HomeMy WebLinkAbout019 - SM-01 - Build Area Duct PlanRA RB RC RD RE RF RG
RA RB RC RD RE RF RG
R1
R4
R6
R8
PLAN NOTES
GRILLES, REGISTERS, AND DIFFUSERS
SYMBOL MANUFACTURER/MODEL MATERIAL & TYPE MAX CFM NOM SIZE NECK SIZE NC REMARKS
SD1
METALAIRE STEEL
115 24x24 6" 15 3
5750 SQUARE PLAQUE FACE
SD2
METALAIRE STEEL
225 24x24 8" 16 3
5750 SQUARE PLAQUE FACE
SD3
METALAIRE STEEL
375 24x24 10" 20 3
5750 SQUARE PLAQUE FACE
SD4
METALAIRE STEEL
225 24x24 8" 20 1,3
5750 SQUARE PLAQUE FACE
SG1
METALAIRE ALUMINUM
225 14X8 12X6 18 4
4002PCF SPIRAL DUCT GRILLE
RG1
METALAIRE ALUMINUM
N/A 24X12 22X10 N/A 2
CC45 EGGCRATE RETURN
RG2
METALAIRE ALUMINUM
N/A 24X24 22X22 N/A 2
CC45 EGGCRATE RETURN
EG1
METALAIRE STEEL
100 8X8 6X6 14 4
RH LOUVER FACE 11/16", SINGLE, 45 DEG
SL1
METALAIRE STEEL
210 4"x48" 8" 18 5
6610 [2] 1" SLOT SLOT DIFFUSER
SCHEDULE REMARKS
EXHAUST FAN SCHEDULE
UNIT
TAG EF-1
SERVES IT CLOSET
MANUFACTURER PANASONIC
MODEL FV-08-11VF5
ELEC
PH-HZ 120/60
DISCONNECT MFR.
FAN
CFM 80
STATIC PRESSURE 0.1
NOTES
NOTES 1
1. FAN ON/OFF WITH THERMOSTAT SM-01
MECHANICAL CONTRACTOR:
CONSTRUCTION NOT INDICATED HEREIN WILL IN NO WAY BE PERMITTED OR CONVEY ADDED
SPECIFIED AND THAT ANY USE OF THESE DESIGNS, EITHER IN WHOLE OR IN PART, FOR OTHER
IT IS THE INTENT OF THIS CONTRACTOR THAT THESE DRAWINGS BE USED ONLY FOR THE PROJECT
INTENT OR RESPONSIBILITY BY METAL MASTERS INC.
NO.
DRAWING ISSUED
DESCRIPTION DATE
1 STATE SUBMITTAL 01-05-18
DRAWN BY:
DRAWING OF:
SCALE:
J. GULDI 1/4" = 1'-0"
BUILDING / AREA
DUCT PLAN
Leech & Russel
2514 East Bethel Avenue, Indianapolis, IN 46203
Phone (317)780-1864 Fax (317)780-7968
FLEXIBLE DUCT
AND NECK SIZE
DIFFUSER/GRILLE TYPE - CFM
TOP & BOTTOM DUCT ELEVATION
TRANSITION FLAT ON TOP
SYMBOL LEGEND
90° ELBOW W/TURNING VANES
ACCESS DOOR IN DUCT
FIRE DAMPER
VOLUME DAMPER
EXHAUST AIR GRILLE
RETURN AIR GRILLE
SUPPLY AIR DIFFUSER
FOT
TOD =
BOD =
SD - 300
12 Ø
FOB TRANSITION FLAT ON LEFT
FD
M MOTORIZED DAMPER
VD
W x H L(x) DUCT SIZE AND LENGTH
W x H DUCT SIZE AND LENGTH
L(x)
W x H L(x) LINED DUCT SIZE AND LENGTH
DIMENSIONS ARE O.D. DUCT SIZE
FLEXIBLE CONNECTION
GENERAL NOTES
1. ALL DUCTWORK TO BE FABRICATED AND INSTALLED
PER S.M.A.C.N.A. STANDARDS, PROJECT
SPECIFICATIONS, ADDENDUMS, AND
SHOP STANDARDS SUBMITTAL PER THIS PROJECT.
2. ALL DUCT ELEVATIONS ARE FROM FINISHED FLOOR
0'-0" UNLESS NOTED ON DRAWINGS.
3. ALL DUCT DIMENSIONS ARE NOTED AS OUTSIDE
DIMENSIONS.
4. ALL SQUARE 90° ELBOWS AND TEES TO HAVE
TURNING VANES.
5. ALL SQUARE 90° ELBOWS AND TEES ARE 6" THROATS
UNLESS NOTED ON DRAWINGS.
6. ALL RADIUS 90° ELBOWS ARE 1
1
2 (x) AT CENTERLINE
UNLESS NOTED ON DRAWINGS.
7. VERIFY LOCATION AND ELEVATION OF DUCT,
ARRANGEMENT OF GRD's, EQUIPMENT AND ACCESS
DOORS AFTER COORDINATION WITH OTHER TRADES.
Job #
7484
1 STATE SUBMITTAL 01-08-18
02/26/18
Nick Mishler