E000
ELECTRICAL
NOTES,
SYMBOLS &
SCHEDULE
MONON & MAIN
SUITE 400
211 W. Main St., Carmel, IN 46032
INVESQUE, INC
MAH JEP
01-08-18
Project Number
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED LABOR, MATERIAL,
EQUIPMENT AND SERVICES NECESSARY TO COMPLETE THE INSTALLATION OF ALL
SYSTEMS INDICATED. THE FINISHED JOB SHALL BE FUNCTIONAL AND COMPLETE IN
EVERY DETAIL INCLUDING ANY AND ALL ITEMS REQUIRED FOR A FULLY
FUNCTIONING SYSTEM.
2. ALL MATERIALS AND WORKMANSHIP SHALL MEET ALL APPLICABLE STATE AND
LOCAL CODES, ORDINANCES, UTILITY COMPANY REGULATIONS AND NATIONALLY
RECOGNIZED CODES AND STANDARDS.
3. DO NOT LOCATE BOXES BACK TO BACK IN WALL PARTITIONS. STAGGER AS
REQUIRED TO MINIMIZE SOUND TRANSMISSION.
4. COORDINATE THE SERVICE INSTALLATION WITH THE UTILITY COMPANY. INSTALL
METER CABINET PROVIDED BY THE UTILITY COMPANY IN ACCORDANCE WITH THE
UTILITY COMPANY'S STANDARDS.
5. PROVIDE ALL GROUNDING AS REQUIRED TO MEET THE UTILITY AND NEC SECTION
250 REQUIREMENTS.
6. ALL ELECTRICAL EQUIPMENT SHALL BE UL LISTED AND LABELED.
7. ALL EQUIPMENT AND DEVICES SHALL BE INSTALLED IN A PROFESSIONAL AND
WORKMANSHIP MANNER AND IN COMPLIANCE WITH NATIONAL ELECTRICAL
CONTRACTORS ASSOCIATION (NECA) RECOMMENDED STANDARDS.
8. MATERIALS SHALL BE RECEIVED AND STORED IN A MANNER TO BEST PROTECT
THE MATERIALS PRIOR TO INSTALLATION. PROTECTIVE COVERS
SHALL REMAIN IN PLACE AS MUCH AS POSSIBLE.
9. HANGERS AND SUPPORTS SHALL BE USED AS REQUIRED TO PROPERLY AND FULLY
SUPPORT ALL ELECTRICAL MATERIALS AND EQUIPMENT IN A PERMANENT MANNER.
10. ALL MATERIALS AND EQUIPMENT USED SHALL BE OF THE TYPE DESIGNED AND
SUITABLE FOR THE MANNER IN WHICH THEY ARE INSTALLED.
11. EQUIPMENT SHALL BE INSTALLED LEVEL, PLUMB AND TRUE WITH THE STRUCTURE
AND OTHER EQUIPMENT AND INSTALLED IN A HORIZONTAL OR VERTICAL POSITION
AS INTENDED.
12. ROUTE RACEWAYS PARALLEL OR PERPENDICULAR TO BUILDING SURFACES OR
EXPOSED STRUCTURAL MEMBERS AND FOLLOW SURFACE CONTOURS IN
ORDER TO PRESENT A NEAT APPEARANCE.
13. GROUP RACEWAYS WHERE POSSIBLE AND COMPLY WITH RECOMMENDED
SPACING STANDARDS.
14. BENDS AND OFFSETS IN PARALLEL RACEWAYS SHALL BE MADE FROM THE
SAME CENTER LINE SO THE BENDS AND OFFSETS REMAIN PARALLEL.
15. TAKE ALL NECESSARY PRECAUTIONS TO PREVENT FOREIGN MATTER FROM
ENTERING RACEWAYS. IF NECESSARY, CLEAN OUT RACEWAYS PRIOR TO
PULLING IN THE CONDUCTORS.
16. ALL WIRE AND CABLE SHALL BE SUITABLE FOR THE TEMPERATURE, CONDITIONS,
AND LOCATIONS WHERE THEY ARE INSTALLED.
17. TAKE ALL NECESSARY PRECAUTIONS WHEN PULLING WIRE AND CABLES TO
PREVENT DAMAGE TO THE INSULATION.
18. ALL CONDUCTORS TO BE PULLED IN A RACEWAY SHALL BE PULLED TOGETHER.
19. KEEP CONDUCTOR SPLICES TO A MINIMUM.
20. TYPICAL DEVICE MOUNTING HEIGHTS (ABOVE THE FINISHED FLOOR TO THE
CENTER OF BOX) ARE AS FOLLOWS:
a. WALL SWITCHES 48”
b.RECEPTACLES 18”
c.COUNTERTOP RECEPTACLES 42” OR 6” ABOVE THE COUNTERTOP
d.DISCONNECTS 72” TO THE TOP OF THE HANDLE
e.PANELBOARDS 72” TO THE TOP
f. TELECOM OUTLETS 18”
g.THERMOSTATS 54”
h.PULL STATIONS 48”
I. VISUAL STROBES 80”
GENERAL NOTES
ELECTRICAL SHEET INDEX
E000 ELECTRICAL NOTES, SYMBOLS, AND SCHEDULES
E101 LIGHTING PLAN
E201 POWER AND SYSTEMS PLAN
E500 ELECTRICAL PANEL SCHEDULES
LABELING AND IDENTIFICATION:
• PROVIDE NAME PLATE LABEL (IDENTIFICATION) TO SERVICE EQUIPMENT,
PANELBOARDS, DISCONNECT SWITCHES AND SIMILAR EQUIPMENT.
• PROVIDE LABEL TO IDENTIFY CIRCUIT NUMBER AT JUNCTION BOXES AND DEVICE
BOXES USING BLACK MARKER.
RACEWAYS:
• EMT, MINIMUM 3/4" CONDUIT, COMPRESSION FITTING, USE FOR EQUIPMENT
CONNECTION, FEEDERS AND BRANCH CIRCUITS. USE PVC40 FOR OUTDOOR
UNDERGROUND INSTALLATIONS.
SUPPORT:
• EMT CONDUIT: CONDUIT STRAP 3 FEET FROM END AND AT EVERY 10 FEET.
CONDUCTORS:
• 600VOLTS, 98% CONDUCTIVITY, COPPER, CLASS B, THHN/THWN
INSULATION, MINIMUM #12AWG. USE EMT CONDUITS FOR #8AWG AND LARGER.
WIRING DEVICES:
• RECEPTACLES: (NEMA 5-20R), DUPLEX, 20 AMP, 125 VAC, GROUNDING TYPE,
WHITE COLOR, HUBBELL 5352 OR EQUAL. MOUNT AT 18" A.F.F. UNLESS
OTHERWISE NOTED.
• GFCI TYPE RECEPTACLE: (NEMA 5-20RGFI), DUPLEX, 20 AMP, 125 VAC, DUPLEX 5 ML
AMP SENSITIVITY TRIP TYPE, HUBBELL GF-5362 OR EQUAL. MOUNT AT 18" A.F.F.
UNLESS OTHERWISE NOTED.
• OCCUPANCY SENSORS (WALL MOUNTED): REFER TO DRAWINGS FOR MODEL
NUMBER. MOUNT AT 48" A.F.F. UNLESS NOTED OTHERWISE.
• COVERPLATES: OFFICE: NYLON SCRATCH PROOF
DOCK: STAINLESS STEEL
• WEATHERPROOF: BELL BOX WITH WEATHERPROOF COVER.
MOTOR STARTERS:
• MANUAL STARTER SHALL BE HORSEPOWER RATED, THERMAL OVERLOAD TYPE WITH
PILOT LIGHT. MOUNT AT +72" A.F.F. TO TOP. SQUARE D 2500 OR EQUAL.
DISCONNECT SWITCHES:
• HEAVY DUTY TYPE, FUSIBLE OR NON FUSIBLE AS INDICATED ON DRAWINGS,
QUICK-MAKE QUICK-BREAK TYPE, HINGE LOCKABLE COVER, OPERATING LEVER.
MOUNTING AT +72" A.F.F. TO TOP. SQUARE D HEAVY DUTY OR EQUAL.
SPECIFICATIONS
GROUNDING:
• GROUNDING SYSTEM SHALL MEET REQUIREMENTS OF NEC ARTICLE 250. BOND
WATER PIPE, BUILDING STRUCTURE, AND 25' OF BARE COPPER WIRE, COPPER CLAD
GROUND ROD 3/4"D x 10'L, AND CONNECT WITH #2/0 AWG BARE COPPER CABLE TO
MAIN SERVICE DISTRIBUTION BUS. PROVIDE A SEPARATE GROUND WIRE WITH
EVERY BRANCH CIRCUIT. TEST IN ACCORDANCE WITH NEC ARTICLE 250.
• PROVIDE AN INTERSYSTEM BONDING TERMINATION FOR THE TELECOMMUNICATIONS
HEAD END EQUIPMENT AND BOND TO THE ELECTRICAL GROUNDING ELECTRODE
SYSTEM
STEP DOWN TRANSFORMER:
• TRANSFORMER HOUSING SHALL BE ENCLOSED IN VENTILATED, DRIP-PROOF
CODE GAUGE STEEL HOUSING, REMOVABLE ACCESS PANELS, RODENT BARRIERS ON
OPENING, PHOSPHATIZED, AND FINISH WITH CORROSION INHIBITING UNDERCOAT
AND ANSI GRAY FINISH.
• CORE AND COIL ASSEMBLY SHALL BE CONSTRUCTED OF CONTINUOUS COPPER
WINDING, HIGH GRADE, NON-AGING, GRAIN ORIENTED SILICON STEEL CORE,
COMPLETELY ISOLATED FROM THE ENCLOSURE USING VIBRATION ABSORBING
MOUNT,FLEXIBLE GROUNDING STRAP.
• TWO 2-1/2% FCAN AND FOUR 2-1/2% FCBN TAPS.
• INSULATION SHALL BE 600VAC, DRY TYPE, AIR COOLED, 220°C TEMPERATURE
CLASS 150°C.
• NOISE LEVEL SHALL BE LESS THAN ANSI STANDARD.
• DRY TYPE TRANSFORMER SHALL BE SIMILAR TO SQUARE D WATCH DOG SERIES OR
EQUAL.
SERVICE PANELBOARD:
• MAIN BUS, NEUTRAL AND GROUND BAR SHALL BE COPPER, NEMA-1
CABINET, GRAY PAINT, NAME PLATE, U.L. LISTED. LISTED TO USE AS
SERVICE ENTRANCE. SIMILAR TO SQUARE D NQOD OR EQUAL.
BRANCH CIRCUIT PANELBOARD:
• MAIN BUS, NEUTRAL BUS, AND GROUND BAR, SHALL BE COPPER, NEMA-1 CABINET,
GRAY PAINT, NAME PLATE, BOLT-ON BREAKERS, DOOR AND
TRIM WITH DOOR-IN-DOOR CONSTRUCTION, U.L. LISTED. PANEL DIRECTORY.
SIMILAR TO SQUARE D NQOD OR EQUAL.
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NUMBER DESCRIPTION LAMP
INPUT
WATTS NOTES
D1 ALPHABET NU4 RD RECESSED DOWNLIGHT LED 32 W OR EQUAL
D2 ALPHABET BETA4 PENDANT LED 34 W OR EQUAL
D3 ALPHABET NU4 RD RECESSED DOWNLIGHT LED 32 W MATCH EXISTING
EX TBD TBD EXIT LIGHT LED 4 W MATCH EXISTING
F1 FINELITE HP-2D DIRECT LINEAR LED 28 W OR EQUAL
F1.1 FINELITE HP-2 WW LINEAR WALLWASH LED 28 W OR EQUAL
K1 COLUMBIA LIGHTING LCAT22 2'x2' TROFFER LED 32 W OR EQUAL
K2 COLUMBIA LIGHTING LCAT22 2'x2' TROFFER WITH ELL14 EMERGENCY BATTERY PACK LED 32 W OR EQUAL
P1 LSI TBD DEEP BOWL ALUMINUM REFLECTOR LED 75 W OR EQUAL
POWER AND SYSTEMS SYMBOL FIRE ALARM SYMBOL SCHEDULE LIGHTING SYMBOL SCHEDULE
SCHEDULE
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
PLAN NOTE
ELECTRICAL PANEL
DUPLEX RECEPTACLE, 16" AFF (TYP)
DUPLEX RECEPTACLE, GROUND FAULT INTERRUPTER
DUPLEX RECEPTACLE, GROUND FAULT INTERRUPTER,
WEATHERPROOF, WITH "WHILE-IN-USE" COVER
DOUBLE DUPLEX RECEPTACLE
SPECIALTY RECEPTACLE
FLOORBOX
FLOOR POKE THRU
TELECOMMUNICATIONS OUTLET
PHONE OUTLET, WALL MOUNTED AT 48"
TV CABLE OUTLET
PUSHBUTTON
START/STOP STATION
JUNCTION BOX, WALL MOUNTED
JUNCTION BOX, CEILING MOUNTED
MOTOR
DISCONNECT SWITCH, NF = NON-FUSED
4'X8' PLYWOOD TELEPHONE BACKBOARD
SPEAKER CEILING MOUNTED
POKE THRU - 4" CORE
FURNITURE FEED - 2" CORE
CARD READER
MOTION SENSOR
REQUEST TO EXIT
NOTE: ALL SYMBOLS INDICATED ARE NOT NECESSARILY USED
ON THE PROJECT.
NOTE: ALL SYMBOLS INDICATED ARE NOT NECESSARILY USED
ON THE PROJECT.
NOTE: ALL SYMBOLS INDICATED ARE NOT NECESSARILY USED
ON THE PROJECT.
MANUAL PULL STATION, 48" AFF (TYP)
SMOKE DETECTOR
SMOKE DETECTOR-DUCT MTD
HEAT DETECTOR
TAMPER SWITCH
FLOW SWITCH
HORN/STROBE NOTIFICATION DEVICE, 80" AFF (TYP)
STROBE ONLY NOTIFICATION DEVICE
SPEAKER NOTIFICATION DEVICE
FIRE ALARM CONTROL PANEL
FIRE ALARM REMOTE ANNUNCIATOR
SWITCH, a = SWITCH LEG, 48" AFF (TYP)
3-WAY SWITCH
SLIDE DIMMER SWITCH
OCCUPANCY SENSOR SWITCH, WALL MOUNTED
PHOTOCELL
TIME CLOCK
2' x 4' LIGHT FIXTURE - XX DENOTES TYPE, a
SIGNIFIES SWITCH LEG, # DENOTES CIRCUIT
EMERGENCY BATTERY PACK
EXIT SIGN, WALL MOUNTED
EXIT SIGN , CEILING MOUNTED
EXTERIOR WALL PACK
PENDANT LIGHT FIXTURE
TIMER SWITCH
NIGHT LIGHT
HORN/STROBE NOTIFICATION DEVICE,
WEATHERPROOF
OCCUPANCY SENSOR SWITCH, CEILING MOUNTED
#
GFI
GFI
WP
TV
J
J
W
NF
S
F
FF
CR
MS
REX
F
S
S
H
TS
FS
D
F
F
V
WP
S
FARA
FACP
OC
PC
TC
S
a
3
D
OC
a
xx
#
T
NL
BACK BOX ROUGH-IN W/ EMPTY 1" CONDUIT
EXTENDED 6" ABOVE CEILING AND PULL-STRING
S
S
S
S
FF FURNITURE FEED - WALL
S HORN/STROBE - CEILING
F
S STROBE ONLY - CEILING
F
FLOORBOX SCHEDULE
MODEL MANUFACTURER DESCRIPTION SIZE
4FF WIREMOLD FLUSH POKE-THRU FURNITURE FEED 4"
6AT WIREMOLD FLUSH POKE-THRU 6"
RC3 WIREMOLD FLUSH POKE-THRU 4"