLIANCE WITH MEP
DRAWINGS.
K. PROVIDE SLIP CHANNELS AT ALL LOCATIONS WHERE WALLS
EXTEND TO A STRUCTURAL MEMBER ABOVE.
L. DOORS ARE TO BE INSTALLED 4" FROM CORNER TO EDGE OF
FRAME TYPICAL.
M. PROVIDE MINIMUM CLEAR HEAD SPACE OF 8'-4" ON FIRST FLOOR
OF GARAGE NORTH OF 3-LINE. REMAINDER OF GARAGE TO
HAVE 7'-2" MINIMUM CLEAR HEAD SPACE. COORDINATE
INSTALLATION HEIGHTS OF ALL MEP ITEMS.
GENERAL PLAN NOTES
EARTH
NOTE: PATTERNS SHOWN REPRESENT CUT MATERIALS IN PLAN OR SECTION, UNLESS NOTED OTHERWISE BELOW.
GRANULAR FILL
CAST-IN-PLACE
CONCRETE
PRECAST CONCRETE,
CAST STONE
CONCRETE MASONRY UNIT
BRICK MASONRY
STONE: LIMESTONE, GRANITE,
MARBLE OR AS NOTED
METAL: TYPE AS NOTED
METAL: ROLLED SHAPES
WOOD FRAMING / BLOCKING:
CONTINOUS
WOOD SHIM
FINISHED WOOD
SHOWN CUT AND ELEVATION
PLYWOOD
PARTICLEBOARD
EIFS
SPRAYED FIREPROOFING
SHOWN ON ROLLED SHAPE
BATT INSULATION: THERMAL OR
ACOUSTICAL, UNO
RIGID INSULATION: THERMAL,
ACOUSTICAL, OR SAFING
SHEATHING: GYPSUM, OR AS
NOTED
GYPSUM WALL BOARD
TILE: CERAMIC, QUARRY, UNO
RESINOUS FLOORING:
TERRAZO, TROWEL-ON, UNO
ACOUSTICAL CEILING TILE
GRATING
SHOWN IN PLAN
INSULATED GLASS:
(SMALL SCALE)
GRATING
MEMBRANE: WATERPROOF,
ROOF, DAMPPROOFING
AIR BARRIER SYSTEM
INSULATED GLASS:
(DETAIL)
TERRA COTTA, STRUCTURAL
CLAY TILE
CARPET, CARPET TILE (DETAIL)
SAND, GROUT
AS NOTED
GLASS FIBER REINFORCED
CONCRETE SIDING OR TRIM
ENGINEERED WOOD: GLUE
LAMINATED
PLASTER ON METAL LATH
WOOD FLOOR, WOOD
SHINGLES, OR SIDING
MATERIALS LEGEND
(DETAIL VIEWS)
(ELEVATION VIEWS)A101
1 SIM
1i
1'-0"
Room Name
XXXXX
DETAIL NUMBER
SHEET NUMBER
DETAIL CALLOUT
ELEVATION NUMBER
SHEET NUMBER
EXTERIOR ELEVATION TAG
SECTION NUMBER
SHEET NUMBER
SECTION MARKER
ATTRIBUTE
WALL TYPE
WALL TAG
CEILING TYPE
CEILING HEIGHT
CEILING TAG1
1
DOOR ID NUMBER
REFER TO DOOR SHEDULE SHEET
ROOM NAME
ROOM NUMBER
ROOM TAG
KEYED NOTE / PLAN NOTE
DEMOLITION NOTE
GLAZING TYPE
NEW CONSTRUCTION
EXISTING CONSTRUCTION
DEMOLISHED CONSTRUCTION
COL COLUMN GRID
CONTROL JOINT
SEALAND AND BACKER ROD
X WALL FINISH TAG
DENOTES DIFFERENT WALL
FINISH LOCATION
KIT OF PARTS NOTE
000000.00
TOILET ACCESSORYTX
FURNITURE / EQUIPMENT TAGFX
WINDOW TYPEX
GL-X
1/ A101
1
A101
ELEVATION NUMBER
SHEET NUMBER
INTERIOR ELEVATION TAG
SPEC SECTION REFERENCE
NOTE NUMBER
SYMBOLS LEGEND
1' - 0"3' - 6"33" TO 36"17" - 19"8"
GRAB BARS
TOILET PAPER DISPENSER
SANITARY NAPKIN DISPOSAL
WALL -MOUNTED OR FLOOR
MOUNTED WATER CLOSET
GRAB BARS
1' - 0"
3' - 0"34" MAX1' - 6"17" TO 19"1' - 3"
PIPE INSULATION FOR
ADA COMPLIANCE 29" MIN CLEAR40" MAX CLEAR3' - 0"1' - 6"42" MAX TO CONTROL3' - 5"1' - 6"42" MAX TO CONTROLTOILET ACCESSORY MOUNTING HEIGHTS
NOTE: REFER TO PROJECT MANUAL FOR COMPLETE TOILET ACCESSORY SPECIFICATIONS.
FIRE STOPPING SCHEDULE AND DETAILS
WALL CONSTRUCTION
FIRE SEAL MATERIAL AS
REQUIRED FOR FIRE RATING
FILLING ANNULAR SPACE
PENETRATING ITEM
CL.
CARPET
D.E.F.S.
CPT.
C.W.
C.M.
ACOUSTICAL
AMERICANS W/DISABILITIES ACT
AMERICANS W/DISABILITIES ACT
ARCHITECT/ENGINEER
C.I.P.
C.F.C.I.
B.O.W.
A.P.
A.V.
A/E
ADAAG
ADA
ACOUS.
FINISH(ED)
TBD TO BE DETERMINED
WELDED WIRE FABRIC
TEMPORARY
TEMPERED
TOP OF MASONRY
TOP OF DECK
TOP OF STEEL
VERIFY IN FIELD
VINYL COMPOSITION TILE
WIDE/WIDTH
WATER CLOSET
TECHNICAL
TOP OF CURB
TELEPHONE
TYPICAL
TOP OF WALL
TOP OF PAVEMENT
TONGUE AND GROOVE
UTILITY
UNIT VENTILATOR
VERTICAL
UNLESS NOTED OTHERWISE
WATER HEATER
WOOD
WITH
VESTIBULE
WEIGHT
ANGLE
MISCELLANEOUS
CENTER LINE
NUMBER
WITHOUT
#
W.W.F.
WD.
W.H.
WT.
W/O
FINISH OPENING
FLOOR
FLUORESCENTFLUOR.
F.O.
FLR.
W.C.
VIF
W
W
W/
VEST.
V.C.T.
UTIL.
U.N.0.
U.V.
V
VERT.
T&G
T.M.
T.S.
T.P.
TYP.
U
T.W.
T.D.
TMPRD.
TEMP.
T.C.
TECH.
TEL.
TACK BOARD
REFLECTED CEILING PLAN
REFERENCE
ROOF DRAIN
RADIUS
REFLECTED
RIGHT HAND
RESILIENT
ROOM
REINFORCED
ROUGH OPENING
SIMILAR
SHEET
SECTION
SOAP DISPENSER
SCHEDULE
SQUARE FEET
SQUARE
SPECIFICATION
SYMMETRICAL
SUSPEND(ED)
STRUCTURAL
STORAGE
STANDARD
STAINLESS STEEL
THICKNESS
CENTERLINE
E
FINISH SYSTEM
EXPOSED
ELECTRICAL CONTRACTOR
ELECTRICAL PANEL
EXTERIOR INSULATION
FAN COIL UNIT
AND EQUIPMENT
FURNISHINGS, FIXTURES
FINISH FLOOR ELEVATION
EACH
ELEVATION
EXPANSION JOINT
EQUAL
ENGINEER
ELEVATOR/ELEVATION
EXISTING
EXTERIOR
ELECTRIC WATER COOLER
EQUIPMENT
FABRICATE/FABRICATOR
FIRE EXTINGUISHER
FIRE HOSE CABINET
FLOOR DRAIN
FIRE EXTINGUISHER CABINET
ELECTRIC/ELECTRICAL
EXP.
F.F.&E.
FIN.
F.H.C.
F.F.E.
F.E.C.
F.E.
F
F.C.U.
FAB.
F.D.
EXT.
EQ.
EQUIP.
EXIST.
E.W.C.
E.P.
ENGR.
ELEV.
E.J.
EL.
ELEC.
E.I.F.S.
E.C.
EA.
SHT.
T.B.
SUSP.
SYM.
T
T.
SIM.
SQ.
S.S.
SPEC.
STRUCT.
STOR.
STD.
R.O.
S
S.D.
SECT.
SCHED.
S.F.
R.D.
REF.
REFL.
RESIL.
R.H.
RM
REINF.
COLD WATER
CONSTRUCTION MANAGER
DIRECT EXTERIOR
FINISH SYSTEM
COORDINATE
CONCRETE
COLUMN
CEILING
CONCRETE MASONRY UNIT
CONTRACTOR
CONTINUOUS
CERAMIC TILE
CONSTRUCTION
DETAIL
DEPARTMENT
DRINKING FOUNTAIN
DOWN
DIMENSION
DISPENSER
DRY MARKER BOARD
DIAMETER
DRAWING
DOWNSPOUT
D
DN
DWG.
DS
D.M.B.
DIM.
DISP.
DEPT.
DET.
D.F.
DIA.
CONT.
C.T.
COOR.
CONTR.
C.M.U.
CONC.
CONST.
COL.
CLG.
R.C.P.
R
R
A
AUDIO/VISUAL
ACCESS PANEL
BOTTOM OF WALL
CONTRACTOR FURNISHED-
CONTRACTOR INSTALLED
CAST-IN-PLACE
ADJUSTABLE
AIR CONDITIONING
ACOUSTICAL CEILING TILE
ALTERNATE
ALUMINUM
ABOVE FINISHED FLOOR
ARCHITECT/ARCHITECTURAL
BOARD
BASEMENT
BUILDING
BITUMINOUS
CABINET
CORNER GUARD
CONTROL JOINT
B
C
C.G.
C.J.
CAB.
BLDG.
BSMT.
BITUM.
BD.
ALUM.
ARCH.
A.F.F.
ALT.
A.C.T.
ADJ.
A/C
ACOUSTICAL CEILING PANELACP
CLEAR(ANCE)CLR
CMP COMPOSITE METAL PANEL
FIRE-RESISTIVEF-R
TOP OFT/O
B/O BOTTOM OF
ACCESSIBILITY GUIDELINES
STEELSTL.
M.D.F.
MB.
M.C.
PROPERTY LINE
OWNER FURNISHED-
OWNER INSTALLED
OWNER FURNISHED-
CONTRACTOR INSTALLED
LENGTH
MARKER BOARD
LONG LEG OUT
LONG LEG VERTICAL
LONG LEG HORIZONTAL
MECH./ELECT./PLUMBING
MEDIUM DENSITY FIBERBOARD
MECHANICAL CONTRACTOR
METAL
MECHANICAL
MAXIMUM
MINIMUM
MISCELLANEOUS
MANHOLE
MANUFACTURER(ING)
MASONRY OPENING
NUMBER
NOT TO SCALE
NOT IN CONTRACT
NO APPLIED FINISH
ON CENTER
OVER ALL
OPENING
OPPOSITE HAND
OUTSIDE DIAMETER
PLASTER
PAIR
PARTICLE BOARD
PLYWOOD
PREFABRICATED
PLASTIC LAMINATE
QUARRY TILE
PAINTED
POUND
LAVATORY
LEFT HAND
Q
Q.T.
P. LAM
PLAS.
PT. BD.
PR.
PWD.
PREFAB.
PTD.
P.L.
O.F.O.I.
OPG.
O.H.
P
O.F.C.I.
O.C.
O.A.
O.D.
O
L
M.O.
MTL.
N
N.A.F.
N.T.S.
NO.
N.I.C.
M.E.P.
MECH.
MFR.
MISC.
MIN.
M.H.
L.L.V.
M
MAX.
L
L.L.O.
L.L.H.
LAV.
LB.
L.H.
OPPOSITEOPP.
GENERAL CONTRACTOR
HEIGHT
HOT WATER
FACE OF BRICK
FACE OF CONCRETE
FACE OF BLOCK
FIREPROOF
FACE OF STUD
FACE OF GYPSUM BD.
FACE OF FINISH
FIELD VERIFY
GENERAL
GAUGE
GLASS
FOOT/FEET
HARDWARE
HOSE BIBB
HEIGHT
HOLLOW METAL
HORIZONTAL
HEATING, VENTILATION &
A.C.
GYPSUM WALL BOARD
GA.
HT.
H.W.
HVAC
HORIZ.
HB
HDWR.
H.M.
G.W.B./GWB
H
H.
G.C.
GEN.
GL.
F.O.G.
G
F.V.
F.O.S.
FPRF.
FT.
F.O.B.
F.O.BR.
F.O.C.
F.O.F.
INFORMATION
INCANDESCENT
INSIDE DIAMETER
INTERIOR
INSULATION
INCAN.
INFO.
INT.
INSUL.
I
I.D.
JOIST BEARING
JANITOR CLOSET
JANITOR
JOINT
J.C.
JST. BRG.
JT.
J
JAN.
ABBREVIATIONS
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A001
GENERAL NOTES,
SYMBOLS AND
LEGENDS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SPECIALTY ACCESSORY SCHEDULE
TYPE ITEM MFR / MODEL REMARKS PROVIDED BY INSTALLED BY
SCALE: 1" = 1'-0"1 WALL PENETRATION
# DESCRIPTION DATE
ACOUSTICAL SEALANT BOTH SIDES
3-5/8" CONTINUOUS METAL
RUNNER DEFLECTION TRACK
CEILING AS OCCURS. REFER RCP
5/8" TYPE 'X' GYPSUM BOARD.
EXTEND TO DECK
3-5/8" INTERIOR METAL FRAMING
AT 16" O.C. EXTEND TO DECK
UNFACED ACOUSTICAL BATT
INSULATION
FLOOR OR ROOF CONSTRUCTION.
REFER TO WALL SECTIONS
3-5/8" CONTINUOUS METAL
RUNNER TRACK
ACOUSTICAL SEALANT AT
PERIMETER OF BOTH SIDES
(2) LAYERS 5/8" TYPE 'X' GYPSUM
BOARD ON EACH SIDE. EXTEND TO
DECK
3-5/8" INTERIOR METAL FRAMING
AT 16" O.C. EXTEND TO DECK
FLOOR LINE
4 7/8"5 5/8"
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.W2 ---47 NGC-2386
DESCRIPTION: 5/8" type X gypsum board applied
vertically to each side of 3-5/8" steel studs 16" o.c.
with 1" type S drywall screws 8" o.c. at vertical joints
and 12" o.c. at floor and ceiling runners and
intermediate studs. Joints staggered 24" on opposite
side. Fill stud cavities with acoustical batt insulation.
LINE OF CEILING
UNDERSIDE OF STRUCTURE
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.W1 -----
DESCRIPTION:
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.W5 2 HR UL U412 --
DESCRIPTION: (2) layers of 5/8" type X gypsum
board applied vertically to both sides of 3-5/8 steel
studs 16" o.c. with 2" type S drywall screws 8" o.c. at
vertical joints and 12" o.c. at floor and ceiling runners
and intermediate studs. Joints staggered 24" on
opposite side. Fill stud cavaties with R13 min. batt
insulation.
3-5/8" CONTINUOUS METAL
RUNNER TRACK
ACOUSTICAL SEALANT AT
PERIMETER OF BOTH SIDES
CEILING AS OCCURS. REFER RCP
ACOUSTICAL SEALANT BOTH SIDES
3-5/8" CONTINUOUS METAL
RUNNER DEFLECTION TRACK
6" TYP.KRAFT-FACED R-13 BATT INSULATION
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.W4 -----
DESCRIPTION:
3-5/8" CONTINUOUS METAL
RUNNER DEFLECTION TRACK
CEILING AS OCCURS. REFER RCP
5/8" TYPE 'X' GYPSUM BOARD.
EXTEND TO DECK
3-5/8" INTERIOR METAL FRAMING
AT 16" O.C. EXTEND TO DECK
3" MINERAL FIBER INSULATION
3-5/8" CONTINUOUS METAL
RUNNER TRACK
4 7/8"
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.W3 1 HR UL UL419 --
DESCRIPTION: 5/8" type X gypsum board applied
vertically to each side of 3-5/8" steel studs 16" o.c.
with 1" type S drywall screws 8" o.c. at vertical joints
and 12" o.c. at floor and ceiling runners and
intermediate studs. Joints staggered 24" on opposite
side. Fill stud cavities with 3" mineral fiber insulation.
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.W6 -----
DESCRIPTION:
FLOOR LINE
4 1/4"
LINE OF CEILING
UNDERSIDE OF STRUCTURE
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.F3 -----
DESCRIPTION: 5/8" type X gypsum board applied
vertically to room side of 3-5/8" steel studs 16" o.c.
with 1" type S drywall screws 8" o.c. at vertical joints
and 12" o.c. at floor and ceiling runners and
intermediate studs. Fill stud cavities with acoustical
batt insulation.
CEILING AS OCCURS. REFER RCP
ACOUSTICAL SEALANT BOTH SIDES
3-5/8" CONTINUOUS METAL
RUNNER DEFLECTION TRACK
6" TYP.FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.W8 -----
DESCRIPTION:
FLOOR OR ROOF CONSTRUCTION.
REFER TO WALL SECTIONS
FLOOR OR ROOF CONSTRUCTION.
REFER TO WALL SECTIONS
FLOOR OR ROOF CONSTRUCTION.
REFER TO WALL SECTIONS
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.W9 2 HR UL U905 --
DESCRIPTION: 7-5/8" cmu in running bond pattern
with horizontal joint reinforcement at 16" o.c.
vertically. Refer to structural for vertical
reinforcement.
8" CMU. REFER TO STRUCTURE
DRAWINGS FOR REINFORCEMENT
FLOOR OR ROOF CONSTRUCTION.
REFER TO WALL SECTIONS
5/8" TYPE 'X' GYPSUM BOARD.
EXTEND TO DECK
3-5/8" INTERIOR METAL FRAMING
AT 16" O.C. EXTEND TO DECK
UNFACED ACOUSTICAL BATT
INSULATION
3-5/8" CONTINUOUS METAL
RUNNER TRACK
ACOUSTICAL SEALANT AT
PERIMETER OF BOTH SIDES
4 1/4"
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.F2 -----
DESCRIPTION: 5/8" type X gypsum board applied
vertically to room side of 3-5/8" steel studs 16" o.c.
with 1" type S drywall screws 8" o.c. at vertical joints
and 12" o.c. at floor and ceiling runners and
intermediate studs.
CEILING AS OCCURS. REFER RCP
3-5/8" CONTINUOUS METAL
RUNNER DEFLECTION TRACK
FLOOR OR ROOF CONSTRUCTION.
REFER TO WALL SECTIONS
5/8" TYPE 'X' GYPSUM BOARD.
EXTEND TO DECK
3-5/8" INTERIOR METAL FRAMING
AT 16" O.C. EXTEND TO DECK
3-5/8" CONTINUOUS METAL
RUNNER TRACK
7 5/8"
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.W7 -----
DESCRIPTION:
FIRE
RATING
REF.DESIGN
No.
STC
RATING
TEST No.F1 -----
DESCRIPTION: 5/8" type X gypsum board applied
vertically to room side of 3-5/8" steel studs 16" o.c.
with 1" type S drywall screws 8" o.c. at vertical joints
and 12" o.c. at floor and ceiling runners and
intermediate studs. Space studs 1" off of
precast/CMU wall and spray foam R20 min.
NOT USEDNOT USED NOT USED
NOT USEDNOT USED
4 1/4"1"
CEILING AS OCCURS. REFER RCP
3-5/8" CONTINUOUS METAL
RUNNER DEFLECTION TRACK
5/8" TYPE 'X' GYPSUM BOARD.
EXTEND TO DECK
3-5/8" INTERIOR METAL FRAMING
AT 16" O.C.
3-5/8" CONTINUOUS METAL
RUNNER TRACK
SPAY FOAM INSULATION R-12.5 MIN.
PRECAST CONCRETE PANEL
SUBSTRATE
A. VERIFY RATED WALLS WITH CODE COMPLIANCE PLAN, SHEET G002.
B. ALL RATED WALL ASSEMBLY CONSTRUCTION SHALL BE SEALED WITH
FIRE/SMOKE RATED SEALANT @ ALL JOINTS AND PENETRATIONS. REFER
TO MECH. SHEET FOR SMOKE DAMPERS.
C. ALL ACCOUSTICAL WALL ASSEMBLY CONSTRUCTION SHALL BE SEALED
WITH SOUND SEALANT @ ALL JOINTS AND PENETRATIONS.
D. WATER RESISTANT GYPSUM WALLBOARD SHALL BE USED IN LIEU OF
TYPE 'X' GYPSUM WALLBOARD IN ALL LOCATIONS WHERE CERAMIC AND
PORCELAIN TILE FINISH IS USED; AS WELL AS ALL RESTROOMS, KITCHEN,
MECHANCAL ROOMS, APPARATUS BAY AND JANITOR CLOSETS.
E. GAGE OF ALL INTERIOR METAL STUD FRAMING TO BE DESIGNED FOR
5 PSF WIND LOADS, STUD HEIGHT AND ADDITIONAL LOADING SUCH AS
MILLWORK OR SUSPENDED ITEMS.
F. ALL WALL FRAMING THAT EXTENDS ABOVE FINISH CEILING TO BE BRACED
TO STRUCTURE ABOVE AT 4'-0" O.C. ALTERNATING DIRECTIONS AS
LIMITING HEIGHTS REQUIRE.
G. ALL WALL FRAMING NOTED TO EXTEND TO CEILING OR 6" ABOVE CEILING
TO BE BRACED TO STRUCTURE AT 4'-0" O.C. ALTERNATING DIRECTIONS.
H. REFER TO REFLECTED CEILING PLAN FOR CEILING MATERIALS AND
HEIGHTS; REFER ROOM FINISH SCHEDULE FOR FINISHES AND SPECIAL
INSTRUCTION.
J. PROVIDE METAL TRIM OR ZIP-STRIPS AT THE EDGES OF ALL GYPSUM
WALLBOARD WHERE IT ABUTS ANOTHER MATERIAL AND WHERE EDGES
ARE EXPOSED TO VIEW.
K. DIVIDE ALL GYPSUM WALLBOARD AREAS WITH CONTROL JOINTS NOT
EXCEEDING 30 FEET IN EITHER DIRECTION OR AS SHOWNOTHERWISE.
PROVIDE RATED CONTROL JOINTS IN FIRE RATED PARTITIONS.
L. PROVIDE HIGH-IMPACT GYPSUM WALLBOARD IN ALL CORRIDORS,
STAIRCASES AND LOBBY AND OTHER SPACES AS NOTED ON PLANS.
M. PROVIDE HORIZONTAL JOINT REINFORCEMENT AT 16" O.C. AT
MASONRY WALLS. PROVIDE VERTICAL REINFORCEMENT PER
STRUCTURAL DRAWINGS AND SPECIFICATIONS.
W1WALL TYPE -REFER
SCHEDULE ON A002
TYPICAL WALL NOTES
WALL TYPE SYMBOL
X HEIGHT ATTRIBUTE
A - WALL TO 6" ABOVE CEILING
C - WALL TO CEILING
XX' - HEIGHT IN FEET
**IF NO ATTRIBUTE: CONSTRUCT
WALL TO STRUCTURE.
STANDARD SYSTEMS
SHAFTWALL SYSTEMS
NOTE: * = AT FRAMING EXCEEDING 12'-0" HEIGHT, PROVIDE BRACING
LINTEL SCHEDULE U.N.O.FRAMING1 5/8"
2-1/2"
2-1/2"
2-1/2"
3-5/8"
3-5/8"
3-5/8"
6"
6"
6"
2-1/2"
C-H STUDS
2-1/2"
C-H STUDS
2-1/2"
C-H STUDS
4"
C-H STUDS
4"
C-H STUDS
6" DBL
E STUDS
6" DBL
E STUDS
</= 6'-0"
> 6'-0" - </= 8'-0"
> 8'-0" - </= 10'-0"DEPTHAT MID HEIGHT LOCATION, BUT NOT TO EXCEED 12'-0" MAX.
SPAN
25--(0.0179")
25--(0.0179")
22--(0.0270")
20--(0.0329")
25--(0.0179")
22--(0.0270")
20--(0.0329")
25--(0.0179")
22--(0.0270")
20--(0.0329")
25--(0.0199")
22--(0.0294")
20--(0.0341")
25--(0.0199")
20--(0.0341")
25--(0.0199")
20--(0.0341")FRAMINGGAUGESTUD 16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
16"
24"
24"
24"
24"
24"
24"
24"
24"
2-4"X16GA. METAL CEE STUDS
2-6"X18GA. METAL CEE STUDS
2-6"X16GA. METAL CEE STUDSSPACINGALLOWABLE L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
L/240
LINTEL SIZEDEFLECTIONFURRING2 HOUR1 LAYER8'-3"
7'-3"
11'-0"
9'-9"
12'-0"
10'-6"
13'-0"
11'-6"
14'-6"
12'-9"
16'-0"
14'-0"
17'-3"
15'-0"
20'-0"
15'-0"
25'-3"
22'-0"
26'-6"
23'-3"RATED12'-1"
14'-11"
15'-3"
16'-11"
18'-2"
26'-3"
28'-0"ONE SIDE*PARTITION1 HOUR1 LAYER9'-6"
8'-3"
12'-6"
10'-9"
13'-0"
11'-6"
14'-0"
12'-3"
16'-0"
13'-6"
17'-3"
15'-0"
18'-3"
16'-0"
20'-0"
15'-0"
26'-0"
22'-9"
27'-6"
24'-0"RATED11'-8"
13'-7"
14'-0"
15'-10"
17'-6"
25'-3"
28'-0"EACH SIDEPARTITION2 LAYERS10'-6"
8'-9"
13'-6"
11'-3"
14'-0"
12'-3"
14'-9"
13'-0"
16'-9"
13'-6"
18'-0"
15'-9"
19'-0"
16'-6"
20'-0"
15'-0"
23'-9"
20'-9"
25'-6"
22'-3"EACH SIDEINTERIOR WALL LIMITING HEIGHTS
REFER FLOOR PLAN
FOR PARTITION TYPE
EXTEND GYPSUM
WALLBOARD TO 1/2" OF
DECK AND INSTALL
ACOUSTICAL SEALANT
DEFLECTION TRACK
ATTACHED WITH
ANCHORS AT 2'-0" O.C.
DO NOT ATTACH GYPSUM
WALLBOARD TO TOP TRACK
COMPOSITE FLOOR OR
ROOF ASSEMBLY
REFER FLOOR PLAN
FOR PARTITION TYPE
CUT GYPSUM WALLBOARD
TO FIT DECK FLUTES DEFLECTION TRACK
ATTACHED WITH
ANCHORS AT 2'-0" O.C.DO NOT ATTACH GYPSUM
WALLBOARD TO TOP TRACK
COMPOSITE FLOOR OR
ROOF ASSEMBLY
1/2" NOM. GAP. FILL WITH
ACOUSTICAL SEALANT .1/4" JOINT TYP.
METAL CONTROL
JOINT
5/8" GYPSUM
WALLBOARD
CONTROL JOINT NON-RATEDGYPSUM PARTITION AT STRUCTURE - PARALLEL GYPSUM PARTITION AT STRUCTURE - PEPENDICULAR
J-MOLD TYP
REFER FLOOR PLAN FOR
PARTITION TYPE
LATERAL SUPPORT (CLIP
ANGLE OR ADJUSTABLE
ANCHOR)
FLOOR ASSEMBLY AS
OCCURS
CMU PARTITION AT STRUCTURE
BOND BEAM
COMPRESSABLE FILLER IN OPEN JOINT
AND BETWEEN FLUTES. PROVIDE
RATED FILLER AT RATED WALLS1"STRUCTURAL FLOOR OR
ROOF ASSEMBLY
6"WALL HEIGHT C = EXTEND TO BOTTOM OF CEILINGWALL HEIGHT A = EXTEND WALL TO 6" ABOVE CEILINGWALL HEIGHT S = EXTEND WALL TO BOTTOM OF STRUCTURAL DECKTYPICAL INTERIOR WALL SECTION
CEILING WHERE
OCCURS
BRACE TO STRUCTURE
AT 4'-0" O.C. AT PARTIAL
HEIGHT WALLS
METAL STUDS. PROVIDE
WIDTH PER WALL TYPE
AND GAGE AS REQUIRED
FOR HEIGHT
5/8" GYPSUM WALLBOARD
TYP. BOTH SIDES (USE TYPE X
FOR RATED ASSEMBLIES)
SOUND ATTENUATION
INSULATION AS SPECIFIED
PER WALL TYPE
CONTINUOUS METAL
RUNNER TRACK
ACOUSTICAL SEALANT AT
ALL JOINTS DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
JK
CH
03/28/2017
A002
INTERIOR WALL
TYPES AND
DETAILS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 3/4" = 1'-0"
INTERIOR WALL TYPES LEGEND
SCALE: 1 1/2" = 1'-0"02 TYPICAL INTERIOR WALL DETAILS
SCALE: 1 1/2" = 1'-0"01 TYPICAL INTERIOR WALL SECTION
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
1
UP
UP
GENERAL PLAN NOTES
A. REFER TO A001-A002 FOR GENERAL NOTES, WALL TYPES, SYMBOLS
AND TYPICAL CONSTRUCTION DETAILS.
B. PROVIDE BULLNOSE CMU AT ALL EXPOSED CMU CORNERS.
C. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM WALLBOARD AT
THE APPARATUS BAY AND ALL ROOMS DIRECTLY OFF OF IT.
D. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM WALLBOARD AT
ALL WET WALLS IN KITCHENS, AND ALL WALLS AND CEILINGS IN
BATHROOMS AND JANITOR CLOSETS.
E. PROVIDE HIGH-IMPACT GYPSUM WALLBOARD AT ALL CORRIDORS,
STAIRCASES AND THE LOBBY.
F. PLAN KEYNOTES APPLY TO SHEETS A101, A102 AND A110.
76521
A
B
C
4
48' - 0"24' - 0"36' - 0"36' - 0"24' - 0"48' - 0"
01
A301
01
A301
216' - 0"
SPEED RAMP
9.375%
3
12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"
60' - 0"120' - 0"36' - 0"
STAIR 2
ST2-1
0' - 0"
STAIR 1
ST1-1
ELEV.
EL1-1
STAIR 3
ST3-1
ELECTRICAL
101
NOTE:
REFER TO A130 SERIES
DRAWINGS FOR PARKING
COUNTS AND STRIPING
NOTES.123' - 10"4"61' - 9"61' - 9"0' - 0"
A120
01
A121
01
828.5
828.5
FIRST FLOOR ELEVATION:
100'-0" = 828.5'
828.4A122
01
03
A301
03
A301
828.50
216' - 0"
02
A202
RISER RM.
102
12' - 0"24' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"02A20101
A202
828.50
0' - 6"
829.00
TRANSITION RAMP
4.2%
OPEN BELOW RAMP
TO STORM DETENTION
AREA01A201
5' - 6"8' - 4 3/8"6' - 3"12' - 0"7' - 0 3/8"23' - 10 1/4"5' - 1 3/8"12' - 0"12' - 0"12' - 0"12' - 0"7' - 10"8' - 1"11' - 11"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"3' - 11"12' - 0"12' - 0"12' - 0"12' - 0"11' - 11"OFFICE
BUILDOUT
SPACE
103
W9
W2
W2
W9
W8
104ST3-1AST3-1 100103103A103B103C
103D
102IT ROOM
104101 2' - 4"F1
F1
F1W5S
15' - 3"11' - 10"10"15' - 10"NOTE:
REFER TO A110 FOR OFFICE
TENANT BUILDOUT DRAWINGS.ST2-1A12' - 0"
P12
P12
NOTE:
OFFICE BUILDING IS NOT IN
PROJECT SCOPE.
P01
P01
4' - 0 3/8"4' - 6 1/2"2' - 0 1/8"4' - 6 1/2"12' - 0 1/8"12' - 0"
P09
P09
P09
P09
828.50'P09
827.50'827.50'
828.16'
828.50'
PERIMETER TYP.
828.50'
PERIMETER TYP.
P22
P22
P06
P06
4' - 2 7/8"5' - 8 3/4"2' - 0 1/4"
GARAGE
FIRST FLOOR
100
DASHED LINE INDICATES FOUNDATION
R-10 RIGID INSULATION AROUND PERIMETER
TO TOP OF FOOTING AND R-15 RIGID FOR A
DISTANCE OF 2'-0" HORIZONTAL BENEATH
CONCRETE SLAB.
REFER TO DWG 06/A310
FOR MANHOLE DETAIL 1' - 4"15' - 6"REFER TO DWG 07/A310
FOR MANHOLE LADDER DETAIL
REFER TO DWG 06/A310
FOR MANHOLE DETAIL
REFER TO DWG 07/A310
FOR MANHOLE LADDER DETAIL 6' - 0"1' - 4"02
A301
02
A301
CMU WALL BETWEEN TOP OF
PRECAST WALL AND BOTTOM
OF PRECAST FLOOR STRUCTURE
ABOVE TYPICAL ALONG WEST
WALL OF OFFICE BUILDOUT4' - 6" TYP.3' - 6"P28
4' - 0"11' - 1"4' - 6" TYP.8' - 0"4' - 6" TYP.6' - 1 3/4"
4' - 6" TYP.
P28
4' - 6" TYP.6' - 6"P30
P30
MECHANICAL EQUIPMENT
P28
5' - 6"4' - 6"4' - 6"7' - 0"1
PROVIDE 3M FILM OVER IT
ROOM WINDOWS.2
FIRST LEVEL
0'-0" 828.50 15' - 0".10' - 8".10' - 8".SECOND LEVEL
15'-0" 843.50
THIRD LEVEL
25'-8" 854.17'
FOURTH LEVEL
36'-4" 864.83'
TOP OF RAMP
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A101
FIRST FLOOR
CONSTRUCTION
PLAN
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032PLAN KEYNOTES
P01 DASHED LINE INDICATES CANOPY ABOVE.
P02 MIDTOWN OFFICE CANOPY - NOT IN CONTRACT.
P03 4-1/2" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P04 PRECAST CONCRETE STAIRCASE. REFER TO PRECAST DRAWINGS.
P05 MIDTOWN OFFICE BUILDING - NOT IN CONTRACT.
P06 BICYCLE RACK TO BE SARIS STACK RACK 20" SPACING. PROVIDE SPACES FOR
50 BICYCLES TOTAL.
P07 MOP SINK. REFER TO PLUMBING DRAWNGS.
P08 ELEVATOR MACHINE-ROOM-LESS TYPE - REFER TO SPECS. INTERIOR FLOOR
FINISH OF CAB TO BE: DAL TILE, NOIR LINEN P689, 12X12 WITH MAPEI
CHARCOAL 47 GROUT.
P09 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS. COORDINATE LOCATION
WITH PRECAST AND TOPPING SLAB SLOPES.
P10 HOLLOW METAL WINDOW. REFER TO GLAZING ELEVATIONS.
P11 ELEVATOR EQUIPMENT. COORDINATE WITH ELEVATOR SPECS AND MEP
DWGS.
P12 WALL MOUNTED FIRE EXTINGUISHER CABINET - REFER TO SPECS.
P13 GALVANIZED TUBE STEEL GUARDRAIL TYPICAL AT ALL OPENINGS. REFER TO
TYPICAL DETAIL 11/A125.
P14 1-1/2" TUBE STEEL GUARDRAIL W/STAINLESS STEEL CABLES. FERRULES, STUDS.
1-1/2" DIAM. STEEL PIPE HANDRAIL. (TYPICAL ON FLOORS 1-2 ONLY). (PAINT
P1). MOUNT TO SIDE OF PRECAST CONCRETE STAIRS.
P15 1-1/2" DIA. STEEL PIPE GUARDRAIL/HANDRAIL SIDE MOUNTED TO PRECAST
STAIRS (PAINT P1).
P16 1-1/2" DIA. STEEL PIPE HANDRAIL ATTACHED TO PRECAST OR CMU WALL.
P17 PROVIDE 42" TALL GUARDRAIL INFILL AT STOREFRONT OPENINGS AT
LANDINGS AND STAIR RUNS. INSET GUARDRAIL INTO WINDOW OPENING.
TOP OF RAIL TO BE PARALLEL WITH FLOOR OR STAIR RUN.
P18 4" WIDE PAINTED STRIPS AT 45 DEGREES; COLOR - YELLOW.
P19 PAINTED PARKING STRIPE; COLOR - YELLOW. TYPICAL.
P20 ADA PAINTED PARKING GRAPHIC; COLOR - BLUE.
P21 PAINTED DIRECTIONAL ARROW; COLOR - YELLOW.
P22 SLOPE TOPPING SLAB TO TRAIN. 2% MAX.
P23 HATCHED AREA DENOTES TRAFFIC BEARING MEMBRANE INSTALLED ON
CONCRETE DECK ABOVE ENCLOSED SPACE ABOVE. TURN MEMBRANE UP
ADJACENT WALLS 6" MIN.
P24 EXTERIOR BLADE SIGN - COORDINATE WITH SIGN CONSULTANT. PROVIDE
ELECTRICAL. CENTER ON PRE-CAST CONCRETE PANEL.
P25 42" GUARDRAIL CLOSURE AT FIRST FLOOR WITH GATE. PROVIDE HASP AND
LATCH.
P26 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER PLUMBING DRAWINGS.
P27 2-1/4" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P28 PIPE BOLLARD WITH PLATE THRU-BOLTED TO PRECAST GARAGE STRUCTURE.
P29 DRY STANDPIPE. REFER TO PLUMBING DRAWINGS
P30 ROOF LEADER PIPING. PROVIDE PAINTED STEEL PIPE PROTECTION - 055000.
SCALE: 1/8" = 1'-0"01 FIRST FLOOR CONSTRUCTION
PLAN
SCALE: 3/32" = 1'-0"
ISOMETRIC
# DESCRIPTION DATE
1 ADDENDUM No 1 4/17/2017
2 ADLS COMMENTS 5/11/2017
UPUP
UP
GENERAL PLAN NOTES
A. REFER TO A001-A002 FOR GENERAL NOTES, WALL TYPES, SYMBOLS
AND TYPICAL CONSTRUCTION DETAILS.
B. PROVIDE BULLNOSE CMU AT ALL EXPOSED CMU CORNERS.
C. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM WALLBOARD AT
THE APPARATUS BAY AND ALL ROOMS DIRECTLY OFF OF IT.
D. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM WALLBOARD AT
ALL WET WALLS IN KITCHENS, AND ALL WALLS AND CEILINGS IN
BATHROOMS AND JANITOR CLOSETS.
E. PROVIDE HIGH-IMPACT GYPSUM WALLBOARD AT ALL CORRIDORS,
STAIRCASES AND THE LOBBY.
F. PLAN KEYNOTES APPLY TO SHEETS A101, A102 AND A110.
76521
A
B
C
4
01
A301
01
A301
RAMP DN RAMP UP
RAMP DOWN
123' - 6"3
NOTE:
REFER TO A130 SERIES
DRAWINGS FOR PARKING
COUNTS AND STRIPING
NOTES.
10' - 8"
10' - 8"
15' - 0"
15' - 0"
12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"24' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 0"12' - 1"11' - 11"12' - 0"12' - 0"
60' - 0"120' - 1"35' - 11"
STAIR 2
ST2-2
ELEV.
EL1-2
STAIR 1
ST1-2
OPEN TO
LEASE SPACE
BELOW
A120
02
A121
04
A122
02
03
A301
03
A301
02
A202 02A20101
A202
01A201ST2-2ST1-217' - 3 5/8"12' - 0"
W9
W9
839.17
839.17
843.50
843.50
P12
P09
P09
P09
P12
P09
P09
P23
P23
P13
P13
P13
P13 TYP. AT EACH
OPENING
TYP. AT EACH
OPENING
TYP. AT EACH
OPENING
TYP. AT EACH
OPENING
01
A310
A125
07 SIM
8' - 0"46' - 5 1/2"8' - 0"11' - 11"
ALIGN END OF
CANOPY W/PANEL
JOINT
P01
P01
P01
ALIGN END OF CANOPY
W/ PANEL JOINTST3-2P03
P03
P03
STAIR 3
ST3-2
NOTE:
OFFICE BUILDING IS NOT IN
PROJECT SCOPE.
GARAGE
SECOND
FLOOR
200
02
A301
02
A301
10' - 6"3' - 2"4' - 6"7' - 0"P28
P30
P30
FIRST LEVEL
0'-0" 828.50 15' - 0".10' - 8".10' - 8".SECOND LEVEL
15'-0" 843.50
THIRD LEVEL
25'-8" 854.17'
FOURTH LEVEL
36'-4" 864.83'
TOP OF RAMP
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A102
SECOND FLOOR
CONSTRUCTION
PLAN
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032PLAN KEYNOTES
P01 DASHED LINE INDICATES CANOPY ABOVE.
P02 MIDTOWN OFFICE CANOPY - NOT IN CONTRACT.
P03 4-1/2" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P04 PRECAST CONCRETE STAIRCASE. REFER TO PRECAST DRAWINGS.
P05 MIDTOWN OFFICE BUILDING - NOT IN CONTRACT.
P06 BICYCLE RACK TO BE SARIS STACK RACK 20" SPACING. PROVIDE SPACES FOR
50 BICYCLES TOTAL.
P07 MOP SINK. REFER TO PLUMBING DRAWNGS.
P08 ELEVATOR MACHINE-ROOM-LESS TYPE - REFER TO SPECS. INTERIOR FLOOR
FINISH OF CAB TO BE: DAL TILE, NOIR LINEN P689, 12X12 WITH MAPEI
CHARCOAL 47 GROUT.
P09 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS. COORDINATE LOCATION
WITH PRECAST AND TOPPING SLAB SLOPES.
P10 HOLLOW METAL WINDOW. REFER TO GLAZING ELEVATIONS.
P11 ELEVATOR EQUIPMENT. COORDINATE WITH ELEVATOR SPECS AND MEP
DWGS.
P12 WALL MOUNTED FIRE EXTINGUISHER CABINET - REFER TO SPECS.
P13 GALVANIZED TUBE STEEL GUARDRAIL TYPICAL AT ALL OPENINGS. REFER TO
TYPICAL DETAIL 11/A125.
P14 1-1/2" TUBE STEEL GUARDRAIL W/STAINLESS STEEL CABLES. FERRULES, STUDS.
1-1/2" DIAM. STEEL PIPE HANDRAIL. (TYPICAL ON FLOORS 1-2 ONLY). (PAINT
P1). MOUNT TO SIDE OF PRECAST CONCRETE STAIRS.
P15 1-1/2" DIA. STEEL PIPE GUARDRAIL/HANDRAIL SIDE MOUNTED TO PRECAST
STAIRS (PAINT P1).
P16 1-1/2" DIA. STEEL PIPE HANDRAIL ATTACHED TO PRECAST OR CMU WALL.
P17 PROVIDE 42" TALL GUARDRAIL INFILL AT STOREFRONT OPENINGS AT
LANDINGS AND STAIR RUNS. INSET GUARDRAIL INTO WINDOW OPENING.
TOP OF RAIL TO BE PARALLEL WITH FLOOR OR STAIR RUN.
P18 4" WIDE PAINTED STRIPS AT 45 DEGREES; COLOR - YELLOW.
P19 PAINTED PARKING STRIPE; COLOR - YELLOW. TYPICAL.
P20 ADA PAINTED PARKING GRAPHIC; COLOR - BLUE.
P21 PAINTED DIRECTIONAL ARROW; COLOR - YELLOW.
P22 SLOPE TOPPING SLAB TO TRAIN. 2% MAX.
P23 HATCHED AREA DENOTES TRAFFIC BEARING MEMBRANE INSTALLED ON
CONCRETE DECK ABOVE ENCLOSED SPACE ABOVE. TURN MEMBRANE UP
ADJACENT WALLS 6" MIN.
P24 EXTERIOR BLADE SIGN - COORDINATE WITH SIGN CONSULTANT. PROVIDE
ELECTRICAL. CENTER ON PRE-CAST CONCRETE PANEL.
P25 42" GUARDRAIL CLOSURE AT FIRST FLOOR WITH GATE. PROVIDE HASP AND
LATCH.
P26 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER PLUMBING DRAWINGS.
P27 2-1/4" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P28 PIPE BOLLARD WITH PLATE THRU-BOLTED TO PRECAST GARAGE STRUCTURE.
P29 DRY STANDPIPE. REFER TO PLUMBING DRAWINGS
P30 ROOF LEADER PIPING. PROVIDE PAINTED STEEL PIPE PROTECTION - 055000.
SCALE: 1/8" = 1'-0"01 SECOND FLOOR CONSTRUCTION
PLAN
SCALE: 3/32" = 1'-0"
ISOMETRIC
# DESCRIPTION DATE
76521
A
B
C
4
01
A301
01
A301
3
RAMP DN RAMP UP
RAMP DOWN
03
A301
03
A301
02
A202
A120
03
A121
05 02A20101
A202
01A201A122
03
05A20103
A201 04A20121' - 4"
849.83
25' - 8"
854.17
A125
07 SIM
P23
P09
P09
P09P09
P09
P12
P12
P13TYP. AT EACH
OPENING
P13
P13
P13
TYP. AT EACH
OPENING
TYP. AT EACH
OPENING
TYP. AT EACH
OPENING
EQ.EQ.ST3-3ST1-3STAIR 1
ST1-3
ELEV.
EL1-3
STAIR 2
ST2-3ST2-3STAIR 3
ST3-3
NOTE:
REFER TO A130 SERIES
DRAWINGS FOR PARKING
COUNTS AND STRIPING
NOTES.
GARAGE
THIRD FLOOR
300
48' - 0"24' - 0"36' - 0"36' - 0"24' - 0"48' - 0"
216' - 0"123' - 10"4"61' - 9"61' - 9"NOTE:
OFFICE BUILDING IS NOT IN
PROJECT SCOPE.
02
A301
02
A301
10' - 6"3' - 2"4' - 6"7' - 0"P28
P30
P30
P24
GENERAL PLAN NOTES
A. REFER TO A001-A002 FOR GENERAL NOTES, WALL TYPES, SYMBOLS
AND TYPICAL CONSTRUCTION DETAILS.
B. PROVIDE BULLNOSE CMU AT ALL EXPOSED CMU CORNERS.
C. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM WALLBOARD AT
THE APPARATUS BAY AND ALL ROOMS DIRECTLY OFF OF IT.
D. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM WALLBOARD AT
ALL WET WALLS IN KITCHENS, AND ALL WALLS AND CEILINGS IN
BATHROOMS AND JANITOR CLOSETS.
E. PROVIDE HIGH-IMPACT GYPSUM WALLBOARD AT ALL CORRIDORS,
STAIRCASES AND THE LOBBY.
F. PLAN KEYNOTES APPLY TO SHEETS A101, A102 AND A110.
FIRST LEVEL
0'-0" 828.50 15' - 0".10' - 8".10' - 8".SECOND LEVEL
15'-0" 843.50
THIRD LEVEL
25'-8" 854.17'
FOURTH LEVEL
36'-4" 864.83'
TOP OF RAMP
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A103
THIRD FLOOR
PLAN
CONSTRUCTION
PLAN
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 1/8" = 1'-0"01 THIRD FLOOR CONSTRUCTION
PLAN
PLAN KEYNOTES
P01 DASHED LINE INDICATES CANOPY ABOVE.
P02 MIDTOWN OFFICE CANOPY - NOT IN CONTRACT.
P03 4-1/2" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P04 PRECAST CONCRETE STAIRCASE. REFER TO PRECAST DRAWINGS.
P05 MIDTOWN OFFICE BUILDING - NOT IN CONTRACT.
P06 BICYCLE RACK TO BE SARIS STACK RACK 20" SPACING. PROVIDE SPACES FOR
50 BICYCLES TOTAL.
P07 MOP SINK. REFER TO PLUMBING DRAWNGS.
P08 ELEVATOR MACHINE-ROOM-LESS TYPE - REFER TO SPECS. INTERIOR FLOOR
FINISH OF CAB TO BE: DAL TILE, NOIR LINEN P689, 12X12 WITH MAPEI
CHARCOAL 47 GROUT.
P09 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS. COORDINATE LOCATION
WITH PRECAST AND TOPPING SLAB SLOPES.
P10 HOLLOW METAL WINDOW. REFER TO GLAZING ELEVATIONS.
P11 ELEVATOR EQUIPMENT. COORDINATE WITH ELEVATOR SPECS AND MEP
DWGS.
P12 WALL MOUNTED FIRE EXTINGUISHER CABINET - REFER TO SPECS.
P13 GALVANIZED TUBE STEEL GUARDRAIL TYPICAL AT ALL OPENINGS. REFER TO
TYPICAL DETAIL 11/A125.
P14 1-1/2" TUBE STEEL GUARDRAIL W/STAINLESS STEEL CABLES. FERRULES, STUDS.
1-1/2" DIAM. STEEL PIPE HANDRAIL. (TYPICAL ON FLOORS 1-2 ONLY). (PAINT
P1). MOUNT TO SIDE OF PRECAST CONCRETE STAIRS.
P15 1-1/2" DIA. STEEL PIPE GUARDRAIL/HANDRAIL SIDE MOUNTED TO PRECAST
STAIRS (PAINT P1).
P16 1-1/2" DIA. STEEL PIPE HANDRAIL ATTACHED TO PRECAST OR CMU WALL.
P17 PROVIDE 42" TALL GUARDRAIL INFILL AT STOREFRONT OPENINGS AT
LANDINGS AND STAIR RUNS. INSET GUARDRAIL INTO WINDOW OPENING.
TOP OF RAIL TO BE PARALLEL WITH FLOOR OR STAIR RUN.
P18 4" WIDE PAINTED STRIPS AT 45 DEGREES; COLOR - YELLOW.
P19 PAINTED PARKING STRIPE; COLOR - YELLOW. TYPICAL.
P20 ADA PAINTED PARKING GRAPHIC; COLOR - BLUE.
P21 PAINTED DIRECTIONAL ARROW; COLOR - YELLOW.
P22 SLOPE TOPPING SLAB TO TRAIN. 2% MAX.
P23 HATCHED AREA DENOTES TRAFFIC BEARING MEMBRANE INSTALLED ON
CONCRETE DECK ABOVE ENCLOSED SPACE ABOVE. TURN MEMBRANE UP
ADJACENT WALLS 6" MIN.
P24 EXTERIOR BLADE SIGN - COORDINATE WITH SIGN CONSULTANT. PROVIDE
ELECTRICAL. CENTER ON PRE-CAST CONCRETE PANEL.
P25 42" GUARDRAIL CLOSURE AT FIRST FLOOR WITH GATE. PROVIDE HASP AND
LATCH.
P26 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER PLUMBING DRAWINGS.
P27 2-1/4" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P28 PIPE BOLLARD WITH PLATE THRU-BOLTED TO PRECAST GARAGE STRUCTURE.
P29 DRY STANDPIPE. REFER TO PLUMBING DRAWINGS
P30 ROOF LEADER PIPING. PROVIDE PAINTED STEEL PIPE PROTECTION - 055000.
SCALE: 3/32" = 1'-0"
ISOMETRIC
# DESCRIPTION DATE
UP
76521
A
B
C
4
01
A301
01
A301
3
RAMP DN RAMP UP
NOTE:
REFER TO A130 SERIES
DRAWINGS FOR PARKING
COUNTS AND STRIPING
NOTES.
STAIR 1
ST1-4
ELEVATOR
LOBBY
401
ELEV.
EL1-4
RAMP DOWN
STAIR 2
ST2-4
03
A301
03
A301
02
A202
A120
04
A121
06 02A20101
A202
01A201A122
04
A121
07
48' - 0"24' - 0"36' - 0"36' - 0"24' - 0"48' - 0"
216' - 0"123' - 10"4"61' - 9"61' - 9"08A20107
A201
05A20106
A201
03
A201 04A201860.50 864.83
36' - 4"32' - 0"
A125
07 SIM
EQ.EQ.
P09
P09
P12
P12
P09
P09
P09
P03
P03
P03
P13
P13
TYP. AT EACH
OPENING
TYP. AT EACH
OPENING
P26
ST3-4ST1-4401STAIR 3
ST3-4
GARAGE
FOURTH
FLOOR
400
NOTE:
OFFICE BUILDING IS NOT IN
PROJECT SCOPE.
02
A301
02
A301
8' - 0"12' - 0"
P30
P241' - 6"402VESTIBULE
402
P28
P28
6"8' - 0"12' - 0"
P10
P10
P10 P10
GENERAL PLAN NOTES
A. REFER TO A001-A002 FOR GENERAL NOTES, WALL TYPES, SYMBOLS
AND TYPICAL CONSTRUCTION DETAILS.
B. PROVIDE BULLNOSE CMU AT ALL EXPOSED CMU CORNERS.
C. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM WALLBOARD AT
THE APPARATUS BAY AND ALL ROOMS DIRECTLY OFF OF IT.
D. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM WALLBOARD AT
ALL WET WALLS IN KITCHENS, AND ALL WALLS AND CEILINGS IN
BATHROOMS AND JANITOR CLOSETS.
E. PROVIDE HIGH-IMPACT GYPSUM WALLBOARD AT ALL CORRIDORS,
STAIRCASES AND THE LOBBY.
F. PLAN KEYNOTES APPLY TO SHEETS A101, A102 AND A110.
FIRST LEVEL
0'-0" 828.50 15' - 0".10' - 8".10' - 8".SECOND LEVEL
15'-0" 843.50
THIRD LEVEL
25'-8" 854.17'
FOURTH LEVEL
36'-4" 864.83'
TOP OF RAMP
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A104
FOURTH FLOOR
PLAN
CONSTRUCTION
PLAN
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 1/8" = 1'-0"01 FOURTH FLOOR CONSTRUCTION
PLAN
PLAN KEYNOTES
P01 DASHED LINE INDICATES CANOPY ABOVE.
P02 MIDTOWN OFFICE CANOPY - NOT IN CONTRACT.
P03 4-1/2" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P04 PRECAST CONCRETE STAIRCASE. REFER TO PRECAST DRAWINGS.
P05 MIDTOWN OFFICE BUILDING - NOT IN CONTRACT.
P06 BICYCLE RACK TO BE SARIS STACK RACK 20" SPACING. PROVIDE SPACES FOR
50 BICYCLES TOTAL.
P07 MOP SINK. REFER TO PLUMBING DRAWNGS.
P08 ELEVATOR MACHINE-ROOM-LESS TYPE - REFER TO SPECS. INTERIOR FLOOR
FINISH OF CAB TO BE: DAL TILE, NOIR LINEN P689, 12X12 WITH MAPEI
CHARCOAL 47 GROUT.
P09 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS. COORDINATE LOCATION
WITH PRECAST AND TOPPING SLAB SLOPES.
P10 HOLLOW METAL WINDOW. REFER TO GLAZING ELEVATIONS.
P11 ELEVATOR EQUIPMENT. COORDINATE WITH ELEVATOR SPECS AND MEP
DWGS.
P12 WALL MOUNTED FIRE EXTINGUISHER CABINET - REFER TO SPECS.
P13 GALVANIZED TUBE STEEL GUARDRAIL TYPICAL AT ALL OPENINGS. REFER TO
TYPICAL DETAIL 11/A125.
P14 1-1/2" TUBE STEEL GUARDRAIL W/STAINLESS STEEL CABLES. FERRULES, STUDS.
1-1/2" DIAM. STEEL PIPE HANDRAIL. (TYPICAL ON FLOORS 1-2 ONLY). (PAINT
P1). MOUNT TO SIDE OF PRECAST CONCRETE STAIRS.
P15 1-1/2" DIA. STEEL PIPE GUARDRAIL/HANDRAIL SIDE MOUNTED TO PRECAST
STAIRS (PAINT P1).
P16 1-1/2" DIA. STEEL PIPE HANDRAIL ATTACHED TO PRECAST OR CMU WALL.
P17 PROVIDE 42" TALL GUARDRAIL INFILL AT STOREFRONT OPENINGS AT
LANDINGS AND STAIR RUNS. INSET GUARDRAIL INTO WINDOW OPENING.
TOP OF RAIL TO BE PARALLEL WITH FLOOR OR STAIR RUN.
P18 4" WIDE PAINTED STRIPS AT 45 DEGREES; COLOR - YELLOW.
P19 PAINTED PARKING STRIPE; COLOR - YELLOW. TYPICAL.
P20 ADA PAINTED PARKING GRAPHIC; COLOR - BLUE.
P21 PAINTED DIRECTIONAL ARROW; COLOR - YELLOW.
P22 SLOPE TOPPING SLAB TO TRAIN. 2% MAX.
P23 HATCHED AREA DENOTES TRAFFIC BEARING MEMBRANE INSTALLED ON
CONCRETE DECK ABOVE ENCLOSED SPACE ABOVE. TURN MEMBRANE UP
ADJACENT WALLS 6" MIN.
P24 EXTERIOR BLADE SIGN - COORDINATE WITH SIGN CONSULTANT. PROVIDE
ELECTRICAL. CENTER ON PRE-CAST CONCRETE PANEL.
P25 42" GUARDRAIL CLOSURE AT FIRST FLOOR WITH GATE. PROVIDE HASP AND
LATCH.
P26 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER PLUMBING DRAWINGS.
P27 2-1/4" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P28 PIPE BOLLARD WITH PLATE THRU-BOLTED TO PRECAST GARAGE STRUCTURE.
P29 DRY STANDPIPE. REFER TO PLUMBING DRAWINGS
P30 ROOF LEADER PIPING. PROVIDE PAINTED STEEL PIPE PROTECTION - 055000.
SCALE: 3/32" = 1'-0"
ISOMETRIC
# DESCRIPTION DATE
1 ADLS COMMENTS 5/11/2017
1
1
1
UP
76521
A
B
C
4
01
A301
01
A301
3 03
A301
03
A301
02
A202 02A20101
A202
01A20148' - 0"24' - 0"36' - 0"36' - 0"24' - 0"48' - 0"
216' - 0"123' - 10"4"61' - 9"61' - 9"A121
08 08A20107
A201
05A20106
A201
03
A201 04A20136' - 4"
42' - 8"
871.17 864.83
RAMP DN
P12
02
A301
02
A301
P28
6' - 5"5' - 0"14' - 5"5' - 0"5' - 0"GENERAL PLAN NOTES
A. REFER TO A001-A002 FOR GENERAL NOTES, WALL TYPES, SYMBOLS
AND TYPICAL CONSTRUCTION DETAILS.
B. PROVIDE BULLNOSE CMU AT ALL EXPOSED CMU CORNERS.
C. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM WALLBOARD AT
THE APPARATUS BAY AND ALL ROOMS DIRECTLY OFF OF IT.
D. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM WALLBOARD AT
ALL WET WALLS IN KITCHENS, AND ALL WALLS AND CEILINGS IN
BATHROOMS AND JANITOR CLOSETS.
E. PROVIDE HIGH-IMPACT GYPSUM WALLBOARD AT ALL CORRIDORS,
STAIRCASES AND THE LOBBY.
F. PLAN KEYNOTES APPLY TO SHEETS A101, A102 AND A110.DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A105
FIFTH FLOOR PLAN
CONSTRUCTION
PLAN
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 1/8" = 1'-0"01 CD PLAN 05 - TOP OF RAMP
PLAN KEYNOTES
P01 DASHED LINE INDICATES CANOPY ABOVE.
P02 MIDTOWN OFFICE CANOPY - NOT IN CONTRACT.
P03 4-1/2" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P04 PRECAST CONCRETE STAIRCASE. REFER TO PRECAST DRAWINGS.
P05 MIDTOWN OFFICE BUILDING - NOT IN CONTRACT.
P06 BICYCLE RACK TO BE SARIS STACK RACK 20" SPACING. PROVIDE SPACES FOR
50 BICYCLES TOTAL.
P07 MOP SINK. REFER TO PLUMBING DRAWNGS.
P08 ELEVATOR MACHINE-ROOM-LESS TYPE - REFER TO SPECS. INTERIOR FLOOR
FINISH OF CAB TO BE: DAL TILE, NOIR LINEN P689, 12X12 WITH MAPEI
CHARCOAL 47 GROUT.
P09 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS. COORDINATE LOCATION
WITH PRECAST AND TOPPING SLAB SLOPES.
P10 HOLLOW METAL WINDOW. REFER TO GLAZING ELEVATIONS.
P11 ELEVATOR EQUIPMENT. COORDINATE WITH ELEVATOR SPECS AND MEP
DWGS.
P12 WALL MOUNTED FIRE EXTINGUISHER CABINET - REFER TO SPECS.
P13 GALVANIZED TUBE STEEL GUARDRAIL TYPICAL AT ALL OPENINGS. REFER TO
TYPICAL DETAIL 11/A125.
P14 1-1/2" TUBE STEEL GUARDRAIL W/STAINLESS STEEL CABLES. FERRULES, STUDS.
1-1/2" DIAM. STEEL PIPE HANDRAIL. (TYPICAL ON FLOORS 1-2 ONLY). (PAINT
P1). MOUNT TO SIDE OF PRECAST CONCRETE STAIRS.
P15 1-1/2" DIA. STEEL PIPE GUARDRAIL/HANDRAIL SIDE MOUNTED TO PRECAST
STAIRS (PAINT P1).
P16 1-1/2" DIA. STEEL PIPE HANDRAIL ATTACHED TO PRECAST OR CMU WALL.
P17 PROVIDE 42" TALL GUARDRAIL INFILL AT STOREFRONT OPENINGS AT
LANDINGS AND STAIR RUNS. INSET GUARDRAIL INTO WINDOW OPENING.
TOP OF RAIL TO BE PARALLEL WITH FLOOR OR STAIR RUN.
P18 4" WIDE PAINTED STRIPS AT 45 DEGREES; COLOR - YELLOW.
P19 PAINTED PARKING STRIPE; COLOR - YELLOW. TYPICAL.
P20 ADA PAINTED PARKING GRAPHIC; COLOR - BLUE.
P21 PAINTED DIRECTIONAL ARROW; COLOR - YELLOW.
P22 SLOPE TOPPING SLAB TO TRAIN. 2% MAX.
P23 HATCHED AREA DENOTES TRAFFIC BEARING MEMBRANE INSTALLED ON
CONCRETE DECK ABOVE ENCLOSED SPACE ABOVE. TURN MEMBRANE UP
ADJACENT WALLS 6" MIN.
P24 EXTERIOR BLADE SIGN - COORDINATE WITH SIGN CONSULTANT. PROVIDE
ELECTRICAL. CENTER ON PRE-CAST CONCRETE PANEL.
P25 42" GUARDRAIL CLOSURE AT FIRST FLOOR WITH GATE. PROVIDE HASP AND
LATCH.
P26 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER PLUMBING DRAWINGS.
P27 2-1/4" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P28 PIPE BOLLARD WITH PLATE THRU-BOLTED TO PRECAST GARAGE STRUCTURE.
P29 DRY STANDPIPE. REFER TO PLUMBING DRAWINGS
P30 ROOF LEADER PIPING. PROVIDE PAINTED STEEL PIPE PROTECTION - 055000.
# DESCRIPTION DATE
1 ADLS COMMENTS 5/11/2017
1
1
1
ROOF TYPES LEGEND
RT:
RL:XX'
X ROOF TYPE
APPROXIMATE ROOF HEIGHT
60 MIL FULLY ADHERED EPDM MEMBRANE ROOFING SYSTEM OVER
TAPERED POLYISOCYANURATE INSULATION OVER CONCRETE DECK.
RT1:
TAPERED INSULATION CRICKETS
1/2":12" MIN. SLOPE.
GENERAL ROOF NOTES
A. PROVIDE MANUFACTURE'S STANDARD DETAILS WHERE MECHANICAL
EQUIPMENT OCCURS, COORDINATE WITH ARCHITECTURE AND MEP.
B. SEE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR
ADDITIONAL ROOF PENETRATION REQUIREMENTS.
76521
A
B
C
4
01
A301
01
A301
3 03
A301
03
A301
02
A202 02A20101
A202
01A20108A20107
A201
05A20106
A201
03
A201 04A2011/8" : 12"
1/8" : 12"
RT:
RL:
RT1
RT:
RL:
RT1
RT:
RL:
RT1
02
A106
03
A106
02
A106
1/8" : 12"1/8" : 12"
R02
R02
R01
R01
R01
R03
R01
R01
R01
R03
R01
R01
R02
R02
R01 R01
03
A106
04
A106
04
A106
02
A106
1/8" : 12"04
A106
03
A106
02
A301
02
A301
24' - 0"10' - 7"3' - 2"16' - 9"35' - 11"
15' - 0"20' - 11"19' - 11"20' - 11"
35' - 11"15' - 10 3/8"3' - 2"19' - 0 3/8"R02
R03
C
EPDM ROOF MEMBRANE
EPDM MEMBRANE TERMINATION AS REQUIRED
FOR ROOF EDGE
SPECIFIED 6" ALUMINUM ROOF EDGE WITH
EXTENSION
P.T. WOOD BLOCKING TO PROVIDE
CONTINUOUS LEVEL BASE FOR ROOF EDGE TRIM
TAPERED INSULATION - REFER TO ROOF
PLAN FOR DIRECTION OF SLOPE
PRE-CAST CONCRETE ROOF PANEL
(PAINT EXPOSED PORTIONS OF PANEL)
P.T. 2x6
4"PRE-CAST CONCRETE WALL PANEL
7
EPDM ROOF MEMBRANE
EPDM MEMBRANE TERMINATION
SPECIFIED 6" ALUMINUM ROOF EDGE WITH
EXTENSION
P.T. WOOD BLOCKING TO PROVIDE
CONTINUOUS LEVEL BASE FOR ROOF EDGE TRIM
TAPERED INSULATION - REFER TO ROOF
PLAN FOR DIRECTION OF SLOPE
PRE-CAST CONCRETE ROOF PANEL
(PAINT EXPOSED PORTIONS OF PANEL)
P.T. 2x6
4"PRE-CAST CONCRETE WALL PANEL
EPDM ROOF MEMBRANE
6" x 6" PREFINISHED ALUMINUM GUTTER
P.T. WOOD BLOCKING TO PROVIDE
CONTINUOUS LEVEL BASE FOR ROOF EDGE TRIM
TAPERED INSULATION - REFER TO ROOF
PLAN FOR DIRECTION OF SLOPE
PRE-CAST CONCRETE ROOF PANEL
(PAINT EXPOSED PORTIONS OF PANEL P1)
P.T. 2x6
WRAP MEMBRANE INTO GUTTER
PRE-CAST CONCRETE WALL PANEL
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
JK
CH
03/28/2017
A106
ROOF PLAN
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032ROOF PLAN KEYNOTES
R01 PRE-MANUFACTURED ALUMINUM ROOF EDGE FASCIA TO MEET ANSI/SPRI
ES1 (077100).
R02 PRE-MANUFACTURED ALUMINUM GUTTER AND DOWNSPOUT -
COORDINATE DOWNSPOUT LOCATION WITH MEP DWGS.
R03 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER TO PLUMBING DRAWINGS.
SCALE: 1/8" = 1'-0"01 CD PLAN 06 - ROOF
SCALE: 1 1/2" = 1'-0"02 ROOF DETAIL - TYP. PERIMETER
SCALE: 1 1/2" = 1'-0"03 ROOF DETAIL - TOP OF SLOPE
SCALE: 1 1/2" = 1'-0"04 ROOF DETAIL - GUTTER
# DESCRIPTION DATE
1 ADLS COMMENTS 5/11/2017
1
1
1
7
A
STAIR 1
ST1-1
ELEV.
EL1-1
06
A120
W9
05
A120
07
A120
P03 TYP.10"9' - 0"9"8'-8" CLR SHAFT9"P089"4' - 0"3' - 6"1' - 2"7 5/8"7'-2 3/8" CLR SHAFT 10"
8' - 8"
10"
PRECAST PANEL w/
SOLID CONCRETE
INFILL LOCATED
BEHIND
P17 TYP. IN
STAIRWELLS
100
P27
1' - 0"
P14
P04
P16
P25UP
P29
7
A
STAIR 1
ST1-2
ELEV.
EL1-2
06
A120
05
A120
07
A120
8"3' - 4"
10"
7'-2 3/8" CLR. SHAFT
7 5/8"10"9' - 0"9"8'-8" CLR. SHAFT9"P17
P03
P03
PRECAST PANEL w/
SOLID CONCRETE
INFILL LOCATED
BEHIND
TYP. IN
STAIRWELLS
TYP. IN
STAIRWELLS
TYP. IN
STAIRWELLS
P27
P089"4' - 0"3' - 6"1' - 2"9"19' - 4"
W9ST1-24' - 1"10"4' - 1"5' - 6 1/2"8' - 3"5' - 6 1/2"
1'- 0".
P16
P15
P04
1' - 0"
P17
UPDNP29
7
A
STAIR 1
ST1-3
ELEV.
EL1-3
06
A120
05
A120
07
A120
8"3' - 4"
7 5/8"7'-2 3/8" CLR. SHAFT 10"
8' - 8"9"9' - 1"9"8' - 8"9"9"19' - 4"10"1' - 2"3' - 6"4' - 0"9"ST1-3P03
P03P17
W9
PRECAST PANEL w/
SOLID CONCRETE
INFILL LOCATED
BEHIND
TYP. IN
STAIRWELLS
TYP. IN
STAIRWELLS
P17
P08
P27
1' - 0"
1' - 0".
5' - 6 1/2"8' - 3"5' - 6 1/2"4' - 1"10"4' - 1"P16
P04
P15 UPDNP29
7
A
ELEVATOR
LOBBY
401
ELEV.
EL1-4
STAIR 1
ST1-4
06
A120
05
A120
07
A120
P111' - 2"3' - 6"2' - 2"1' - 10"9"P08 10"9' - 0"9"8'-8" CLR SHAFT9"7 5/8"7'-2 3/8" CLR SHAFT 10"
1' - 4"3' - 4"7' - 10 7/8"8' - 4 1/4"
9"9"3' - 4"
9"19' - 4"10"ST1-4401P03
PRECAST PANEL w/
SOLID CONCRETE
INFILL LOCATED
BEHINDW9
P17
P17
TYP. IN
STAIRWELLS
TYP. IN
STAIRWELLS
P27
5' - 6 1/2"8' - 3"5' - 6 1/2"9"4' - 1"10"4' - 1"1' - 0".
P15
P04
P16
DNP29
P10
2' - 10"4' - 0"2' - 7"9' - 9"10"P28
FIRST FLOOR
0' - 0"
SECOND FLOOR
15' - 0"
7
THIRD FLOOR
25' - 8"
FOURTH FLOOR
36' - 4"
ROOF
50' - 4"15' - 0"10' - 8"10' - 8"05
A120A106
02
SIM.
A310
04
SIM.17 EQ. R'S = 9' - 8".10 EQ. R'S = 5' - 4".10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"5' - 6 1/2"9 T'S @ 11" = 8' - 3"5' - 6 1/2"
16 T'S @ 11" = 14' - 8"5' - 6 1/2"
P14
P04
P15
P16
FROM LEVEL 1 TO 2
P04
P15
FIRST FLOOR
0' - 0"
SECOND FLOOR
15' - 0"
7
THIRD FLOOR
25' - 8"
FOURTH FLOOR
36' - 4"
ROOF
50' - 4"
ELEVATOR PIT
-5' - 0"
A310
02
A310
03 13' - 1"3' - 2 7/8"14' - 0"ELEVATOR HOISTWAY BEAM -
REFER TO STRUCTURAL DWGS.7' - 0"5'-0" PIT DEPTH6' - 6"1' - 11"8' - 5"6' - 6"1' - 11"8' - 5"6' - 6"1' - 11"8' - 5"6' - 6"1' - 11"8' - 5"SPANDREL
GLAZING IN 2-1/4"
STOREFRONT FRAME
PRECAST PANEL w/
SOLID CONCRETE
INFILL LOCATED
BEHIND
A106
02
SIM.
A310
05
FIRST FLOOR
0' - 0"
SECOND FLOOR
15' - 0"
A
THIRD FLOOR
25' - 8"
FOURTH FLOOR
36' - 4"
ROOF
50' - 4"
06
A120
07
A120A106
02
SIM.
A310
04
SIM.6' - 6"1' - 11"8' - 5"6' - 6"1' - 11"8' - 5"6' - 6"1' - 11"8' - 5"6' - 6"1' - 11"8' - 5"7' - 0"2' - 2"3' - 6"
P16
P15
P16
P15
P04
P04
P14
P16
P04
4' - 1"10"4' - 1"DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A120
STAIR 1 PLANS
AND SECTIONS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032PLAN KEYNOTES
P01 DASHED LINE INDICATES CANOPY ABOVE.
P02 MIDTOWN OFFICE CANOPY - NOT IN CONTRACT.
P03 4-1/2" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P04 PRECAST CONCRETE STAIRCASE. REFER TO PRECAST DRAWINGS.
P05 MIDTOWN OFFICE BUILDING - NOT IN CONTRACT.
P06 BICYCLE RACK TO BE SARIS STACK RACK 20" SPACING. PROVIDE SPACES FOR
50 BICYCLES TOTAL.
P07 MOP SINK. REFER TO PLUMBING DRAWNGS.
P08 ELEVATOR MACHINE-ROOM-LESS TYPE - REFER TO SPECS. INTERIOR FLOOR
FINISH OF CAB TO BE: DAL TILE, NOIR LINEN P689, 12X12 WITH MAPEI
CHARCOAL 47 GROUT.
P09 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS. COORDINATE LOCATION
WITH PRECAST AND TOPPING SLAB SLOPES.
P10 HOLLOW METAL WINDOW. REFER TO GLAZING ELEVATIONS.
P11 ELEVATOR EQUIPMENT. COORDINATE WITH ELEVATOR SPECS AND MEP
DWGS.
P12 WALL MOUNTED FIRE EXTINGUISHER CABINET - REFER TO SPECS.
P13 GALVANIZED TUBE STEEL GUARDRAIL TYPICAL AT ALL OPENINGS. REFER TO
TYPICAL DETAIL 11/A125.
P14 1-1/2" TUBE STEEL GUARDRAIL W/STAINLESS STEEL CABLES. FERRULES, STUDS.
1-1/2" DIAM. STEEL PIPE HANDRAIL. (TYPICAL ON FLOORS 1-2 ONLY). (PAINT
P1). MOUNT TO SIDE OF PRECAST CONCRETE STAIRS.
P15 1-1/2" DIA. STEEL PIPE GUARDRAIL/HANDRAIL SIDE MOUNTED TO PRECAST
STAIRS (PAINT P1).
P16 1-1/2" DIA. STEEL PIPE HANDRAIL ATTACHED TO PRECAST OR CMU WALL.
P17 PROVIDE 42" TALL GUARDRAIL INFILL AT STOREFRONT OPENINGS AT
LANDINGS AND STAIR RUNS. INSET GUARDRAIL INTO WINDOW OPENING.
TOP OF RAIL TO BE PARALLEL WITH FLOOR OR STAIR RUN.
P18 4" WIDE PAINTED STRIPS AT 45 DEGREES; COLOR - YELLOW.
P19 PAINTED PARKING STRIPE; COLOR - YELLOW. TYPICAL.
P20 ADA PAINTED PARKING GRAPHIC; COLOR - BLUE.
P21 PAINTED DIRECTIONAL ARROW; COLOR - YELLOW.
P22 SLOPE TOPPING SLAB TO TRAIN. 2% MAX.
P23 HATCHED AREA DENOTES TRAFFIC BEARING MEMBRANE INSTALLED ON
CONCRETE DECK ABOVE ENCLOSED SPACE ABOVE. TURN MEMBRANE UP
ADJACENT WALLS 6" MIN.
P24 EXTERIOR BLADE SIGN - COORDINATE WITH SIGN CONSULTANT. PROVIDE
ELECTRICAL. CENTER ON PRE-CAST CONCRETE PANEL.
P25 42" GUARDRAIL CLOSURE AT FIRST FLOOR WITH GATE. PROVIDE HASP AND
LATCH.
P26 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER PLUMBING DRAWINGS.
P27 2-1/4" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P28 PIPE BOLLARD WITH PLATE THRU-BOLTED TO PRECAST GARAGE STRUCTURE.
P29 DRY STANDPIPE. REFER TO PLUMBING DRAWINGS
P30 ROOF LEADER PIPING. PROVIDE PAINTED STEEL PIPE PROTECTION - 055000.
SCALE: 1/4" = 1'-0"01 ENLARGED STAIR 1-1
SCALE: 1/4" = 1'-0"02 ENLARGED STAIR 1-2
SCALE: 1/4" = 1'-0"03 ENLARGED STAIR 1-3
SCALE: 1/4" = 1'-0"04 ENLARGED STAIR 1-4
SCALE: 1/4" = 1'-0"06 STAIR 1 N-S SECTION
SCALE: 1/4" = 1'-0"07 ELEVATOR 1 N-S SECTION
SCALE: 1/4" = 1'-0"05 STAIR 1 E-W SECTION
# DESCRIPTION DATE
1 ADLS COMMENTS 5/11/2017
1
1
1
1
7
C
STAIR 2
ST2-1 02
A121
03
A121
9"19' - 4"10"4"6"9' - 0"9"ST2-1AP03
P03
3' - 4"8"10"ST2-11' - 0"
6' - 3 1/2"6' - 1"8' - 6 1/2"4' - 11"10"4' - 10"P16
P04
P14
P17 TYP. AT
STAIRS
P25UP P29
7
C
STAIR 2
ST2-2
02
A121
03
A121
19' - 4"10"4"6"9' - 0"9"ST2-2P03
P03P17
P17
TYP. IN
STAIRWELLS
TYP. IN
STAIRWELLS
9"8"3' - 4"
1' - 0".
1' - 0"
6' - 3 1/2"8' - 3"6' - 4 1/2"4' - 11"10"4' - 10"P16
P15
P04 DNUPP29
7
C
02
A121
03
A121
4"6"9' - 0"9"9"8"3' - 4"
9"19' - 4"10"
P03
P03
P17
P17TYP. IN
STAIRWELLSST2-31' - 0"
1' - 0".4' - 11"10"4' - 10"6' - 3 1/2"8' - 3"6' - 4 1/2"
P16
P15
P04 DNUPP29
7
C
02
A121
03
A121
P17
P03
P03
STAIR 2
ST2-4 4' - 10"10"4' - 11"1' - 0".
P16
P17
P04
P17DN P29 8' - 5 3/8"10' - 3"4"1' - 6"3' - 4"8' - 6"4' - 0"3' - 7"
20' - 11"19' - 0 3/8"2' - 10"4' - 0"402
VESTIBULE
402
P10
P10
P28
P10
FIRST FLOOR
0' - 0"
SECOND FLOOR
15' - 0"
7
THIRD FLOOR
25' - 8"
FOURTH FLOOR
36' - 4"
ROOF
50' - 4"
03
A121 A106
02
SIM.
A310
04 SIM.
A310
05
SIM.10' - 8"10' - 8"15' - 0"10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 9 1/4"10 EQ. R'S = 5' - 9 1/4"6 EQ. R'S = 3' - 5 1/2"P14
P16
P04
P15
P04
P16
P16
P15
P16
FIRST FLOOR
0' - 0"
SECOND FLOOR
15' - 0"
C
THIRD FLOOR
25' - 8"
FOURTH FLOOR
36' - 4"
ROOF
50' - 4"
02
A121 A106
02
SIM.
A310
04
SIM.
A310
05
SIM.
03
A106
1
C
09
A121
4' - 11"18 T'S @ 11" = 16' - 6"3' - 4"3' - 8"
42" GUARDRAIL FOR CANE
DETECTION LOCATED AT 6'-8"
CLEAR
UP
1
C
09
A121
3' - 1 1/4"4' - 1 1/2"18' - 0"4' - 11"DN
C
LEVEL 3.5
32' - 0"
LEVEL 4.5
42' - 8"
19 TREADS @12"4' - 11"19 EQ. R'S = 10' - 8"4' - 0 3/4"6 3/4"P17
P04
P15
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A121
STAIR 2 AND 4
PLANS AND
SECTIONS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 1/4" = 1'-0"01 ENLARGED STAIR 2-1
SCALE: 1/4" = 1'-0"04 ENLARGED STAIR 2-2
SCALE: 1/4" = 1'-0"05 ENLARGED STAIR 2-3
SCALE: 1/4" = 1'-0"06 ENLARGED STAIR 2-4
SCALE: 1/4" = 1'-0"02 STAIR 2 N-S SECTION
SCALE: 1/4" = 1'-0"03 STAIR 2 E-W SECTION
SCALE: 1/4" = 1'-0"07 ENLARGED STAIR 4-4
SCALE: 1/4" = 1'-0"08 ENLARGED STAIR 4-5
SCALE: 1/4" = 1'-0"09 STAIR 4 E-W SECTION
PLAN KEYNOTES
P01 DASHED LINE INDICATES CANOPY ABOVE.
P02 MIDTOWN OFFICE CANOPY - NOT IN CONTRACT.
P03 4-1/2" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P04 PRECAST CONCRETE STAIRCASE. REFER TO PRECAST DRAWINGS.
P05 MIDTOWN OFFICE BUILDING - NOT IN CONTRACT.
P06 BICYCLE RACK TO BE SARIS STACK RACK 20" SPACING. PROVIDE SPACES FOR
50 BICYCLES TOTAL.
P07 MOP SINK. REFER TO PLUMBING DRAWNGS.
P08 ELEVATOR MACHINE-ROOM-LESS TYPE - REFER TO SPECS. INTERIOR FLOOR
FINISH OF CAB TO BE: DAL TILE, NOIR LINEN P689, 12X12 WITH MAPEI
CHARCOAL 47 GROUT.
P09 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS. COORDINATE LOCATION
WITH PRECAST AND TOPPING SLAB SLOPES.
P10 HOLLOW METAL WINDOW. REFER TO GLAZING ELEVATIONS.
P11 ELEVATOR EQUIPMENT. COORDINATE WITH ELEVATOR SPECS AND MEP
DWGS.
P12 WALL MOUNTED FIRE EXTINGUISHER CABINET - REFER TO SPECS.
P13 GALVANIZED TUBE STEEL GUARDRAIL TYPICAL AT ALL OPENINGS. REFER TO
TYPICAL DETAIL 11/A125.
P14 1-1/2" TUBE STEEL GUARDRAIL W/STAINLESS STEEL CABLES. FERRULES, STUDS.
1-1/2" DIAM. STEEL PIPE HANDRAIL. (TYPICAL ON FLOORS 1-2 ONLY). (PAINT
P1). MOUNT TO SIDE OF PRECAST CONCRETE STAIRS.
P15 1-1/2" DIA. STEEL PIPE GUARDRAIL/HANDRAIL SIDE MOUNTED TO PRECAST
STAIRS (PAINT P1).
P16 1-1/2" DIA. STEEL PIPE HANDRAIL ATTACHED TO PRECAST OR CMU WALL.
P17 PROVIDE 42" TALL GUARDRAIL INFILL AT STOREFRONT OPENINGS AT
LANDINGS AND STAIR RUNS. INSET GUARDRAIL INTO WINDOW OPENING.
TOP OF RAIL TO BE PARALLEL WITH FLOOR OR STAIR RUN.
P18 4" WIDE PAINTED STRIPS AT 45 DEGREES; COLOR - YELLOW.
P19 PAINTED PARKING STRIPE; COLOR - YELLOW. TYPICAL.
P20 ADA PAINTED PARKING GRAPHIC; COLOR - BLUE.
P21 PAINTED DIRECTIONAL ARROW; COLOR - YELLOW.
P22 SLOPE TOPPING SLAB TO TRAIN. 2% MAX.
P23 HATCHED AREA DENOTES TRAFFIC BEARING MEMBRANE INSTALLED ON
CONCRETE DECK ABOVE ENCLOSED SPACE ABOVE. TURN MEMBRANE UP
ADJACENT WALLS 6" MIN.
P24 EXTERIOR BLADE SIGN - COORDINATE WITH SIGN CONSULTANT. PROVIDE
ELECTRICAL. CENTER ON PRE-CAST CONCRETE PANEL.
P25 42" GUARDRAIL CLOSURE AT FIRST FLOOR WITH GATE. PROVIDE HASP AND
LATCH.
P26 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER PLUMBING DRAWINGS.
P27 2-1/4" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P28 PIPE BOLLARD WITH PLATE THRU-BOLTED TO PRECAST GARAGE STRUCTURE.
P29 DRY STANDPIPE. REFER TO PLUMBING DRAWINGS
P30 ROOF LEADER PIPING. PROVIDE PAINTED STEEL PIPE PROTECTION - 055000.
# DESCRIPTION DATE
1 ADLS COMMENTS 5/11/2017
1
1
1
1
A
STAIR 3
ST3-1
ELECTRICAL
101
05
A122
5"19' - 9"9"6' - 8"
06
A122
ST3-1
ST3-1A10110"9' - 0"9"8"W8W88"3' - 4"
3' - 4"9' - 9"P03P17TYP. IN
STAIRWELLS
2' - 2"3' - 4"3' - 6"P25
1' - 0"
P16
P04
P14
5' - 6 1/2"8' - 3"5' - 6 1/2"4' - 1"10"4' - 1"UPP29
1
A
05
A122
06
A122
ST3-28"3' - 4"
5"19' - 9"9"3' - 0"3' - 4"3' - 6"STAIR 3
ST3-2
ROUGH OPENING FOR
DOOR BY RESIDENTIAL
DEVELOPER
5' - 6 1/2"8' - 3"5' - 6 1/2"4' - 1"10"4' - 1"1' - 0"
1' - 0".
P16
P04
P15
P17 TYP. IN
STAIRWELLS
UPDNP29
1
A
05
A122
06
A122
5"19' - 9"9"
8"3' - 4"10"9' - 0"9"ST3-3STAIR 3
ST3-3
1' - 0"
1' - 0".
5' - 6 1/2"8' - 3"5' - 6 1/2"4' - 1"10"4' - 1"P04
P15
P16ROUGH OPENING FOR
DOOR BY RESIDENTIAL
DEVELOPER
P17 TYP. IN
STAIRWELLS
UPDNP29
1
A
05
A122
06
A122
5"19' - 9"9"10"9' - 0"9"9"3' - 4"ST3-4P26
STAIR 3
ST3-4
4' - 0"1' - 6"4' - 1"10"4' - 1"P15
P16
P04
5' - 6 1/2"8' - 3"5' - 6 1/2"
1' - 0".DNP29
P10
FIRST FLOOR
0' - 0"
1
LOW PARAPET
40' - 4"
LEVEL 1.5
10' - 8"
LEVEL 2.5
21' - 4"
LEVEL 3.5
32' - 0"
06
A122
B/PRECAST 45' - 0"
828.50
A310
04
A106
02
5' - 11 1/2"8' - 3"5' - 6 1/2"
839.17
849.83
860.50
10' - 8"10' - 8"10' - 8"P14
P17
P17
P04
P17
P15
P15
10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"10 EQ. R'S = 5' - 4"FIRST FLOOR
0' - 0"
A
05
A122
LEVEL 1.5
10' - 8"
LEVEL 2.5
21' - 4"
LEVEL 3.5
32' - 0"
LEVEL 4.5
42' - 8"
A310
04
A106
02
4' - 1"10"4' - 1"
P04
P16
P15
P14
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A122
STAIR 3 PLANS
AND SECTIONS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 1/4" = 1'-0"01 ENLARGED STAIR 3-1
SCALE: 1/4" = 1'-0"02 ENLARGED STAIR 3-2
SCALE: 1/4" = 1'-0"03 ENLARGED STAIR 3-3
SCALE: 1/4" = 1'-0"04 ENLARGED STAIR 3-4
SCALE: 1/4" = 1'-0"05 STAIR 3 N-S SECTION
SCALE: 1/4" = 1'-0"06 STAIR 3 E-W SECTION
PLAN KEYNOTES
P01 DASHED LINE INDICATES CANOPY ABOVE.
P02 MIDTOWN OFFICE CANOPY - NOT IN CONTRACT.
P03 4-1/2" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P04 PRECAST CONCRETE STAIRCASE. REFER TO PRECAST DRAWINGS.
P05 MIDTOWN OFFICE BUILDING - NOT IN CONTRACT.
P06 BICYCLE RACK TO BE SARIS STACK RACK 20" SPACING. PROVIDE SPACES FOR
50 BICYCLES TOTAL.
P07 MOP SINK. REFER TO PLUMBING DRAWNGS.
P08 ELEVATOR MACHINE-ROOM-LESS TYPE - REFER TO SPECS. INTERIOR FLOOR
FINISH OF CAB TO BE: DAL TILE, NOIR LINEN P689, 12X12 WITH MAPEI
CHARCOAL 47 GROUT.
P09 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS. COORDINATE LOCATION
WITH PRECAST AND TOPPING SLAB SLOPES.
P10 HOLLOW METAL WINDOW. REFER TO GLAZING ELEVATIONS.
P11 ELEVATOR EQUIPMENT. COORDINATE WITH ELEVATOR SPECS AND MEP
DWGS.
P12 WALL MOUNTED FIRE EXTINGUISHER CABINET - REFER TO SPECS.
P13 GALVANIZED TUBE STEEL GUARDRAIL TYPICAL AT ALL OPENINGS. REFER TO
TYPICAL DETAIL 11/A125.
P14 1-1/2" TUBE STEEL GUARDRAIL W/STAINLESS STEEL CABLES. FERRULES, STUDS.
1-1/2" DIAM. STEEL PIPE HANDRAIL. (TYPICAL ON FLOORS 1-2 ONLY). (PAINT
P1). MOUNT TO SIDE OF PRECAST CONCRETE STAIRS.
P15 1-1/2" DIA. STEEL PIPE GUARDRAIL/HANDRAIL SIDE MOUNTED TO PRECAST
STAIRS (PAINT P1).
P16 1-1/2" DIA. STEEL PIPE HANDRAIL ATTACHED TO PRECAST OR CMU WALL.
P17 PROVIDE 42" TALL GUARDRAIL INFILL AT STOREFRONT OPENINGS AT
LANDINGS AND STAIR RUNS. INSET GUARDRAIL INTO WINDOW OPENING.
TOP OF RAIL TO BE PARALLEL WITH FLOOR OR STAIR RUN.
P18 4" WIDE PAINTED STRIPS AT 45 DEGREES; COLOR - YELLOW.
P19 PAINTED PARKING STRIPE; COLOR - YELLOW. TYPICAL.
P20 ADA PAINTED PARKING GRAPHIC; COLOR - BLUE.
P21 PAINTED DIRECTIONAL ARROW; COLOR - YELLOW.
P22 SLOPE TOPPING SLAB TO TRAIN. 2% MAX.
P23 HATCHED AREA DENOTES TRAFFIC BEARING MEMBRANE INSTALLED ON
CONCRETE DECK ABOVE ENCLOSED SPACE ABOVE. TURN MEMBRANE UP
ADJACENT WALLS 6" MIN.
P24 EXTERIOR BLADE SIGN - COORDINATE WITH SIGN CONSULTANT. PROVIDE
ELECTRICAL. CENTER ON PRE-CAST CONCRETE PANEL.
P25 42" GUARDRAIL CLOSURE AT FIRST FLOOR WITH GATE. PROVIDE HASP AND
LATCH.
P26 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER PLUMBING DRAWINGS.
P27 2-1/4" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P28 PIPE BOLLARD WITH PLATE THRU-BOLTED TO PRECAST GARAGE STRUCTURE.
P29 DRY STANDPIPE. REFER TO PLUMBING DRAWINGS
P30 ROOF LEADER PIPING. PROVIDE PAINTED STEEL PIPE PROTECTION - 055000.
# DESCRIPTION DATE
1 ADLS COMMENTS 5/11/2017
1
1
3' - 6"3' - 0"3"3"ø 0' - 6"7"1' - 0"1 1/2" TUBE STEELRAILS - PAINTED1/4" DIA. STAINLESS STEEL CABLE w/FERRULES AND STUDSPRE-CAST CONCRETE STRINGERAND LANDING1-1/2" DIA. STEEL HAND RAIL - PAINTED5'- 0" MAX.3 1/2"3/4"3/4"5"3/4"3"5"1/4" PAINTED STEEL CORNER PLATE w/FASTENER (4 ANCHORS IN EACH STEELPLATE w/2" min EMBEDMENT)5"3/4"3 1/2"3/4"5"3/4"1/4" PAINTED STEEL CORNER PLATE w/FASTENER (4 ANCHORS IN EACH STEELPLATE w/2" min EMBEDMENT)3 1/2"3/4"3/4"8"3/4"6 1/2"3/4"5"3"1/4" PAINTED STEEL PLATE w/FASTENER (4 ANCHORS IN EACH STEELPLATE w/2" min EMBEDMENT)1/4" PAINTED STEEL PLATE w/FASTENER (4 ANCHORS IN EACH STEELPLATE w/2" min EMBEDMENT)PRE-CAST CONCRETESTRINGER ANDLANDINGø 0' - 6"4" O.C. MAX1-1/2" DIA. STEEL GUARDAND HANDRAIL w/1/2"PICKETS (PAINTED)1/4" PAINTED STEELBASE PLATE w/FASTENER(TYPICAL INTERMEDIATE CONDITION)1-1/2" DIA. STEEL GUARDAND HAND RAIL w/ 1/2"PICKETS (PAINTED).PRE-CAST CONCRETESTRINGER AND LANDING3"1 1/2"ø 0' - 6"ø 0' - 4"1/4" PAINTED STEELPLATE w/FASTENER (4 ANCHORS IN EACHSTEEL PLATE w/2" min EMBEDMENT)3 1/2"3/4"3/4"5"3/4"3"5"1 1/2" O.D. STEEL PIPE RAILS - PAINTED1/2" DIA. STEEL BAR PICKETS - PAINTED1-1/2" DIA. STEEL GUARD ANDHAND RAIL (PAINTED)3"4' - 2"PRE-CAST CONCRETE STAIR ANDLANDING1 1/2" O.D. STEEL PIPEHANDRAIL - PAINTED3' - 0"3"3/4"3 1/2"3/4"1/4" PAINTED STEELPLATE w/FASTENER (4 ANCHORS IN EACHSTEEL PLATE w/2" min EMBEDMENT)ANCHOR PER MANUFACTURERREQUIREMENTS1-1/2" DIA. STEEL PIPEHANDRAIL (PAINT)PRE-CAST CONCRETE PANELPRE-CAST CONCRETESTRINGER ANDLANDINGø 0' - 6"1-1/2" TUBE STEELGUARDRAIL3"3"1/4" STAINLESS STEELCABLE w/FERRULES ANDSTUDS7"1' - 0"1/4" PAINTED STEELBASE PLATE w/FASTENER(TYPICAL INTERMEDIATE CONDITION)1-1/2" TUBE STEEL GUARDRAILPRE-CAST CONCRETESTRINGER AND LANDING3"1 1/2"ø 0' - 6"1/4" STAINLESS STEELCABLE w/FERRULES AND STUDS3"3"3"3"7"1' - 0"1/4" PAINTED STEEL CORNERPLATE w/FASTENER (4 ANCHORS IN EACHSTEEL PLATE w/2" min EMBEDMENT)1-1/2' DIA. GALVANIZED STEELPIPE GUARDRAIL w/1/2" PICKETS@ 4" o.c.PRE-CAST SILL (BELOW)PRE-CAST CONCRETE PANEL4" TYP.GALVANIZED STEEL PLATE w/FASTENERS (ATTACH AT EACHCORNERS OF GUARDRAIL)5'-2 7/8" (TYP) V.I.F.4'-2 7/8" (TYP)4"4"4 1/2"3' - 7 1/2"4' - 0"4" o.c. MAX1-1/2' DIA. GALVANIZED STEELPIPE GUARDRAIL w/1/2" PICKETS@ 4" o.c.GALVANIZED STEEL PLATE w/FASTENERS (ATTACH AT EACHCORNERS OF GUARDRAIL)5-2 7/8" (TYP.) V.I.F.1 1/2" TUBE STEEL GUARDRAIL - PAINTED1/4" STAINLESS STEEL CABLE w/FERRULES AND STUDS1-1/2" DIA. STEEL GUARD ANDHAND RAIL (PAINTED)PRE-CAST CONCRETE STAIR ANDLANDING1 1/2" O.D. STEEL PIPEHANDRAIL - PAINTED3' - 0"3"3' - 6"3"3"1/4" PAINTED STEELPLATE w/FASTENER (4 ANCHORS IN EACHSTEEL PLATE w/2" min EMBEDMENT)3"5"3 1/2"3/4"3/4"1 1/2" O.D. STEEL PIPE GUARDRAILS - PAINTED1/2" DIA. STEEL BAR PICKETS - PAINTEDPRE-CAST CONCRETE STRINGERAND LANDING5'- 0" MAX1-1/2" DIA. STEEL HAND RAIL - PAINTEDø 0' - 6"3' - 0"3' - 6"4" O.C. MAX7"1' - 0"3 1/2"3/4"3/4"5"3/4"3"5"1/4" PAINTED STEEL CORNER PLATE w/FASTENER (4 ANCHORS IN EACH STEELPLATE w/2" min EMBEDMENT)3 1/2"3/4"3/4"8"3/4"6 1/2"3/4"5"3"1/4" PAINTED STEEL PLATE w/FASTENER (4 ANCHORS IN EACH STEELPLATE w/2" min EMBEDMENT)1/4" PAINTED STEEL PLATE w/FASTENER (4 ANCHORS IN EACH STEELPLATE w/2" min EMBEDMENT)5"3/4"3 1/2"3/4"5"3/4"1/4" PAINTED STEEL CORNER PLATE w/FASTENER (4 ANCHORS IN EACHSTEEL PLATE w/2" min EMBEDMENT)1-1/2' DIA. GALVANIZED STEELPIPE GUARDRAIL w/1/2" PICKETS@ 4" o.c.PRE-CAST SILL (BELOW)PRE-CAST CONCRETE PANELGALVANIZED STEEL PLATE w/FASTENERS (ATTACH AT INTERIORFACE OF EACH OPENING INPRECAST)3'-11 3/8" V.I.F.4'-2 7/8" (TYP)4"3 1/2"ALUMINUM STOREFRONT GLAZING SYSTEM3' - 6"4" o.c. MAX1-1/2' DIA. GALVANIZED STEELPIPE GUARDRAIL w/1/2" PICKETS@ 4" o.c.GALVANIZED STEEL PLATE w/FASTENERS (ATTACH AT INTERIORFACE OF EACH OPENING INPRECAST)4'-2 7/8" V.I.F.3'-11 3/8' V.I.F.DANDRIDGEDREWW H IT E HITAR-19400087ARCTECSTATE OFNo.DNDINAAAIIREGISTEREDNDINAAIHITARCTECDANDRIDGEDREWW H IT EREVISIONS:DRAWN BYDATE ISSUEDCHECKED BYScope DrawingsThese drawings indicate the general scope of the project interms of architectural design concept, the dimensions of thebuilding, the major architectural elements and the type ofstructural, mechanical and electrical systems. The drawingsdo not necessarily indicate or describe all work required forfull performance and completion of the requirements of thecontract. On the basis of the general scope indicated ordescribed, the trade contractors shall furnish all itemsrequired for the proper execution and completion of work.PROJECT NUMBER:618 East Market StreetIndianapolis, Indiana 46202phone 317/264.8162a x i s a r c h . c o mConstruction Manager:Civil Engineer:Structural Engineer:MEP Engineer:Owner:Carmel Redevelopment Commission30 West Main Street, Suite 200Carmel, Indiana 46032317.571.2492Garmong Construction Services5988 North Michigan RoadIndianapolis, Indiana 46228317.682.1001Corrie Meyer, Executive DirectorJKCH03/28/2017A125STAIR DETAILS17003Civil & Environmental Consultants, Inc.530 East Ohio Street, Suite G317.655.7777Vector Consulting1005 North Senate Avenue317.632.4444Fink Roberts & Petrie9449 Priority Way West Drive, Suite 200317.872.8400Indianapolis, IN 46204Indianapolis, IN 46202Indianapolis, IN 46240MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 1" = 1'-0"01STAIR - TYPCIAL CABLE RAIILINGELEVATIONSCALE: 1 1/2" = 1'-0"02STAIR PIPE STRINGER AT SLABSCALE: 1 1/2" = 1'-0"04STAIR PIPE STRINGER AT FLOORDOWNSCALE: 1 1/2" = 1'-0"09STAIR PIPE RAILING AT FLOOREDGESCALE: 1 1/2" = 1'-0"06STAIR HANDRAIL AT PRECASTWALLSCALE: 1 1/2" = 1'-0"03STAIR CABLE STRINGER AT SLABSCALE: 1 1/2" = 1'-0"05STAIR CABLE STRINGER AT FLOORDOWNSCALE: 1" = 1'-0"07GARAGE - TYPICAL GUARDRAILPLANSCALE: 1" = 1'-0"11GARAGE - TYPICAL GUARDRAILELEVATIONSCALE: 1 1/2" = 1'-0"10STAIR CABLE RAILING AT FLOOREDGESCALE: 1" = 1'-0"08STAIR - TYPCIAL PIPE RAILINGELEVATION1# DESCRIPTION DATESCALE: 1" = 1'-0"12GARAGE - TYPICAL GUARDRAILPLAN @ STAIRWELLSCALE: 1" = 1'-0"13GARAGE - TYPICAL GUARDRAILELEVATION @ STAIRWELLS
UP
UP1' - 0"4"2' - 8"1' - 0"4"8"120.00°R 0' - 4"2' - 8"R 2' - 0"4" TYP.ACCESSIBILITY PARKING
SYMBOL
VAN TEXT WHERE SHOWN 1' - 4"8"8' - 0"2' - 0"2' - 0"R 4' - 0"12' - 0"1' - 0"
2' - 0"
15' - 6"
2' - 0"2' - 0"2' - 0"2' - 6"2' - 0"2' - 0"2' - 0"
R 4' - 0"1' - 0"10' - 0"2' - 0"2' - 0"2' - 0"
1' - 0"
PAINTED GRAPHIC APAINTED GRAPHIC B
PAINTED GRAPHIC C
15' - 6"
2' - 0"2' - 0"2' - 6"2' - 0"2' - 0"2' - 6"2' - 0"2' - 0"2' - 0"
R 4' - 0"1' - 0"PAINTED GRAPHIC D
PARKING COUNT:
ADA = 6
ADA VAN = 2
STANDARD = 41
TOTAL = 49
OPEN BELOW RAMP
TO STORM DETENTION
AREA
14 SP @ 8'-6" = 119' - 0"6 SP @ 8'-6" = 51' - 0"11 SP @ 8'-6" = 93' - 6"2' - 0".10 SP @ 8'-6" = 85' - 0"33' - 11 3/4"
8' - 0"8' - 0"8' - 0"8' - 0"18' - 0"24' - 5"18' - 0"18' - 0"23' - 2"18' - 0"
P21
P19
P18
P18
P20
8' - 0"8' - 0"5' - 0"8' - 0"8' - 0"5' - 0"8' - 0"R 5'.6' - 10"9' - 0"4' - 6"9' - 0"P18
P21
FIRST LEVEL
0'-0" 828.50 15' - 0".10' - 8".10' - 8".SECOND LEVEL
15'-0" 843.50
THIRD LEVEL
25'-8" 854.17'
FOURTH LEVEL
36'-4" 864.83'
TOP OF RAMP
RAMP DOWN
PARKING COUNT:
ADA = 0
ADA VAN = 0
STANDARD = 77
TOTAL = 77
OPEN TO
LEASE SPACE
BELOW
20 SP @ 8' - 6" = 170' - 0"
14 SP @ 8' - 6" = 119' - 0"
8 SP @ 8' - 6" = 68' - 0"
11 SP @ 8' - 6" = 93' - 6"2' - 11"9 SP @ 8' - 6" = 76' - 6"8' - 6"8' - 6"10 SP @ 8' - 6" = 85' - 0"4 SP @ 8' - 6" = 34' - 0"
P21
P21
P19P19
P18
P18
P1818' - 0"24' - 5"18' - 0"18' - 0"24' - 5"18' - 0"24' - 0"18' - 0".
18' - 0".24' - 0"DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
04/13/2017
A130
PARKING LAYOUT
PLANS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 1/2" = 1'-0"04 STRIPING ADA DETAIL
SCALE: 1/4" = 1'-0"03 STRIPING DETAIL
PLAN KEYNOTES
P01 DASHED LINE INDICATES CANOPY ABOVE.
P02 MIDTOWN OFFICE CANOPY - NOT IN CONTRACT.
P03 4-1/2" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P04 PRECAST CONCRETE STAIRCASE. REFER TO PRECAST DRAWINGS.
P05 MIDTOWN OFFICE BUILDING - NOT IN CONTRACT.
P06 BICYCLE RACK TO BE SARIS STACK RACK 20" SPACING. PROVIDE SPACES FOR
50 BICYCLES TOTAL.
P07 MOP SINK. REFER TO PLUMBING DRAWNGS.
P08 ELEVATOR MACHINE-ROOM-LESS TYPE - REFER TO SPECS. INTERIOR FLOOR
FINISH OF CAB TO BE: DAL TILE, NOIR LINEN P689, 12X12 WITH MAPEI
CHARCOAL 47 GROUT.
P09 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS. COORDINATE LOCATION
WITH PRECAST AND TOPPING SLAB SLOPES.
P10 HOLLOW METAL WINDOW. REFER TO GLAZING ELEVATIONS.
P11 ELEVATOR EQUIPMENT. COORDINATE WITH ELEVATOR SPECS AND MEP
DWGS.
P12 WALL MOUNTED FIRE EXTINGUISHER CABINET - REFER TO SPECS.
P13 GALVANIZED TUBE STEEL GUARDRAIL TYPICAL AT ALL OPENINGS. REFER TO
TYPICAL DETAIL 11/A125.
P14 1-1/2" TUBE STEEL GUARDRAIL W/STAINLESS STEEL CABLES. FERRULES, STUDS.
1-1/2" DIAM. STEEL PIPE HANDRAIL. (TYPICAL ON FLOORS 1-2 ONLY). (PAINT
P1). MOUNT TO SIDE OF PRECAST CONCRETE STAIRS.
P15 1-1/2" DIA. STEEL PIPE GUARDRAIL/HANDRAIL SIDE MOUNTED TO PRECAST
STAIRS (PAINT P1).
P16 1-1/2" DIA. STEEL PIPE HANDRAIL ATTACHED TO PRECAST OR CMU WALL.
P17 PROVIDE 42" TALL GUARDRAIL INFILL AT STOREFRONT OPENINGS AT
LANDINGS AND STAIR RUNS. INSET GUARDRAIL INTO WINDOW OPENING.
TOP OF RAIL TO BE PARALLEL WITH FLOOR OR STAIR RUN.
P18 4" WIDE PAINTED STRIPS AT 45 DEGREES; COLOR - YELLOW.
P19 PAINTED PARKING STRIPE; COLOR - YELLOW. TYPICAL.
P20 ADA PAINTED PARKING GRAPHIC; COLOR - BLUE.
P21 PAINTED DIRECTIONAL ARROW; COLOR - YELLOW.
P22 SLOPE TOPPING SLAB TO TRAIN. 2% MAX.
P23 HATCHED AREA DENOTES TRAFFIC BEARING MEMBRANE INSTALLED ON
CONCRETE DECK ABOVE ENCLOSED SPACE ABOVE. TURN MEMBRANE UP
ADJACENT WALLS 6" MIN.
P24 EXTERIOR BLADE SIGN - COORDINATE WITH SIGN CONSULTANT. PROVIDE
ELECTRICAL. CENTER ON PRE-CAST CONCRETE PANEL.
P25 42" GUARDRAIL CLOSURE AT FIRST FLOOR WITH GATE. PROVIDE HASP AND
LATCH.
P26 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER PLUMBING DRAWINGS.
P27 2-1/4" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P28 PIPE BOLLARD WITH PLATE THRU-BOLTED TO PRECAST GARAGE STRUCTURE.
P29 DRY STANDPIPE. REFER TO PLUMBING DRAWINGS
P30 ROOF LEADER PIPING. PROVIDE PAINTED STEEL PIPE PROTECTION - 055000.
SCALE: 1/16" = 1'-0"01 FIRST FLOOR STRIPING PLAN
SCALE: 3/32" = 1'-0"
ISOMETRIC
SCALE: 1/16" = 1'-0"02 SECOND FLOOR CONSTRUCTION
PLAN
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
1
UP
UP
PARKING COUNT:
ADA = 0
ADA VAN = 0
STANDARD = 87
TOTAL = 87
20 SP @ 8' - 6" = 170' - 0"2' - 11"9 SP @ 8' - 6" = 76' - 6"8' - 6"14 SP @ 8' - 6" = 119' - 0"
14 SP @ 8' - 6" = 119' - 0"
20 SP @ 8' - 6" = 170' - 0"10 SP @ 8' - 6" = 85' - 0"P21
P19
P19
P21
P18
P18
PARKING COUNT:
ADA = 0
ADA VAN = 0
STANDARD = 85
TOTAL = 85
20 SP @ 8' - 6" = 170' - 0"2' - 11"9 SP @ 8' - 6" = 76' - 6"8' - 6"14 SP @ 8' - 6" = 119' - 0"8 SP @ 8' - 6" = 68' - 0"20 SP @ 8' - 6" = 170' - 0"
P21
P19
P18
P18
P19
P21
PARKING COUNT:
ADA = 0
ADA VAN = 0
STANDARD = 84
TOTAL = 84
6' - 2".6' - 6".10 SP @ 8' - 6" = 85' - 0"
10 SP @ 8' - 6" = 85' - 0"18' - 0"16' - 6"P19
P18
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
Author
Checker
04/13/2017
A131
PARKING LAYOUT
PLANS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032PLAN KEYNOTES
P01 DASHED LINE INDICATES CANOPY ABOVE.
P02 MIDTOWN OFFICE CANOPY - NOT IN CONTRACT.
P03 4-1/2" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P04 PRECAST CONCRETE STAIRCASE. REFER TO PRECAST DRAWINGS.
P05 MIDTOWN OFFICE BUILDING - NOT IN CONTRACT.
P06 BICYCLE RACK TO BE SARIS STACK RACK 20" SPACING. PROVIDE SPACES FOR
50 BICYCLES TOTAL.
P07 MOP SINK. REFER TO PLUMBING DRAWNGS.
P08 ELEVATOR MACHINE-ROOM-LESS TYPE - REFER TO SPECS. INTERIOR FLOOR
FINISH OF CAB TO BE: DAL TILE, NOIR LINEN P689, 12X12 WITH MAPEI
CHARCOAL 47 GROUT.
P09 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS. COORDINATE LOCATION
WITH PRECAST AND TOPPING SLAB SLOPES.
P10 HOLLOW METAL WINDOW. REFER TO GLAZING ELEVATIONS.
P11 ELEVATOR EQUIPMENT. COORDINATE WITH ELEVATOR SPECS AND MEP
DWGS.
P12 WALL MOUNTED FIRE EXTINGUISHER CABINET - REFER TO SPECS.
P13 GALVANIZED TUBE STEEL GUARDRAIL TYPICAL AT ALL OPENINGS. REFER TO
TYPICAL DETAIL 11/A125.
P14 1-1/2" TUBE STEEL GUARDRAIL W/STAINLESS STEEL CABLES. FERRULES, STUDS.
1-1/2" DIAM. STEEL PIPE HANDRAIL. (TYPICAL ON FLOORS 1-2 ONLY). (PAINT
P1). MOUNT TO SIDE OF PRECAST CONCRETE STAIRS.
P15 1-1/2" DIA. STEEL PIPE GUARDRAIL/HANDRAIL SIDE MOUNTED TO PRECAST
STAIRS (PAINT P1).
P16 1-1/2" DIA. STEEL PIPE HANDRAIL ATTACHED TO PRECAST OR CMU WALL.
P17 PROVIDE 42" TALL GUARDRAIL INFILL AT STOREFRONT OPENINGS AT
LANDINGS AND STAIR RUNS. INSET GUARDRAIL INTO WINDOW OPENING.
TOP OF RAIL TO BE PARALLEL WITH FLOOR OR STAIR RUN.
P18 4" WIDE PAINTED STRIPS AT 45 DEGREES; COLOR - YELLOW.
P19 PAINTED PARKING STRIPE; COLOR - YELLOW. TYPICAL.
P20 ADA PAINTED PARKING GRAPHIC; COLOR - BLUE.
P21 PAINTED DIRECTIONAL ARROW; COLOR - YELLOW.
P22 SLOPE TOPPING SLAB TO TRAIN. 2% MAX.
P23 HATCHED AREA DENOTES TRAFFIC BEARING MEMBRANE INSTALLED ON
CONCRETE DECK ABOVE ENCLOSED SPACE ABOVE. TURN MEMBRANE UP
ADJACENT WALLS 6" MIN.
P24 EXTERIOR BLADE SIGN - COORDINATE WITH SIGN CONSULTANT. PROVIDE
ELECTRICAL. CENTER ON PRE-CAST CONCRETE PANEL.
P25 42" GUARDRAIL CLOSURE AT FIRST FLOOR WITH GATE. PROVIDE HASP AND
LATCH.
P26 DOWNSPOUT. TIE INTO FLOOR DRAIN. REFER PLUMBING DRAWINGS.
P27 2-1/4" EXTERIOR ALUMINUM AND GLASS STOREFRONT SYSTEM. REFER TO
ELEVATIONS FOR GLAZING TYPE AND MULLION SPACING.
P28 PIPE BOLLARD WITH PLATE THRU-BOLTED TO PRECAST GARAGE STRUCTURE.
P29 DRY STANDPIPE. REFER TO PLUMBING DRAWINGS
P30 ROOF LEADER PIPING. PROVIDE PAINTED STEEL PIPE PROTECTION - 055000.
SCALE: 1/16" = 1'-0"01 THIRD FLOOR STRIPING PLAN
SCALE: 1/16" = 1'-0"02 FOURTH FLOOR STRIPING PLAN
SCALE: 1/16" = 1'-0"03 TOP OF RAMP STRIPING PLAN
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
1
FIRST FLOOR
0' - 0"
FIRST FLOOR
0' - 0"
SECOND FLOOR
15' - 0"
76521
THIRD FLOOR
25' - 8"
FOURTH FLOOR
36' - 4"
ROOF
50' - 4"
43
LOW PARAPET
40' - 4"
LEVEL 1.5
10' - 8"
LEVEL 2.5
21' - 4"
LEVEL 3.5
32' - 0"
LEVEL 4.5
42' - 8"10' - 8"10' - 8"10' - 8"4' - 0"10' - 8"10' - 8"15' - 0"843.50
854.17
864.83
828.50
STORM WATER DETENTION
PRECAST CONCRETE WALL PANELS
PRECAST CONCRETE TEES WITH TOPPING SLAB
PRECAST CONCRETE ROOF SLAB WITH TPO
ROOFING OVER TAPERED INSULATION
9 7/8"1' - 2 3/8"
6 5/8"11 3/8"
FIRST FLOOR
0' - 0"
SECOND FLOOR
15' - 0"
A B C
THIRD FLOOR
25' - 8"
FOURTH FLOOR
36' - 4"
ROOF
50' - 4"
01
A301
HIGH PARAPET
46' - 8"
LOW PARAPET
40' - 4"
LEVEL 1.5
10' - 8"
LEVEL 2.5
21' - 4"
ELEVATOR PIT
-5' - 0"
LEVEL 3.5
32' - 0"
LEVEL 4.5
42' - 8"
02
A301
FIRST FLOOR
0' - 0"
FIRST FLOOR
0' - 0"
SECOND FLOOR
15' - 0"
76521
THIRD FLOOR
25' - 8"
FOURTH FLOOR
36' - 4"
ROOF
50' - 4"
43
HIGH PARAPET
46' - 8"
LOW PARAPET
40' - 4"
LEVEL 1.5
10' - 8"
LEVEL 2.5
21' - 4"
ELEVATOR PIT
-5' - 0"
LEVEL 3.5
32' - 0"
LEVEL 4.5
42' - 8"10' - 8"10' - 8"10' - 8"10' - 8"10' - 8"10' - 8"15' - 0"STORM WATER DETENTION
PRECAST CONCRETE LIGHT WALL PANELS
PRECAST CONCRETE TEES WITH
TOPPING SLAB
PRECAST CONCRETE ROOF SLAB WITH TPO
ROOFING OVER TAPERED INSULATION
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A301
BUILDING
SECTIONS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032KIT OF PARTS
SCALE: 3/32" = 1'-0"01 N-S BUILDING SECTION 1
SCALE: 3/32" = 1'-0"03 E-W BUILDING SECTION
SCALE: 3/32" = 1'-0"02 N-S BUILDING SECTION 2
# DESCRIPTION DATE
1 ADLS COMMENTS 5/11/2017
1
FIRST FLOOR
0' - 0"
SECOND FLOOR
15' - 0"
C
LEVEL 1.5
10' - 8"
PRECAST CONCRETE WALL PANELS
PRECAST CONCRETE TEE'S
TOPPING SLAB WITH WASH FOR
DRAINAGE
3"3"3' - 0"
CAST-IN-PLACE FOUNDATION WALL
14' - 0"
0' - 0"
EXTERIOR SITE PAVEMENT BY OTHERS. REFER TO CIVIL
DRAWINGS
SPOECIFIED ALUMINUM AND GLASS STOREFRONT
SYSTEM. REFER TO BUILDING ELEVATIONS
PRECAST CONCRETE WALL PANEL
PRECAST CONCRETE TEE'S
TOPPING SLAB WITH WASH FOR
DRAINAGE
INFILL FROM TOP OF PRECAST TO
BOTTOM OF PRECAST TEE'S WITH 1-HOUR
RATED 8" CMU WALL
A002
02 SIM
PROVIDE POSITIVE CONNECTION
TO TOP OF PRECAST WALL
ACOUSTICAL CEILING AS OCCURS. REFER TO CEILING PLAN
5/8" GYPSUM WALLBOARD LID OVER VAPOR BARRIER
OVER 3-5/8" INTERIOR METAL FRAMING SYSTEM
SUSPENDED FROM TEE'S ABOVE.
F1 S
F1 S
EXTEND PERIMETER WALLS TO ABOVE
GYPSUM WALLBOARD LID.
R-38 FIBERGLASS BATT INSULATION (2-LAYERS) OR
BLOW-IN CELLULOSE INSULATION. COORDINATE
ACCESS POINTS IN LID FOR INSTALLATION.
UNCONDITIONED SPACE
CEILING PLENUM AREA.
INSTALL ALL PIPING, DUCTWORK
ETC. IN THIS SPACE
A310
01
TRAFFIC BEARING MEMBRANE ON
DECK ABOVE ENCLOSED SPACES
GYPSUM WALLBOARD AT WINDOW HEAD. FURR OUT
WITH HAT CHANNELS AND SPRAY FOAM THE CAVITY
A310
05
COMPRESSIBLE JOINT FILLER
4 1/2"3"DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
04/13/2017
A302
WALL SECTIONS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 1/2" = 1'-0"01 OFFICE SECTION
# DESCRIPTION DATE
1 ADDENDUM No. 1 4/13/2017
1
SECOND FLOOR
15' - 0"
C
TURN TRAFFIC MEMBRANE UP WALL 6"
SEALANT CANT PER TRAFIC
MEMBRANE MFR DIRECTIONS
TOPPING SLAB WITH 3" THICK WASH
TRAFFIC BEARING MEMBRANE
WATERSTOP INSTALLED BETWEEN
PRECAST TEE AND PRECAST WALL
PANEL PRIOR TO TOPPING SLAB
INSTALLATION
PRECAST TEE
FIRST FLOOR
0' - 0"
ELEVATOR PIT
-5' - 0"5' - 0"STAINLESS STEEL SILL
AND SUPPORT BRACKETS
STAINLESS STEEL ELEVATOR
JAMB AND DOOR
PRECAST STRUCTURE w/
CONCRETE TOPPING
ELEVATOR TRACK SYSTEM
PRE-CAST CONCRETE WALL
PANEL
SUMP PIT LADDER
CONCRETE FOOTING -
REFER TO STRUCTURAL
DWGS.
DAMP-PROOFING AT
WALLS AND FLOOR OF
ELEVATOR PIT
DAMP-PROOFING AT
WALLS AND FLOOR OF
STORMWATER DETENTION
11"
SEALANT JOINT AT
SEAM IN CONCRETE
SUMP PUMP AND PIT
- COORDINATE LOCATION
w/ELEVATOR MFR AND
MEP.
STAINLESS STEEL SILL
AND SUPPORT BRACKETS
PRECAST STRUCTURE w/
CONCRETE TOPPING
8" CMU WALL
STAINLESS STEEL ELEVATOR
JAMB AND DOOR
SEALANT JOINT AT SEAM
IN CONCRETE POUR
11"
CONCRETE TEE - REFER TO
STRUCTURAL DWGS.
FIRST FLOOR
0' - 0"
A
5" CONCRETE SLAB
PRECAST CONCRETE
WALL PANEL
CAST-IN-PLACE
CONCRETE
FOUNDATION WALL -
REFER TO STRUCTURAL
DWGS.
7
LEVEL 1.5
10' - 8"
STRUCTURAL STEEL C-CHANNEL - REFER TO
STRUCTURAL DWGS (PAINT)
TURN DOWN TPO MIN. 2"
ALUMINUM EDGE METAL AND CONTINIOUS CLEAT
(PAINTED)
P.T. WOOD BLOCKING
TPO MEMBRANE ROOF
EXTERIOR GRADE 3/4" PLYWOOD SHEATHING
TPO MEMBRANE TERMINATION WITH SURFACE
MOUNTED COUNTERFLASHING
STRUCTURAL STEEL HSS JOIST -
REFER TO STRUCTURAL DWGS (PAINT)
1-1/2" METAL DECK - REFER TO STRUCTURAL
DWGS (PAINT)
STEEL ROD AND PLATE TIE-BACK -
REFER TO STRUCTURAL DWGS (PAINT)
TREATED 2X BLOCKING AND CANT
STRIP
EXTEND EPDM UP WALL OF PRECAST
w/TERMINATION BAR AND SEALANT
1' - 3"6"8"1 1/2"PRECAST CONCRETE WALL PANEL
8"1 1/2"ELEVATION
SECTION
WALL BRACKET
STEEL RUNG WITH ANTI-SLIP
TREAD
3"1' - 6"
CAST IN PLACE FOUNDATION
WALL
8"5' - 0"PARKING DECK
1/2" x 2-1/2" STEEL FLAT BARS
SPACE SUPPORTS 60" O.C. MAX8"MANHOLE COVER
1' - 4"
2' - 0"
8"DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
JK
CH
03/28/2017
A310
SECTION DETAILS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032KIT OF PARTS
SCALE: 1 1/2" = 1'-0"01 PERIMETER WATERPROOFING
ABOVE ENCLOSED SPACES
SCALE: 3/4" = 1'-0"02 ELEVATOR SILL DETAIL - FIRST
FLOOR
SCALE: 3/4" = 1'-0"03 ELEVATOR SILL DETAIL - SECOND
FLOOR
SCALE: 3/4" = 1'-0"04 FOUNDATION DETAIL (TYPICAL)
SCALE: 1 1/2" = 1'-0"05 ROOF CANOPY SECTION
SCALE:NTS06Manhole Cover Detail
SCALE: 1" = 1'-0"07 LADDER - MANHOLE ACCESS
# DESCRIPTION DATE
2 x 2 LAY-IN CEILING GRID
GYPSUM BOARD CEILING
OR GYPSUM BOARD BULKHEAD
CEILING TYPE
CEILING HEIGHT
X
X
EXPOSED STRUCTURE
CEILING LEGEND
GENERAL CEILING PLAN NOTES
A. REFER TO CEILING PLAN FOR ALL CEILING HEIGHTS.
B. ALL GRIDS ARE CENTERED IN ROOMS EACH DIRECTION UNLESS
NOTED OTHERWISE.
C. LOCATE CEILING GRIDS WITHIN ROOMS SUCH THAT BORDERS
CONTAIN NOT LESS THAN 1/2 TILE WIDTH, UNLESS OTHERWISE
INDICATED.
D. CENTER PENETRATIONS IN ACOUSTICAL CEILING SYSTEMS WITHIN
INDIVIDUAL CEILING PANELS, SUCH AS SPRINKLER HEADS, DIFFUSERS,
LIGHT FIXTURES, ETC., UNLESS OTHERWISE INDICATED.
E. PAINT ALL EXPOSED GYPSUM WALLBOARD SURFACES UNLESS NOTED
OTHERWISE. REFER TO FINISH PLAN FOR COLORS.
F. ALL EXPOSED DUCTWORK, PIPING, CONDUITS ETC. SHALL BE PAINTED.
COLOR TO MATCH CEILING OR EXPOSED STRUCTURE UNLESS
OTHERWISE NOTED.
G. PROVIDE CONTROL JOINTS IN GYPSUM WALLBOARD CEILINGS AT 20'
MAXIMUM. VERIFY LOCATIONS WITH ARCHITECT PRIOR TO
INSTALLATION.
H. COORDINATE REFLECTED CEILING PLAN WITH MECHANICAL,
PLUMBING, ELECTRICAL, AND LIFE SAFETY PLANS. PROVIDE
COORDINATION DRAWINGS FOR REVIEW PRIOR TO CEILING
INSTALLATION.
I. LIGHT FIXTURES, SPRINKLER HEADS, HVAC SUPPLY AND RETURN GRILLES
ARE SHOWN FOR LOCATION ONLY. REFER TO MEP DRAWINGS FOR
ADDITIONAL INFO.
J. PROVIDE ACOUSTICAL CEILING HOLD-DOWN CLIPS IN VESTIBULES. IN
ROOMS WITH EXTERIOR ENTRANCE DOORS PROVIDE HOLD-DOWN
CLIPS FOR 10' IN ALL DIRECTION OF DOORWAY.
CEILING TAG
4 x 4 LAY-IN CEILING GRID
7
A A
7
P1
P1
C05
C02
EQ.EQ.EQ.EQ.
C01
35' - 11"EQ.EQ.C05
STAIR 1
ST1-4
ELEVATOR
LOBBY
401
C05
C02
C02
C02
C02 EQ.EQ.EQ.EQ.
3' - 0 1/2"8' - 11"3' - 0 1/2"10' - 1 1/2"10' - 9 1/2"2' - 0 1/2"6' - 0"6' - 7 1/2"5' - 4"20' - 0"C02
16' - 10"3' - 2"C04C04
C04C04
20' - 11"
7
C C
7
15' - 0"20' - 11"19' - 0 3/8"35' - 11"15' - 10 3/8"3' - 2"C05 C05
C02
P14' - 7 1/4"6' - 4 3/4"5' - 5"2' - 7 1/2"3' - 0 1/2"8' - 11"13' - 6"10' - 5 1/2"
EQ.EQ.EQ.EQ.EQ.EQ.EQ.EQ.EQ.EQ.EQ.EQ.
C02
C02
C02
C05 C05
VESTIBULE
402
STAIR 2
ST2-4
C04C04
C04C04
P1
1
A A
1
10' - 7"C05
C02EQ.EQ.EQ.EQ.EQ.EQ.P1
P1
STAIR 3
ST3-4
12' - 0"
1"
8' - 10"
C05
C04C04
24' - 0"3' - 2"20' - 11"DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
JK
CH
03/28/2017
A401
REFLECTED
CEILING PLANS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032REFLECTED CEILING KEYNOTES
C01 BOND BEAM HEADER AT CMU WALL.
C02 1" X 1/2" REVEAL IN PRECAST ROOF PANEL. PAINT P1.
C03 DRYWALL LID AT 14'-0" ABOVE ENTIRE OFFICE AREA.
C04 REFER TO MEP DRAWINGS FOR LIGHTING AND HVAC ITEMS INSTALLED IN
CEILINGS.
C05 ELECTRICAL LIGHTING - REFER TO MEP DWGS.
CEILING TYPES
TYPE DESCRIPTION
A ACOUSTICAL PANEL TYPE A IN GRID TYPE A. 24" X 24" ACOUSTICAL
CEILING TO BE ARMSTRONG OPTIMA 3355 SQUARE TEGULAR
INSTALLED IN 9/16" SILHOUETTE XL BOLT SLOT 1/8"
REVEAL SUSPENSION GRID.
B GYPSUM WALLBOARD CEILING ON GRID SUSPENSION SYSTEM.
REFER TO FINISH PLAN FOR PAINTING.
C NO CEILING IN THIS ROOM - PAINTED EXPOSED STRUCTURE.
SCALE: 1/4" = 1'-0"01 FOURTH FLOOR REFLECTED
CEILING PLAN - STAIR 1
SCALE: 1/4" = 1'-0"02 FOURTH FLOOR REFLECTED
CEILING PLAN - STAIR 2
SCALE: 1/4" = 1'-0"03 FOURTH FLOOR REFLECTED
CEILING PLAN - STAIR 3
# DESCRIPTION DATE
1 ADLS COMMENTS 5/11/2017
1
DOOR & FRAME MATERIAL ABBREVIATIONS
GENERAL DOOR NOTES
MATERIALS:
HM = HOLLOW METAL
IHM = INSULATED HOLLOW METAL
SCW = SOLID CORE WOOD
AL = ALUMINUM
STL = STEEL, GALVANIZED
IMP = INSULATED METAL PANEL
A. REFER TO THE PROJECT MANUAL FOR DOOR HARDWARE SETS.
B. ALL HOLLOW METAL DOORS AND FRAMES TO RECIEVE 3-COAT PAINT
SYSTEM - PRIME, INTERMEDIATE AND FINISH COATS. REFER TO PAINTING
SPECIFICATION. REFER TO FINISH PLAN AND EXTERIOR ELEVATIONS FOR
COLOR.REFER TO THE PROJECT MANUAL FOR THE GLAZING SCHEDULE.
C. REFER TO A000 FOR GLAZING SCHEDULE.
DOOR SCHEDULE REMARKS
1. DOOR IS INSTALLED IN A THERMALLY BROKEN ALUMINUM STOREFRONT
SYSTEM. REFER EXTERIOR ELEVATIONS AND FRAME ELEVATIONS.
2. COILING COUNTER DOOR.
3. REFER TO FRAME ELEVATIONS FOR DETAILS.
FINISHES:
CA = CLEAR ANODIZED
PRE = FACTORY PREFINISHED
PT = PAINTED
1" CLEAR INSULATING GLASS WITH LOW-E COATING, HEAT
STRENGTHENED
1/4" FULLY TEMPERED LOW-E CLEAR FLOAT GLASS
IGL-1
GL-1
1" CLEAR INSULATING GLASS WITH LOW-E COATING, FULLY TEMPEREDIGL-2
**REFER TO PROJECT MANUAL FOR COMPLETE GLAZING SPECIFICATION.
**CONTRACTOR TO PROVIDE FULLY TEMPERED LITES IN ALL LOCATIONS
REQUIRED BY CODE INCLUDING BATHROOMS AND WITHIN 30" OF FLOOR
GLAZING SCHEDULE
1/4" FULLY TEMPERED CLEAR FLOAT GLASSGL-2
1/4" FULLY TEMPERED SPANDREL GLASSGL-2
FG NFG
REF. SCHED.REF. SCHED.REF. SCHED.REF. SCHED.REF. SCHED.REF. SCHED.REF. SCHED.REF. SCHED.F1 F2
2"REF. SCHED.2"2"REF. SCHED.HOLLOW
METAL FRAME
HOLLOW
METAL FRAME
F3
HOLLOW
METAL FRAME4"REF. SCHED.2"REF. SCHED.2"3' - 6"4' - 0"4' - 0"
GL-1
2" TYP.
HOLLOW METAL FRAME CLIP4"2"
INTERIOR WALL CONSTRUCTION
REFER TO PLANS FOR TYPE
DOUBLE STUD AT JAMB TYP.
HOLLOW METAL FRAME - REFER
SCHEDULE
DOOR - REFER SCHEDULE
SEALANT JOINT TYP.4 7/8"INTERIOR WALL CONSTRUCTION
REFER TO PLANS FOR TYPE
HOLLOW METAL FRAME - REFER SCHEDULE
DOOR - REFER SCHEDULE
SEALANT JOINT AT FRAME PERIMETER TYP.
4 7/8"
METAL STUD HEADER. SIZE PER OPENING
WIDTH
HOLLOW METAL FRAME
- REFER SCHEDULE
DOOR - REFER SCHEDULESEALANT AT PERIMETER TYP.
CMU WALL
7 5/8"2"
CMU FRAME CLIP
6"BULLNOSE 7 5/8"1"4 1/4"2"6"HOLLOW METAL FRAME -
REFER SCHEDULE
DOOR - REFER SCHEDULE
SEALANT AT PERIMETER TYP.
BOTH SIDES
CONCRETE MASONRY UNIT
5/8" GYPSUM WALLBOARD
3-5/8" INTERIOR METAL FRAMING
SPECIFIED SPRAY-APPLIED
INSULATION
BULLNOSE
HOLLOW METAL FRAME
- REFER SCHEDULE
DOOR - REFER SCHEDULE
SEALANT JOINT
TYP. AT PERIMETER
BOND BEAM REFER TO
STRUCTRUAL DWG'S
4"4"HOLLOW METAL FRAME -
REFER SCHEDULE
SEALANT AT PERIMETER TYP.
BOTH SIDES
5/8" GYPSUM
WALLBOARD
3-5/8" INTERIOR METAL
FRAMING
SPECIFIED SPRAY-APPLIED
INSULATION
7 5/8"1"4 1/4"
1"6"
DOOR - REFER TO SCHEDULE
CONCRETE MASONRY UNIT.
BOND BEAM LINTEL
HOLLOW METAL FRAME -
REFER SCHEDULE
DOOR - REFER SCHEDULE
SEALANT JOINT AT
PERIMETER TYP. BOTH SIDES
PRECAST CONCRETE WALL
PANEL
2"3/4" CHAMFER
HOLLOW METAL FRAME -
REFER SCHEDULE
DOOR - REFER SCHEDULE
SEALANT AT PERIMETER TYP.
BOTH SIDES
PRECAST CONCRETE WALL PANEL
2"6"3/4" CHAMFER
THERMALLY BROKEN
STOREFRONT FRAME
DOOR - REFER SCHEDULE
SEALANT AT PERIMETER TYP.
BOTH SIDES
PRECAST CONCRETE WALL
PANEL WITH THIN BRICK9"1"4 1/4"5/8" GYPSUM WALLBOARD
3-5/8" INTERIOR METAL FRAMING
SPECIFIED SPRAY-APPLIED
INSULATION
3"4 1/2"8"3/8"
SPRAY FOAM VOIDS
3"4 1/2"
9"1"4 1/4"
SPECIFIED SPRAY-APPLIED
INSULATION
3-5/8" INTERIOR METAL
FRAMING
5/8" GYPSUM WALLBOARD
SEALANT AT PERIMETER TYP.
BOTH SIDES
THERMALLY BROKEN
STOREFRONT FRAME
PRECAST CONCRETE
WALL PANEL
DOOR - REFER TO SCHEDULE
SPRAY FOAM VOIDS
THERMALLY BROKEN
STOREFRONT FRAME
DOOR - REFER SCHEDULE
SEALANT AT PERIMETER TYP.
BOTH SIDES
PRECAST CONCRETE WALL
PANEL WITH THIN BRICK9"3"4 1/2"8"3/8"
SPRAY FOAM VOIDS
3"4 1/2"
9"
SEALANT AT PERIMETER TYP.
BOTH SIDES
THERMALLY BROKEN
STOREFRONT FRAME
PRECAST CONCRETE
WALL PANEL
DOOR - REFER TO SCHEDULE
SPRAY FOAM VOIDS
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A501
DOOR SCHEDULE
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 1/4" = 1'-0"
DOOR TYPES
SCALE: 1/4" = 1'-0"
FRAME TYPES
DOOR SCHEDULE - GARAGE
OPENING #ROOM NAME
DOOR FRAME DETAILS LABEL
HDWR
SET REMARKSWIDTHHEIGHTTHICKNESSMATERIALELEVATIONFINISHGLAZINGELEVATIONMATERIALFINISHHEADJAMBSILLFIRE RATING100 GARAGE FIRST FLOOR 3' - 0" 8' - 0" 1 3/4" AL FG PRE GL-1 F4 AL PRE H6 J6 S1 -
101 ELECTRICAL 3' - 0" 7' - 0" 1 3/4" HM F PT - F2 HM PT H2 J2 S2 -
102 RISER RM. 3' - 0" 7' - 0" 1 3/4" HM F PT - F1 HM PT H1 J1 - -
103 OFFICE BUILDOUT SPACE 3' - 0" 8' - 0" 1 3/4" AL FG PRE IGL2 F3 AL PRE H5 J5 S1 -
103A OFFICE BUILDOUT SPACE 3' - 0" 8' - 0" 1 3/4" AL FG PRE IGL2 F3 AL PRE H5 J5 S1 -
103B OFFICE BUILDOUT SPACE 3' - 0" 8' - 0" 1 3/4" AL FG PRE IGL2 F3 AL PRE H5 J5 S1 -
103C OFFICE BUILDOUT SPACE 3' - 0" 7' - 0" 1 3/4" IHM F PT - F2 HM PT H4 J4 S2 90 MIN
103D OFFICE BUILDOUT SPACE 3' - 0" 7' - 0" 1 3/4" IHM F PT - F2 HM PT H4 J4 S2 90 MIN
104 IT ROOM 3' - 0" 7' - 0" 1 3/4" IHM F PT - F2 HM PT H4 J4 S2 -
401 ELEVATOR LOBBY 3' - 0" 7' - 0" 1 3/4" IHM G PT GL-1 F2 HM PT H3 J3 S2 -
402 VESTIBULE 3' - 0" 7' - 0" 1 3/4" IHM G PT GL-1 F2 HM PT H3 J3 S2 -
ST1-2 STAIR 1 3' - 0" 7' - 0" 1 3/4" HM G PT GL-2 F1 HM PT H3 J3 -
ST1-3 STAIR 1 3' - 0" 7' - 0" 1 3/4" HM G PT GL-2 F1 HM PT H3 J3 -
ST1-4 STAIR 1 3' - 0" 7' - 0" 1 3/4" IHM G PT GL-2 F1 HM PT H3 J3 -
ST2-1 STAIR 2 3' - 0" 8' - 0" 1 3/4" AL FG PRE GL-1 F4 AL PRE H6 J6 S1 -
ST2-1A STAIR 2 3' - 0" 7' - 0" 1 3/4" HM N PT GL-2 F1 HM PT H3 J3 -
ST2-2 STAIR 2 3' - 0" 7' - 0" 1 3/4" HM G PT GL-2 F1 HM PT H3 J3 -
ST2-3 STAIR 2 3' - 0" 7' - 0" 1 3/4" HM G PT GL-2 F1 HM PT H3 J3 -
ST2-4 STAIR 2 3' - 0" 7' - 0" 1 3/4" HM G PT GL-2 F1 HM PT H3 J3 -
ST3-1 STAIR 3 3' - 0" 7' - 0" 1 3/4" HM N PT GL-2 F1 HM PT H3 J3 -
ST3-1A STAIR 3 3' - 0" 7' - 0" 1 3/4" HM G PT GL-2 F1 HM PT H3 J3 -
ST3-2 STAIR 3 3' - 0" 7' - 0" 1 3/4" HM G PT GL-2 F1 HM PT H3 J3 -
ST3-3 STAIR 3 3' - 0" 7' - 0" 1 3/4" HM G PT GL-2 F1 HM PT H3 J3 -
ST3-4 STAIR 3 3' - 0" 7' - 0" 1 3/4" HM G PT GL-2 F1 HM PT H3 J3 -
SCALE: 3" = 1'-0"J1 DETAIL HM JAMB AT 4 7/8" WALL
SCALE: 3" = 1'-0"H1 DETAIL HM HEAD AT 4 7/8" WALL
SCALE: 3" = 1'-0"J2 JAMB DETAIL
SCALE: 3" = 1'-0"J4 JAMB DETAIL
SCALE: 3" = 1'-0"H2 HEAD DETAIL
SCALE: 3" = 1'-0"H4 HEAD DETAIL
SCALE: 3" = 1'-0"H3 HEAD DETAIL
SCALE: 3" = 1'-0"J3 JAMB DETAIL
SCALE: 3" = 1'-0"J5 JAMB DETAIL
SCALE: 3" = 1'-0"H5 HEAD DETAIL
SCALE: 3" = 1'-0"J6 JAMB DETAIL
SCALE: 3" = 1'-0"H6 HEAD DETAIL
# DESCRIPTION DATE
1 ADLS COMMENTS 5/11/2017
1
HOLLOW METAL DOOR
ALUM. THRESHOLD
SET IN BED OF SEALANT
EXPANSION JOINT
CONCRETE SLAB /
FOUNDATION - REFER
STRUCTURAL DWG'S
INTERIOR EXTERIOR
EXTERIOR PAVING - REFER
LANDSCAPE / CIVIL DWG'S
SLOPE
HOLLOW METAL DOOR
ALUM. THRESHOLD
SET IN BED OF SEALANT CONCRETE SLAB /
FOUNDATION - REFER
STRUCTURAL DWG'S
PRE FINISHED ALUM. DOOR
ALUM. THRESHOLD
SET IN BED OF SEALANT
EXPANSION JOINT
FLOOR FINISH - SEE FLOOR
FINISH
CONCRETE SLAB /
FOUNDATION - REFER
STRUCTURAL DWG'S
INTERIOR EXTERIOR
EXTERIOR PAVING - REFER
LANDSCAPE / CIVIL DWG'S
REFER TO ELEVATIONS FOR
GLAZING TYPE
TRANSOM BAR
THERMALLY BROKEN ALUMINUM AND GLASS
STOREFRONT SYSTEM
THERMALLY BROKEN STOREFRONT
DOOR - REFER SCHEDULE
INSULATED GLAZING - REFER ELEVATIONS
FOR TYPE
4 1/2"2"INTERIOR WALL CONSTRUCTION
REFER TO PLANS FOR TYPE
ALUMINUM AND GLASS STOREFRONT SYSTEM
GLAZING - REFER ELEVATIONS.
SHIM AND SEALANT JOINT TYP.
REF. PLAN
METAL STUD HEADER. SIZE PER OPENING
WIDTH
3/8"ALUMINUM AND GLASS STOREFRONT SYSTEM
SHIM AND SEALANT JOINT TYP.
PRECAST CONCRETE PANEL
REFER ELEVATION FOR GLAZING TYPE
ALUMINUM AND GLASS STOREFRONT
SYSTEM
DOOR - REFER SCHEDULE
GLAZING - REFER ELEVATIONS
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
CH
CH
03/28/2017
A502
DOOR AND
STOREFRONT
DETAILS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032SCALE: 3" = 1'-0"S2 HM FRAME SILL DETAIL EXTERIOR1
SCALE: 3" = 1'-0"S1 HM DOOR SILL DETAIL INTERIOR1
SCALE: 3" = 1'-0"S3 STOREFRONT EXTERIOR - SILL
DETAIL1
SCALE: 3" = 1'-0"04 HEAD DETAIL: STOREFRONT
SCALE: 3" = 1'-0"05 HEAD DETAIL: INTERIOR
STOREFRONT
SCALE: 3" = 1'-0"03 JAMB DETAIL: INTERIOR
STOREFRONT
SCALE: 3" = 1'-0"02 STOREFRONT INTERIOR - JAMB
DETAIL1
# DESCRIPTION DATE
DANDRID G E DREW
WHI
TEH I T
AR-19400087
ARC TEC
STATE OF
No.
DNDI NAA AIIREGISTERE
D
NDI NA AI
H I TARC TECDANDRIDGEDREWWHITEREVISIONS:
DRAWN BY
DATE ISSUED
CHECKED BY
Scope Drawings
These drawings indicate the general scope of the project in
terms of architectural design concept, the dimensions of the
building, the major architectural elements and the type of
structural, mechanical and electrical systems. The drawings
do not necessarily indicate or describe all work required for
full performance and completion of the requirements of the
contract. On the basis of the general scope indicated or
described, the trade contractors shall furnish all items
required for the proper execution and completion of work.
PROJECT NUMBER:
618 East Market Street
Indianapolis, Indiana 46202
phone 317/264.8162
a x i s a r c h . c o m
Construction Manager:
Civil Engineer:
Structural Engineer:
MEP Engineer:
Owner:
Carmel Redevelopment Commission
30 West Main Street, Suite 200
Carmel, Indiana 46032
317.571.2492
Garmong Construction Services
5988 North Michigan Road
Indianapolis, Indiana 46228
317.682.1001
Corrie Meyer, Executive Director
JK
CH
03/28/2017
A503
GLAZING
ELEVATIONS
17003
Civil & Environmental Consultants, Inc.
530 East Ohio Street, Suite G
317.655.7777
Vector Consulting
1005 North Senate Avenue
317.632.4444
Fink Roberts & Petrie
9449 Priority Way West Drive, Suite 200
317.872.8400
Indianapolis, IN 46204
Indianapolis, IN 46202
Indianapolis, IN 46240
MIDTOWN SOUTH GARAGECARMEL REDEVELOPMENT COMMISSION580 VETERANS WAYCARMEL, INDIANA 46032# DESCRIPTION DATE