HomeMy WebLinkAbout18020131 Building PlansRELEASE
10. HLL UUUR rlMIV ULr-3 3rlHLL Dr- Ur I rlC Lr-VCR I irr-, rlHRU VV HRC 3rlHLL Dr- I V I U U IV I CU IVU rl1 UrICR I rlMIV 40 HDUVr- r1IV 13 rl r L U U rC.
19. ALLACCESS PANELS SHALLBE 24"X30" UNLESS OTHERWISE NOTED.
20. ALLGLASS UNITS LOCATED IN HAZARDOUS LOCATIONS AS INDICATED IN IBC 2406.3 SHALLCOMPLY WITH TEST REQUIREMENTS OF CONSUMER
PRODUCT SAFETY COMMISSION 16, CFR PART 1201 FOR HUMAN IMPACT LOADS.
21. ALLSAW CUTTING AND CORING LOCATIONS SHALLBE REVIEWED IN FIELD BYTHE GENERALCONTRACTOR PRIOR TO CUTTING/CORING.
22. ALLWOOD IS TO BE FIRE -RETARDANT TREATED PER AWPA C20 AND C27 AND SHALLNOT HAVE A FLAME SPREAD OF GREATER THAN 25 WHEN TESTED
IN ACCORDANCE WITH ASTM E-84. PER IBC SECTION 2303.2.
S.F. /
OCCUPANT
EGRESS
EXITS
EXITS
EGRESS
USE
AREA
PERSON
LOAD
REQUIRED
REQUIRED
PROVIDED
WIDTH
O.L. X .20 =
PROVIDED
IBCTABLE
IBC 1005.1
IBCTABLE
1004.1.1
1021.1
M USE GROUP
743 SQ. FT.
30
25
36"
1
1
36"
SPACEF30A
26 FIREBLOCKING SHALLBE INSTALLED AT ALLINTERCONNECTIONS BETWEEN VERTICALAND HORIZONTALSPACES SUCH AS OCCUR AT SOFFITS OVER
GR ESS:
23. ALLEXTERIOR WOOD BLOCKING IS TO BE PRESSURE TREATED PER AWPA U1 AND M4.
REQ'D PROVIDED
24. ALL FASTENERS, CONNECTORS, OR OTHER HARDWARE IN DIRECT CONTACT WITH PRESERVATIVE TREATED OR FIRE RETARDANT TREATED WOOD SHALL
EGRESS WIDTH (OCC LOAD x .2") = 25 x .2" = 5" 36" IBC SECTION 1005.1
BE STAINLESS STEELTYPE 304 OR TYPE 316, OR HOT -DIPPED GALVANIZED STEELASTM A653, CLASS G-185 WITH 1.85 OUNCES OF ZINC PER SQUARE
FOOTTO REDUCE THE CORROSION PROCESS.
NUMBER OF EXITS: 1 1 IBC SECTION 1021.2
EXIT ACCESS TRAVELDISTANCE: 250'-0" 35'-11" IBC TABLE 1016.1
25. FIREBLOCKING SHALLBE INSTALLED IN CONCEALED SPACES OF STUD WALLAND PARTITIONS, INCLUDING FURRED OR STUDDED -OFF SPACES OF
COMMON PATH OF TRAVEL: 75'-0" 11'-6" IBC SECTION 1014.3
MASONRY OR CONCRETE WALLS, AND AT THE CEILING AND FLOOR OR ROOF LEVELS. PER IBC SECTION 717.2.2.
PLUMBING FIXTURES PROVIDED: IBC TABLE 2902.1
CABINETS, DROP CEILINGS, COVE CEILINGS AND SIMILAR LOCATIONS. PER IBC SECTION 717.2.3.
27. REQUIRED FLAME SPREAD RATING: INTERIOR FINISH OF WALLS AND CEILINGS SHALLHAVE A FLAME SPREAD RATING NOT GREATER THAN THAT
DESIGNATED BYTHE CLASS PRESCRIBED FOR THE VARIOUS GROUPS LISTED IN IBC TABLE 803.5, WHEN TESTED IN ACCORDANCE WITH IBC SECTION
803.2.
28. PROVIDE PORTABLE FIRE EXTINGUISHERS WITH U.L. LABELAND A RATING OF NOT LESS THAN 4A 80B:C WITH 75 FT TRAVELDISTANCE TO ALL POSITIONS
OF BUILDING OR AS DIRECTED BYTHE FIRE DEPARTMENT FIELD INSPECTOR.
WATER CLOSET/URINALS
LAVATORIES
MS
USE
OCC.
CALC.
MALE/FEMALE
CALC.
MALE/FEMALE
1
OCCUPANT LOAD M
25
1:50
.25/.25
1:80
.15/.15
REQUIRED NUMBER
OF FIXTURES
.25/.25
.15/.15
1
NUMBER OF FIXTURES
PROVIDED
1
1
1
AREA OF WORK
ACCESSIBILITY INFORMATION
SITE LOCATION MAP
PROJECT TEAM
1. ACCESS TO THESE FACILITIES SHALLBE PROVIDED AT PRIMARY ENTRANCES.
PROJECT OWNER
ARCHITECT
MEP ENGINEER
2. THE SLOPE OF PUBLIC WALKS SHALLNOT EXCEED MAX. CROSS SLOPE 2 %.
Washington Prime Group
red architecture + planning
red architecture + planning
3. WALKING SURFACES SLOPING GREATER THAN 2 % SHALLBE SLIP RESISTANT.
4. PROVIDE A 60" x 60" MIN. LANDING ON STRIKE SIDE OF DOOR WITH 44" MINIMUM WIDTH IN DIRECTION OF TRAVEL.
PROJECT LOCATION
180 East Broad Street
Colu mbu s,Ohio 43215
855 Grandview Ave, Suite295
Colu mbu s,Ohio 43215
855 Grandview Ave, Suite295
Colu mbu s,Ohio 43215
5. WALKS SHALLEXTEND 24 TOTHE SIDE OF THE STRIKE EDGE OF DOOR OR GATE T HAT SWINGS TOWARD THE WALK.
P:614.887.5664
P:614.487.8770
P:614.487.8770
6. EVERY REQUIRED EXIT DOORWAY SHALLBE SIZED FOR A DOOR NOT LESS THAN 3'-0" WIDE BY 6'-8" HIGH CAPABLE OF OPENING 90 DEGREES AND
CONTACT: Chad Biniker
F: 614.487.8777
CONTACT: Stephan Sahayda
F:614.487.8777
CONTACT: DougSmelker
MOUNTED SO THATTHE CLEAR WIDTH OF THE EXIT SHALLBE A MINIMUM OF 32".
7. THRESHOLDS TO BE A MAXIMUM OF i"ABOVE THE ADJACENT FINISHED FLOOR.
CONTRACTOR
8. MAXIMUM EFFORT TO OPERATE DOORS SHALLNOT EXCEED 5 LBS FOR INTERIOR DOORS AND 15 LBS FOR EXTERIOR DOORS.
9. THE BOTTOM 10" OF ALLDOORS EXCEPT AUTOMATIC SLIDERS SHALLHAVE A SMOOTH UNINTERRUPTED SURFACE.
TBD
10. THE BUILDING SHALLCOMPLY WITH THE AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES (ADAAG) AND ANSI A117.1-2009, INCLUDING
BUT NOT LIMITED TO IBC CHAPTER 11.
11. CONTROLS AND OPERATING MECHANISMS SHALLBE ACCESSIBLE AND HAVE MOUNTING HEIGHTS COMPLYING WITH ANSI 4.27.
RIFE
CNN RULjIbhROOM, DIRECTIONAL, AND INFORMATION SIGNS SHALLBE ACCESSIBLE DESIGN COMPLYING WITH ANSI 4.13 AND 4.30.
Suubjeatto morepdG of State andLocal Codes
0tp of Camal
DATE: 03/07/18
Nick Mishler
• • un Ln O n
ra r-1 rr_ n
ra N N � r-
(3) M 00 00
• .� 00 00
> •-
�O
ra
' Lr)Ln C (6
00 Z3
0
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE + PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
v
z
w
Ln
W
N
>
0
nro
=
0
1
Z)
0
00
C^
L
Z)0
J
Q
zmo
J
N
m
(DW
Q
LU
LU
J
Q
�
Q
z
�o
()
O
Wa
z
o
Q
�m
M>_z
a
w
U
J
LU
z~
cn
U
�
�
V)
w
m
Q O
Q
0
(�
rl
U Li
�:
r-I
PROJECT NUMBER:
W P GO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
SHEET:
COVER SHEET
Celili
z_
18" MIN.
FRONT APPROACH, PULLSIDE
FIGURE 404.2.3.2 (a)
RECESSED DOOR
FRONT APPROACH, PUSH SIDE
FIGURE 404.2.3.5 (b)
NOTE -
Y = 48" IF DOOR HAS
BOTH A CLOSER AND
LATCH
z
c.l 22" MIN.
u
HINGE APPROACH, PUSH SIDE
FIGURE 404.2.3.2 (e)
a
rn
00
RELEASED IFCR CONSTRUCH
Suubjeul to aumpliamce with all regulatimms
at State and Ilocal Endles
IC'Itp u Caimal
ntro
DATE: 03/07/18
Nick Mishler
I- � II
z
0 18" MIN. 00
x
RECESSED DOOR
FRONT APPROACH, PULLSIDE
FIGURE 404.2.3.5 (a)
z
00
^ 12" MIN.00
� In
RECESSED DOOR
FRONT APPROACH, PUSH SIDE
WITH BOTH CLOSER AND LATCH
FIGURE 404.2.3.2 (c)
NOTE -
Y = 54" IF DOOR HAS
A CLOSER
BO
24" MIN.
LATCH APPROACH, PULLSIDE
FIGURE 404.2.3.2 (f)
i z II � li
I� z
00 X = 22" MIN.
POCKET/ FOLDING DOOR POCKET/ FOLDING DOOR
FRONT APPROACH POCKET OR HINGE APPROACH
FIGURE 404.2.3.3 (a) FIGURE 404.2.3.3 (b)
WITHOUT DOOR WITHOUT DOOR
FRONT APPROACH SIDE APPOACH
FIGURE 404.2.3.4 (a) FIGURE 404.2.3.4 (b)
NOTE : X = 12" IF DOOR HAS
BOTH A CLOSER AND LATCH
z_
00
FRONT APPROACH, PUSH SIDE
FIGURE 404.2.3.2 (b)
42" }
NOTE-
X = 36" MIN. IF Y = 60"
X=42" IFY=54"
HINGE APPROACH, PULLSIDE
FIGURE 404.2.3.2 (c & d)
NOTE -
Y = 48" IF DOOR HAS
A CLOSER
cz_
G
24' I N
u
L }
LATCH APPROACH, PUSH SIDE
FIGURE 404.2.3.2 (9)
z I
X=24" MIN.
J
POCKET / FOLDING DOOR
STOP OR LATCH APPROACH
FIGURE 404.2.3.3 (c)
MANEUVERING CLEARANCES AT DOORS
1/4" = 1'-0"
x
a
2
1� a
x
a
FIGURE 303.2 FIGURE 303.3
VERTICALCHANGE IN LEVEL BEVELED CHANGE IN LEVEL
CHANGES IN LEVEL
N.T.S.
12" MIN. 36" MIN. 12" MIN.
10 10
N
z_
60" MIN. m
CIRCULAR T-SHAPED
FIGURE 304.3 (a) FIGURE 304.3 (b)
WHEELCHAIR TURNING
1/4" = 1'-0"
37" MIN_
HINGED DOOR
FIGURE 404.2.2 (a)
32�
Cl
32" MIN.
1
FOLDING DOOR
FIGURE 404.2.2 (c)
CLEAR DOO RWA
1/4" = 1'-0"
X
a
in 2
0
10" MA)qLl
.1
UNOBSTRUCTED SIDE REACH
FIGURE 308.3.1
-9--� SIDE REACH
4" MAX.
I I
OF
n'
x o 11
x
N 12" MAX. 12" MAX. a
n N
x
n
N
FIGURE 307.2 FIGURE 307.3
LIMITS OF PROTRUDING OBJECTS POST -MOUNTED PROTRUDING OBJECTS
PROTRUDING OBJECTS
1/4" = 1'-0"
1pm m m m
42" MIN. 42" MIN. 36" MIN. 36" MIN.
24" MA 48" MIN. 24" MAX. X < 48" X < 48"
180 DEGREE TURN 180 DEGREE TURN (EXCEPTION)
FIGURE 403.5 FIGURE 403.5.1
CLEAR WIDTH AT 180 DEGREE TURN
r5--� CLEAR WIDTH OF AN ACCESSIBLE ROUTE
SLIDING DOOR
FIGURE 404.2.2 (b)
36" MIN.
MO N
DOORWAYS WITHOUT DOORS
FIGURE 404.2.2 (d)
YWIDTH &DEPTH
a
� a
a 2
0 1.0
m
10" MAX 10" - 24" MAX.
UNOBSTRUCTED HIGH SIDE REACH
FIGURE 308.3.2 (a)
1/4" = 1'-0"
0
Of
O
O
— 0
� z
00
0
0
FIGURE 404.2.5 (a) FIGURE 404.2.5 (b) FIGURE 404.2.5 (c)
TWO HINGED DOORS IN SERIES
1/4" = 1'-0"
48" MIN.
2
L _
UNOBSTRUCTED
FORWARD REACH
FIGURE 308.2.1
10 FO RWA
X
a
2
00
UNOBSTRUCTED HIGH
FORWARD REACH
FIGURE 308.2.2 (a)
RD REACH
> 20"-25" M
AREA OF
REFUGE
ARE
RFF
OF \
G
�\
z
a
ARIES
2
-
SEE FIGURE
00
�
12/A0.2
TACTILE
CHARACTERS
Of
Lu
z
w
U
F-
Z
C�
VARIES - COORD:
IN FIELD
cZ
4 G
CLEAR FLOOR SPACE,
18 MIN. CENTERED ON TACTILE
CHARACTERS
ARC OF DOOR SWING
FIGURE 703.3.10 FIGURE 703.3.11
HEIGHT OF RAISED CHARACTERS LOCATION OF SIGNS AT DOORS
ABOVE FLOOR
COMMUNICATION
ELEMENTS AND FEATURES
1/4" = 1'-0"
91,
EDGE OF
DOOR FRAME
O O
z_
- y
�\ to
RESTROOM
FAMILY
MEN
STAIRS
11/2" HIGH WHITE
LETTERING ON
BLACKBACKGROUND
z_
0
WOMEN
PROVIDE (1) SIGN PER TOILET
COMPLYING WITH ANSI 2009, SECTION 703.
SIGN TO HAVE RAISED AND BRAILLE
CHARACTERS AND PICTORIALSYMBOL
OF ACCESSIBILITY. MOUNT 5'-0" TO
CENTERLINE A.F.F.
BLACKPLASTIC (FIELD)
74M.
BACKGROUND w/ WHITE RAISED OR
DEPRESSED EMBLEMS (NOTE- EMBLEMS
& LETTERING MUST BE RAISED OR
UNOBSTRUCTED HIGH
DEPRESSED MIN. 1/32" TYPICAL)
FORWARD REACH
FIGURE 308.2.2 (b)
1/4" = 1'-0" G0.1 1/4" = 1'-0"
48" MIN. N �
n n
v__ x x
ri z_
z z 0
0
0 CD
o
13�
00
M, %
X > 24" , 36" MIN. , 60" MIN.
CLEARFLOORSPACE FORWARD APPROACH PARALLELAPPROACH FORWARD APPROACH PARALLELAPPROACH
FIGURE 303.5 FIGURE 303.5 (a) FIGURE 303.5 (b) FIGURE 305.7 (a) FIGURE 305.7 (b)
MINIMUM CLEAR FLOOR SPACE FOR WHEELCHAIRS
1/4" = 1'-0"
EXIT
Nouns
SOON
moons
INTERNATIONALSYMBOL INTERNATIONALTDD INTERNATIONALSYMBOL
OF ACCESSIBILITY SYMBOL OF ACCESS FOR HEARING
FIGURE 703.6.3.1 FIGURE 703.6.3.2 LOSS
FIGURE 703.6.3.3
ADASIGNAGE
1/4" = 1'-0"
• • un Ln O n
ru r-1 ri r_ n
ru N N � r-
(3) M 00 00
• .� O 00 00
> •—
�O
' Ln (13
Ln E
00 Z3
O
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE + PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
uj
W
��-I
N
O
=
0
1
D
0
5m
L
00
CL
�
J
O
Q
zm0
J
N m
(DW
Q
Lu
W
Lu
JQQ
�
z
�
V)
o
O
Wa
zo
p
�m
CE
ILL�z
waJ
U
W
z~
cn
U
w
M
�
Q O00
Q
O
(�
rl
U Li
rl
PROJECT NUMBER:
W P GO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
ADAAG / ANSI DETAILS
SHEET:
GOel
NOTE : 0" X 48" OF CLEAR FLOORSPACE IS REQUIRED
IN EVERY RESTROOM. WHEN 30" X 48" CLEARFLOOR
SPACE IS PROVIDED BEYOND THE ARC OF THE DOOR
SWING, THE DOOR IS PERMITTED TO SWING INTO THE
CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR
ANY FIXTURE. DOOR MAY SWING INTO A REQUIRED
WHEELCHAIRTURNING SPACE. PER2009 ANSI
SECTION 603.2.2, AN EXCEPTION IS MADE IN SINGLE
7'-2" OCCUPANCY TOILET ROOMS TO ALLOW DOOR TO 7'-2"
SWING INTO THE REQUIRED FIXTURE CLEAR FLOOR OR
60" MIN. GROUND SPACE \ WHEN ANOTHER CLEAR FLOOROR 60" MIN.
16" 52" 16"-18" GROUND SPACE IS PROVIDED OUTSIDE THE RADIUS OF 16" 52" 16"-1
THE DOOR SWING_01
WALLHUN4&�
LAVATORY
FLOOR MOUN
WALLHUNG
TANK -TYPE WATER
��J•�
LAVATORY
��� O��
CLOSET��l���Prn
O C
�0
SHADE AREAS
30" MIN x 48" MIN.
C� /
SHADE AREAS =
CLEAR SPACE
30" MIN x 48" MIN.
_
CLEAR SPACE
L FLOOR MOUNTED
TANK -TYPE WATER
(A) CLOSET
MINIMUM CLEAR DIMENSIONAL
REQUIREMENTS - INWARD DOOR SWING (B)
MINIMUM CLEAR DIMENSIONAL
SINGLEOCCUPANT TOILET ROOM REQUIREMENTS- OUTWARDDOORSWING
1/4" = 1'-0"
4" MAX. OR 52" MIN. WALLMOUNTED W.C.
4" MA OR 55" MIN. FLOOR MOUNTED
32" MIN. a
DOOR o
z_
Ln
m
u u
42" MIN. 12" MAX.
56" WALLMOUNTED W.C.
X = 42" 59" MIN. FLOOR MOUNTED W.0
STANDARD STALL
FIGURES 604.9.3.1 (a & b)
TO I LET STALLS
1/4" = 1'-0"
DOOR SHALLNOT SWING INTO
THE REQUIRED MIN. AREA OF
THE COMPARTMENT
00
56" MIN. WALLMOUNTED W.C.
36" MIN. 59" MIN. FLOOR MOUNTED W.C.
STANDARD STALL
(END OF ROW)
FIGURES 604.9.3.1 (c)
54" MIN.
36" MII N. 39"-41"
12" MI 2" MAX. z_
24" MIN, 42" MIN. rn
c-I c-I
m r
PROTRUDI - z -1 -
m an
rn DISPENSER ' cn can
`" rnBELOW GRAB - =
BAR
4" MIN.
42" MAX.
REAR WALL
SIDE WALL
FIGURE 604.5.2
FIGURE 604.4
FIGURE 604.5.1
FIGURE 604.7 (a)
FIGURE 604.11.4
WATER
CLOSET GRAB BARS
1/4" = 1'-0"
a
rn
00
o
,r"
RELEASED IFCR CONSTRUCTION
Suubjeut to aurnpliance with all regulatimns
of State and Vocal Endles
ICltp of Cannel
ntro
DATE: 03/07/18
Nick Mishler
Fol
X
2 Q Q x X z—
00
a� -
�. �. m.
" MAX.
8" MIP
17" MIN.
Fol
X a a z-
00 -
a� -
�. �. m.
" MAX.
6" MIP
17" MIN.
oor
FIGURE 606.3
2 LAV. CLEARANCES
G0.2 1/4" = 1'-0"
m
i�
42" MIN. A, 2" MAX.
66" MIN. WALL MOUNTED W.C.
X = 42" 69" MIN. FLOOR MOUNTED W.C.
AMBULATORY STALL
FIGURES 604.10
48' MIN
36"
BACK
18"
J
J
J
O J
CONTROLAREA
a
z �
O
F
N
x
m
00
bo
m
rn
CONTROLWALL
36" BY 36" STALLGRAB 36" BY 36" STALLSHOWER
BARS AT SHOWER STALL SIZE AND CLEARANCES
10 SHOWER REQUIREMENTS
1/4" = 1'-0"
48" MIN.
19" MACl
X.
11
z_
0
m
17" MIN.
Tj
48" MIN.
19" MAX.
z_
F_
rn
17" MIN.''
LAV. CLEAR FLOOR SPACE
1/4" = 1'-0"
18" N
OTHER FIXTURES NOT
ALLOWED WITHIN THIS AREA
LAV.
60" MIN.
CLEARANCE FOR
WATER CLOSET
FIGURE 604.3
W.C. CLEAR
FLOOR SPACE
GG 1/4" = 1'-0"
13 1/2" MIN. 13 1/2" MIN. PARTITION PARTITION
" MIN. 6" MIN.
x
a _
� z z
WALLHUNG TYPE STALLTYPE
FIGURE 605.2 (a) FIGURE 605.2 (b)
7 URINAL CLEARANCES
1/4" = 1'-0"
23" MAX
x Q
2 N
N Lln cL
O
1 1/2" MAX
Lu
16"M
SHOWER SEAT DESIGN
NOTE-
Y=36" WHEELCHAIRACCESSIBLE
Y= 38" -43" STANDING PERSONS
5" MAX. 15" MIN.
8" MIN. 6" MAX.
SPOUT HEIGHT AND
KNEE CLEARANCE
FIGURE 602.5 (b)
DRINKING FOUNTAINS
1/4" = 1'-0"
ELEVATION ADULT ELEVATION CHILDREN
FIGURE 604.9.5 (a) FIGURE 604.9.5 (b)
TOILET STALLS CLEARHEIGHT
1/4" = 1'-0"
PLAN
FIGURE 604.9.5 (c)
• • un Ln O n
ru r-1 ri r_ n
ru N N � r-
(3) M 00 00
• .� O 00 00
> •—
�O
' LnLn C (13
00 Z3
0
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE + PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
w
uj
N
O
NO
=
0
1
Z)
5m
00
Z)
J
O
O
Q
zm0
J
N
m
(DW
Q
L u
W
LJJ
cl:�
J
Q
�
Q
z
�o
()
OWa
z0
�o
0
CE
�
�z
a
w
U
J
Lu
z
~
cn
U
�
�
V)
w
Cn
R:I-
Q O
Qo
00
(�
rl
U L L
rl
PROJECT NUMBER:
W P GO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
ADAAG / ANSI DETAILS
SHEET:
G0s2
a
1.0
0
0
N
RELEASED IFCR CONSTRUCTION
Suubjeut to aornpliance with all regofatimns
of State and Ilmeal Endles
ICltp of Cannel
ntro DATE: 03/07/18
Nick Mishler
LIFE SAFETY PLAN
1/4" = 1'-0"
27'-1"
LIFE SAFETY GENERAL NOTES
A. 36 INCHES REQUIRED AISLE WIDTH MINIMUM. IBC SEC 1017.3.
B. ONE EXIT OR ACCESS DOORWAY REQUIRED FOR B,M USES UNDER 50 OCCUPANTS. IBC TABLE
1015.1
C. NO DEAD END CORRIDORS OVER 20'-0" IN LENGTH. (50'-0" ALLOWED FOR B, MUSE WITH FULLY
AUTOMATED SPRINKLER SYSTEM). IBC SEC 1018.4
D. MAXIMUM COMMON PATH TRAVELDISTANCE TO AN EXIT IS 75'-0". MEASURED ATTHE MOST
REMOTE POINT ALONG THE NATURALAND UNOBSTRUCTED PATH OF HORIZONTALAND VERTICAL
TRAVELTO THE EXIT FOR A SPACE WITH MORE THAN 1 EGRESS. FOR B, S OCCUPANCIES, WHERE
THE SPACE IS PROVIDED WITH A FULLY AUTOMATED SPRINKLER SYSTEM, THE MAXIMUM DISTANCE
IS 100'-0". IBC TABLE 1014.3
E. MAXIMUM EXIT ACCESS TRAVELDISTANCE IS 250'-0" WITH SPRINKLERS. (MUSE), AND 300'-0"
WITH SPRINKLERS (B USE). IBC TABLE 1016.2
F. WALKING SURFACES THAT ARE PART OF AN ACCESSIBLE ROUTE SHALLCOMPLY WITH 2O10 ADA SEC
403.
G. TRANSITIONS AT DOORWAYS AND BETWEEN FLOORING MATERIALS SHALL NOT BE GREATER THAN
1/2". 2010 ADA SEC 404.2.5
H. DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED MEANS OF EGRESS WIDTH BY
MORE THAN 7 INCHES. DOORS IN ANY POSITION SHALLNOT REDUCE THE REQUIRED WIDTH BY
MORE THAN ONE HALF. IBC SEC 1005.7.1.
CODED NOTESO
1. LEASE LINE.
6. EMERGENCY LIGHTING. REFER TO MEP
DRAWINGS.
2. PROPOSED FIRE EXTINGUISHER LOCATION.
7. EXISTING STRUCTURALCOLUMN TO REMAIN.
3. EXISTING ELECTRIC PANELAND TRANSFORMER
LOCATION. REFER TO ELECTRICALDRAWINGS.
4. ADJACENT TENANT, N.I.C.
5. EXISTING 1—HR RATED DEMISING WALL.
FIRE EXTINGUISHER NOTES
1. G.C. TO PROVIDE MIN. OF 1 FIRE EXTINGUISHERS. G.C. TO VERIFY AND COORDINATE LOCATIONS
AND QUANTITIES WITH LOCALFIRE MARSHAL.
2. PER IFC, THE MINIMUM IS A 2A1013C EXTINGUISHER WITHIN 75' OF TRAVELDISTANCE OF ALL
AREAS.
3. NFPA INSPECTION TAGS SHALL BE ATTACHED TO ALL FIRE EXTINGUISHERS.
CALCULATIONS
LEASE AREA
743 S.F.
LEASE AREA CALCULATIONS
F30A (MERCANTILE)
743 S.F.
1 : 30 SF
25
CODE COMPLIANCE
MEANS OF EGRESS — INDIANA BLDG CODE (IBC 2006)
MEANS OF EGRESS — REQUIRED
1 MEANS OF EGRESS
EACH SPACE PROVIDED
1 MEANS OF EGRESS
MAX COMMON PATH OF TRAVEL
ALLOWED
75'-0"
(FULLY SPRINKLERED)
PROVIDED
35'-11"
FIRE —RESISTANCE RATINGS —
EXISTING DEMISING
WALLS-
(TYPE 1113, SPRINKLERED)
1 HIR RATED
LEGEND
36" CLEAR FLOOR SPACE
DIRECTION OF TRAVEL
• Ln Ln O I-
> Ol
N N
Qjm0000
�tR*rI^
•O Z3 O 00 00
> to •— q*
�O
>✓ vi l0 l!7
ty0 �
Lnaj m
Ln E +1 L
00
O
U
COPYRIGHT 2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE + PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
w
Ln
Lu
N
O
=
0
1
Z)
0
00
CL
Z)0
J
Q
zm0
J
N
m
(DW
Q
Lu
Lu
J
Q
�z
Q
�o
()
O
Wa
z0
�CE
a
z
m
w
U
J
Lu
z~
cn
U
�
�
V)
w
M
Q O
Q
O
(�
rl
U LL
�:
r-I
PROJECT NUMBER:
WPGO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
LIFE SAFETY PLAN
SHEET:
G0.3
a
m77
ai
00
I
O
N
RELEASED IFCR CONSTRUCTION
Suubjeut to aornpliance with all regofatimns
of State and Ilmeal Endles
ICltp of Cannel
ntro DATE: 03/07/18
Nick Mishler
ARCH ITECTURALFLOOR AND FINISH PLAN
1/4" = 1'-0"
REFLECTED CEILING PLAN
1/4" = 1'-0"
y
WALLPARTITION SCHEDULE
SYMBOL
DIAGRAM
DESCRIPTION
DETAIL
RATING
5/8" GYPSUM BOARD TO 1/2" ABOVE FRAMING
A 1
3 5/8" (20 GA) METALSTUDS @ 24" O.C.
CONTINUOUS SOUND BATTS
8/A8.1
---
5/8" GYPSUM BOARD TO 1/2" ABOVE FRAMING
12'-0" A.F.F.
NOTES:
1. FIELD VERIFY ALL DIMENSIONS. DIMENSIONS ARE TO THE FACE SHEATHING UNLESS NOTED OTHERWISE.
2. PROVIDE VERTICALCONTROLJOINTS AT 30'-0" O.C. MAX. SEE DETAILS 4/A1.2 AND 5/A1.2.
3. ALLPARTITIONS THAT ARE TO BE BUILTTO DECK SHALL INCLUDE ANY STRUCTURE (JOISTS, BEAMS, ETC.) THAT MAY
NEED TO BE FRAMED OUT IN ORDER TO PROVIDE DRYWALLTO DECK. ALLPENETRATIONS AND FLUTES IN DECKSHALL
BE SEALED AS REQUIRED.
4. PROVIDE A GALVANIZED STEELSHEET DEEP LEG DEFLECTION TRACK(20 GA.), 'SLP-TRK' BY SLIPTRACKSYSTEMS, INC. AT
ALLFRAMING THAT EXTENDS FROM THE SLAB TO THE UNDERSIDE OF THE STRUCTURE ABOVE. SECURE DEFLECTION
TRACKTO STRUCTURE WITH FASTENERS AT 2'-0" O.C. MAXIMUM. DO NOT SECURE TRACKTO VERTICALSTUDS.
PROVIDE MINIMUM OF 5/8" TO TOP OF METALSTUD.
5. ALLBOTTOM TRACKRUNNERS ARE TO BE HELD IN PLACE WITH FASTENERS AT 2'-0" O.C. MAX WITH HILTI POWER
DRIVER ANCHOR ICBO #2388, .0145" DIAMETER SHANK WITH 1 1/8" MINIMUM PENETRATION. SEE DETAILS 4/A1.2
6. PROVIDE HORIZONTALBRIDGING IN ALLPARTITION FRAMING ATA MINIMUM OF 6'-0" O.C. VERTICALLY. GENERAL
CONTRACTOR TO COORDINATE WITH METALSTUD MANUFACTURER TO DETERMINE IF HORIZONTAL BRIDGING IS
REQUIRED FOR METALSTUD PARTITION WALLS THAT HAVE GYPSUM BOARD ON BOTH SIDES THAT EXTEND FROM
FINISHED FLOOR TO UNDERSIDE OF STRUCTURE ABOVE.
7. METALSTUD NON-STRUCTURALWALLSYSTEMS ARE TO FOLLOW ASTM C754 & ASTM C645.
8. ALLGYPSUM BOARD IS TO BE 5/8" THICK UNLESS NOTED OTHERWISE. PROVIDE TYPE'X' GYPSUM BOARD AT ALLFIRE
RATED PARTITIONS.
9. TAPE, MUD, AND SAND GYPSUM BOARD SMOOTH READY FORTENANT FINISHES AT INTERIOR FACE OF ALLGYPSUM
BOARD SURFACES. PROVIDE ASTM C840 LEVEL4 FINISH UNLESS NOTED OTHERWISE.
10. ALLPLYWOOD BLOCKING IS TO BE FIRE RETARDANT TREATED.
11. PROVIDE FIRE SAFING AT ALLPARTITION/FURRING CAVITIES AT CEILING LEVELS OPEN TO CEILING PLENUMS.
SYMBOLLEGEND
O
FLOOR PLAN CODED NOTE
(SEE SCHEDULE ON THIS SHEET)
XX
WALLTYPE TAG
(SEE SCHEDULE ON THIS SHEET)
XXX
DOORTAG
(SEE SCHEDULE ON SHEET 8.1)
WALLLEGEND
EXISTING WALL/PARTITION TO REMAIN
NEW WALL/PARTITION
REFLECTED CEILING PLAN LEGEND
®
24" x 24" SUPPLY AIR DIFFUSER
(SEE MECHANICALSHEETS)
❑O
24" X 24" RECESSED TROUGH LIGHT
REFER TO ELECTRICALDRAWINGS
24" x 24" RETURN AIR GRILLE
(SEE MECHANICALSHEETS)
24" X 48" ACOUSTICALCEILING TILE -
ARMSTRONG 1851 DUNE OR APPROVED
EQUAL.
NOTE -
SEE MECHANICALAND ELECTRICALSHEETS FOR ALL FIXTURE SPECIFICATIONS, WIRING, AND POWER REQUIREMENTS.
GENERAL FLOOR PLAN NOTES
A. ALLUNMARKED WALLS SHALLBE THE SAME AS THE CLOSEST MARKED WALLTYPE. SEE THIS SHEET FOR WALL/PARTITION
SCHEDULE.
B. GENERAL CONTRACTOR TO PROVIDE ALL NEW WALLS INDICATED ON FLOOR PLAN. SEE WALL/PARTITION SCHEDULE FOR
ALLWALLTYPES.
C. ALL EXISTING WALLS AFFECTED BY DEMO WORKTO BE PATCHED AND REPAIRED. PROVIDE ASTM C840 LEVEL4 FINISH
UNLESS NOTED OTHERWISE.
D. REFER TO MEP DRAWINGS FOR ADDITIONALSCOPE OF WORK.
ARCH ITECTRUALFLOOR
PLN CODED NOTES O
1.
EXISTING STRUCTURALCOLUMN TO REMAIN
8. REMOVE EXTERIOR CERAMIC GLAZED TILE UNER
STOREFRONTTO EXTERIORSHEATHING. INSTALLNEW
2.
EXISTING DEMISING WALL. TAPE, SPACKLE, AND SAND AS
MASONRY VENEER PER MANUFACTURER'S
REQUIRED TO PROVIDE LEVEL4 FINISH READY TO
INSTRUCTIONS.
RECEIVE TENANT SELECTED FINISHES
3.
EXISTING ELECTRICALPANELS AND TRANSFORMER.
REFER TO MEP DRAWINGS.
4.
ADJACENT SPACE. N.I.C.
5.
LEASE LINE
6.
EXISTING EXTERIOR SIDEWALK
7.
EXISTING STOREFRONT.
FINISH SCHEDULE
MARK
MANUFACTURER
DESCRIPTION
NOTES
WALL BASE
B
TBD
RUBBER
4" COVE
COLOR: TBD BY TENANT
WALLS
PT-1
SHERMAN WILLIAMS
PAINT
COLOR: TBD BY TENANT
P-
TBD
FRP PANEL
COLOR: TBD BY TENANT
CEILING
C-1
ARMSTRONG
CEILING TILE
COLOR: DUNE 1851
GENERALNOTES
aim0:11:1:ir l:14:1i1IN1011111:fATMI►MUMgo]:a1[el:Is.]:1Fil191
2. ALLEMERGENCY FIXTURES, LIGHTS AND STROBES SHALLBE ALIGNED OR CENTERED ON WALLS
REFLECTED CEILING PLAN CODED NOTES O
1. EXISTING STRUCTURALCOLUMN TO REMAIN.
2. LIGHT FIXTURE. REFER TO ELECTRICALPLANS.
3. MECHANICAL DIFFUSER. REFER TO MECHANICAL
PLANS FOR ADDITIONALINFORMATION.
4. EXISTING SOFFIT.
SYMBOL LEGEND
OFLOOR
PLAN CODED NOTE
(SEE SCHEDULE ON THIS SHEET)
FINISH HEIGHT TAG
ALL MODIFICATIONS TO SPRINKLER SYSTEM/ FIREALARM
SYSTEM SHALL BE PERFORMED BY LICENSED SPRINKLER/
FIRE ALARM CONTRACTOR UNDER A SEPARATE PERMIT AT
DISCRETION OF CONTRACTOR
•� LnLnOn
r-1 r-I rl
� N N rl r-
O M 00 00
• .�_ O 00 00
> •-
0
f6cuLn
Ln E 4'
00 Z3
O
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE + PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
w
75;
Ln
W
N
>
0
nro
=
0
1
Z)
o
00
CL
Z)0
J
Q
zmo
J
N
m
(DW
Q
W
Lu
J
Q
�z
Q
�o
()
O
Wa
z0
�o
�m
M>-z
a
w
U
J
Lu
z~
cn
U
�
�
V)
w
M
Q O
Q
0
(�
rl
U LL
�:
r-I
PROJECT NUMBER:
W P GO07
ISSUE DATE
PERMIT FEB. 01, 2018
ARCH ITECTURALFLOOR
PLAN AND REFLECTED
CEILING PLAN
SHEET:
Alel
ENLARGED RESTROOM PLAN
1/2" = 1'-0"
2 E LEVAT I O N
1/4" = 1'-0"
a
00
Ln
0
0
N
RELEASED IFCR CONSTRUCTION
Suubjeut to aornpliance with all regofatimns
of State and Ilmeal Endles
ICltp of Cannel
ntro
DATE: 03/07/18
Nick Mishler
YP BOARD
FRP
0
m
3 E LEVAT I O N
1/4" = 1'-0"
GYPBOARD
RUBBER BASE
4 ELEVATION
1/4" = 1'-0"
IOARD
I:11.1:1evlq
5 E LEVAT I O N
A 1.2 1/4" = 1'-0"
IOARD
TOILET ROOM ACCESSORIES
MARK
DESCRIPTION/MANUFACTURER
NOTES
TOILET PAPER DISPENSER -
MOUNT AT 24" A.F.F. TO CENTERLINE FURTHER EDGE
1
BOBRICKB-6857
36" FROM REAR WALL
GRAB BAR - 42" LONG, 1 1/4"-1 1/2" DIA.,
MOUNT 12" FROM REAR WALL
2
BOBRICKB-6206x42
33" - 36" A.F.F.
GRAB BAR - 36" LONG, 1 1/4"-1 1/2" DIA.,
MOUNT 6" FROM SIDE WALL
3
BOBRICKB-6206x36
33" - 36" A.F.F.
GRAB BAR - 18" LONG, 1 1/4"-1 1/2" DIA.,
MOUNT CENTERLINE OF BOTTOM RAIL
4
BOBRICKB-6206x18
39" - 41" A.F.F.
FRAMED 1/4" MIRROR - 24" WIDTH X 36" HIGH
MOUNT WITH BOTTOM OF REFLECTIVE
5
BOBRICKB-294
SURFACE AT 40" A.F.F.
6
WALLMOUNTED SOAP DISPENSER
MOUNT TOP OF UNIT AT 4'-1" A.F.F.
BOBRICKB-4112
7
SURFACE MOUNTED PAPER TOWEL DISPENSER
MOUNT TOP OF UNIT AT 5'-8" A.F.F.
BOBRICKB-4262
8
SANITARY NAPKIN DISPOSAL(WOMEN'S ONLY)
MOUNT PER MANUFACTURER'S SPECIFICATIONS
BOBRICKB-353
REFER TO SHEET G0.3 FOR ADDITIONAL INFORMATION ON
ACCESSIBILITY MOUNTING REQUIREMENTS
•� LnLnOn
r-1 r-I rl n
� N N rl r-
O M 00 00
4-1n r-
• .�_ O 00 00
> •-
0
cubA �
Ln
Ln E 4'
00
O
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE + PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
w
75;
Ln
W
N
>
0
nro
=
0
1
Z)
0CL
5m
L
00
Z)0
J
Q
zmo
J
N
M
I�
(DW
Q
W
Lu
�V)
JQQ
�
z
�o
0
Wa
z0
�m
CE
LL<z
a
w
U
J
Lu
z~
cn
U
�
�
V)
w
m
Q 0
Q
0
00
(�
rl
U LL
�
r-I
PROJECT NUMBER:
W P GO07
ISSUE DATE
PERMIT FEB. 01, 2018
ENLARGED
RESTROOM PLAN
AND ELEVATIONS
SHEET:
Als2
5/8" 35/8�5/8"
5/8" GWB OVER METAL
FRAMING AS SCHEDULED
20 GA. MTLSTUD TYP @
HEAD
CONT. SEALANT BOTH SIDES
KNOCKDOWN FRAME,
PRIMED
DOOR PER SCHEDULE
DOOR HEAD DETAIL
1" = 1'-0"
RELEASED IFCR CONSTRUCTION
Suufv�ankto �aaupdGaNca wrltlo aIV ragaf�timna
at State and Ilmeail Endlen
IC'Itp at Caimal
DATE: 03/07/18
Nick Mishler
c /oll o c /oll c /oll
5/8" GWB OVER METAL
FRAMING AS SCHEDULED
DBL. 20 GA. MTLSTUDSTYP @
JAMBS
CONT. SEALANT BOTH SIDES
KNOCKDOWN FRAME, W/ (3)
JAMB ANCHORS PER SIDE,
PRIMED
DOOR PER SCHEDULE
DOORJAMB DETAIL
1" = 1'-0"
3'-0"
FLUSH PANELSOLID CORE
WOOD DOOR
1 DOOR ELEVATION_
1/4" = 1'-0"
DOORJAMB SILL
1" = 1'-0"
DOOR PER SCHEDULE
METAL FRAME BEYOND
WEATHERSTRIP
ADA COMPLIANT THRESHOLD
SET IN SEALANT
EXPANSION JOINT
DOOR AND FRAME SCHEDULE
DOOR
FRAME
IDETAILS
RATING
NOTES
NO.
LOCATION
SIZE
MATERIAL
FINISH
ELEV.
HARDWARE SET
PROFILE MATERIAL FINISH JELEV.
IHEAD JJAMB7SILL
100
ENTRY
EXISTING
---
---
---
1
EXISTING
101
RESTROOM
T-0" x 7'-0" x 1 3/4"
SOLID CORE
WOOD
PAINT
1/A8.1
2
3/A8.1
K.D.H.M.
I PAINT
I 2/A8.1
I 4/A8.1
I 5/A8.1
I 6/A8.1
NOTES:
1.
ALL DOOR LOCKSETS / PASSAGE SETS SHALL BE OF THE LEVER HANDLE TYPE. HARDWARE SHALL BE MOUNTED NO HIGHER THAN 48" ABOVE FINISHED FLOOR (MOUNTED BETWEEN 44" TO 48").
PROVIDE LEVER HANDLE AT ALL HANDICAPPED ACCESSIBLE DOORS. MAXIMUM PULL FORCES FOR INTERIOR DOORS TO BE 5.0 LBS FORCE. MAXIMUM PULL FORCES FOR EXTERIOR DOORS TO BE
15.0 LBS FORCE.
2.
PER ADAAG 4.16.6 - MINIMUM MANEUVERING CLEARANCE AT DOORS THAT ARE NOT AUTOMATIC OR POWER -ASSISTED / FOR FRONT APPROACHES TO PUSH SIDE OF DOORS, NOT EQUIPPED WITH
LATCH AND CLOSER SHALLHAVE MANEUVERING SPACE THAT IS THE SAME WIDTH AS DOOR OPENING AND EXTENDS 48-INCHES MINIMUM PERPENDICULARTO THE DOORWAY. DOORS WILLBE
PROVIDED WITH 36" X 48" MANEUVERING CLEARANCE ON PUSH SIDE WHEN NOT EQUIPPED WITH LATCH AND CLOSER. AT PULLSIDE OF DOOR, 18-INCH EXTENSION BEYOND LATCH SIDE OF DOOR
IS PROVIDED.
3.
VERIFY ALLROUGH OPENING SIZES AND REQUIREMENTS WITH DOOR MANUFACTURER.
4.
INTERIOR SOLID CORE WOOD DOORS TO BE BIRCH VENEER PAINT GRADE. PAINT WOOD DOORS SEMI -GLOSS AS SCHEDULED.
5.
PROVIDE SOLID F.R.T. WOOD BLOCKING WITHIN STUD WALL FRAMING ADJACENT TO STRIKE PLATE. BLOCKING TO EXTEND MIN. 12" ABOVE AND BELOW STRIKE PLATE.
6.
ALL LOCKSETS TO BE PROVIDED WITH REMOVABLE CONSTRUCTION CORE CYLINDERS SUPPLIED BY HARDWARE MANUFACTURER. CONTRACTOR TO PROVIDE OWNER WITH PERMANENT CORE
CYLINDERS FOR MASTER KEYING BY CONTRACTOR AT THE COMPLETION OF THE PROJECT.
7.
ALL HARDWARE TO COMPLY W/THE LATEST REQUIREMENTS OF ADAAG/ANSI.
8.
KEYING SEQUENCE TO BE COORDINATED W/ OWNER'S PROPERTY MANAGER.
9.
PAINT FRAME AND DOOR TO MATCH MALLSTANDARDS.
2" 3'-0" 2"
N
0
n
INTERIOR (16 GA.)
WELDED
HOLLOW METAL
FRAME ELEVATION
1/4" = 1'-0"
NEW BREAKMETALTRIM CAP
TO MATCH STOREFRONT.
5/8" GWB
DOOR HARDWARE SCHEDULE
HARDWARE SET #1 - ENTRY
QTY.
DESCRIPTION
MANUFACTURER
NUMBER
FINISH
3 EA.
HINGES
IVES
5BB1 4.5 x 4.5
652
1 EA.
SURFACE BOLT
IVES
SB453 8" TB
652
1 EA.
ENTRANCE/OFFICE LOCK
SCHLAGE
ND50HD RHO
626
1 EA.
WALLSTOP
IVES
WS33
626
HARDWARE SET #2 - RESTROOM
QTY.
DESCRIPTION
MANUFACTURER
NUMBER
FINISH
3 EA.
HINGES
IVES
5BB1 4.5 x 4.5
652
1 EA.
PRIVACY LOCK
SCHLAGE
S219OD-JUP 200 SERIES
NICKEL
2 EA.
WALLSTOP
IVES
WS33
626
2 EA.
SILENCER
IVES
SR64
GRY
1 EA.
CLOSER
LCN
4010
ALUM
ALLLOCKABLE DOORS SHALLBE EQUIPPED WITH REMOVABLE CORE HARDWARE, MANUFACTURED BY "SCHLAGE".
HARDWARE TO BE SUPPLIED FROM THE MANUFACTURER WITH "SCHLAGE" REMOVABLE CORE CYLINDERS WITH
CONSTRUCTION MASTER -KEYING.
2„ 5/8"
00
Ln
00
a Z
0 z
N
Lu
V1
Of LuoC
=a
a
11
w
�0
>
LU
LL
0
of
00
Ln
\
Ln
HOLLOW
METAL
3 FRAME PROFILE
A$.1 3" = 1'-0"
EXTERIORWALL DETAIL
1" = 1'-0"
EXISTING STOREFRONT
EXISTING VENEER
CONSTRUCTION
NEW MASONRY VENEER.
FINISH TBD BY OWNER.
WALLBRACING AS REQUIRED
T.O. METAL STUD
PARTITION, REFER TO WALL
BRACING LEGEND ABOVE
REFER TO PLANS
T.O. STUD
REFER TO PLANS
B.O. SUSPENDED CEILING
FULLWIDTH SOUND BATT
INSULATION
IICrda 1.1 197e\:111
1► i�re���rn.��
i�i►i�y:�rrz•�:�e��Yya�.l��r�.
100'-0"
Y FINISHED FLOOR
WALLSECTION
1/2" = 1'-0"
•� •LnLnOn
ro r-1 ri r- n
ro N N r-� r-
O M 00 00
. .�_ O 00 00
> •-
0
cubA �
Ln
Ln E 4'
00 Z3
O
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE + PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
v
z
w
75;
Ln
W
N
>
O
=
O
1
Z)
�
Im
0
0
CL
Z)
J
0
Q
Q
zmo
J
N
M
I�
(DW
Q
Lu
Lu
J
Q
Crz
Q
�o
()
0
Wa
z0
�m
CE
LL<z
a
w
U
J
Lu
z~
cn
U
�
�
�
w
m
Rl-
Q O
Q
o
(�
rl
U LL
�:
r-I
PROJECT NUMBER:
W P GO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
DOOR SCHEDULE AND
DETAILS
SHEET:
A8ol
SHEET NOTES:
GENERAL
A. WHERE ITEMS/ELEMENTS ARE INDICATED HEREIN TO BE LISTED/APPROVED, THE INTENT OF THIS
L. FIRE PROTECTION ITEMS AND ELEMENTS SHALL BE INSTALLED WITH DUE REGARD TO
2. ALL RODS, ANGLES, RAILS, STRUTS, BRACES, PLATES, PLATFORMS, ETC., REQUIRED
5. SPRINKLERS; AS SPECIFIED ON PLANS.
SPECIFICATION IS THAT SAID ITEM/ELEMENT SHALL BE LISTED BY ALL APPLICABLE
PRESERVATION OF THE STRENGTH OF STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE TO
FOR SUSPENSION AND/OR SUPPORT OF PIPING, AND ALL MISCELLANEOUS
MATERIAL/CONSTRUCTION STANDARDS, AND SUBJECT TO FINAL APPROVAL (INCLUDING
WALLS, SURFACES AND OTHER STRUCTURES THROUGH INSTALLATION, BEARING SUPPORT OR
SPECIALTIES AND ITEMS/ELEMENTS REQUIRED FOR THE ATTACHMENT OF HANGERS
A. SPARE SPRINKLER HEAD CABINET - PROVIDE CABINET AT MAIN RISER LOCATION WITH
METHODS OF INSTALLATION) BY ALL REVIEW/INSPECTION/APPROVAL AUTHORITIES.
SUBSEQUENT USAGE OF FIRE PROTECTION ITEMS AND ELEMENTS. NO FRAMING OR OTHER
AND SUPPORTS TO THE STRUCTURE.
SPRINKLER HEADS AND HEAD WRENCH(ES) FOR EMERGENCY USE. SPARE HEAD
QUANTITIES TO BE AS SPECIFIED BY NFPA PAMPHLET NO. 13, CORRESPONDING
B. UNLESS INDICATED OTHERWISE, ALL FIRE PROTECTION CONTRACT ITEMS/ELEMENTS (PIPE, FITTINGS,
SUPPORT STRUCTURE SHALL BE CUT NOTCHED OR BORED IN EXCESS OF LIMITATIONS SPECIFIED
D. UNLESS OTHERWISE NOTED, HANGERS SHALL BE AS FOLLOWS:
PROPORTIONALLY TO THE TOTAL NUMBER OF EACH TYPE INSTALLED IN THE BUILDING.
VALVES, SPECIALTIES, FIXTURES, EQUIPMENT, ETC.) MATERIALS, CONSTRUCTION, PERFORMANCE,
IN THE BUILDING CODE, OR BY THE MANUFACTURER OF THE FRAMING OR OTHER SUPPORT
B. ALL SPRINKLER HEADS IN LIGHT AND ORDINARY HAZARD OCCUPANCY APPLICATIONS TO
TESTING AND METHODS OF INSTALLATION TO BE AS LISTED/APPROVED BY ALL APPLICABLE
STRUCTURE, AS CONFIRMED IN ADVANCE OF WORK BY THE FIRE PROTECTION CONTRACTOR.
l . PIPING 8" SIZE AND SMALLER, HANGER SHALL BE SIMILAR TO GRINNELL FIG. 69, WITH
BE LISTED/APPROVED "QUICK RESPONSE'' TYPE.
GALVANIZED ADJUSTABLE NUT AND CARBON STEEL BAND.
MATERIAL/CONSTRUCTION/INSTALLATION STANDARDS FOR SAME, AND BE IN ACCORDANCE
FIRE PROTECTION PIPING SYSTEM - WET
C. SPRINKLER HEADS AS MANUFACTURED/PROVIDED BY RELIABLE, AUTOMATIC, CENTRAL,
WITH THE REQUIREMENTS OF ALL REVIEW/INSPECTION/APPROVAL AUTHORITIES. THIS INCLUDES,
2. PIPING 10'' SIZE AND LARGER, HANGER SHALL BE SIMILAR TO GRINNELL FIG. 260,
GRINNELL, VIKING OR VICTAULIC MAY BE FURNISHED AT THE CONTRACTOR'S OPTION.
BUT IS NOT LIMITED TO, THE STANDARDS AND AUTHORITIES REFERENCED IN THIS SPECIFICATION. IN
PRODUCTS
CARBON STEEL, ADJUSTABLE WROUGHT CLEVIS TYPE.
THE ABSENCE OF SUCH STANDARDS AND/OR REQUIREMENTS, THE ITEM/ELEMENT
1. PIPING AND FITTINGS
3. TRAPEZE HANGERS
EXECUTION
MANUFACTURER'S RECOMMENDATIONS, AS CONFIRMED BY THE FIRE PROTECTION CONTRACTOR
IN ADVANCE, SHALL BE FOLLOWED.
A. PIPE SHALL BE SCHEDULE 40 BLACK STEEL WITH CLASS 125 CAST OR MALLEABLE IRON
A. WHERE SEVERAL PIPES OCCUR AT THE SAME ELEVATION, TRAPEZE TYPE
1. INSTALLATION
SCREWED FITTINGS PER NFPA STANDARDS. THE CONTRACTOR HAS THE OPTION TO
HANGERS MAY BE USED. TRAPEZE HANGERS SHALL BE SIMILAR TO GRINNELL
C. ALL FIRE PROTECTION CONTRACT ITEMS/ELEMENTS SHALL HAVE THE MANUFACTURER'S MARK OR
PROVIDE SCHEDULE 10 BLACK STEEL PIPE FOR 2" TO 6" (INCLUSIVE) PIPE SIZE WITH
FIG. 46 WITH GRINNELL FIG. 137 U-BOLT OR FIG. 262 STRAP. BRACKET SHALL
A. PROVIDE DRAIN VALVES AND AUXILIARY DRAINS PER NFPA REQUIREMENTS, AND AT LOW
NAME AND THE QUALITY OF THE PRODUCT OR IDENTIFICATION OF SAME CAST, EMBOSSED,
LISTED/APPROVED ROLL GROOVED MECHANICAL COUPLING FITTINGS AS SPECIFIED HEREIN.
BE GRINNELL FIG. 195.
POINTS OF SYSTEM TO ALLOW COMPLETE DRAINAGE. CONTRACTOR TO BE RESPONSIBLE
THREADED FITTINGS OR CUT GROOVE COUPLINGS NOT PERMITTED WITH SCHEDULE 10
TO INSTALL SPRINKLER SYSTEM TO DRAIN PROPERLY. PIPING SHALL BE INSTALLED TO
STAMPED OR INDELIBLY MARKED ON EACH ITEM/ELEMENT IN ACCORDANCE WITH THE
PIPE.
DRAIN AT THE MAIN RISER WHENEVER POSSIBLE.
STANDARDS UNDER WHICH THEY ARE ACCEPTED AND APPROVED PER APPLICABLE CODE(S).
3. VALVES AND SPECIALTIES
B. ALL SCHEDULE 10 PIPE SHALL USE LISTED/APPROVED GROOVED FITTINGS WITH
A. WEDGE DISC BRONZE GATE VALVES -LISTED/APPROVED OUTSIDE SCREW AND YOKE, , ,
B. INSTALL VALVES AND SPECIALTIES WHERE INDICATED AND/OR AS REQUIRED FOR
APPROVAL.
D. CONNECTIONS TO EXISTING BUILDING UTILITIES SHALL BE MADE WITH APPROVED MATERIALS OF
MALLEABLE IRON MECHANICAL COUPLINGS SIMILAR TO THAT MANUFACTURED BY
SCREWED TYPE FOR SIZE 2" AND SMALLER, FLANGED FOR SIZES 2-1/2'' AND LARGER,
THE SAME TYPE AS, OR LISTED FOR COMPATIBILITY WITH, EXISTING MATERIALS. MATERIAL TYPES
VICTAULIC. THE CONTRACTOR MAY, AT HIS OPTION FOR SCHEDULE 40 PIPE 2" SIZE AND
WITH IRON BODY AND BRONZE FITTINGS. COUNTERCLOCKWISE OPENING AND 175 PSIG
C. THE ENTIRE SPRINKLER SYSTEM INSTALLATION SHALL CONFORM TO THE REQUIREMENTS
TO BE VERIFIED BY THIS CONTRACTOR IN THE FIELD IN ADVANCE OF WORK.
LARGER, USE LISTED/APPROVED GROOVED FITTINGS AND MALLEABLE IRON MECHANICAL
WORKING PRESSURE. USE NON -RISING -STEM TYPE FOR POST INDICATING VALVE
OF NFPA PAMPHLET NO. 13.
COUPLINGS SIMILAR TO THAT MANUFACTURED BY VICTAULIC.
ASSEMBLIES.
D. PIPING MUST BE LINED UP PARALLELING AND AT RIGHT ANGLES TO THE BUILDING WALLS
E. UNLESS INDICATED OTHERWISE, ALL FIRE PROTECTION PIPING SHALL BE IN ACCORDANCE WITH
l . COUPLINGS SHALL BE SIMILAR TO VICTAULIC RIGID STYLE 005 FIRELOCK WITH EDPM
1. WHERE GATE VALVES ARE INDICATED ON PLANS, THE CONTRACTOR MAY, AT HIS
AND OTHER PRIMARY STRUCTURAL ELEMENTS; ANGULAR OFFSETS SUCH AS 45' CUTS
THE FOLLOWING STANDARDS IN REGARD TO MATERIALS, CONSTRUCTION,
GASKET AND HOUSING FABRICATED IN TWO OR MORE PARTS OF MALLEABLE IRON
OPTION, USE BUTTERFLY VALVES AS SPECIFIED IN SECTION 15027, PROVIDED THEY
ACROSS CORNERS AND ELSEWHERE WILL NOT BE PERMITTED UNLESS SPECIFICALLY
DIMENSIONS/TOLERANCES AND METHODS OF INSTALLATION (AS APPLICABLE), AND SHALL BE
CASTINGS. LISTED OUTLET COUPLINGS MAY BE USED SUBJECT TO APPROVAL BY ALL
ARE LISTED/APPROVED FOR FIRE PROTECTION SERVICE.
SHOWN.
SO LISTED. FINAL APPROVAL FOR USE IS SUBJECT OF THE REQUIREMENTS OF THE REVIEW AND
REVIEW AND INSPECTION AUTHORITIES. FINAL ASSEMBLIES SHALL BE RATED FOR 175
PSIG WORKING PRESSURE.
E. THIS CONTRACTOR MUST ASSUME THE FULL RESPONSIBILITY OF VERIFYING PRESENT
INSPECTION AUTHORITIES.
B. WATER PRESSURE GAUGES - LISTED/APPROVED 3-1/2" BRASS PRESSURE GAUGES RANGE
ELEVATIONS IN THE FIELD AND MAKING ANY ADJUSTMENTS AS MAY BE NECESSARY, ALL
2. ASSEMBLY AND INSTALLATION OF COUPLINGS TO BE IN ACCORDANCE WITH THE
0 TO 300 PSIG, WITH NPT MALE PIPE CONNECTION. INSTALL AT EACH INSPECTOR'S TEST
OF WHICH MUST BE INCLUDED IN HIS PROPOSAL PRICE.
F. STEEL PIPE, MALLEABLE AND CAST IRON FITTINGS AND JOINING METHODS; SHALL BE PER
MANUFACTURER'S RECOMMENDATIONS.
CONNECTION, ALARM VALVE AND ELSEWHERE AS REQUIRED, AND/OR AS SHOWN ON
PLANS.
F. PROVIDE SLEEVES FOR PIPES WHERE PIPING PENETRATES MASONRY WALLS. ALL PIPE
APPLICABLE ASTM/ANSI/ASME STANDARDS.
3. PIPE GROOVING SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S
PENETRATIONS THROUGH MASONRY WALLS SHALL BE ADEQUATELY SEALED WITH MORTAR
SPECIFICATIONS. ROLL GROOVING ONLY PERMITTED FOR SCHEDULE 10 PIPE: ROLL OR
C. CONTRACTOR TO FURNISH AND INSTALL IDENTIFICATION SIGNAGE WHERE REQUIRED,
OR APPROVED FIRE RESISTANT CAULKING.
G. WHERE STANDARDS, CODES OR GUIDELINES ARE REFERENCED HEREIN AND THROUGHOUT THE
CUT GROOVING MAY BE USED FOR SCHEDULE 40 PIPE, AT THE CONTRACTOR'S
SIMILAR TO RELIABLE MODEL A. AS A MINIMUM, AN ENGRAVED SIGN SHALL BE PROVIDED
FIRE PROTECTION CONTRACT DOCUMENTATION, INCLUDING PLANS AND SPECIFICATIONS, THE
OPTION.
AT THE MAIN SUPPLY RISER/CONTROL VALVE INDICATING BASIC DESIGN INFORMATION.
2. SPRINKLER HEADS
LATEST VERSION/EDITION SHALL BE APPLIED, UNLESS THE BUILDING CODE REFERENCES ANOTHER
4. THE CONTRACTOR MAY, AT HIS OPTION, PROVIDE EQUAL MECHANICAL COUPLINGS AS
D. SPRINKLER VALVES AND ACCESSORIES AS MANUFACTURED/PROVIDED BY RELIABLE,
VERSION/EDITION, WHICH SHALL TAKE PRECEDENCE.
MANUFACTURED BY ITT GRINNELL, ANVIL GRUVLOK OR CENTRAL SPRINK, MEETING ALL
AUTOMATIC, CENTRAL, GRINNELL, VIKING OR VICTAULIC MAY BE FURNISHED AT THE
A. QUANTITY AND LOCATION OF SPRINKLER HEADS TO BE DETERMINED BY THE FIRE
H. REFER TO PROJECT DOCUMENTATION FURNISHED WITH THE COMPLETE CONSTRUCTION
REQUIREMENTS LISTED FOR GROOVED PIPING INSTALLATION.
CONTRACTOR'S OPTION.
ACCORDANCE WITH SPECIFICATIONS ON PLANS.
PACKAGE IN ADVANCE OF WORK FOR OVERALL COORDINATION AND VERIFICATION OF
5. ELEMENTS DESCRIBED ELSEWHERE IN THIS SPECIFICATION MAY BE PROVIDED WITH
REQUIREMENTS AT WORK OF OTHER TRADES RELATING TO, INTERFACING WITH, AND/OR
COMPATIBLE ALTERNATE CONNECTIONS WHEN INSTALLED IN MECHANICAL COUPLING
4. ALARM INITIATING DEVICES
B. UNLESS INDICATED OR REQUIRED OTHERWISE, NOMINAL SPRINKLER HEAD OPERATING
PIPING SYSTEMS. THE MECHANICAL COUPLING CONNECTIONS FOR THESE ELEMENTS
TEMPERATURE RATINGS TO BE AS FOLLOWS:
IMPACTING WORK IN THE FIRE PROTECTION CONTRACT. THIS INCLUDES EXACT LOCATIONS,
MUST BE PROVIDED BY THE MANUFACTURER WITH APPROPRIATE LISTINGS,
A. GATE VALVE SUPERVISORY SWITCHES - FURNISH AND INSTALL LISTED/APPROVED
1. FINISHED, GENERAL ACCESS AREAS - 175 DEGREES F.
QUANTITIES, PHYSICAL SIZES, ROUGH -IN DETAILS, PIPE ROUTING, CONNECTION SIZES, ETC., FOR
APPROVALS AND PRESSURE RATINGS AS SPECIFIED. THIS INCLUDES VALVES,
SUPERVISORY SWITCHES ON ALL TYPES OF SHUT-OFF VALVES CAPABLE OF INTERRUPTING
2. NON -FINISHED, RESTRICTED ACCESS AREAS (MECHANICAL/ELECTRICAL UTILITY
ITEMS INCLUDED BOTH IN THE FIRE PROTECTION CONTRACT AND UNDER SEPARATE CONTRACT.
APPURTENANCES, EQUIPMENT AND OTHER ELEMENTS INSTALLED IN OR CONNECTED TO
FLOW IN THE SPRINKLER SYSTEM.
COORDINATE INSTALLATION AND INTERFACE REQUIREMENTS WITH THE APPROPRIATE
MECHANICAL COUPLING PIPING SYSTEMS.
ROOMS, STORAGE ROOMS, ETC.) - 200 DEGREES F.
CONTRACTOR(S) IN ADVANCE OF WORK.
2. PIPING HANGERS AND SUPPORTS
B. FLOW SWITCH - LISTED/APPROVED VANE -TYPE WATERFLOW DETECTOR WITH PIPE SADDLE
3. THE FIRE PROTECTION CONTRACTOR IS RESPONSIBLE TO DETERMINE IF
CONNECTION FITTING, U-BOLT SECURING ASSEMBLY, ADJUSTABLE PNEUMATIC RETARD TO
SPRINKLERS WITH TEMPERATURE RATINGS OTHER THAN THOSE INDICATED HEREIN ARE
I. INCLUDE ANY MINOR DETAILS, ITEMS AND/OR ELEMENTS ESSENTIAL TO NECESSARY APPROVALS
A. PIPING SHALL BE ADEQUATELY SUPPORTED BY MEANS OF HANGERS AND SUPPORTS, AND
PREVENT FALSE ALARMS AND TWO (2) SETS OF FORM "C" CONTACTS. MAXIMUM
PRESSURE RATING OF 300 PSIG.
REQUIRED DUE TO SPECIFIC CONDITIONS AT EACH INSTALLATION, AND PROVIDE
AND SUCCESSFUL OPERATION IN ADDITION TO THE ITEMS SPECIFIED HEREIN AND SHOWN ON
BE IN COMPLIANCE WITH NFPA PAMPHLET 13. CARRY OVERHEAD LINES DIRECTLY ON
SPRINKLERS WITH APPROPRIATE TEMPERATURE RATING AT THESE LOCATIONS.
PLANS.
SUPPORTS OR SUSPEND BY HANGERS FROM SUPPORTS. FURNISH REQUIRED SUPPORTING
STEEL, HANGERS, ETC.
C. PRESSURE SWITCH - FURNISH PRESSURE DIFFERENTIAL TYPE SWITCH ASSEMBLIES FOR
C. RECESS SPRINKLER HEADS TO BE INSTALLED WITH DEFLECTORS NO GREATER THAN 1 /2"
J. WHERE EXISTING ITEMS/ELEMENTS ARE INDICATED TO BE REUSED AS A PART OF NEW WORK, THE
ALARM ACTUATION, ADJUSTABLE TYPE FOR SUPERVISORY FUNCTIONS. SWITCHES TO BE
FROM MAXIMUM RECESSED CAPABILITY. DEFLECTORS OF ADJACENT HEADS TO BE AT
B. PIPING AT EQUIPMENT AND CONTROL VALVES, ETC. SHALL BE SUPPORTED SO THAT
AUTOMATIC RESETTING, SINGLE POLE/DOUBLE THROW. MAXIMUM PRESSURE RATING OF
SAME ELEVATION, PLUS OR MINUS 1 /4".
FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR ACTION REQUIRED TO ASSURE THAT SUCH
THOSE ELEMENTS/ITEMS CAN BE REMOVED WITHOUT PROVIDING ADDITIONAL SUPPORT
300 PSIG.
ITEMS/ELEMENTS WILL FUNCTION PROPERLY IN THE COMPLETED REVISED SETTING, AND BE IN
ELEMENTS. PIPING SHALL NOT INTRODUCE ANY STRAINS OR DISTORTIONS ON CONNECTED
D. SPRINKLER HEADS TO BE ALIGNED IN RESPECT TO STRUCTURE, AND ADJACENT HEADS TO
COMPLIANCE WITH THE REQUIREMENTS OF THE REVIEW, INSPECTION AND APPROVAL
EQUIPMENT. VERTICAL PIPING SHALL BE SUPPORTED AT BASE OF RISER.
D. ALARM INITIATING DEVICES AS MANUFACTURED/PROVIDED BY FCI, NOTIFIER, HONEYWELL,
PRESENT A UNIFORM, EVEN LINEAR APPEARANCE.
AUTHORITIES. THIS INCLUDES REMOVAL, CLEANING AND/OR RECONDITIONING OF
POTTER, SYSTEM SENSOR OR ANY OF THE MANUFACTURERS LISTED FOR SPRINKLER
ITEMS/ELEMENTS IF REQUIRED.
C. THE FOLLOWING ITEMS SHALL BE PROVIDED:
EQUIPMENT AND ACCESSORIES MAY BE FURNISHED AT THE CONTRACTOR'S OPTION.
E. SPRINKLER HEAD TYPE AND FINISH TO BE DETERMINED BY THE ARCHITECT AND
1. SUPPLEMENTARY CHANNELS, PLATES, ETC. WHERE SUPPORTS ARE REQUIRED BETWEEN
CONSTRUCTION MANAGER. SEE FIRE PROTECTION GENERAL NOTES ON THIS SHEET.
K. SEE GENERAL "FIRE PROTECTION NOTES'' ON PLANS FOR ADDITIONAL CONDITIONS AND
BUILDING STRUCTURAL MEMBERS, SPANNING THE SPACE AND ATTACHED TO BUILDING
REQUIREMENTS RELATIVE TO THE FIRE PROTECTION CONTRACT.
STRUCTURAL MEMBERS BY WELDING OR BOLTING.
Ln
0
00
r o
RELEASED IFCR CONSTRUCTION
5uud9ezttncnmiplanumwith 311llse9ubtmma _
of State and lmeal Endes
0tp at Caimal
ntro DATE: 03/07/18
Nick Mishler
FLOOR PLAN - FIRE PROTECTION
1 /4" = 1'-0"
EN
SPRINKLER HEAD LOCATION NOTES:
l . ALL LOCATIONS INDICATED ARE TO BE MAINTAINED WITHIN PLUS OR MINUS 1 /2",
AND ALIGNED WITH ADJACENT HEADS FOR A UNIFORM, EVEN APPEARANCE OF
COMPLETED INSTALLATION. POSITIONS INDICATED APPLY TO FULL SIZE SMOOTH
SURFACE TILES, AS WELL AS FULL SIZE SUB-GRIDDED (SCORED OR GRAPHICALLY
DIVIDED) SURFACE TILES. THE APPEARANCE OF THE FINISHED CEILING TILE FACE AS
INSTALLED OVERRIDES THE ACTUAL PHYSICAL DIMENSIONS OF THE TILE FOR
PLACEMENTS INDICATED HEREIN. VERIFY CEILING TILE TYPES FROM ARCHITECTURAL
DOCUMENTATION.
2. RECESSED PENDANT SPRINKLER HEADS TO BE INSTALLED WITH DEFLECTORS AT SAME
ELEVATION AS ADJACENT SPRINKLERS IN SAME AREA/ENCLOSURE, PLUS OR MINUS
1 /4''. RECESSED HEADS TO BE INSTALLED SO DEFLECTOR IS A MAXIMUM OF 1" BELOW
THE ELEVATION OF THE CEILING PLANE. CONCEALED HEADS TO BE INSTALLED WITH
COVERS FLUSH TO CEILING PLANE IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
3. INSTALLATION OF ALL SPRINKLER HEADS TO BE COORDINATED WITH STRUCTURE AND
WORK OF OTHER TRADES, VERIFIED IN ADVANCE BY THE FIRE PROTECTION
CONTRACTOR.
4. VERIFY EXACT TYPE, FINISH AND LOCATION OF ALL HEADS WITH ARCHITECT AND
AND CONSTRUCTION MANAGER PRIOR TO CONSTRUCTION.
24"x24" CEILING TILE
12"x48" CEILING TILE
24"x48" CEILING TILE
N
N
12" 12"lo
ol
10
18" 6"
12"xl2" CEILING TILE
12"x48" CEILING TILE
24"x48" CEILING TILE
DETAIL - SPRINKLER HEAD LOCATION
N.T.S.
FIRE PROTECTION MATERIAL &EQUIPMENT SCHEDULE
l . FINAL DECISION ON THE FINISH AND OR COLOR AND STYLE OF SPRINKLER HEADS TO BE DETERMINED BY
THE ARCHITECT DURING THE REVIEW PROCESS.
2. THE ARCHITECT RESERVES THE RIGHT TO RELOCATE OR ADD SPRINKLER HEADS TO THE SPRINKLER
CONTRACTOR'S LAYOUT.
FIRE PROTECTION SPRINKLER HEADS
A. RECESSED PENDENT HEADS; SIMILAR TO VIKING MODEL VK302 WITH 1 /2" STD. ORIFICE, 1 /2" NPT INLET,
OUTLET SPRAY DEFLECTOR, 5.6 "K" FACTOR & ADJUSTABLE TWO-PIECE ESCUTCHEON. ESCUTCHEON &
HEAD TO BE FURNISHED WITH MANUFACTURER APPLIED WHITE FINISH. HEAD TO BE LISTED "QUICK
RESPONSE'' TYPE. SIDEWALL HEADS (IF REQUIRED) TO BE SIMILAR, WITH HORIZONTAL DEFLECTOR. INLET,
ADJUSTABLE DRY BARREL AND COMPRESSED CENTER STRUT ACTUATOR. PENDENT AND SIDEWALL
HEADS FOR USE IN AREAS WITH CONCEALING "FINISH" STRUCTURE WITH CONCEALED SUPPLY PIPING.
B. CONCEALED PENDENT HEADS: TO BE USED IN ALL CEILINGS UNLESS NOTED OTHERWISE. SIMILAR TO
VIKING MODEL VK462 WITH 1 /2'' STD. ORIFICE, 1 /2'' NPT INLET, OUTLET SPRAY DEFLECTOR, 5.6 "K"
FACTOR, ADJUSTABLE TWO-PIECE ESCUTCHEON AND COVERPLATE WITH MANUFACTURER APPLIED
WHITE FINISH. HEAD TO BE LISTED''QUICK RESPONSE" TYPE. UNLESS NOTED OTHERWISE, IN AREAS WITH
DRYWALL, PANELBOARD OR OTHER DROP CEILING STRUCTURE WITH CONCEALED SUPPLY PIPING.
HEADS LOCATED IN WOOD PANELS TO BE PROVIDED WITH MANUFACTURER APPLIED FINISH COLOR
FOR COVERPLATE AS APPROVED BY THE OWNER'S REPRESENTATIVE IN ADVANCE OF INSTALLATION.
EQUAL MANUFACTURER'S: RELIABLE, VIKING, AUTOMATIC, CENTRAL, GUARDIAN, VICTAULIC,
POTTER-ROEMER OR GRINNELL MAY BE PROVIDED AT THE CONTRACTOR'S OPTION
NOTE;
A. FOR BIDDING PURPOSE THIS CONTRACTOR SHALL PROVIDE CONCEALED HEADS IN ALL DRYWALL
CEILINGS AND/OR SPECIAL CONSTRUCTION CEILINGS. FOR ALL ACOUSTICAL TILE CEILINGS THIS
CONTRACTOR SHALL PROVIDE RECESSED SPRINKLER HEADS. ALL FINISHES AND OR COLORS OF
SPRINKLER HEADS SHALL BE DETERMINED BY THE ARCHITECT USING THE STANDARD AVAILABLE
COLORS OR FINISHES AVAILABLE FROM THE MANUFACTURER.
FIRE PROTECTION SPRINKLER PIPING
A. WET SPRINKLER PIPING, ASTM LISTED SCHEDULE 40 BLACK STEEL PIPE WITH THREADED IRON FITTINGS, OR
SCHEDULE 40 BLACK STEEL ROLL GROOVED PIPE WITH GASKETED IRON MECHANICAL COUPLINGS
SIMILAR TO VICTAULIC SERIES 005 FIRELOCK RIGID TYPE. PIPING SIZES 2-1/2" AND LARGER MAY BE ASTM
LISTED SCHEDULE 10 BLACK STEEL ROLL GROOVED PIPE WITH MECHANICAL COUPLINGS AS PREVIOUSLY
SPECIFIED. ALL GROOVED PIPING TO BE ROLL TYPE; CUT GROOVES NOT PERMITTED. PIPING
INSTALLATION TO BE RATED FOR 175 PSIG WORKING PRESSURE.
B. ALL FIRE PROTECTION PIPING TO BE IN ACCORDANCE NFPA PAMPHLET NO. 13, NFPA 9.1 AND NFPA
9.1.3 REQUIREMENTS FOR MATERIALS AND METHODS OF INSTALLATION.
C. HANGERS TO BE SIMILAR TO GRINNELL FIG. 69 WITH GALVANIZED ADJUSTABLE NUT AND CARBON
STEEL BAND. INSTALL IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, NFPA 9.1 AND NFPA 9.1.3
REQUIREMENTS FOR MATERIALS AND METHODS OF INSTALLATION.
D. TESTING OF PIPING TO MEET NFPA REQUIREMENTS.
FIRE PROTECTION NOTES:
A. PROVIDE ALTERATIONS AND MODIFICATIONS AS NECESSARY TO FURNISH AND INSTALL A COMPLETE
FULLY AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM INCLUDING PIPING, HANGERS, VALVES,
ALARMS, SUPPORTS AND SPRINKLER HEADS PER NFPA PAMPHLET NO. 13. THE SYSTEM SHALL COMPLY
WITH ALL REQUIREMENTS OF LOCAL, STATE AND FEDERAL AUTHORITIES AND LANDLORD'S INSURING
AGENCY.
B. ALL WORK SHALL BE PERFORMED BY AN APPROVED AUTOMATIC FIRE PROTECTION SPRINKLER
CONTRACTOR. SHOP DRAWINGS AND CALCULATIONS SHALL BE PREPARED BY A REGISTERED
PROFESSIONAL ENGINEER. APPROVED CONTRACTOR AND THE CONTRACTOR'S REGISTERED
ENGINEER SHALL BE LICENSED WITH THE PROPER AUTHORITIES FOR THE STATE OF TENNESSEE.
C. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL INTENT OF WORK. FINAL CONSTRUCTION
DOCUMENTS, HYDRAULIC CALCULATIONS AND PERMITTING SHALL BE BY THE FIRE PROTECTION
CONTRACTOR.
D. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR THE EXACT NUMBER, DENSITY, TYPE
AND LOCATION OF SPRINKLER HEADS AS WELL AS PIPING LAYOUTS INCLUDED IN THE SET OF
CERTIFIED STAMPED SHOP DRAWINGS PROVIDED BY THE FIRE PROTECTION CONTRACTOR.
E. ALL AUTHORITIES HAVING JURISDICTION SHALL BE NOTIFIED AT LEAST THREE (3) WORKING DAYS PRIOR
TO COMMENCEMENT OF WORK.
F. FIRE PROTECTION CONTRACTOR SHALL PROVIDE TENANT SPRINKLER SYSTEM SHUT-OFF VALVE AND
VALVE TAMPER SWITCH AND COORDINATE ELECTRICAL REQUIREMENTS WITH THE ELECTRICAL
CONTRACTOR.
G. SPECIAL CONSIDERATION SHALL BE GIVEN TO AREAS THROUGHOUT THE BUILDING SUCH AS DROPPED
SOFFITS, LIGHTING SOFFITS AND RECESSED STORAGE RACKS THAT NECESSITATE ADDITIONAL
SPRINKLER HEADS.
H. RUN PIPING HORIZONTALLY AND AT RIGHT ANGLES TO WALLS AND CEILINGS. CENTER SPRINKLER
HEADS IN BOTH HORIZONTAL DIRECTION WITH RESPECT TO CEILING COMPONENTS, SUCH AS CEILING
GRID, LIGHT FIXTURES, HVAC DIFFUSERS AND SPEAKERS OR AS DIRECTED BY OWNER'S
REPRESENTATIVE.
I. PROVIDE MAIN DRAINS AND AUXILIARY DRAINS WHERE NECESSARY.
J. PROVIDE TEST CONNECTIONS AT MOST REMOTE POINT OF MAIN PORTION OF EACH SPRINKLER
SYSTEM.
K. LAYOUT THE SPRINKLER PIPING SO THAT THERE IS A MINIMUM SEPARATION OF 12" BETWEEN THE
CEILING HEIGHT AND THE BOTTOM OF THE SPRINKLER PIPE OR ROUTE PIPING AROUND LIGHT FIXTURES
TO AVOID CONFLICTS.
L. ALL PIPING SHALL BE ROUTED IN THE SUSPENDED CEILING SPACE, CONCEALED IN WALLS AND BEHIND
FIXED FURNISHINGS, UNLESS OTHERWISE INDICATED. ALL PIPING EXPOSED TO VIEW SHALL BE ROUTED
AS HIGH AS POSSIBLE AND TIGHT TO THE UNDERSIDE OF THE STRUCTURE.
M. REFER TO ARCHITECTURAL DRAWINGS OR CONSULT ARCHITECT FOR EXACT LOCATION OF FIXTURES,
EQUIPMENT, ETC. AND FINAL FINISHED ELEVATIONS PRIOR TO ANY INSTALLATION WORK.
N. EXISTING SYSTEMS THAT REQUIRE RELOCATION AND SERVE EXISTING FIXTURES OR EQUIPMENT OR
AREAS THAT MUST REMAIN ACTIVE, SHALL BE RELOCATED DURING OWNER SCHEDULED SHUT -DOWNS.
TEMPORARY CONNECTIONS AND EXTENSIONS OF REQUIRED SYSTEMS SHALL BE PROVIDED AS NEEDED
AND AT THE CONTRACTOR'S EXPENSE.
O. CONTRACTOR SHALL VISIT THE SITE AND DOCUMENT EXISTING CONDITIONS WITHIN THE LIMITS OF
DEMOLITION, PRIOR TO START OF ANY WORK. FORWARD TO ARCHITECT/ENGINEER, FOR REVIEW,
ONE (1) COPY OF EQUIPMENT AND SYSTEMS BEING REMOVED BY DEMOLITION WORK AND NEW
INSTALLATION WORK. LIMITS OF DEMOLITION AREA SHALL BE AS INDICATED ON DRAWINGS
PREPARED BY THE ARCHITECTURAL CONSULTANT.
P. CAREFULLY REVIEW THE INTERIOR DESIGN, ARCHITECTURAL, STRUCTURAL AND ELECTRICAL
DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL ITEMS TO BE REMOVED, RELOCATED, OR
ACCOMMODATED; INCLUDE ALL COSTS IN BASE BID FOR THIS WORK.
Q. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING DUCTWORK SHOP
DRAWINGS FROM HVAC CONTRACTOR AND COORDINATING ROUTING OF SPRINKLER PIPING. ANY
RELOCATION REQUIRED BY FIRE PROTECTION CONTRACTOR'S FAILURE TO COORDINATE SHALL BE
DONE AT NO COST OR DELAY TO THE OWNER.
R. DRAINING AND REFILLING OF SYSTEMS AS REQUIRED FOR DEMOLITION AND/OR NEW INSTALLATIONS
WORK, SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR. MINIMIZE ANY AND ALL SHUTDOWNS OF
THE FIRE PROTECTION SYSTEM. WHEN REQUESTING A SHUTDOWN, GIVE PROPER NOTICE TO OWNER
WHEN MAKING SHUTDOWNS AND PAY ANY FEES REQUIRED, PERFORM ANY DUTIES REQUIRED BY
OWNER WHEN MAKING A SHUTDOWN, FILL OUT A SHUTDOWN NOTICE FORM ANSWERING ALL ITEMS
REQUESTED SUCH AS TIME AND LOCATION OF SHUTDOWN, SYSTEMS AFFECTED, AREAS AFFECTED,
ETC.. PROVIDE FIRE WATCH AS REQUIRED DURING A SHUTDOWN. DURATION OF SHUTDOWNS SHALL
BE KEPT TO A MINIMUM. IN NO CASE SHALL THE FIRE PROTECTION SYSTEM BE SHUTDOWN DURING OFF
HOURS OF WORK DAY WITHOUT A FIRE WATCH. SYSTEM SHALL BE RETURNED TO NORMAL OPERATING
CONDITIONS AT END OF WORK DAY.
S. ALL SPRINKLERS IN CEILINGS SHALL BE RECESSED PENDENT HEADS OF WHATEVER TYPE AND FINISH
APPROVED BY THE ARCHITECT AND CONSTRUCTION MANAGER. ALL SPRINKLERS IN OPEN CEILING
AREA SHALL BE UPRIGHT PENDENT TYPE OF FINISH APPROVED BY THE ARCHITECT AND CONSTRUCTION
MANAGER. EXACT LOCATIONS OF EACH AND EVERY SPRINKLER WILL BE APPROVED BY THE
ARCHITECT AND CONSTRUCTION MANAGER. SUBMIT PRODUCTS AND SPRINKLER LOCATIONS TO THE
ARCHITECT AND CONSTRUCTION MANAGER FOR APPROVAL PRIOR TO THE SHOP DRAWING
PROCESS.
T. THE FIRE PROTECTION CONTRACTOR SHALL PERFORM A FLOW TEST. INFORMATION FROM THE
CONTRACTOR'S FLOW TEST SHALL BE USED FOR THE CONTRACTOR'S HYDRAULIC CALCULATIONS AND
SHALL INCLUDE A 10%SAFETY FACTOR.
U. ALL SPRINKLER HEADS SHALL BE QUICK RESPONSE EXCEPT IN HIGH TEMPERATURE AREAS.
CODED NOTES: O
l . MODIFY THE EXISTING F.P. SPRINKLER INSTALLATION WITHIN THIS SPECIFIC AREA AS REQUIRED BY THE
NEW ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL LAYOUT. THIS INCLUDES, BUT IS
NOT LIMITED TO, REVISING THE EXISTING SPRINKLER PIPING LAYOUT AS REQUIRED BY INSTALLATION OF
NEW WORK, AS WELL AS THE COORDINATION OF NEW SPRINKLER HEADS AND THE REVISED/NEW
SPRINKLER PIPING LAYOUT WITH BOTH EXISTING AND NEW DUCTWORK, AIR DEVICES, LIGHTING,
SPEAKERS, CEILING FEATURES, AND STRUCTURAL MEMBERS. PROTECTION/ COVERAGE TO BE PER
NFPA PAMPHLET 13 ORDINARY HAZARD OCCUPANCY REQUIREMENTS.
2. MODIFY THE EXISTING F.P. SPRINKLER INSTALLATION WITHIN THIS SPECIFIC AREA AS REQUIRED BY THE
NEW ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL LAYOUT. THIS INCLUDES, BUT IS
NOT LIMITED TO, REVISING THE EXISTING SPRINKLER PIPING LAYOUT AS REQUIRED BY INSTALLATION OF
NEW WORK, AS WELL AS THE COORDINATION OF NEW SPRINKLER HEADS AND THE REVISED/NEW
SPRINKLER PIPING LAYOUT WITH BOTH EXISTING AND NEW DUCTWORK, AIR DEVICES, LIGHTING,
SPEAKERS, CEILING FEATURES, AND STRUCTURAL MEMBERS. PROTECTION/ COVERAGE TO BE PER
NFPA PAMPHLET 13 LIGHT HAZARD OCCUPANCY REQUIREMENTS.
THIS DRAWING IS NOT BEING SUBMITTED FOR PLAN APPROVAL PURPOSES
THIS PLAN IS PREPARED TO ASSIST FIRE PROTECTION (SUB) CONTRACTORS IN SUBMITTING A BID. SUCCESSFUL
LICENSED FIRE PROTECTION (SUB)CONTRACTOR SHALL PREPARE DETAILED CONSTRUCTION DRAWINGS,
PERFORM DETAILED HYDRAULIC FLOW CALCULATIONS, PAY FOR PLAN APPROVAL FEES, OBTAIN PERMITS,
AND SUBMIT DOCUMENTS TO AUTHORITY(IES) HAVING JURISDICTION FOR REVIEW.
Ln Ln p r-
ro N N r-
�m0000
. .� =3 O 00 00
> cn ._
C �O
L vi lfl lD
X
Ln a) ro
Ln E *�
00
O
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE+ PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
W
G
L.ii
W
N
\
O
=
0
5�
G
Z)
Co
0
2
Oo
Z)o
J
Q
zm0
J
N
M
(Dw
W
JUG
2�
'
as
�z
�o
V)
O'a
'�
Q
zo
M�z
�
m
W
Q
U
J
W
(D~
cn
<Mq
o
�
w
Sao
<
<
00
rl
U L
rl
PROJECT NUMBER:
W P GO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
FLOOR PLAN
FIRE PROTECTION
SHEET:
F P a 1
a
0
0
00
00
RELEASED IFCR CONSTRUCTION
5uud9ezttn cnmiplanum with 311l1se9ulations _
of State and lmeal Endes
0tp at Caimal
ntro DATE: 03/07/18
Nick Mishler
DEMOLITION AND FLOOR PLAN - MECHANICAL
1 /4"=1 '-0"
FLOOR PLAN - PLUMBING
1 /4"=1-0"
MECHANICAL CODED NOTES: (D
1. COMPLETELY DEMOLISH EXISTING RTU AND ALL ASSOCIATED CURBS AND ACCESSORIES. COORDINATE
WORK WITH ELECTRICAL CONTRACTOR. REPAIR / MODIFY ROOF PENETRATION AS NECESSARY FOR NEW
RTU-1 INSTALLATION.
2. PROVIDE NEW PACKAGED ROOFTOP UNIT (RTU-1)AND CURB PER SCHEDULE. PROVIDE WITH SPECIFIED
ACCESSORIES AND ASSOCIATED ADDITIONAL ITEMS NEEDED FOR A COMPLETE INSTALLATION.
COORDINATE NEW WORK WITH ELECTRICAL CONTRACTOR. ENSURE ROOFTOP PENETRATIONS ARE
FLASHED / COUNTER -FLASHED AND SEALED WEATHER -TIGHT. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS. REFER TO INSTALLATION DETAIL.
3. PROVIDE TRANSFER GRILLES (Gl) IN LAY -IN CEILING PER SCHEDULE FOR RETURN AIR TO RTU.
4. PROVIDE FULL-SIZED RETURN AIR DUCT DROP.
5. ENSURE UNDERCUT IN DOOR.
6. ABOVE CEILING IN DASHED OUTLINED AREA TO BE CONSIDERED PLENUM RETURN AREA. ALL MATERIALS
TO BE INSTALLED IN THIS AREA MUST BE PLENUM -RATED.
7. EXHAUST FAN / LIGHT COMBINATION FIXTURE PROVIDED BY EC. MC TO PROVIDE 4" EXHAUST DUCT TO
ROOF PENETRATION. ENSURE ROOF PENETRATION IS LOCATED AT LEAST 10' FROM NEAREST OUTDOOR
AIR INTAKE. ENSURE ROOF PENETRATION IS SEALED WEATHER -TIGHT.
PLUMBING CODED NOTES: O
1. PROVIDE 4" SANITARY CONNECTION INTO SPACE FROM EXISTING SANITARY MAIN OF EQUAL OR
GREATER SIZE. VERIFY EXACT LOCATION, SIZE, AND INVERT AND FLOW OF CONNECTION POINT PRIOR
TO BID. COORDINATE TRENCHING AND WITH GC AND LANDLORD. CUT, BACKFILL AND PATCH AS
REQUIRED.
2. CONNECT NEW DCW SERVICE TO EXISTING 1" DCW ROUGH -IN. PROVIDE SHUT-OFF VALVE AT POINT OF
CONNECTION.
3. PROVIDE NEW ELECTRIC WATER HEATER PER SCHEDULE. INSTALL ABOVE RESTROOM CEILING ON DRAIN
PAN, AVOIDING RESTROOM EXHAUST FAN. PROVIDE FULL-SIZE INDIRECT HARD -PIPED RELIEF VALVE
DRAIN TO MOP SINK WITH 3'' AIR GAP ROUTED CLOSE TO WALL AS POSSIBLE.
4. PROVIDE 3" VENT THROUGH ROOF FOR RESTROOM VENT. INSTALL PER DETAIL ON THIS SHEET, ENSURING
AT LEAST 10' CLEARANCE FROM ANY OUTSIDE AIR INTAKE. VENT TO BE CPVC, PLENUM -RATED MATERIAL.
5. ABOVE CEILING IN DASHED OUTLINED AREA TO BE CONSIDERED PLENUM RETURN AIR AREA. ALL
MATERIALS TO BE INSTALLED IN THIS AREA MUST BE PLENUM -RATED.
3'' VTR
2 -\ -
� I
2"
i
2" I LAV-1
�I CO-1
13„ - WC-1
4"
2"
\�4
\ / MS-1
\ � ool 3„-
CO -I
SANITARY STACK - PLUMBING
N.T.S.
MECHANICAL ABBREVIATIONS
(D)
DEMOLITION
DN
DOWN
(E)
EXISTING
EA
EXHAUST AIR
(F)
FUTURE
EFF
EFFICIENCY
(R)
(RELOCATE)
EXH
EXHAUST
AAV
AUTOMATIC AIR VENT
MFR
MANUFACTURER
AFF
ABOVE FINISHED FLOOR
N/A
NOT APPLICABLE
BAS
BUILDING AUTOMATIC SYSTEM
NTS
NOT TO SCALE
BDD
BACKDRAFT DAMPER
OA
OUTSIDE AIR
BFP
BACKFLOW PREVENTER
RA
RETURN AIR
BOB
BOTTOM OF BEAM
SA
SUPPLY AIR
BOD
BOTTOM OF DUCT
TCP
TEMPERATURE CONTROL PANEL
BOP
BOTTOM OF PIPE
TYP
TYPICAL
BOS
BOTTOM OF STRUCTURE
UNO
UNLESS NOTED OTHERWISE
MECHANICAL LEGEND
SUPPLY DUCT UP
GRILLE/REGISTER
SUPPLY DUCT DOWN
��
TURNING VANES
RETURN DUCT UP
L-
VOLUME DAMPER
RETURN DUCT DOWN
OT
THERMOSTAT
SD
SMOKE DETECTOR
LINEAR DIFFUSER WITH FLEX CONNECTION
N_
SPIN -IN WITH VOLUME DAMPER
DIFFUSER WITH FLEX CONNECTION
450 RETURN DUCT TAP WITH VOL. DAMPER
PLUMBING ABBREVIATIONS
(D)
DEMOLITION
HP
HORSEPOWER
(E)
EXISTING
MS
MOP SINK
CAP
CAPACITY
N/A
NOT APPLICABLE
CFM
CUBIC FEET PER MINUTE
NTS
NOT TO SCALE
CO
CLEANOUT
PSI
POUNDS PER SQUARE INCH
DCW
DOMESTIC COLD WATER
TMV
THERMOSTATIC MIXING VALVE
DHW
DOMESTIC HOT WATER
TYP
TYPICAL
OF
DEGREES FAHRENHEIT
UNO
UNLESS NOTED OTHERWISE
FD
FLOOR DRAIN
V
VENT
GPH
GALLONS PER HOUR
VTR
VENT THRU ROOF
GPM
GALLONS PER MINUTE
WC
WATER CLOSET
PLUMBING LEGEND
EXISTING SANITARY
---->*-
BALANCING VALVE
SAN
SANITARY
BALL VALVE
----GW----
GREASE WASTE
�'��
CHECK VALVE
-
DOMESTIC COLD WATER
CONNECT TO EXISTING
- - - -
DOMESTIC HOT WATER
SOH-
PLUG VALVE
- - - - -
DOMESTIC HOT WATER RETURN
��
PRESSURE REGULATOR
- - - - -
VENT
_C9
RELIEF VALVE
0__
PIPE TURNED UP
SOLENOID VALVE
C-
PIPE TURNED DOWN
STRAINER
FLOOR PENETRATION MARKER
Q
WATER HAMMER ARRESTOR
MECHANICAL GENERAL NOTES:
1. ALL WORK TO BE PERFORMED TO MEET ALL STATE, CITY & LOCAL CODE REQUIREMENTS.
2. ALL ROOF CUTTING AND PATCHING TO BE BY THE GENERAL CONTRACTOR..
3. HVAC CONTRACTOR IS TO COORDINATE WITH OTHER TRADES BEFORE INSTALLING DUCTWORK. IF THE
HVAC CONTRACTOR FAILS TO COORDINATE WITH OTHER TRADES AND THE WORK MUST BE ALTERED THE
HVAC CONTRACTOR WILL CHANGE IT AT HIS OWN EXPENSE.
4. ONCE THE SYSTEM IS COMPLETE THE AIR SIDE SHALL BE BALANCED.
5. COORDINATE THE EXACT LOCATION OF ALL GRILLES, REGISTERS & DIFFUSER WITH ARCHITECTURAL
REFLECTED CEILING PLAN. ALSO COORDINATE MOUNTING HEIGHTS OF FIXTURES.
6. HVAC CONTRACTOR IS TO SUBMIT TO THE ARCHITECT FOR REVIEW ELECTRONIC COPY OF ALL
EQUIPMENT & MATERIAL TO BE USED ON THE PROJECT.
7. HVAC CONTRACTOR IS TO VISIT THE SITE PRIOR TO SUBMITTING A BID & INCLUDE IN THE BID ANY ITEMS
NECESSARY FOR A COMPLETE & OPERATIONAL SYSTEM.
8. DRAWINGS ARE SCHEMATIC IN NATURE & HVAC CONTRACTOR IS TO INCLUDE ANY ITEMS REQUIRED
FOR A COMPLETE & OPERATIONAL SYSTEM WHETHER SHOWN OR NOT SHOWN ON THE DRAWINGS.
9. HVAC CONTRACTOR TO FURNISH ALL PERMITS REQUIRED FOR HIS PORTION OF THE WORK.
FIELD VERIFY ALL CONDITIONS:
DESIGN DRAWINGS ARE DIAGRAMMATIC. THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING OR
AWARD OF CONTRACT TO INSPECT EXISTING FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL LABOR
AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING CONDITIONS.
THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER PRIOR TO BIDDING FOR
INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE
DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER AFTER BIDDING WILL BE
FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS COST.
BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND ORDINANCES AND
SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH
GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT
ARCHITECT, ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND
DESIGN INTENT.
PLUMBING GENERAL NOTES:
1. ALL WORK TO BE INSTALLED TO MEET ALL STATE, CITY & LOCAL CODE REQUIREMENTS.
2. PLUMBING CONTRACTOR TO VISIT THE SITE PRIOR TO SUBMITTING BID, INCLUDE ANY ADDITIONAL ITEMS
REQUIRED FOR A COMPLETE & OPERATIONAL SYSTEM.
3. PLUMBING CONTRACTOR TO FURNISH ALL PERMITS REQUIRED FOR THEIR WORK.
4. PLUMBING CONTRACTOR TO COORDINATE ALL WORK WITH OTHER TRADES. IF PLUMBING
CONTRACTOR FAILS TO COORDINATE WITH OTHER TRADES AND WORK IS REQUIRED TO BE ALTERED, THE
PLUMBING CONTRACTOR WILL BE RESPONSIBLE FOR THE WORK AT THEIR OWN EXPENSE.
5. VERIFY LOCATION, SIZE & INVERTS OF ALL UTILITIES PRIOR TO STARTING WORK.
6. ALL CUTTING OF EXISTING FLOORS, EXCAVATION & BACK FILL TO BE PART OF THE PLUMBING
CONTRACTOR BID. PATCHING OF FLOORS & ROOF TO BE BY GENERAL CONTRACTOR.
7. COORDINATE ALL FLOOR PENETRATIONS WITH STRUCTURAL DRAWINGS. SET SLEEVES IN FLOORS AND
WALLS AND ATTACHMENTS FOR HANGERS AS CONSTRUCTION PROGRESSES. ALL PENETRATIONS MUST
BE SEALED AND HELD AS TIGHT TO COLUMNS OR WALLS AS POSSIBLE.
8. ALL PIPING SHALL BE CONCEALED INSIDE WALLS, BELOW FLOORS OR ABOVE CEILINGS UNLESS
INDICATED OTHERWISE.
9. ALL PIPING SHALL BE SLOPED AS PER THE MINIMUM GRADE REQUIRED BY CODE (UNLESS NOTED
OTHERWISE) FOR EACH PARTICULAR PIPE SIZE.
10. DO NOT RUN PLUMBING PIPING DIRECTLY ABOVE ELECTRICAL PANELS OR THROUGH OTHER WATER
SENSITIVE AREAS.
11. ALL EQUIPMENT, PIPING, APPURTENANCES SHALL BE PROTECTED FROM DEBRIS AND DAMAGE.
SENSITIVE EQUIPMENT SHALL NOT BE DELIVERED TO THE JOB SITE UNTIL IT IS TO BE INSTALLED. PIPING
ENDS SHALL BE CLOSED BY TEMPORARY MEANS WHEN PORTIONS OF THE SYSTEM ARE NOT COMPLETE.
12. LOCATE ALL VALVES WHERE THEY ARE ACCESSIBLE FOR SERVICE AND USE. WHERE ACCESS PANELS ARE
REQUIRED COORDINATE SELECTION AND LOCATION WITH ARCHITECT.
13. ALL PENETRATIONS AT FLOORS AND RATED PARTITIONS SHALL HAVE A UL CLASSIFIED FIRE STOP SYSTEM
TESTED TO ASTM E814 AND UL 1497 BY UNDERWRITERS LABORATORIES. FIRE STOP SYSTEMS SHALL BE
PROSET SYSTEMS, PENSIL FIRESTOP SYSTEMS OR 3M COMPANY.
14. PLUMBING CONTRACTOR TO COORDINATE WITH GC AND TENANT ON EXACT LOCATION OF
ROUGH -INS.
15. PLUMBING CONTRACTOR TO VERIFY INVERT OF ALL TIE-IN POINTS INDICATED ON PLAN PRIOR TO
INSTALLATION. NOTIFY ARCHITECT/ENGINEER IMMEDIATELY IF EXISTING INVERT WILL BE INSUFFICIENT.
DRAWING INDEX
M1.1
MECHANICAL AND PLUMBING PLAN
M2.1
MECHANICAL AND PLUMBING SCHEDULES AND DETAILS
M3.1
PLUMBING SPECIFICATIONS
M3.2
MECHANICAL SPECIFICATIONS
M3.3
I MECHANICAL SPECIFICATIONS
ro N N r-
M 00 00
. .� =3 O 00 00
> cn ._
�O
L vi lfl lD
t]A �
Ln
Ln E +' 4--
00 =5
O
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE+ PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
W
75;
Lr)
W
N
O
=
O
Z)
-
Co
0
2
Oo
Z)O
J
Q
zmo
J
N
M
(Dw
W
JUG
2�
'
as
�z
�o
V)
O'�'a
Q
zo
��z
0m
W
Q
U
J
W
(D~
V)
v02
<M<
V)w
Sao
<
00
rl
U L
rl
PROJECT NUMBER:
W P GO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
MECHANICAL AND
PLUMBING PLAN
SHEET:
PACKAGED ROOFTOP UNIT SCHEDULE
BASED ON TRANE U.N.O
UNIT DATA
PERFORMANCE DATA
COOLING DATA
HEATING DATA
ELECTRCIAL DATA
NOMINAL
EFFICIENCY
TOTAL
MIN. OA
ESP
TOTAL
SENSIBLE
E.A.T (°F)
INPUT
OUTPUT
TAG
MODEL
FAN (HP)
REFRIG.
FUEL TYPE
VOLT
PH
MCA
MOCP
WEIGHT
COMMENTS
TONS
(SEER)
CFM
CFM
(IN. WC)
MBH
MBH
DB/WB
(kW)
(MBH)
RTU-1
THC036E3EGA
3
15.0
1200
360
0.4
1.0
38.5
27
80° / 67°
R410-A
18 (3PH)
61.47
ELECTRIC
208
3
51.6
60
1000 LB
1-5
COMMENTS: 1. HAIL GUARD 4. FACTORY PROVIDED ENTHALPY ECONOMIZER AND BAROMETRIC RELIEF
2. 14" ROOF CURB 5. PROVIDE WITH DIGITAL PROGRAMMABLE THERMOSTAT
3. FACTORY PROVIDED DISCONNECT
TAG -NECK SIZE
CFM
GRILLES, REGISTERS, AND DIFFUSERS SCHEDULE D = DIFFUSER G=GRILLE R=REGISTER
BASED ON TITUS U.N.O.
UNIT DATA
PERFORMANCE DATA
TAG
FUNCTION
MODEL
FACE SIZE
FRAME TYPE
MATERIAL
FINISH
BALANCE DAMPER
MAX N.C.
COMMENTS
D1
SUPPLY
OMNI
24"x 24"
LAY -IN
ALUMINUM
STANDARD
-
25
1,2
G1
RETURN
50F
24"x 24"
LAY -IN
ALUMINUM
STANDARD
-
25
NOTES: 1. ALL SUPPLY DIFFUSERS TO BE INSULATED VIA FACTORY SYSTEM. 2. MATCH DUCT SIZES WITH SIZES ON PLANS.
EXHAUST FAN SCHEDULE
BASED ON COOK U.N.O
UNIT DATA
PERFORMANCE DATA
BELT OR
TAG
MODEL
FUNCTION
FAN TYPE
CFM
ESP
COMMENTS
DIRECT
NUTONE 7
EF
RESTROOM EXHAUST
CEILING MOUNTED LIGHT / FAN
70
0.10
-
1,2
(PROVIDED BY
BY EC)
NOTES: 1. MC TO PROVIDE 4" EXHAUST DUCT TO ROOF
2. EXHAUST FAN / LIGHT COMBO TO BE PROVIDED BY ELECTRICAL CONTRACTOR
VACUUM RELIEF VALVE
t-DCW - - - O
t-DHWR-y-FZ�HOly 'I"111lI-IHO�
RP-1
T
O
ET-1 I =
PROVIDE 4" DEEP OVERFLOW PAN AND
DRAIN TO MOP BASIN
PLUMBING FIXTURE SCHEDULE
FIXTURE
ACCESSORIES
TAG
ITEM
MANUF.
MODEL
DCW
DHW
DRAIN
VENT
ITEM
MANUF.
MODEL
DESCRIPTION
WC-1
WATER CLOSET
STANDARD
2467.016
1/2"
-
3"
2"
SEAT
OLSONITE
95CTSS
ADA COMPLIANT FLOOR MOUNTED WHITE VITREOUS CHINA TANK TYPE WATER CLOSET WITH ELONGATED SIPHON JET BOWL, PRESSURE -
ASSISTED FLUSHING SYSTEM, 1.6 GPF, 16-1/2" RIM HEIGHT, CHROME FLUSH LEVER AND TANK WITH LOCKING COVER DEVICE (*: MODEL
NUMBER TO VARY BASED ON FLUSH LEVER ORIENTATION). PROVIDE HEAVY-DUTY PLASTIC OPEN FRONTSEAT LESS COVER. PROVIDE TANK
COVER LOCKS. PROVIDE CHROME PLATED BRASS LOOSE KEY ANGLE STOP WITH CHROME PLATED FLEXIBLE COPPER SUPPLY RISER.
PROVIDE TANK WITH FLUSH LEVER ON WIDE SIDE OF ROOM. INSTALLATION TO COMPLY WITH ADA ACCESSIBILITY REQUIREMENTS.
LOCKING COVER
AMERICAN STD.
*4142.6
LAV-1
LAVATORY
KOHLER
K-2084
1/2"
1/2"
1-1/2'
1-1/2"
FAUCET
MOEN
6190
ADA COMPLIANT WALL MOUNTED WHITE VITREOUS CHINA LAVATORY WITH SINGLE FAUCET HOLE AND OVERFLOW. PROVIDE LEAD FREE
CHROME PLATED SINGLE LEVER SINGLE HOLE FAUCET WITH 0.5 GPM FLOW RATE, PROVIDE CHROME PLATED GRID STRAINER DRAIN WITH
CHROME PLATED BRASS TAILPIECE. PROVIDE CHROME PLATED BRASS P-TRAP WITH CLEANOUT, WALL BEND AND WALL FLANGE. PROVIDE
CHROME PLATED BRASS LOOSE KEY ANGLE STOP WITH CHROME PLATED FLEXIBLE COPPER SUPPLY RISERS. PROVIDE CHROME FINISH ASSE
1070 LISTED UNDER -SINK THERMOSTATIC MIXING VALVE SET AT 105°F. PROVIDE MOLDED VINYL SAFETY COVERS FOR ALL EXPOSED SUPPLY
AND DRAIN PIPING BELOW LAVATORY. PROVIDE RIGID IN -WALL CONCEALED LAVATORY SUPPORT SYSTEM. INSTALLATION TO COMPLY
WITH ADA ACCESIBILITY REQUIREMENETS.
DRAIN
K R
57248
TRAP
McGUIGUI RE
8912CBEC0
SUPPLY
McGUIRE
LF2165LK
TMV
WATTS
LFUSG-B-M2-SC
PIPING COVER
TRUEBRO
LAV-GUARD 2 E-Z
CARRIER
ZURN
Z1231
MS-1
MOP SINK
MUSTEE
63M
1/2"
1/2"
3"
1-1/2"
FAUCET
T&S BRASS
B-0665-BSTR
FLOOR MOUNTED ONE-PIECE MOLDED HIGH IMPACT RESISTANT DURASTONE STRUCTURAL FIBERGLASS MOP SERVICE BASIN WITH INTEGRAL
MOLDED -IN DRAIN AND REMOVABLE STAINLESS STEEL STRAINER. PROVIDE CHROME PLATED CAST BRASS SERVICE SINK FAUCET WITH
COLOR -CODED METAL CROSS HANDLES, QUARTER -TURN CERAMIC DISC CARTRIDGES, INTEGRAL SERVICE STOPS, INTEGRAL CHECK
STOPS, 6" CAST BRASS SPOUT WITH VACUUM BREAKER, 3/4" HOSE THREAD OUTLET, PAIL HOOK AND ADJUSTABLE WALL BRACE. INSTALL
FAUCET AT36" ABOVE FINISH FLOOR. PROVIDE HEAVY-DUTY STAINLESS STEEL WALL MOUNTED HOSE BRACKET.
HOSE BRACKET
MUSTEE
65.700
PLUMBING EQUIPMENT SCHEDULE
TAG
ITEM
MANUFACTURER
MODEL NO.
COMMENTS
ELECTRIC DOMESTIC WATER
ELECTRIC DOMESTIC WATER HEATER, ETL LISTED. 3500 W, 30 GAL CAPACITY, 14 GPH RECOVERY RATE @ 100' F
EWH-1
gRADFORD WHITE
LE130L3-3
HEATER
TEMPERATURE RISE. PROVIDE WITH DRAIN PAN AND DRAIN TO MOP SINK BELOW.
ALL BRASS BODY TRAP PRIMER VALVE, PRESSURE DROP OF 5 - 10 PSIG OPENS VALVE, OPERATING RANGE: 35 - 75 PSIG,
TP-1
TRAP PRIMER
PRECISION PLUMBING
PR-500
1/2" MALE NPT INLET CONNECTION, 1/2" FEMALE NPT OUTLET CONNECTION.
DRAIN AND CLEANOUT SCHEDULE
TAG
ITEM
MANUFACTURER
MODEL NO.
COMMENTS
CAST IRON FLOOR DRAIN WITH SECONDARY DRAINAGE/ANCHOR FLANGE, WEEPHOLES, ADJUSTABLE FRAME AND GRATE WITH POLISHED
FD-1
FLOOR DRAIN
ZURN
ZN-415
NICKEL BRONZE FINISH, 6" DIAMETER ROUND TOP WITH SQUARE OPENINGS AND BOTTOM GASKET CONNECTION OUTLET.
CAST IRON BODY ADJUSTABLE CLEANOUT WITH ANCHOR FLANGE, POLISHED NICKEL BRONZE ROUND SCORIATED FRAME AND TOP, AND
co-]
FLOOR CLEANOUT
ZURN
ZN-1400
BOTTOM GASKET CONNECTION OUTLET.
�Z�Z�1�1�►[eZK�71_��7:711Vr
DRAIN LINE SAME SIZE AS
NIPPLE ON DRAIN PAN
CAPPED TEE FOR
CLEANOUT
2"MIN.
a
rn
N
RELEASED IFCR CONSTRUCTION
rsahiedtogumplanum with 311llsegulmums _
u95tate and Ilocal Endles
0tp at Cairemal
ntro
DATE: 03/07/18
Nick Mishler
RTU
ROOF CU
ROOF
`PRIME TRAP BEFORE
UNIT START-UP
A(IN) B(IN)
DRAWTHRU COIL FAN INLET STATIC "A" /2+1
RTU CONDENSATE DRAIN DETAIL
N.T.S
SUPPORT BY GC
BURNER THERMOSTAT AND PRESSURE
REGULATOR FURNISHED WITH WATER HEATER
CEILING
SIZED WITH AGA/CGA TEMPERATURE STEAM
RATING 10% OVER HEATER INPUT PROVIDE A
HARD COPPER RELIEF
VALVE COPPER DISCHARGE LINE. FULL SIZE OF
VALVE OUTLET TO END OVER TO MS-1 WITH AN AIR
GAP 2 TIMES THE PIPE DIAMETER.
�---DCW -�--Z
I
_--AUTOMATIC TRAP PRIMER VALVE
DRAIN VALVE. ROUTE 1" DRAIN LINE TO MOP BASIN BELOW FINISHED FLOOR
REFER TO SPECIFICATIONS AND PLUMBING FIXTURE SCHEDULE. PIPING ARRANGEMENT SHOWN IS
SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS. REFER TO FLOOR PLAN FOR PIPE SIZES. SET WATER
HEATER THERMOSTAT AT 140°F. PROVIDE SEISMIC STRAP OR BRACING AND FLEXIBLE CONNECTORS
TO WATER AND GAS CONNECTIONS IF/AS REQUIRED BY LOCAL AUTHORITIES.
ELECTRIC WATER HEATER DETAIL
N.T.S.
WOOD DECK
WOOD BEAM
FLAT WASHER
THROUGH BOLT ---
TOP BEAM
C-CLAMP IF
STEEL BAR JOIST
ADJUSTABLE
BAND HANGER
FOR PIPING
FOUR INCH OR
LESS
DO NOT HANG PIPE FROM
BOTTOM OF JOISTS
STRUCTURAL ANGLE
DOUBLE NUT
ATTACHMENT
/-ALL -THREAD ROD. —
LENGTH AS REQUIRED
FOR PIPE SLOPE
PROVIDE COPPER OR
NON-METALLIC
COATING WHERE
HANGERS CONTACT
BARE COPPER PIPE
CLEVIS HANGER FOR PIPE OVER
FOUR INCH
PROVIDE A ONE FOOT LENGTH
OF NON -COMPRESSIBLE
INSULATION AT HANGERS FOR
ALL PIPE 2" AND LARGER
PROVIDE GALVANIZED STEEL SADDLE FOR ALL INSULATED
PIPE LARGER THAN 3/4''. VERIFY INSULATION THICKNESS WHEN
SIZING HANGERS
PROVIDE UPPER ATTACHMENT AS REQUIRED FOR CASES NOT SHOWN HERE. DO NOT
INSTALL HANGER INSIDE INSULATION OR OTHERWISE PENETRATE VAPOR BARRIER. DO NOT
HANG ONE PIPE FROM ANOTHER. TRAPEZE HANGERS MAY BE USED FOR MULTIPLE
PARALLEL PIPES. HANGER SPACING FOR PIPE SIZE: COPPER: 4''=12'; 3''=1 1'; 2-1 /2"=10'; 2"=9';
1-1 /2''=8'; 1-1 /4''=7', 1"=6', 3/4''=6', 1 /2"=5'. CAST IRON: 10' AND ONE NEAR ALL JOINTS.
STEEL: 4"=14'; 3"=12'; 2-1 /2"=1 l'; 2''=10'; 1-1 /2''=9'; 1 '=7; 3/4"=6'; 1 /2"=5'. LOCATE HANGERS
AS CLOSE AS POSSIBLE TO TURNS AND TEES OF PIPE. PROVIDE SUPPLEMENTARY STEEL
STRUTS BETWEEN JOISTS IF REQUIRED. LOCATE HANGERS TO TAKE LOAD OFF OF
EQUIPMENT CONNECTIONS. ANCHOR WATER PIPE AGAINST SWAYING DUE TO CHANGES
IN WATER VELOCITY. PROVIDE SEISMIC BRACING IF/AS REQUIRED BY LOCAL AUTHORITIES.
CHAINS OR PERFORATED STRAP IRON OR STEEL IS NOT ACCEPTABLE. REFER TO CODES
AND SPECIFICATIONS FOR FURTHER INFORMATION.
PIPE HANGER DETAIL
N.T.S.
GASKET (SUPPLIED
WITH CURB)
FACTORY FABRICATED
ROOF CURB
z
1� I ROOF FLASHI
EXISTING STRUCTURE
INDOOR DUCT INSULATIO
PACKAGED
ROOFTOP UNIT
FLEXIBLE DUCT
CONNECTION
DUCTWORK
EXPANDING POLYURETHANE
FOAM INSUL. AROUND PERIM.
OF DUCT IN METAL DECK
NOTES: PLANE
1. IN -FILL BETWEEN EQUIPMENT CURB AND DUCTWORK,
ALL SIDES WITH BATT. INSULATION (TYP.).
PACKAGED ROOFTOP UNIT DETAIL
N.T.S
COVER VALVE BODIES WITH -
INSULATION, BUT NOT UNIONS
DISTRIBUTION UNIT IF 2 OR MORE FLOOR
DRAINS ARE BEING FED FROM ONE TAP
Ifilm
lulml
1/2" TYPE X" COPPER TUBING
I I
PIPING ROUTED IN WALLS
WHEN APPLICABLE.
SLEEVE
PIPING BELOW CONCRETE SLAB.
SLOPE TO DRAIN
TRAP PRIMER DETAIL
N.T.S.
FLOOR DRAIN
SANITARY PIPING
ROOF STRUCTURE SHOWN FOR
REFERENCE ONLY. REFER TO PIPE
HANGER DETAIL.
TAPE JOINTS
MITER THE INSULATION AT TEES AND ELBOWS
FIBERGLASS INSULATION
SO THAT THERE ARE NO GAPS AT JOINTS.
PROVIDE ONE-PIECE PRE -MOULDED PVC
PROVIDE A ONE FOOT LENGTH OF
FITTING COVERS
NON -COMPRESSIBLE INSULATION AT
HANGERS FOR ALL PIPE 2'' AND LARGER
PROVIDE INSULATION ON DOMESTIC
HOT/COLD WATER PIPES, STORM WATER
REFER TO OTHER DETAILS FOR TREATMENT
PIPES, AND CONDENSATE DRAIN PIPING IN
OF INSULATION AT PENETRATION OF
WALLS AND CHASES
WALLS AND FIREWALLS
a a
, n
a a
PROVIDE FIBERGLASS INSULATION WITH ALL -SERVICE JACKET WITH VAPOR BARRIER ON ALL
COLD/HOT WATER PIPING AND CONDENSATE DRAIN
PIPE. REFER TO SPECIFICATIONS FOR
FURTHER INFORMATION REGARDING INSULATION.
INSTALL ALL ITEMS PER SPECIFICATIONS
AND MANUFACTURERS INSTRUCTIONS. MAINTAIN
VAPOR BARRIER ON COLD PIPING BY
MEANS OF SEALANT AND TAPE. FLAME -SPREAD AND SMOKE -DEVELOPED INDEXES SHALL
NOT EXCEED 25/50. SEAL EXPOSED ENDS OF FIBERGLASS
INSULATION WITH ADHESIVE
MASTIC.
PIPE INSULATION DETAIL
N.T.S.
NOTE: VENT TO BE LOCATED NO LESS THAN
12'-0'' HORIZONTALLY FROM ANY BUILDING
FRESH AIR INTAKE AND NO LESS THAN 3'-0''
VERTICAL ABOVE ANY BUILDING FRESH AIR
INTAKE.
----------- STAINLESS STEEL CLAMP
NOTE: ALL CUTTING, FLASHING AND
SEALING OF ROOF SHALL BE DONE BY
00 N LANDLORD'S ROOFING CONTRACTOR AT
I r THIS CONTRACTOR'S EXPENSE.
ROOF
RIGID INSULATION
ROOF DECK PIPE CLAMP ANCHOR TO
MEDIUM EXPANSION CLIP ANGLE
INSULATING FOAM
INSTALL 1/2" THICK
FIBERGLASS INSULATION TO REFER TO PLANS FOR
FIRST 90 EIBON OR A MAX EXACT SIZE AND LOCATION
OF 5-2" VERT
VENT THROUGH ROOF DETAIL
N.T.S.
> 01 c-I r- r-
� N N r- r-
N M 00 00
. .� =5 O 00 00
>
L =; _ _ �0
L av m
Ln E +� 4
00 =3
O
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE + PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
W
2
Ln
N
\W
O
=
0
Z)
Co
0
G
Oo
Z)
J
o
Q
z
J
Co
N
M
(D
w
Q
w
w
ILu
�V)
JQQ
Q=z
Q
a-o
Q
L1J
~
Io
z
0
ro
�z
�Co
=
W
j
J
z
Vow
Qrn�
=a
Vw
��Q0Q00
PROJECT NUMBER:
W P GO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
MECHANICAL AND PLUMBING
SCHEDULES AND DETAILS
SHEET:
M2ol
SPECIFICATIONS - DIVISION 22 - PLUMBING
GENERAL CONDITIONS
SERVICE/TRANSMISSION MEDIUM (WATER, AIR, GAS, ETC.) AND METHODS OF INSTALLATION (AS APPLICABLE),
AND SHALL BE SO LISTED. FINAL APPROVAL FOR USE IS SUBJECT TO THE REQUIREMENTS OF THE REVIEW AND
h. HANGER RODS MUST BE PERPENDICULAR BEFORE INSULATION IS INSTALLED.
WATER HAMMER ARRESTORS
A. GENERAL
INSPECTION AUTHORITIES:
BUILDING SOIL, WASTE AND VENT SYSTEM
1. SIMILAR TO ZURN SHOCKTROL SERIES Z-1700, SIZED AND INSTALLED AS RECOMMENDED BY THE MANUFACTURER
1. THIS CONTRACT SHALL INCLUDE A VISIT TO THE JOB SITE AND TAKE INTO CONSIDERATION MECHANICAL,
a. CAST IRON PIPE, FITTINGS AND JOINING METHODS; PER APPLICABLE ASTM/ANSI/ASME/CISPI STANDARDS.
1. APPLICATIONS FOR SANITARY AND VENT SYSTEMS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING:
FOR SPECIFIC CONDITIONS AT EACH LOCATION.
ELECTRICAL AND GENERAL TRADE WORK IN PLACE AND WORK TO BE PUT INTO PLACE PRIOR TO BIDDING.
REROUTING OF DUCTWORK, PIPING, AND EQUIPMENT, AS REQUIRED TO MISS THIS WORK SHALL BE
b. COPPER/COPPER ALLOY/BRASS PIPE/TUBE, FITTINGS AND JOINING METHODS; PER APPLICABLE
a. SANITARY AND VENT PIPING FROM DESIGNATED POINTS WITH ALL CONNECTIONS.
2. EQUAL SHOCK ABSORBERS AS MANUFACTURED BY J.R. SMITH, JOSAM, SIOUX CHIEF OR PRECISION PLUMBING
ACCOMPLISHED AT NO ADDITIONAL COST TO THE OWNER.
ASTM/ANSI/ASME STANDARDS. IN ADDITION, WHERE UTILIZED FOR POTABLE WATER SERVICE, ALL ELEMENTS
PRODUCTS MAY BE PROVIDED AT THE CONTRACTOR'S OPTION.
SHALL BE PER APPLICABLE NSF STANDARDS.
b. DRAINAGE AND VENT PIPING FOR ALL OTHER MISCELLANEOUS SYSTEMS OR EQUIPMENT AS INDICATED ON
DRAINS, CLEANOUTS, AND DRAINAGE SPECIALTIES
B. SCOPE OF WORK
DOCUMENTS AND AS REQUIRED.
4. ALL PLUMBING CONTRACT ITEMS/ELEMENTS SHALL HAVE THE MANUFACTURER'S MARK OF NAME AND THE
1. GENERAL
1. THE WORK INCLUDES MODIFICATION TO THE EXISTING PLUMBING SYSTEM AND PROVIDING NEW MATERIALS,
QUALITY OF THE PRODUCT OR IDENTIFICATION OF SAME CAST, EMBOSSED, STAMPED OR INDELIBLY MARKED ON
c. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SANITARY PIPING FINAL CONNECTIONS AND ALL
FITTINGS AND ACCESSORIES NECESSARY FOR A COMPLETE FUNCTIONING PLUMBING SYSTEM. THE WORK ALSO
EACH ITEM/ELEMENT IN ACCORDANCE WITH THE STANDARDS UNDER WHICH THEY ARE ACCEPTED AND
INDIRECT PIPING FROM EQUIPMENT TO DRAIN TO COMPLETE THE SANITARY WASTE AND VENT PIPING SYSTEM
e. FURNISH AND INSTALL DRAINS, CLEANOUTS AND DRAINAGE SPECIALTIES AS INDICTED ON THE DRAWINGS,
INCLUDES ROUGH -IN AND FINAL CONNECTIONS TO EQUIPMENT PROVIDED BY OTHERS. ALL WORK SHALL BE IN
APPROVED PER APPLICABLE CODE(S).
AND TO COMPLETE THE INDIRECT DRAINAGE PIPING SYSTEM TO OPERATE ALL EQUIPMENT AND FIXTURES
AND ELSEWHERE AS REQUIRED FOR COMPLETE DRAINAGE, ACCESS AND SPECIAL FUNCTION/OPERATION AT
ACCORDANCE WITH OWNER'S REQUIREMENTS, STATE AND LOCAL CODES AND/OR ORDINANCES AND IS
PROPERLY.
ALL ITEMS/ELEMENTS AND AREAS REQUIRING SAME AND FOR PROPER INTEGRATION WITH THE BUILDING
SUBJECT TO INSPECTION.
5. PLUMBING UTILITY CONNECTIONS PROVIDE FOR ITEMS OR ELEMENTS NOT INCLUDED IN THE PLUMBING
DRAINAGE SYSTEM.
CONTRACT.
2. SCOPE
2. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, TOOLS, INCIDENTALS, DETAILS, ETC. NECESSARY TO
f. UNLESS INDICATED OTHERWISE, ALL ITEMS/ELEMENTS AND THEIR COMPONENT PARTS DESCRIBED HEREIN TO
PROVIDE A COMPLETE, OPERATIONAL AND APPROVED PLUMBING SYSTEM, INCLUDING BUT NOT LIMITED TO ALL
a. UNLESS INDICATED OTHERWISE, THE PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL ALL TRAPS AND
a. FURNISH A COMPLETE SYSTEM OF INTERIOR SOIL WASTE DRAINAGE (INCLUDES SANITARY AND VENT PIPING)
BE OF METALLIC CONSTRUCTION WHEN SUCH IS AVAILABLE FOR THE BASE SPECIFIED ITEM/ELEMENT. USE OF
ITEMS AND ELEMENTS DESCRIBED IN THE PLUMBING SPECIFICATION AND SHOWN ON THE PLUMBING DRAWINGS,
STOPS (AS APPLICABLE) AS REQUIRED FOR ITEMS FURNISHED UNDER SEPARATE CONTRACT. THIS INCLUDES
FROM BUILDING FIXTURES, EQUIPMENT, AND ANY OTHER ELEMENTS REQUIRING THE SAME.
PLASTIC, COMPOSITE, OR OTHER NON-METALIC COMPONENTS AND/OR MATERIALS BY LISTED ALTERNATE
AND AS REQUIRED FOR COORDINATION AND/OR INTERFACE WITH WORK UNDER SEPARATE CONTRACT AS
ITEMS WITH CONNECTIONS BY THE PLUMBING CONTRACTOR OR WITH CONNECTIONS UNDER SEPARATE
3. PRODUCTS
ITEMS/ELEMENTS IS PROHIBITED.
INDICATED BY COMPLETE CONSTRICTION DOCUMENTATION PACKAGE.
CONTRACT.
a. DRAINAGE WASTE AND VENT (DWV) PIPING TO BE AS FOLLOWS (INCLUDES SANITARY, VENT, STORM &
2. PRODUCTS
3. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR SATISFACTORILY ADDRESSING ALL REVIEW AND INSPECTION
b. UNLESS INDICATED OTHERWISE, FIXTURE TRAPS ABOVE FLOOR SLAB CONNECTED TO THE SANITARY WASTE
GREASE WASTE):
AUTHORITIES REQUIREMENTS AND DIRECTIVES IN REGARD TO METHODS OF INSTALLATION NECESSARY FOR FINAL
SYSTEM SHALL BE CAST BRASS P-TRAPS WITH INTEGRAL CLEANOUT. P-TRAPS BELOW FLOOR SLAB TO BE CAST
a. THIS CONTRACTOR MAY, AT HIS OPTION, USE ABS PLASTIC PLUGS IN LIEU OF BRONZE PLUGS WHERE
APPROVAL.
IRON, LESS CLEANOUT. SEE DRAWINGS FOR SIZES.
1. ASTM A 74, CISPI HS 74 CAST IRON SERVICE WEIGHT HUB AND SPIGOT PIPE AND FITTINGS WITH NEOPRENE
SPECIFIED, EXCEPT ABS PLUGS SHALL NOT BE PERMITTED IN RETURN AIR PLENUMS OR AT EXPOSED
GASKETS OR ASTM A 888, CISPI 301 CAST IRON SERVICE WEIGHT HUBLESS PIPE AND FITTINGS WITH ASTM C
LOCATIONS. LOCATION OF THE RETURN AIR PLENUM TO BE CONFIRMED WITH THE HVAC CONTRACTOR.
C. SUBSTITUTIONS AND MISCELLANEOUS EQUIPMENT
c. UNLESS INDICATED OTHERWISE, FIXTURE TRAPS CONNECTED TO WASTE OR DRAIN SYSTEMS OTHER THAN THE
1277, CISPI 310 HUBLESS COUPLINGS. HUBLESS COUPLINGS TO BE INSTALLED ABOVE GRADE ONLY.
SANITARY WASTE SYSTEM SHALL BE OF THE SAME MATERIAL AND CONSTRUCTION TYPE AS THE ASSOCIATED
b. EQUAL DRAINS, DRAINAGE SPECIALTIES AND CLEANOUTS AS MANUFACTURED BY ZURN, ZURN LC, JOSAM,
1. THE BIDDING OF THIS WORK WILL CONTEMPLATE THE USE OF EQUIPMENT AND MATERIALS EXACTLY AS SPECIFIED
PIPING SYSTEM. P-TRAPS TO BE PROVIDED AS INDICATED ON THE DRAWINGS.
2. ASTM D 2665, SCHEDULE 40 TYPE 1, GRADE 1 PVC DWV PIPE AND ASTM D 2665, MADE TO ASTM D 3311,
SIOUX CHIEF, WATTS, JRS PRODUCTS, OR J.R. SMITH MAY BE FURNISHED AT THE CONTRACTOR'S OPTION.
HEREIN. WHERE ONE OR MORE NAMES OF MANUFACTURERS ARE MENTIONED ANY ONE MAY BE UTILIZED.
FITTINGS WITH ASTM F 656 ADHESIVE PRIMER AND ASTM D 2564 SOCKET SOLVENT SOLDER JOINTS AND
2. ALTERNATIVE EQUIPMENT MAY BE BID AS A SUBSTITUTION TO THAT SPECIFIED WITH THE APPROPRIATE DEDUCT
d. UNLESS INDICATED OTHERWISE, SUPPLY ROUGH -INS TO BE FURNISHED WITH ACCESSIBLE SHUT OFFS AT
CONNECTIONS. PLASTIC PIPING NOT PERMITTED FOR INSTALLATION IN RETURN AIR PLENUMS OR
3. EXECUTION
NOTED. HOWEVER; THE EQUIPMENT SUBSTITUTED SHALL MEET ALL SPECIFICATIONS IN DESIGN AND BE SUBJECT TO
CONNECTIONS POINTS. SHUT OFFS AT SUPPLY ROUGH -INS FOR FIXTURES (SINKS, LAVATORIES, ETC.) TO BE
LOCATIONS EXPOSED TO RETURN AIR PLENUMS.
a. PROVIDE A COMPATIBLE FASTENING ASSEMBLY WITH INTERNAL SECONDARY DRAINAGE FLANGE AND
OWNER AND/OR ENGINEER APPROVAL. ANY ADDITIONAL COST INCURRED DUE TO SUBSTITUTION SHALL BE THE
ANGLES TYPE COMPRESSION STOPS. SHUT OFFS AT SUPPLY ROUGH -INS FOR EQUIPMENT OF OTHER ELEMENTS
WEEPHOLES FOR ALL ITEMS SPECIFIED HEREIN BEING INSTALLED IN STRUCTURES HAVING A WATER PROOF
RESPONSIBILITY OF THE CONTRACTOR AT NO EXPENSE TO THE OWNER.
TO BE IN -LINE VALVES AS SPECIFIED FOR INDIVIDUAL SERVICES.
4. EXECUTION
MEMBRANE, FLASHING, VAPOR BARRIER, OR SIMILAR ELEMENT PROVIDED UNDER SEPARATE CONTRACT.
e. UNLESS INDICATED OTHERWISE, WHERE CONNECTION ELEMENTS DESCRIBED HEREIN ARE EXPOSED IN
a. ALL CAST IRON SOIL PIPE SHALL BE BITUMASTIC COATED INSIDE AND OUTSIDE. ALL CAST IRON PIPING
INSTALLATION CONDITIONS TO BE VERIFIED FROM ARCHITECTURAL DOCUMENTATION AND COORDINATED
3. MISCELLANEOUS ITEMS NECESSARY TO COMPLETE THE PIPING SYSTEMS SUCH AS FITTING, HANGERS, ETC., CAN
LOCATIONS OTHER THAN THE RESTRICTED ACCESS UTILITY OR MAINTENANCE AREAS, ALL METALLIC
(INCLUDING JOINTS AND CONNECTIONS) SHALL BE INSTALLED IN ACCORDANCE WITH STANDARDS AS SET
WITH THE APPROPRIATE CONTRACTOR.
BE OF ANY RECOGNIZED MANUFACTURER PROVIDED THESE ITEMS MEET MINIMUM STANDARDS AS SET BY THE
COMPONENTS TO BE FURNISHED WITH A POLISHED CHROME FINISH. WALL OR OTHER STRUCTURE PIPING
FORTH BY THE CAST IRON SOIL PIPE INSTITUTE (CSPI).
b. COUNTER FLASHING (WHEN REQUIRED) FOR ITEMS SPECIFIED HEREIN IS TO BE COMPATIBLE WITH
ENGINEER.
PENETRATIONS AT THESE LOCATION TO BE PROVIDED WITH POLISHED CHROME FINISH ESCUTCHEONS.
b. AT THE CONTRACTOR'S OPTION, HUBLESS CAST IRON SOIL PIPE MAY BE JOINED BY USING HEAVY DUTY
WATERPROOF MEMBRANE, VAPOR BARRIER, FLASHING, OR SIMILAR ELEMENTS PROVIDED UNDER SEPARATE
D. DRAWINGS
EXECUTION GENERAL
"CLAMP ALL" COUPLINGS IN LIEU OF "NO -HUB" COUPLINGS. COUPLINGS ARE TO BE MADE OF 24 GAUGE
CONTRACT AT THE INTERFACE POINT. COUNTER FLASHING TO BE PROVIDED AND SET IN PLACE BY THE
1. DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO SHOW THE APPROXIMATE LOCATION OF OUTLETS,
TYPE 304 STAINLESS STEEL WITH HI -TORQUE CLAMPS AND NEOPRENE GASKETS. COUPLINGS SHALL BE
PLUMBING CONTRACTOR. BUT WILL BE MADE WATERTIGHT BY THE CONTRACTOR INSTALLING THE
EQUIPMENT AND PIPING.
1. WHERE STANDARDS, CODES OR GUIDELINES ARE REFERENCED HERIN AND THROUGHOUT THE PLUMBING
INSTALLED AND TESTED IN ACCORDANCE WITH THE MANUFACTURE'S RECOMMENDATIONS.
MEMBRANE, VAPOR BARRIER, FLASHING OR SIMILAR ELEMENTS PROVIDED UNDER SEPARATE CONTRACT.
CONTRACT DOCUMENTATION, INCLUDING PLANS AND SPECIFICATIONS, THE LATEST VERSION/EDITION SHALL BE
INSTALLATION CONDITIONS TO BE VERIFIED FROM ARCHITECTURAL DOCUMENTATION AND COORDINATED
2. THE EXACT LOCATION OF OUTLETS, EQUIPMENT AND PIPING MAY BE CHANGED FROM TIME TO TIME AS WORK
APPLIED, UNLESS THE BUILDING CODE REFERENCES ANOTHER VERSION/EDDITION, WHICH SHALL TAKE
c. PLASTIC PIPING SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S SPECIFICATIONS AND
WITH THE APPROPRIATE CONTRACTOR.
PROGRESSES. UNDER THIS CONTRACT ALL LOCATIONS SHALL BE VERIFIED WITH ALL TRADES AND THAT THEY ARE
PRECEDENCE.
RECOMMENDATIONS, WITH PARTICULAR ATTENTION TO REQUIREMENTS FOR JOINING METHODS, SUPPORT,
ACCORDING TO THE LATEST INFORMATION AVAILABLE. SHOULD THIS NOT BE DONE THE WORK WILL BE
AND ALLOWANCES FOR EXPANSION AND CONTRACTION. PLASTIC PIPING SHALL NOT BE INSTALLED IN ANY
c. THIS CONTRACTOR SHALL RESPONSIBLE FOR HAVING ALL DRAINS, CLEANOUTS AND OTHER ITEMS SO
CHANGED AT NO ADDITIONAL EXPENSE TO THE OWNER.
2. REFER TO PROJECT DOCUMENTATION FURNISHED WITH THE COMPLETE CONSTRUCTION PACKAGE IN ADVANCE
RETURN AIR PLENUM OR CHASE THAT IS USED FOR RETURN AIR.
A
NOTED INSTALLED FLUSH AND LEVEL WITH FINISH WALL, FLOOR ORR OTHER STRUCTURE AS APPLIES.
OF WORK FOR OVERALL COORDINATION AND VERIFICATION OF REQUIREMENTS AT WORK OF OTHER TRADES
COORDINATE INSTALLATION WITH CONTRACTOR'S PROVIDING ASSOCIATED STRUCTURE, INCLUDING
3. THE OWNER RESERVES THE RIGHT TO MAKE MINOR CHANGES IN LOCATION OF EQUIPMENT AND PIPING
RELATING TO, INTERFACING WITH, AND/OR IMPACTING WORK IN THE PLUMBING CONTRACT. THIS INCLUDES
d. COORDINATE INSTALLATION WITH STRUCTURE, EXISTING CONDITIONS AND WORK OF OTHER TRADES AT AND
REQUIRED ELEVATIONS AND DIMENSIONAL LOCATIONS. ITEMS NOT PROPERLY INSTALLED SHALL BE REMOVED
ARRANGEMENTS UP TO THE TIME OF ROUGH -IN WITHOUT ADDITIONAL COSTS TO THE OWNER.
EXACT LOCATIONS, QUANTITIES, PHYSICAL SIZES, ROUGH -IN DETAILS, PIPE ROUTING, CONNECTION SIZES, ETC.,
ADJACENT TO SOIL, WASTE AND VENT SERVICE PIPING INSTALLATION.
AND REPLACED TO THE SATISFACTION OF THE OWNERS' ON -SITE REPRESENTATIVE.
FOR ITEMS INCLUDING BOTH IN THE PLUMBING CONTRACT AND UNDER SEPARATE CONTRACT. COORDINATE
4. THE DRAWINGS AND SPECIFICATION ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIALS OR
INSTALLATION AND INTERFACE REQUIREMENTS WITH THE APPROPRIATE CONTRACTOR(S) IN ADVANCE OF
DOMESTIC WATER PIPING SYSTEMS
d. ALL ITEMS AND ACCESSORIES SPECIFIED HEREIN ARE TO BE INSTALLED IN ACCORDANCE WITH THE
LABOR CALLED FOR IN ONE SHALL BE FURNISHED EVEN THOUGH NO MENTIONED IN BOTH. ANY MATERIAL OR
WORK.
1. GENERAL
MANUFACTURER'S RECOMMENDATIONS, AND IN ACCORDANCE THE THE REQUIREMENTS OF THE
LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS BUT WHICH IS
INSPECTION/APPROVAL AUTHORITIES.
OBVIOUSLY NECESSARY TO COMPLETE THE WORK AND WHICH IS USUALLY INCLUDED IN WORK OF A SIMILAR
3. INCLUDE ANY MINOR DETAILS, ITEMS AND/OR ELEMENTS ESSENTIAL TO NECESSARY APPROVALS AND
a. THE DOMESTIC WATER PIPING SYSTEM SHALL INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING:
CHARACTER SHALL BE FURNISHED UNDER THIS CONTRACT.
SUCCESSFUL OPERATION IN ADDITION TO THE ITEMS SPECIFIED HEREIN AND SHOWN ON THE DRAWINGS.
e. WITH THE EXCEPTION OF CLEANOUTS, ALL ITEMS SPECIFIED ARE TO HAVE CONNECTION SIZE SAME AS
1. COLD WATER SUPPLY, HOT WATER SUPPLY.
CONNECTED PIPING SIZE SHOWN ON THE DRAWINGS, UNLESS DIRECTED OTHERWISE.
E. CLEANING UP
4. SEE GENERAL "PLUMBING NOTES" ON DRAWINGS FOR ADDITIONAL CONDITIONS AND REQUIREMENTS RELATIVE
TO THE PLUMBING CONTRACT.
2. PRODUCTS
f. CLEANOUTS ARE TO HAVE OUTLET SIZE, CONNECTION PIPE AND FITTINGS OF SAME SIZE AS SHOWN ON
1. UNLESS OTHERWISE NOTED, ALL EXCESS MATERIALS AND DEBRIS CAUSED BY THIS WORK SHALL BE COME THE
PLANS FOR WASTE/DRAIN PIPING BEING SERVED, UP TO AND INCLUDING 3" SIZE. CLEANOUTS ARE TO HAVE
PROPERTY OF THE CONTRACTOR AND PROMPTLY BE REMOVED FROM THE SITE. ALL FIXTURES AND EQUIPMENT
5. PLUMBING ITEMS AND ELEMENTS SHALL BE INSTALLED WITH DUE REGARD TO PRESERVATION OF THE STRENGTH
a. PIPE AND FITTINGS.
OUTLET SIZE, CONNECTING PIPE AND FITTINGS OF 4" SIZE WHEN SHOWN ON THE DRAWINGS SERVING
INSTALLED SHALL BE THOROUGHLY CLEANED WEEKLY. ALL MOTORS AND EQUIPMENT SHALL BE COVERED OR
OF STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE TO WALLS, SURFACES AND OTHER STRUCTURES
1. ABOVE GROUND PIPING UP TO AND INCLUDING 3" SIZE TO BE ASTM B88, ANSI/NSF 61 TYPE L HARD
WASTE/DRAIN PIPING 4" SIZE AND LARGER.
OTHERWISE PROTECTED FORM CONSTRUCTION DUST AND DEBRIS. NO EQUIPMENT OTHER THAN THOSE
THROUGH INSTALLATION, BEARING SUPPORT OF SUBSEQUENT USAGE OF PLUMBING ITEMS AND ELEMENTS. NO
DRAWN COPPER TUBE WITH WROUGHT COPPER FITTINGS AND SOCKET SOLDER JOINTS AND
DESIGNED TO ARE TO BE EXPOSED TO INCLEMENT WEATHER. TOUCH UP ALL SCRATCHES AND REPAIR ANY DENTS
FRAMING OR OTHER SUPPORT STRUCTURE SHALL BE CUT, NOTCHED OR BORED IN EXCESS OF LIMITATIONS
CONNECTIONS. TEE DRILL MECHANICAL SADDLE CONNECTIONS MAY BE UTILIZED FOR BRANCH
g• COORDINATE LOCATIONS OF ITEMS SPECIFIED HEREIN, AND INSTALLED IN OR AT STRUCTURE PROVIDED
IN EQUIPMENT.
SPECIFIED IN THE BUILDING CODE, OR BY THE MANUFACTURER OF THE FRAMING OR OTHER SUPPORT
TAKE -OFFS. PIPING BELOW GRADE 2" DIAMETER AND SMALLER SHALL BE ASTM B88 LISTED/APPROVED TYPE
UNDER SEPARATE CONTRACT, RELATIVE TO FOUNDATIONS, BEAMS AND OTHER STRUCTURE ELEMENTS TO
STRUCTURE, AS CONFIRMED IN ADVANCE OF WORK BY THE PLUMBING CONTRACTOR.
K SOFT COPPER TUBING IN A SINGLE LENGTH WITH NO IN -LINE COUPLINGS OR JOINTS. COMPLETED
AVOID CONFLICTS. MAKE MINOR ADJUSTMENTS AS REQUIRED FOR PROPER INSTALLATION, CLEARANCE
F. CUTTING AND PATCHING
AND ACCESSIBILITY. REFER TO ARCHITECTURAL/STRUCTURAL DOCUMENTATION IN ADVANCE OF WORK AND
SLEEVES
INSTALLATION TO BE RATED 135 S.W.P AND 400 W.O.G.
COORDINATE INSTALLATION WITH THE APPROPRIATE CONTRACTOR.
1. CUTTING FOR OPENINGS, WHEN NECESSARY, SHALL BE DONE BY THIS CONTRACTOR WITH SUCH TOOLS AND
METHODS AS TO PREVENT UNNECESSARY DAMAGE TO SURROUNDING AREAS OR EQUIPMENT.
1. SLEEVE MATERIAL: BLACK STEEL PIPE, MACHINE CUT, LARGE ENOUGH TO ALLOW 1/4" CLEARANCE ALL AROUND
2. BALL VALVES 3" SIZE AND SMALLER SHALL BE LEAD-FREE TWO-PIECE BRONZE BODY BALL VALVE, SOLDERED
PIPE AND PIPE COVERING. USE MACHINE CUT COPPER SLEEVES FOR NON -INSULATED COPPER PIPE.
CONNECTIONS, UNION CONNECTION BODY, TEFLON SEATS, FULL PORT WITH BLOW OUT PROOF STEM,
PIPE ANCHORS, HANGERS AND SUPPORTS
2. FILL SPACE IN ALL AREAS PACKING WHERE REQUIRED TO MAINTAIN FIRE RATING, OPENINGS SHALL BE
ADJUSTABLE PACKING GLAND, CHROME PLATED BRONZE BALL AND LEVER HANDLE LABELED FOR THE
TEMPORARILY FIRE STOPPED UNTIL PERMANENT FIRE STOPPING IS DONE. THIS INCLUDES HOLES LEFT DUE TO
2. SLEEVES IN PARTITIONS TO HAVE LENGTH EQUAL TO THE THICKNESS OF FINISHED PARTITIONS. SLEEVES IN FLOORS
SERVICE CONTROLLED. DESIGN FOR 150 S.W.P. AND 400 W.O.G. EQUAL TO APOLLO 70LF SERIES.
1. ALL PIPING SHALL BE SEPARATELY HUNG AND SUPPORTED FROM APPROVED STRUCTURAL MEMBERS OR
REMOVAL OF PIPING.
OF FINISHED AREAS TO PROJECT 2" ABOVE THE FINISHED FLOOR. SLEEVES IN FLOORS OF NON -FINISHED AREAS
CONCRETE OVERHEAD STRUCTURE ONLY. NO PIPE SHALL BE HUNG FROM ROOF DECK, PIPE DUCTS, OR OTHER
TO PROJECT 2" ABOVE THE FINISHED FLOOR. FILL SPACE BETWEEN PIPE AND SLEEVES INTO EXPOSED AREAS WITH
3. VALVES BY MILWAUKEE, NIBCO OR WATTS MAY BE FURNISHED AT THE CONTRACTOR'S OPTION.
COMPONENTS OR EQUIPMENT OF OTHER TRADES.
3. PATCHING SHALL MATCH EXISTING SURFACES IN KIND AND FINISH, AND SHALL BE DONE BY THE GENERAL
CONTRACTOR.
SEALING COMPOUND. REAM ALL SLEEVES BEFORE INSTALLING.
5. ALL DOMESTIC WATER PIPING SHALL BE CLEAN, FLUSHED AND TESTED PER STATE AND LOCAL HEALTH
2. PROVIDE LISTED/APPROVED ADJUSTABLE HANGERS, INSERTS, BRACKETS, CLAMPS, SUPPLEMENTAL STEEL AND
PLUMBING INSULATION
DEPARTMENT REQUIREMENTS.
OTHER DEVICES REQUIRED FOR PROPER SUPPORT OF ALL PIPE LINES.
4. NO STRUCTURAL MEMEBER WILL BE CUT INTO WITHOUT THE EXPRESSED PERMISSION THE OWNER'S
REPRESENTATIVE.
RE
1. GENERAL
6. ALL DOMESTIC WATER PIPING SHALL BE CERTIFIED SAFE FOR HUMAN CONSUMPTION BY A CERTIFIED
3. HANGERS SHALL BE DESIGNED TO ALLOW FOR EXPANSION AND CONTRACTION AND TO ALLOW INSULATION
PROFESSIONAL BY THE STATE OF WEST VIRGINIA (BACTERIAL CERTIFICATION NUMBER) EMPLOYED BY A
(WHERE APPLICABLE) TO RUN CONTINUOUSLY THROUGH HANGERS.
G. GUARANTEE
a. PROVIDE LISTED INSULATION COVER FOR ALL ITEMS/ELEMENTS AS SPECIFIED HEREIN, AS SHOWN ON
TESTING LABORATORY THAT STATES THE SYSTEM MEETS THE DEPARTMENT OF HEALTH REQUIREMENTS AND IS
DRAWINGS, AND FOR ANY OTHER ITEMS/ELEMENTS REQUIRING SAME.
APPROVED FOR HUMAN CONSUMPTION.
4. WIRE OR STRAP HANGERS ARE NOT PERMITTED. ADJUST HANGERS SO AS TO DISTRIBUTE WEIGHT LOAD EQUALLY
1. ALL LABOR AND MATERIALS FURNISHED UNDER THIS CONTRACT SHALL BE GUARANTEED FOR A PERIOD OF ONE
ON ATTACHMENTS.
(1) YEAR FORM THE DATE OF FINAL ACCEPTANCE BY THE OWNER WHICH WILL COMMENCE UPON THE FINAL
b. INSULATE PIPING AND ASSOCIATED ACCESSORIES AND APPURTENANCES INCLUDING IN THE FOLLOWING
7. SOLDER AND FLUX MATERIAL SHALL BE CERTIFIED "LEAD FREE" AND LISTED FOR USE WITH POTABLE WATER
INSPECTION BY THE ENGINEER. DURING THIS TIME, ALL LEAKS, CORRECTION OF ALL THE FAILURES TO SUCH
SYSTEMS:
SYSTEMS.
5. USE OF TRAPEZE HANGERS DO NOT PERMIT THE ELIMINATION OF THE PIPING INSULATION TO NOT BE
MATERIAL AND THE CORRECTION OF ALL DISCREPANCIES WITH THE PLUMBING CODE, THE CONTRACT
1. DOMESTIC COLD WATER AND HOT WATER.
3. EXECUTION
CONTINUOUS THRU THE HANGER.
DRAWINGS, AND THE PROJECT SPECIFICATIONS SHALL BE DONE UNDER THIS CONTRACT AT NO ADDITIONAL
6. NO PIPE SHALL BE SUPPORTED FROM ANOTHER PIPE. ALL HANGERS SHALL BE PLUMBED BEFORE INSULATION IS
EXPENSE TO THE OWNER.
2. PRODUCTS
a. ALL PIPING THAT SUPPLIES A FLUSH VALVE, SOLENOID VALVE (OTHER THAN SLOW -CLOSING TYPE) SPRING
APPLIED AND ALL HANGERS SHALL BE DOUBLE NUTTED. ALL HANGERS SHALL MEET LOCAL CODE REQUIREMENTS.
H. EXCAVATION AND BACKFILL
a. ALL INSULATING MATERIALS, INCLUDING JACKETS, CEMENTS, ADHESIVES, VAPOR BARRIERS, ETC., SHALL BE
RETURN OPERATOR OR OTHER QUICK CLOSING TYPE DEVICE SHALL HAVE A SHOCK ABSORBER INSTALLED IN
ALL PLASTIC PIPE SHALL BE INSTALLED AND SUPPORTED PER MANUFACTURERS INSTRUCTIONS.
U.L. LISTED, WITH A FLAME SPREAD RATING NOT TO EXCEED25, AND A SMOKE DEVELOPMENT RATING NOT
ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. UNLESS INDICATED OTHERWISE, WHERE
1. THIS CONTRACTOR SHALL EXCAVATE AND BACKFILL ALL TRENCHES AND OTHER EXCAVATIONS REQUIRED FOR
TO EXCEED 50. ALL EXTERIOR FINISHES SHALL HAVE A MINIMUM SERVICE TEMPERATURE LIMIT (FSTM 70) OF
MULTIPLE FIXTURES OR EQUIPMENT IN ADJACENT LOCATIONS (SUCH AS WITHIN A CHASE OR OTHER
PLUMBING FIXTURES
LAYING DRAINS, SEWERS, APPURTENANCES AND OTHER EXCAVATIONS REQUIRED FOR HIS WORK.
MINUS 50 TO 220 DEGREES F.
ENCLOSURE) ARE SUPPLIED BY COMMON PIPING MANIFOLD, A PROPERLY SIZED AND INSTALLED SHOCK
ABSORBER MAY BE UTILIZED.
1. GENERAL
2. EARTH FILL: SOIL AS APPROVED BY THE OWNER'S REPRESENTATIVE, FREE OF ORGANIC SOIL, SOD, ROOTS,
b. MOLDED PLASTIC FITTING COVERS SHALL BE U.L. LISTED WITH A FLAME SPREAD RATING NOT TO EXCEED 25,
WOOD METAL RUBBISH DEBRIS LUMPS OR EXCESSIVE AMOUNTS OF CLAY AND ROCKS GREATER THAN 2" IN
AND A SMOKE DEVELOPMENT RATING NOT TO EXCEED 50.
b. RUN ALL WATER PIPING LEVEL AND CONCEAL WHENEVER POSSIBLE. PIPING TO BE INSTALLED TO ALLOW
a. FURNISH AND INSTALL ALL PLUMBING FIXTURES AND ASSOCIATED ACCESSORIES AS SPECIFIED HEREIN AT
DIAMETER; CAPABLE OF BEING COMPACTED INTO DENSE AND STABLE CONDITIONS AS SPECIFIED.
COMPLETE DRAIN DOWN OF SYSTEM BACK TO MAIN RISER AT BASE OF SYSTEM WHENEVER POSSIBLE.
LOCATIONS INDICATED ON THE DRAWINGS. FIXTURES TO BE PROVIDED FREE OF DEFECTS AND SET IN A NEAT,
c. INSULATED THICKNESS IS BASED ON INSULATION HAVING THERMAL RESISTANCE IN THE RANGE OF 4.0 HR F.
FINISHED AND UNIFORM MANNER.
3. ALL UNDERGROUND PIPING SHALL BE INSTALLED ON A MINIMUM OF A 3" BED OF COMPACTED SAND. ALL
FT2/BTU TO 4.6 HR F. FT2/BTU PER INCH OF THICKNESS ON A FLATSURFACE AT A MEAN TEMPERATURE OF 75
c. COORDINATE INSTALLATION WITH STRUCTURE, SITE CONDITIONS AND WORK OF OTHER TRADES AT AND
UNDERGROUND PIPING SHALL BE BACKFILLED BY HAND TO A LEVEL OF 6" ABOVE THE PIPE WITH CLEAN SAND.
DEGREES F. MINIMUM INSULATION THICKNESS SHALL BE INCREASED FOR MATERIALS HAVING R VALUES LESS
ADJACENT TO DOMESTIC WATER SERVICE PIPING INSTALLATIONS.
b. WHERE FIXTURES ARE INDICATED TO BE HANDICAP ACCESSIBLE, INSTALL AS DIRECTED HEREIN AND IN
ALL BACKFILL SHALL BE MADE IN LIFTS NOT TO EXCEED 12". EACH LIFT SHALL BE MECHANICALLY COMPACTED
THAN 4.0 OR MAY BE REDUCED FOR MATERIALS HAVING R VALUES GREATER THAN 4.6 TO GIVE EQUIVALENT
4. FLUSHING AND STERILIZATION
COMPLIANCE WITH THE CODES AND GUIDELINES REFERENCED.
TO A MINIMUM OF 92% MODIFIED PROCTOR.
"R" VALUES.
2. PRODUCTS
4. PROTECT ALL UTILITIES SHOWN ON DRAWINGS OR ENCOUNTERED IN THE CONSTRUCTION WORK. ANY DAMAGE
"MICRO-LOK"
a. FLUSH OUT ALL DOMESTIC WATER PIPING SYSTEMS TO REMOVE ALL DIRT AND GREASE FROM PIPING AND
TO UTILITIES SHALL BE REPAIRED BY THIS CONTRACTOR TO OWNER'S SATISFACTION, WITHOUT COST TO THE
d. PIPE COVERS SHALL BE SIMILAR TO JOHNS MANVILLE GLASS FIBER INSULATION, RATED FOR 850
EQUIPMENT BEFORE SYSTEMS ARE PLACED INTO OPERATION. CLEAN STRAINERS AFTER EACH FLUSHING UNTIL
a. PLUMBING FIXTURES, TRIM, FITTINGS, ACCESSORIES, APPURTENANCES, ETC. NOT INCLUDED HEREIN ARE AS
DEGREES F. WITH A FACTORY APPLIED AP-T ALL-PURPOSE SELF-SEALING VAPOR BARRIER JACKET. BUTT STRIPS
THE STRAINER REMAINS CLEAN.
SPECIFIED ON PLAN.
OWNER.
SHALL BE MINIMUM 3" WIDE, AND OF SAME MATERIAL AS JACKET. EQUAL MATERIALS, INCLUDING THICKNESS
5. THIS CONTRACTOR SHALL REMOVE ANY UNUSABLE OF SURPLUS EXCAVATED MATERIAL FROM THE SITE.
AND CONDUCTIVITY RATINGS/LISTINGS. AS MANUFACTURED BY OWENS CORNING, KNAUF OR MANSON
b. AFTER DOMESTIC WATER LINES ARE ALL INSTALLED, STERILIZE LINES AS PRESCRIBED BY AWWA-C-651.
b. CHINA PLUMBING FIXTURES AND ACCESSORIES AS MANUFACTURED BY SLOAN.
MAY BE FURNISHED, AT THE CONTRACTOR'S OPTION. WHERE INSULATION THICKNESS IS INDICATED FOR
STERILIZATION SHALL BE DONE UNDER IMMEDIATE -ON-THE-JOB SUPERVISION OF A WATER TESTING
c. BATTERY POWERED, SENSOR ACTIVATED FAUCETS AND ACCESSORIES AS MANUFACTURED BY SLOAN.
I. RECORD DRAWINGS
COVER HEREIN. IT IS NOMINAL THICKNESS REQUIRED THICKNESS.
LABORATORY REGULARLY ENGAGED IN THE SERVICE AND SHALL BE DONE PER THEIR INSTRUCTIONS. ALL FEES
1. THIS CONTRACTOR SHALL KEEP AN ACCURATE RECORD OF ALL DEVIATIONS FROM CONTRACT DRAWINGS AND
e. ALL CEMENTS, ADHESIVES, FINISHES, AND ASSOCIATED MATERIALS SHALL BE SIMILAR TO THAT PROVIDED BY
FOR TESTING AND TEST EQUIPMENT SHALL BE PAID BY THIS CONTRACTOR.
d. SEATS FOR WATER CLOSETS AS MANUFACTURED BY BEMIS, CHURCH, OR OLSONITE MAY BE FURNISHED AT
SPECIFICATIONS. HE SHALL NEATLY AND CORRECTLY ENTER IN COLORED PENCIL ANY DEVIATIONS ON THE BLUE
FOSTER. EQUAL MATERIALS AS PROVIDED BY CHILDERS OR VIMASCO MAY BE FURNISHED AT THE
c. FURNISH A CERTIFICATE OF STERILIZATION AND APPROVAL FOR HUMAN CONSUMPTION SIGNED BY A
THE CONTRACTOR'S OPTION. ALL SEATS ARE TO BE FURNISHED WITH SELF-SUSTAINING STAINLESS STEEL CHECK
PRINTS OR BLUE LINE DRAWINGS. AT COMPLETION OF THE PROJECT DELIVER DRAWINGS TO OWNER'S
CONTRACTOR'S OPTION.
PROFESSIONAL ENGINEER REGISTERED WITHIN THE STATE AND REGULARLY IN THE EMPLOY OF THE TESTING
HINGES UNLESS NOTED OTHERWISE.
REPRESENTATIVE.
LABORATORY. CERTIFICATION SHALL BE FURNISHED TO THE ARCHITECT/ENGINEER PRIOR TO ANY PAYMENT IS
e. EQUIVALENT FIXTURE CARRIERS AS MANUFACTURED BY ZURN, JOSAM, J. R. SMITH, MIFAB, OR WATTS MAY BE
PERMITS AND FEES
f. LONGITUDINAL LAP JOINTS AND BUTT STRIPS FOR GLASS FIBER PIPING INSULATION SHALL BE SECURED WITH
MADE.
FURNISHED AT THE CONTRACTOR'S OPTION.
STAPLES ON THREE (3) INCH CENTERS, AND SEALED WITH AN APPROVED VAPOR BARRIER ADHESIVE WHERE
1. THE PLUMBING CONTRACTOR SHALL APPLY FOR AND PAY ANY REVIEW INSPECTION, PERMIT, LICENSE, TESTING
APPLICABLE. STAPLES ARE NOT REQUIRED WHEN INSULATION UTILIZES A "DOUBLE" ADHESIVE SELF-SEALING
d. STERILIZATION: CHLORINATING MATERIAL EITHER LIQUID CHLORINE MEETING AWWA STANDARD B301,
f. UNLESS INDICATED OTHERWISE, ALL EXPOSED METALLIC PARTS, PIPING, TRIM, FITTINGS, ACCESSORIES,
AND/OR OTHER SERVICE FEES REQUIRED BY ALL REVIEW/INSPECTION/APPROVAL AUTHORITIES IN CONNECTION
SYSTEM.
SODIUM OR CALCIUM HYPOCHLORITE MEETING AWWA STANDARD B300.
APPURTENANCES, ETC, ASSOCIATED WITH PLUMBING FIXTURES SHALL BE POLISHED CHROME FINISH WHEN
WITH THE WORK UNDER THIS CONTRACT.
6. EXECUTION
AVAILABLE. PROVIDE POLISHED CHROME PLATED BRASS ESCUTCHEONS ON PIPING AT ALL EXPOSED
3. EXECUTION
STRUCTURE PENETRATIONS (WALLS, FLOORS, CEILINGS, CASEWORK, ETC,) AND AT ALL FIXTURE
2. ALL WORK SHALL ALSO BE INSTALLED IN ACCORDANCE WITH REGULATIONS OF THE FIRE UNDERWRITERS HAVING
a. COVER DOMESTIC COLD WATER AND HOT WATER PIPING WITH V THICKNESS GLASS FIBER PIPE INSULATION.
a. WITH ALL OUTLETS CLOSED, FILL SYSTEM TO WORKING PRESSURE AND CLOSE VALVE AT SUPPLY MAIN.
CONNECTIONS.
JURISDICTION AND LOCAL UTILITIES. CONTRACTOR SHALL ALSO SECURE ANY PERMITS OR PAY ANY FEES TO THE
LOCAL UTILITY COMPANIES FOR THE WORK REQUIRED.
b. ALL APPURTENANCES AND ACCESSORIES SUCH AS VALVES, FLANGES, UNIONS, ETC. INSTALLED IN
b. A CLEANING SOLUTION CONTAINING NOT LESS THAN 150 PARTS PER MILLION OF CHLORINE SHALL BE
g. AT ALL HANDICAP ACCESS LAVATORIES AND/OR SINKS WITH EXPOSED SUPPLY AND DRAIN PIPING BELOW,
PRODUCTS GENERAL
REFERENCED PIPING SHALL BE WRAPPED WITH FULL THICKNESS INSULATION AND COVERED WITH A LISTED
INTRODUCED INTO THE SYSTEM.
PROVIDE PRE -FABRICATED CLOSED CELL VINYL INSULATION/COVER ASSEMBLIES WITH SEAMLESS PVC
1. WHERE ITEMS/ELEMENTS ARE INDICATED HEREIN TO BE LISTED/APPROVED. THE INTENT OF THE SPECIFICATION IS
MOLDED PLASTIC FITTING COVER, OR AN OPEN MESH GLASS CLOTH SHALL BE FIRE RESISTANT MASTIC.
c. EACH OUTLET, HOT AND COLD, SHALL BE TESTED DURING FILL TO PROVE THE PRESENCE OF CHLORINE AT
JACKET FOR ALL SUPPLY (FULL RANGE OF HOT, COLD AND TEMPERED) AND DRAIN PIPING. ASSEMBLY TO BE
SIMILAR TO MCGUIRE PRO -WRAP SERIES, OFFSET DRAINS (IF USED) TO BE PROVIDED WITH COVER ASSEMBLIES
THAT SAID ITEM/ELEMENT SHALL BE LISTED BY ALL APPLICABLE MATERIAL/CONSTRUCTION STANDARDS, AND
c. USE 12" LONG SECTIONS OF CALCIUM SILICATE RIGID INSULATION, WITH JACKET SAME AS ADJACENT PIPE
THAT OUTLET AND VALVES AND FAUCETS SHALL BE OPENED AND CLOSED SEVERAL TIMES DURING THE
SPECIFICALLY DESIGNED FOR SAME. ASSEMBLIES TO BE LISTED BY MANUFACTURER AS HANDICAP ACCESS
SUBJECT TO FINAL APPROVAL (INCLUDING METHODS OF INSTALLATION) BY ALL REVIEW/INSPECTION/APPROVAL
COVERING FOR TRANSFER OF SUPPORT TO PIPING AT EACH HANGER, WITHOUT STRESS TO THE PIPE
DISINFECTING TIME PERIOD.
COMPLIANT.
AUTHORITIES.
COVERING ASSEMBLY. AT THE CONTRACTOR'S OPTION, AN APPROVED WOOD OR HIGH -DENSITY (20 LB./CU.
d. WATER PIPING SYSTEMS SHALL REMAIN FILLED FOR A PERIOD OF 24 HOURS AND EACH OUTLET SHALL BE
2. UNLESS INDICATED OTHERWISE, ALL PLUMBING CONTRACT ITEMS/ELEMENTS (PIPE, FITTINGS, VALVES,
FT.) FIBERGLASS BLOCK MAY BE SUBSTITUTED FOR THE RIGID INSULATION SECTION. VAPOR BARRIER TO BE
AGAIN TESTED AND SHALL PRODUCE NOT LESS THAN 100 PARTS PER MILLION OF CHLORINE AT THE END OF
3. EXECUTION
SPECIALTIES, FIXTURES, EQUIPMENT, ETC.) MATERIALS, CONSTRUCTION, PERFORMANCE, TESTING AND METHODS
MAINTAINED THROUGHOUT.
THE RETENTION PERIOD.
a. PROVIDE INDIVIDUAL ACCESSIBLE STOP VALVES ON ALL FIXTURES AND EQUIPMENT SUPPLY PIPING.
OF INSTALLATION TO BE AS LISTED/APPROVED BY ALL APPLICABLE MATERIAL/ CONSTRUCTION/ INSTALLATION
d. ALL APPLICATIONS SHALL BE MADE ON CLEAN, DRYSURFACES WITH ALL JOINTS BUTTED FIRMLY TOGETHER.
e. ALL OUTLETS SHALL BE OPENED WIDE AND THE MAIN SUPPLY VALVES OPENED. FLUSHING SYSTEM WITH
b. INSTALL ALL FIXTURES ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.
STANDARDS FOR SAME, AND BE IN ACCORDANCE WITH THE REQUIREMENTS OF ALL REVIEW/INSPECTION/
e. INSULATION MUST RUN CONTINUOUS THROUGH HANGERS, SLEEVES AND WALL FOR ALL COLD WATER AND
WATER UNTIL THE CHLORINE CONTENT IS NOT GREATER THAN 0.2 PARTS PER MILLION OR UNTIL APPROVED BY
APPROVAL AUTHORITIES. THIS INCLUDES, BUT IS NOT LIMITED TO, THE STANDARDS AND AUTHORITIES REFERENCED
THE HEALTH DEPARTMENT. FLUSH DRAIN VALVES.
C. MOUNTING HEIGHTS OF FIXTURES AS ASSOCIATED EQUIPMENT AS INDICATED ON ARCHITECTURAL
IN THIS SPECIFICATION. IN THE ABSENCE OF SUCH STANDARDS AND/OR REQUIREMENTS, THE
HOT WATER PIPING.
DRAWINGS.
ITEM/ELEMENTMANUFACTURER'S RECOMMENDATIONS, AS CONFIRMED BY THE PLUMBING CONTRACTOR IN
f. INSULATION SHALL NOT BE APPLIED UNTIL GENERAL CONSTRUCTION HAS PROGRESSED SUFFICIENTLY TO
f. AFTER FINAL FLUSHING ALL AERATORS ON PLUMBING BRASS SHALL BE REMOVED, CLEANED AND
ADVANCE, SHALL BE FOLLOWED.
MINIMIZE POTENTIAL FOR PHYSICAL OR MOISTURE DAMAGE TO THE COVER ASSEMBLY. ALL DAMAGED
REINSTALLED.
d. JOINTS FORMED WHERE FIXTURES COME INTO CONTACT WITH WALLS OF FLOORS SHALL BE SEALED
WATERTIGHT WITH AND APPROVED SEALING COMPOUND, COORDINATE INSTALLATION AND COLOR WITH
3. UNLESS INDICATED OTHERWISE, ALL PLUMBING PIPING SHALL BE IN ACCORDANCE WITH THE FOLLOWING
COVER SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE.
g. STERILIZATION TEST MAY BE PERFORMED AT THE SAME TIME THE PRESSURE TEST IS PLACED ON THE SYSTEM.
THE CONSTRUCTION MANAGER.
STANDARDS IN REGARD TO MATERIALS, CONSTRUCTION, DIMENSIONS/TOLERANCES, TYPE OF
g, INSTALL PROTECTIVE SLEEVE ON ALL INSULATED, EXPOSED PIPES PENETRATING THE FLOOR STRUCTURE.
RELEASED IFCR CONSTRUCTION
at State and lmeal Endles
0tp at Caimal
DATE: 03/07/18
Nick Mishler
• Ln Ln O I-
� Ol c-I � �
N N � rl_
M 00 00
. .� =3 O 00 00
> cn ._
�O
� vi lfl lD
aA �
Lna) ro
Ln E +1 L
00 =5
O
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE+ PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
W
5
G
L.ii
W
N
\
O
=
0
5�
G
V)
Z)
Co
0
2
Oo
Z)O
J
Q
zm0
J
N
M
(Dw
~
Lu
W
JUG
2�
QQ
V)
Q°Ca_
a
O
Lu
~o
O0
M
z
Co
W
Q
U
J
W
(D~
V)
w
�o
M<
<q
PROJECT NUMBER:
W P GO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
SPECIFICATIONS
PLUMBING
610: 15
M3ol
19
SPECIFICATIONS - DIVISION 23 - HVAC
GENERAL MECHANICAL REQUIREMENTS:
MECHANICAL CONTRACTOR SHALL SUBMIT COMPLIANCE CHECKLIST TO BUILDING OFFICIAL UPON SUBSTANTIAL
COMPLETION OF PROJECT.
PROVIDE EQUIPMENT INDICATED ON THE DRAWINGS, AND AS REQUIRED FOR A COMPLETE FUNCTIONING SYSTEM.
DEFINITIONS:
FURNISH MEANS TO SUPPLY AND DELIVER TO PROJECT SITE, READY FOR INSTALLATION.
INSTALL MEANS TO PLACE IN POSITION AND MAKE CONNECTIONS FOR SERVICE OR USE.
PROVIDE MEANS TO FURNISH AND INSTALL, COMPLETE AND READY FOR INTENDED USE.
COORDINATION:
COORDINATE WITH THE WORK OF OTHER SECTIONS, EQUIPMENT FURNISHED BY OTHERS, REQUIREMENTS OF THE OWNER,
AND WITH THE CONSTRAINTS OF THE EXISTING CONDITIONS OF THE PROJECT SITE.
DUCT DIMENSIONS:
UNLESS OTHERWISE NOTED, DUCT DIMENSIONS ON THE DRAWINGS ARE INSIDE CLEAR DIMENSIONS.
END OF SECTION
SECTION 230700 - HVAC INSULATION
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. SURFACE -BURNING CHARACTERISTICS:
1. INDOOR INSULATION AND RELATED MATERIALS: TO BE FACTORY LABELED DESIGNATING MAXIMUM
FLAME -SPREAD INDEX OF 25 OR LESS, AND SMOKE -DEVELOPED INDEX OF 50 OR LESS ACCORDING TO
ASTM E 84.
2.2 INSULATION MATERIALS
A. FLEXIBLE ELASTOMERIC: CLOSED -CELL, SPONGE- OR EXPANDED -RUBBER MATERIALS. COMPLY WITH ASTM C 534,
TYPE I FOR TUBULAR MATERIALS AND TYPE II FOR SHEET MATERIALS.
B. MINERAL -FIBER BLANKET INSULATION: COMPLY WITH ASTM C 553, TYPE II AND ASTM C 1290, TYPE I.
1. FSK JACKET: ALUMINUM -FOIL, FIBERGLASS -REINFORCED SCRIM WITH KRAFT-PAPER BACKING; COMPLYING WITH
ASTM C 1136, TYPE II.
2. FSK TAPE: FOIL -FACE, VAPOR -RETARDER TAPE MATCHING FACTORY -APPLIED JACKET WITH ACRYLIC ADHESIVE;
COMPLYING WITH ASTM C 1136.
C. MINERAL -FIBER, PIPE AND TANK INSULATION: COMPLYING WITH ASTM C 1393, TYPE II OR TYPE IIIA CATEGORY 2, OR
WITH PROPERTIES SIMILAR TO ASTM C 612, TYPE IB; AND HAVING FACTORY -APPLIED ASJ JACKET. NOMINAL DENSITY
IS 2.5 LB/CU. FT. OR MORE. THERMAL CONDUCTIVITY (K-VALUE) AT 100 DEG F IS 0.29 BTU X IN./H X SQ. FT. X DEG F
OR LESS.
1. ASJ: WHITE, KRAFT-PAPER, FIBERGLASS -REINFORCED SCRIM WITH ALUMINUM -FOIL BACKING; COMPLYING WITH
ASTM C 1136, TYPE I.
2. ASJ TAPE: WHITE VAPOR -RETARDER TAPE MATCHING FACTORY -APPLIED JACKET WITH ACRYLIC ADHESIVE,
COMPLYING WITH ASTM C 1136.
D. FLEXIBLE ELASTOMERIC ADHESIVE: COMPLY WITH MIL-A-24179A,TYPE II, CLASS I.
E. MINERAL -FIBER ADHESIVE: COMPLY WITH MIL-A-3316C, CLASS 2, GRADE A.
F. VAPOR -BARRIER MASTIC: WATER BASED; SUITABLE FOR INDOOR AND OUTDOOR USE ON BELOW AMBIENT
SERVICES; COMPLY WITH MIL-PRF-19565C, TYPE II.
PART 3 - EXECUTION
3.1 INSULATION INSTALLATION
A. COMPLY WITH REQUIREMENTS OF THE MIDWEST INSULATION CONTRACTORS ASSOCIATION'S "NATIONAL
COMMERCIAL & INDUSTRIAL INSULATION STANDARDS" FOR INSULATION INSTALLATION ON PIPES AND EQUIPMENT.
B. INSULATION INSTALLATION AT INTERIOR WALL AND PARTITION PENETRATIONS (THAT ARE NOT FIRE RATED): INSTALL
INSULATION CONTINUOUSLY THROUGH WALLS AND PARTITIONS.
C. INSULATION INSTALLATION AT FIRE -RATED WALL, PARTITION, AND FLOOR PENETRATIONS: INSTALL INSULATION
CONTINUOUSLY THROUGH PENETRATIONS. SEAL PENETRATIONS. COMPLY WITH REQUIREMENTS IN SECTION 078400.
D. FLEXIBLE ELASTOMERIC INSULATION INSTALLATION:
1. SEAL LONGITUDINAL SEAMS AND END JOINTS WITH ADHESIVE TO ELIMINATE OPENINGS IN INSULATION THAT
ALLOW PASSAGE OF AIR TO SURFACE BEING INSULATED.
2. INSULATION INSTALLATION ON PIPE FITTINGS AND ELBOWS: INSTALL MITERED SECTIONS OF PIPE INSULATION.
SECURE INSULATION MATERIALS AND SEAL SEAMS WITH ADHESIVE TO ELIMINATE OPENINGS IN INSULATION THAT
ALLOW PASSAGE OF AIR TO SURFACE BEING INSULATED.
E. MINERAL -FIBER INSULATION INSTALLATION:
1. INSULATION INSTALLATION ON STRAIGHT PIPES AND TUBES: WHERE VAPOR BARRIERS ARE INDICATED, SEAL
LONGITUDINAL SEAMS, END JOINTS, AND PROTRUSIONS WITH VAPOR -BARRIER MASTIC AND JOINT SEALANT.
2. FOR INSULATION WITH FACTORY -APPLIED JACKETS ON ABOVE AMBIENT SURFACES, SECURE LAPS WITH
OUTWARD CLINCHED STAPLES AT 6 INCHES O.C.
3. FOR INSULATION WITH FACTORY -APPLIED JACKETS ON BELOW AMBIENT SURFACES, DO NOT STAPLE
LONGITUDINAL TABS BUT SECURE TABS WITH ADDITIONAL ADHESIVE AS RECOMMENDED BY INSULATION
MATERIAL MANUFACTURER AND SEAL WITH VAPOR -BARRIER MASTIC AND FLASHING SEALANT.
4. BLANKET INSULATION INSTALLATION ON DUCTS AND PLENUMS: SECURE WITH ADHESIVE AND INSULATION PINS.
5. FOR DUCTS AND PLENUMS WITH SURFACE TEMPERATURES BELOW AMBIENT, INSTALL A CONTINUOUS UNBROKEN
VAPOR BARRIER.
F. PLENUMS AND DUCTS REQUIRING INSULATION:
1. CONCEALED SUPPLY AIR.
2. CONCEALED AND EXPOSED OUTDOOR AIR.
3. CONCEALED AND EXPOSED RETURN AIR LOCATED IN NONCONDITIONED SPACE.
3.2 DUCT AND PLENUM INSULATION SCHEDULE
RETAIN " ONE OF" OPTION IN PARAGRAPHS IN THIS ARTICLE TO ALLOW CONTRACTOR TO SELECT PIPING MATERIALS FROM
THOSE RETAINED.
A. CONCEALED DUCT INSULATION SHALL BE 1-1/2" THICK MINERAL -FIBER BLANKET WITH A 1.5-LB/CU. FT. NOMINAL
DENSITY.
3.3 HVAC PIPING INSULATION SCHEDULE
A. CONDENSATE PIPING: INSULATION SHALL BE 1 " THICK FLEXIBLE ELASTOMERIC.
B. REFRIGERANT PIPING: INSULATION SHALL BE 1 " THICK FLEXIBLE ELASTOMERIC.
END OF SECTION 230700
SECTION 233100 - HVAC DUCTS AND CASINGS
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE."
B. STRUCTURAL PERFORMANCE: DUCT HANGERS AND SUPPORTS SHALL WITHSTAND THE EFFECTS OF GRAVITY LOADS
AND STRESSES WITHIN LIMITS AND UNDER CONDITIONS DESCRIBED IN SMACNA'S "HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE".
C. COMPLY WITH NFPA 96 FOR DUCTS CONNECTED TO COMMERCIAL KITCHEN HOODS.
RELEASED IFCR CONSTRUCTION
5uuh;ezttn cnmiplanum with 311l1regwlmu ma _
m95tate and lmeal Endles
0tp at Cairemal
ntro
DATE: 03/07/18
Nick Mishler
2.2 DUCTS
A. GALVANIZED -STEEL SHEET: ASTM A 653/A 653M, AND A 924 WITH G90 HOT -DIP GALVANIZED COATING.
1. GALVANIZED COATING DESIGNATION: G90.
2. FINISHES FOR SURFACES EXPOSED TO VIEW: MILL PHOSPHATIZED. DUCTWORK SHALL BE CLEANED OF DEBRIS
AND OIL, THEN WIPED DOWN WITH VINEGAR OR OTHER SURFACE PREPARING CHEMICAL TO PREPARE DUCT
FOR PAINT.
B. JOINT AND SEAM TAPE, AND SEALANT: COMPLY WITH UL 181 A. PROVIDE POLYMERIC RUBBER TYPE SEALANT FOR
USE ON BOTH INTERIOR LOCATED DUCTWORK AND DUCTWORK EXPOSED TO OUTDOOR CONDITIONS. SEALER
SHALL HAVE HIGH BONDING STRENGTH FOR SURE, FIRST TIME SEALING OF JOINTS IN LOW, MEDIUM, AND HIGH
PRESSURE DUCT SYSTEMS. SEALER SHALL BE HIGH IN SOLID CONTENT. PROVIDE A TWO PART TAPE SEALING SYSTEM,
CONSISTING OF WOVEN FIBER TAPE IMPREGNATED WITH A GYPSUM MINERAL COMPOUND, AND A MODIFIED
ACRYLIC/SILICONE ACTIVATOR THAT REACTS EXOTHERMICALLY WITH THE TAPE. TWO PART TAPE SEALING SYSTEM
MUST BE RATED FOR BOTH INDOOR AND OUTDOOR APPLICATION. TAPE SHALL NOT CONTAIN ASBESTOS.
C. METAL DUCT FABRICATION: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE."
2.3 ACCESSORIES
A. VOLUME DAMPERS AND CONTROL DAMPERS: SINGLE -BLADE AND MULTIPLE OPPOSED -BLADE DAMPERS, STANDARD
LEAKAGE RATING, AND SUITABLE FOR HORIZONTAL OR VERTICAL APPLICATIONS; FACTORY FABRICATED AND
COMPLETE WITH REQUIRED HARDWARE AND ACCESSORIES.
1. ROUND VOLUME DAMPERS: PROVIDE MINIMUM 20 GAUGE GALVANIZED STEEL FRAME AND BLADES, MINIMUM
3/8" SQUARE STEEL AXLE, MOLDED SYNTHETIC BEARINGS, WITH LOCKING POSITION REGULATOR. REGULATOR
SHALL BE POSITIONED WITH SHEET METAL BRACKET BEYOND DUCT COVERING. WHERE POSITIONING REGULATOR
IS NOT ACCESSIBLE, PROVIDE COUPLING AND EXTENSION ROD WITH REGULATOR FOR CEILING OR WALL
INSTALLATION, AS REQUIRED.
2. RECTANGULAR VOLUME DAMPERS: PROVIDE MINIMUM 16 GAUGE GALVANIZED STEEL CHANNEL FRAME, 16
GAUGE GALVANIZED STEEL BLADES, MINIMUM '/2" HEXAGONAL AXLE, BOLDED SYNTHETIC BEARINGS, WITH 3/8"
SQUARE PLATED STEEL CONTROL SHAFT. LINKAGES SHALL BE CONCEALED IN THE FRAME. OPERATING SHAFT
SHALL EXTEND BEYOND FRAME AND DUCT TO A LOCKING QUADRANT WITH ADJUSTABLE LEVER. MAXIMUM
BLADE WIDTH SHALL NOT EXCEED 6".
B. FLEXIBLE DUCT CONNECTORS: FLAME -RETARDED OR NONCOMBUSTIBLE FABRICS, COATINGS, AND ADHESIVES
COMPLYING WITH UL 181, CLASS 1. CONNECTOR TO BE 30 OUNCE, NEOPRENE COATED, FIBERGLASS FABRIC.
C. FLEXIBLE DUCTS: FACTORY ASSEMBLED, UL 181, CLASS 1, WITH 1-1/2-INCH THICK (R-5 MIN.), 1 PCF FIBERGLASS
INSULATION AND REINFORCED OUTER PROTECTIVE COVER/VAPOR BARRIER. FLEXIBLE DUCT SHALL MEET NFPA 90A
WITH FLAME SPREAD UNDER 25, SMOKE DEVELOPED UNDER 50, AND SHALL BE RATED FOR MINIMUM 2-INCH WG
PRESSURE AND 0 TO 250OF TEMPERATURE. PROVIDE SCREW -OPERATED METAL ADJUSTABLE CLAMPING DEVICES. USE
TWIST -LOCK CONICAL TAP COLLARS AT CONNECTIONS INTO SHEET METAL DUCTWORK. MAXIMUM EXTENDED
LENGTH OF FLEXIBLE DUCT SHALL NOT EXCEED 5 FEET.
D. TURNING VANES: PROVIDE FABRICATED TURNING VANES AND VANE RUNNERS, CONSTRUCTED IN ACCORDANCE
WITH SMACNA "HVAC DUCT CONSTRUCTION STANDARDS". PROVIDE TURNING VANES CONSTRUCTED OF CURVED
BLADES, SUPPORTED WITH BARS PERPENDICULAR TO BLADES, AND SET INTO SIDE STRIPS SUITABLE FOR MOUNTING IN
DUCTWORK. FOLLOW SMACNA GUIDELINES FOR SPACING SUPPORT, AND CONSTRUCTION. ALL BLADES SHALL BE
DOUBLE THICKNESS AIRFOIL TYPE.
E. BIRD SCREENS AND FRAMES: PROVIDE BIRD SCREENS THAT CONFORM TO ASTM E 2016, NO. 2 MESH, ALUMINUM OR
STAINLESS STEEL. PROVIDE "MEDIUM -LIGHT" RATED ALUMINUM SCREENS. PROVIDE "LIGHT" RATES STAINLESS STEEL
SCREENS.
F. DUCT -MOUNTED ACCESS DOORS: FABRICATE ACCESS PANELS ACCORDING TO SMACNA'S "HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE"; FIGURES 2-10, "DUCT ACCESS DOORS AND PANELS," AND 2-11,
"ACCESS PANELS - ROUND DUCT."
PART 3 - EXECUTION
3.1 INSTALLATION
A. INSTALL DUCTWORK, ACCESSORIES, AND SUPPORTS ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE" UNLESS OTHERWISE INDICATED.
B. SEAL DUCTS TO THE FOLLOWING SEAL CLASSES ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE": 1-INCH WG, SEAL CLASS A.
C. CONCEAL DUCTS FROM VIEW IN FINISHED AND OCCUPIED SPACES.
D. AVOID PASSING THROUGH OR ABOVE ELECTRICAL EQUIPMENT SPACES AND ENCLOSURES.
E. CLEAN DUCT SYSTEMS BEFORE TESTING, ADJUSTING, AND BALANCING.
3.2 TESTING, ADJUSTING, AND BALANCING
A. BALANCE AIRFLOW WITHIN DISTRIBUTION SYSTEMS, INCLUDING SUBMAINS, BRANCHES, AND TERMINALS TO
INDICATED QUANTITIES PER SPECIFICATIONS.
END OF SECTION 233100
SECTION 233713 - DIFFUSERS, REGISTERS, AND GRILLES
PART1- GENERAL
1.1 SECTION REQUIREMENTS
A. SUBMITTALS:
1. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED, INCLUDING COLOR CHARTS FOR FACTORY
FINISHES.
PART 2 - PRODUCTS
2.1 DIFFUSERS, REGISTERS, AND GRILLES:
A. REFER TO SCHEDULES FOR FINISH TYPE, COLOR, MATERIAL, AND MOUNTING.
PART 3 - EXECUTION
3.1 INSTALLATION
A. INSTALL DIFFUSERS, REGISTERS, AND GRILLES LEVEL AND PLUMB.
B. CEILING -MOUNTED OUTLETS AND INLETS: DRAWINGS INDICATE GENERAL ARRANGEMENT OF DUCTS, FITTINGS, AND
ACCESSORIES. MAKE FINAL LOCATIONS WHERE INDICATED, AS MUCH AS PRACTICAL. FOR UNITS INSTALLED IN
LAY -IN CEILING PANELS, LOCATE UNITS IN THE CENTER OF PANEL UNLESS OTHERWISE INDICATED. WHERE
ARCHITECTURAL FEATURES OR OTHER ITEMS CONFLICT WITH INSTALLATION, NOTIFY ARCHITECT FOR A
DETERMINATION OF FINAL LOCATION.
C. AFTER INSTALLATION, ADJUST DIFFUSERS, REGISTERS, AND GRILLES TO AIR PATTERNS INDICATED, OR AS DIRECTED,
BEFORE STARTING AIR BALANCING.
END OF SECTION 233713
SECTION 237413 - PACKAGED ROOFTOP UNITS
1.1 SUMMARY
A. THIS SECTION INCLUDES PACKAGED, ROOFTOP UNITS WITH THE FOLLOWING COMPONENTS AND ACCESSORIES:
1. DIRECT -EXPANSION COOLING.
2. ELECTRIC RESISTANCE HEATING.
3. ECONOMIZER OUTDOOR -AND RETURN -AIR DAMPER SECTION.
4. INTEGRAL, SPACE TEMPERATURE CONTROLS.
5. ROOF CURBS.
1.2 SECTION REQUIREMENTS
A. SUBMITTALS:
1. PRODUCT DATA: INCLUDE MANUFACTURER'S TECHNICAL DATA FOR EACH RTU, INCLUDING RATED CAPACITIES,
DIMENSIONS, REQUIRED CLEARANCES, CHARACTERISTICS, FURNISHED SPECIALTIES, AND ACCESSORIES.
PART 2 - PRODUCTS
2.1 CASING
A. GENERAL FABRICATION REQUIREMENTS FOR CASINGS: FORMED AND REINFORCED INSULATED PANELS, FABRICATED
TO ALLOW REMOVAL FOR ACCESS TO INTERNAL PARTS AND COMPONENTS, WITH JOINTS BETWEEN SECTIONS
SEALED.
B. EXTERIOR CASING MATERIAL: GALVANIZED STEEL WITH FACTORY -PAINTED FINISH, WITH PITCHED ROOF PANELS AND
KNOCKOUTS WITH GROMMET SEALS FOR ELECTRICAL AND PIPING CONNECTIONS AND LIFTING LUGS.
1. CASING THICKNESS: 16 G/'HUGE::: FlilCl(.
C. CASING INSULATION AND ADHESIVE: COMPLY WITH NFPA 90A.
1. MATERIALS: ASTM C 1071,TYPE I.
2. THICKNESS: 1/2 INCH
3. LINER MATERIALS SHALL HAVE AIR -STREAM SURFACE INSULATED WITH A MINIMUM 1/2-IN. THICK, MINIMUM 1 1/2
LB DENSITY, FLEXIBLE FIBERGLASS INSULATION BONDED WITH A PHENOLIC BINDER, NEOPRENE COATED ON THE
AIR SIDE.
4. LINER ADHESIVE: COMPLY WITH ASTM C 916, TYPE I.
D. UNIT SHALL HAVE A THRU-THE-BASE GAS AND ELECTRICAL CONNECTIONS.
2.2 FANS
OPTION A OR B:
A. DIRECT -DRIVEN SUPPLY -AIR FANS: DOUBLE WIDTH, BACKWARD INCLINED, CENTRIFUGAL; WITH PERMANENTLY
LUBRICATED, MOTOR RESILIENTLY MOUNTED IN THE FAN INLET. ALUMINUM OR PAINTED -STEEL WHEELS, AND
GALVANIZED- OR PAINTED -STEEL FAN SCROLLS.
B. BELT -DRIVEN SUPPLY -AIR FANS: DOUBLE WIDTH, FORWARD CURVED, CENTRIFUGAL; WITH PERMANENTLY
LUBRICATED, SINGLE -SPEED MOTOR INSTALLED ON AN ADJUSTABLE FAN BASE RESILIENTLY MOUNTED IN THE CASING.
ALUMINUM OR PAINTED -STEEL WHEELS, AND GALVANIZED- OR PAINTED -STEEL FAN SCROLLS.
C. CONDENSER -COIL FAN: DIRECT DRIVE, PROPELLER, MOUNTED ON SHAFT OF PERMANENTLY LUBRICATED MOTOR
WITH THERMAL OVERLOAD PROTECTION.
D. POWER EXHAUST: FORWARD CURVED, SHAFT MOUNTED ON PERMANENTLY LUBRICATED MOTOR.
2.3 COILS
A. SUPPLY -AIR REFRIGERANT COIL:
1. ALUMINUM -PLATE FIN AND SEAMLESS INTERNALLY GROOVED COPPER TUBE IN STEEL CASING WITH
EQUALIZING -TYPE VERTICAL DISTRIBUTOR.
2. POLYMER STRIP SHALL PREVENT ALL COPPER COIL FROM CONTACTING STEEL COIL FRAME OR CONDENSATE
PAN.
3. CATHODIC EPDXY COATING.
4. CONDENSATE DRAIN PAN: GALVANIZED STEEL WITH CORROSION -RESISTANT COATING FORMED WITH PITCH
AND DRAIN CONNECTIONS.
B. OUTDOOR -AIR REFRIGERANT COIL:
1. ALUMINUM -PLATE FIN AND SEAMLESS INTERNALLY GROOVED COPPER TUBE IN STEEL CASING WITH
EQUALIZING -TYPE VERTICAL DISTRIBUTOR.
2. POLYMER STRIP SHALL PREVENT ALL COPPER COIL FROM CONTACTING STEEL COIL FRAME OR CONDENSATE
PAN.
3. CATHODIC EPDXY COATING.
C. HOT -GAS REHEAT REFRIGERANT COIL (OPTIONAL):
1. ALUMINUM -PLATE FIN AND SEAMLESS INTERNALLY GROOVED COPPER TUBE IN STEEL CASING WITH
EQUALIZING -TYPE VERTICAL DISTRIBUTOR.
2. POLYMER STRIP SHALL PREVENT ALL COPPER COIL FROM CONTACTING STEEL COIL FRAME OR CONDENSATE
PAN.
3. CATHODIC EPDXY COATING.
2.4 REFRIGERANT CIRCUIT COMPONENTS
A. NUMBER OF REFRIGERANT CIRCUITS: TWO
B. COMPRESSOR: HERMETIC, SCROLL, MOUNTED ON VIBRATION ISOLATORS; WITH INTERNAL OVERCURRENT AND
HIGH -TEMPERATURE PROTECTION, INTERNAL PRESSURE RELIEF AND CRANKCASE HEATER.
C. REFRIGERATION SPECIALTIES:
1. REFRIGERANT: R-410A
2. EXPANSION VALVE WITH REPLACEABLE THERMOSTATIC ELEMENT.
3. REFRIGERANT FILTER/DRYER.
4. MANUAL -RESET HIGH-PRESSURE SAFETY SWITCH.
5. AUTOMATIC -RESET LOW-PRESSURE SAFETY SWITCH.
6. MINIMUM OFF -TIME RELAY.
7. AUTOMATIC -RESET COMPRESSOR MOTOR THERMAL OVERLOAD.
8. BRASS SERVICE VALVES INSTALLED IN COMPRESSOR SUCTION AND LIQUID LINES.
9. LOW -AMBIENT KIT HIGH-PRESSURE SENSOR.
10. HOT -GAS REHEAT SOLENOID VALVE WITH A REPLACEABLE MAGNETIC COIL.
2.5 AIR FILTRATION
A. PROVIDE 2" THROW -AWAY FIBERGLASS FILTERS.
2.7 DAMPERS
A. OUTDOOR AND RETURN AIR MIXING DAMPERS: PARALLEL OR OPPOSED -BLADE GALVANIZED -STEEL DAMPERS
MECHANICALLY FASTENED TO CADMIUM PLATED FOR GALVANIZED -STEEL OPERATING ROD IN REINFORCED
CABINET. CONNECT OPERATING RODS WITH COMMON LINKAGE AND INTERCONNECT LINKAGES SO DAMPERS
OPERATE SIMULTANEOUSLY.
1. DAMPER MOTOR: MODULATING WITH ADJUSTABLE MINIMUM POSITION.
2. RELIEF AIR DAMPER: GRAVITY ACTUATED, WITH BIRD SCREEN AND HOOD.
2.8 ELECTRICAL POWER CONNECTION
A. PROVIDE FOR SINGLE CONNECTION OF POWER TO UNIT WITH UNIT -MOUNTED DISCONNECT SWITCH ACCESSIBLE
FROM OUTSIDE UNIT AND CONTROL -CIRCUIT TRANSFORMER WITH BUILT-IN OVERCURRENT PROTECTION.
2.9 CONTROLS
A. BASIC UNIT CONTROLS:
1. CONTROL -VOLTAGE TRANSFORMER.
2. WALL -MOUNTED THERMOSTAT OR SENSOR WITH THE FOLLOWING FEATURES:
a.HEAT-COOL-OFF SWITCH.
b. FAN ON -AUTO SWITCH.
c. FAN -SPEED SWITCH.
d. AUTOMATIC CHANGEOVER.
e. ADJUSTABLE DEADBAND.
f. EXPOSED SET POINT.
g.EXPOSED INDICATION.
h. DEGREE F INDICATION.
i. UNOCCUPIED -PERIOD -OVERRIDE PUSH BUTTON.
j. DATA ENTRY AND ACCESS PORT TO INPUT TEMPERATURE AND HUMIDITY SET POINTS, OCCUPIED AND
UNOCCUPIED PERIODS, AND OUTPUT ROOM TEMPERATURE AND HUMIDITY, SUPPLY -AIR TEMPERATURE,
OPERATING MODE, AND STATUS.
3. WALL -MOUNTED HUMIDISTAT OR SENSOR WITH THE FOLLOWING FEATURES:
a.EXPOSED SET POINT.
b. EXPOSED INDICATION.
4. REMOTE WALL -MOUNTED ANNUNCIATOR PANEL WITH KEYED ACCESS FOR EACH UNIT:
a.LIGHTS TO INDICATE POWER ON, UNIT ALARM OR FAILURE, SMOKE DETECTION.
B. DDC CONTROLLER:
2. SAFETY CONTROL OPERATION:
a. SMOKE DETECTORS: STOP FAN AND CLOSE OUTDOOR -AIR DAMPER IF SMOKE IS DETECTED. PROVIDE
ADDITIONAL CONTACTS FOR ALARM INTERFACE TO FIRE ALARM CONTROL PANEL.
b. FIRE ALARM CONTROL PANEL INTERFACE WHERE APPLICABLE.
c. LOW -DISCHARGE TEMPERATURE: STOP FAN AND CLOSE OUTDOOR -AIR DAMPER IF SUPPLY AIR TEMPERATURE
IS LESS THAN 40°F.
RETAIN FIRST SUBPARAGRAPH BELOW FOR AIR-TO-AIR HEAT -PUMP FEATURE.
d.DEFROST CONTROL FOR CONDENSER COIL: PRESSURE DIFFERENTIAL SWITCH TO INITIATE DEFROST SEQUENCE.
3. UNIT SHALL BE CAPABLE OF DIRECT COMMUNICATION WITH GENERIC OPEN PROTOCOL SUCH AS BACNET
MS/TP, LONTALK, OR MODUS. THIS WILL ALLOW THE UNIT TO INTEGRATE WITH A FACILITY ENERGY MANAGEMENT
SYSTEM.
4. SCHEDULED OPERATION: OCCUPIED AND UNOCCUPIED PERIODS ON SEVEN-DAY CLOCK WITH A MINIMUM OF
FOUR PROGRAMMABLE PERIODS PER DAY.
5. UNOCCUPIED PERIOD:
a. HEATING SETBACK: 10°F.
b. COOLING SETBACK: SYSTEM OFF.
c. OVERRIDE OPERATION: TWO HOURS.
6. SUPPLY FAN OPERATION:
a. OCCUPIED PERIODS: RUN FAN CONTINUOUSLY.
b. UNOCCUPIED PERIODS: CYCLE FAN TO MAINTAIN SETBACK TEMPERATURE.
7. REFRIGERANT CIRCUIT OPERATION:
a. OCCUPIED PERIODS: CYCLE OR STAGE COMPRESSORS, AND OPERATE HOT -GAS BYPASS TO MATCH
COMPRESSOR OUTPUT TO COOLING LOAD TO MAINTAIN ROOM TEMPERATURE AND HUMIDITY. CYCLE
CONDENSER FANS TO MAINTAIN MAXIMUM HOT -GAS PRESSURE. OPERATE LOW -AMBIENT CONTROL KIT TO
MAINTAIN MINIMUM HOT -GAS PRESSURE.
b. UNOCCUPIED PERIODS: CYCLE COMPRESSORS AND CONDENSER FANS FOR HEATING TO MAINTAIN
SETBACK TEMPERATURE.
8. HOT -GAS REHEAT -COIL OPERATION (OPTIONAL):
a. OCCUPIED PERIODS: HUMIDISTAT OPENS HOT -GAS VALVE TO PROVIDE HOT -GAS REHEAT, AND CYCLES
COMPRESSOR.
b. UNOCCUPIED PERIODS: REHEAT NOT REQUIRED.
9. GAS FURNACE OPERATION:
a. OCCUPIED PERIODS: STAGE BURNER TO MAINTAIN ROOM TEMPERATURE.
b. UNOCCUPIED PERIODS: CYCLE BURNER TO MAINTAIN SETBACK TEMPERATURE.
10. FIXED MINIMUM OUTDOOR -AIR DAMPER OPERATION:
a. OCCUPIED PERIODS: OPEN TO 25 PERCENT.
b. UNOCCUPIED PERIODS: CLOSE THE OUTDOOR -AIR DAMPER.
11. ECONOMIZER OUTDOOR -AIR DAMPER OPERATION:
a. OCCUPIED PERIODS: OPEN TO 25 PERCENT FIXED MINIMUM INTAKE, AND MAXIMUM 100 PERCENT OF THE
FAN CAPACITY TO COMPLY WITH ASHRAE CYCLE II. CONTROLLER SHALL PERMIT AIR -SIDE ECONOMIZER
OPERATION WHEN OUTDOOR AIR IS LESS THAN 60 ° F. USE MIXED -AIR TEMPERATURE AND SELECT BETWEEN
OUTDOOR -AIR AND RETURN -AIR ENTHALPY TO ADJUST MIXING DAMPERS DURING ECONOMIZER CYCLE
OPERATION, LOCK OUT COOLING.
b. UNOCCUPIED PERIODS: CLOSE OUTDOOR -AIR DAMPER AND OPEN RETURN -AIR DAMPER.
2.10 ACCESSORIES
A. DUPLEX, 115-V, GROUND -FAULT -INTERRUPTER OUTLET WITH 15-A OVERCURRENT PROTECTION. INCLUDE
TRANSFORMER IF REQUIRED.
B. LOW -AMBIENT KIT STAGED DOWN TO 0°F.
C. FILTER DIFFERENTIAL PRESSURE SWITCH WITH SENSOR TUBING ON EITHER SIDE OF FILTER. SET FOR FINAL FILTER
PRESSURE LOSS.
D. HAIL GUARDS OF GALVANIZED STEEL, PAINTED TO MATCH CASING.
E. DUCT MOUNTED SMOKE DETECTOR IN RETURN AIR STREAM CAPABLE OF SHUTTING DOWN THE UNIT IN THE PRESENCE
OF SMOKE DETECTION.
2.11 ROOF CURBS
A. MATERIALS: GALVANIZED STEEL WITH CORROSION -PROTECTION COATING, WATERTIGHT GASKETS, AND
FACTORY -INSTALLED WOOD NAILER; COMPLYING WITH N RCA STANDARDS.
1. CURB INSULATION AND ADHESIVE: COMPLY WITH NFPA 90A OR NFPA 90B.
a. MATERIALS: ASTM C 1071,TYPE I OR II.
b. THICKNESS: 1-1/2 INCHES.
2. APPLICATION: FACTORY APPLIED WITH ADHESIVE AND MECHANICAL FASTENERS TO THE INTERNAL SURFACE OF
CURB.
a. LINER ADHESIVE: COMPLY WITH ASTM C 916, TYPE I.
b. MECHANICAL FASTENERS: GALVANIZED STEEL, SUITABLE FOR ADHESIVE ATTACHMENT, MECHANICAL
ATTACHMENT, OR WELDING ATTACHMENT TO DUCT WITHOUT DAMAGING LINER WHEN APPLIED AS
RECOMMENDED BY MANUFACTURER AND WITHOUT CAUSING LEAKAGE IN CABINET.
c. LINER MATERIALSSHALL HAVE AIR -STREAM SURFACE INSULATED WITH A MINIMUM 1/2-IN. THICK, MINIMUM 1
1/2 LB DENSITY, FLEXIBLE FIBERGLASS INSULATION BONDED WITH A PHENOLIC BINDER, NEOPRENE COATED
ON THE AIR SIDE.
d. LINER ADHESIVE: COMPLY WITH ASTM C 916, TYPE I.
B. CURB HEIGHT: 14 INCHES TYPICAL. PROVIDE 24 INCH CURB IN AREAS WITH EXPECTED HEAVY SNOWFALL.
• Ln Ln O I-
> Ol c-I � �
N N � rl_
M 00 00
. .� =3 O 00 00
> cn .-
�O
L vi lfl lD
t]A �
Ln a) Cu
Ln E +1 L
00 =5
O
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE+ PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
W
75;G
L.ii
W
N
\
O
=
0
5�
G
Z)
Co
0
2
Oo
Z)o
J
Q
zm0
J
N
M
(Dw
W
JUG
2�
'
QQ
�z
�o
V)
O'�'a
C)
zo
M�z
�m
W
Q
U
J
W
(D~
cn
U
<
�
�
�
w
M
Sao
<
<q
00
rl
U L
rl
PROJECT NUMBER:
W P GO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
SPECIFICATIONS
MECHANICAL
SHEET:
M3o2
SPECIFICATIONS -DIVISION 23 - HVAC (CONTINUED)
PART 3 - EXECUTION
3.1 EXAMINATION
A. EXAMINE SUBSTRATES, AREAS, AND CONDITIONS, WITH INSTALLER PRESENT, FOR COMPLIANCE WITH REQUIREMENTS
FOR INSTALLATION TOLERANCES AND OTHER CONDITIONS AFFECTING PERFORMANCE OF RTUS.
B. EXAMINE ROUGHING -IN FOR RTUS TO VERIFY ACTUAL LOCATIONS OF PIPING AND DUCT CONNECTIONS BEFORE
EQUIPMENT INSTALLATION.
C. EXAMINE ROOFS FOR SUITABLE CONDITIONS WHERE RTUS WILL BE INSTALLED.
D. PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED.
3.2 INSTALLATION
A. ROOF CURB: INSTALL ON ROOF STRUCTURE, LEVEL AND SECURE. INSTALL RTUS ON CURBS AND COORDINATE ROOF
PENETRATIONS AND FLASHING WITH ROOF CONSTRUCTION. RTUS TO UPPER CURB RAIL, AND SECURE CURB BASE TO
ROOF FRAMING OR CONCRETE BASE WITH ANCHOR BOLTS.
3.3 CONNECTIONS
A. . THE FOLLOWING ARE SPECIFIC CONNECTION REQUIREMENTS:
1. INSTALL DUCTS TO TERMINATION AT TOP OF ROOF CURB.
2. REMOVE ROOF DECKING ONLY AS REQUIRED FOR PASSAGE OF DUCTS. DO NOT CUT OUT DECKING UNDER
ENTIRE ROOF CURB.
3.4 COORDINATION
A. CONTRACTOR TO COORDINATE WITH KITCHEN EQUIPMENT SUPPLIER TO ENSURE THAT THE RTUS ARE COORDINATED
WITH THE KITCHEN EQUIPMENT, PARTICULARLY THE EXHAUST HOODS AND THE MAKE-UP AIR UNIT, TO PROPERLY
PRESSURIZE THE BUILDING/SPACE.
B. CONTRACTOR TO ENSURE THAT ALL THERMOSTATS AND SENSORS ARE COMPATIBLE WITH THE RTU CONTROLS.
3.5 FIELD QUALITY CONTROL
A. MANUFACTURER'S FIELD SERVICE: ENGAGE A FACTORY -AUTHORIZED SERVICE REPRESENTATIVE TO INSPECT, TEST,
AND ADJUST COMPONENTS, ASSEMBLIES, AND EQUIPMENT INSTALLATIONS, INCLUDING CONNECTIONS. REPORT
RESULTS IN WRITING.
B. PERFORM TESTS AND INSPECTIONS AND PREPARE TEST REPORTS.
1. MANUFACTURER'S FIELD SERVICE: ENGAGE A FACTORY -AUTHORIZED SERVICE REPRESENTATIVE TO INSPECT
COMPONENTS, ASSEMBLIES, AND EQUIPMENT INSTALLATIONS, INCLUDING CONNECTIONS, AND TO ASSIST IN
TESTING. REPORT RESULTS IN WRITING.
C. TESTSAND INSPECTIONS:
1. AFTER INSTALLING RTUS AND AFTER ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED, TEST UNITS FOR COMPLIANCE
WITH REQUIREMENTS.
2. OPERATIONAL TEST: AFTER ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED, START UNITS TO CONFIRM PROPER
MOTOR ROTATION AND UNIT OPERATION.
3. TEST AND ADJUST CONTROLS AND SAFETIES. REPLACE DAMAGED AND MALFUNCTIONING CONTROLS AND
EQUIPMENT.
D. REMOVE AND REPLACE MALFUNCTIONING UNITS AND RETEST AS SPECIFIED ABOVE.
3.6 STARTUP SERVICE
A. ENGAGE A FACTORY -AUTHORIZED SERVICE REPRESENTATIVE TO PERFORM STARTUP SERVICE.
B. COMPLETE INSTALLATION AND STARTUP CHECKS ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS AND
DO THE FOLLOWING:
1. INSPECT FOR VISIBLE DAMAGE TO UNIT CASING, FURNACE COMBUSTION CHAMBER, COMPRESSOR, COILS, AND
FANS.
2. VERIFY THAT LABELS ARE CLEARLY VISIBLE, CLEARANCES HAVE BEEN PROVIDED FOR SERVICING, CONTROLS ARE
CONNECTED AND OPERABLE, AND FILTERS ARE INSTALLED.
3. CLEAN CONDENSER COIL AND FURNACE AND INSPECT FOR CONSTRUCTION DEBRIS.
4. REMOVE PACKING FROM VIBRATION ISOLATORS.
5. VERIFY LUBRICATION ON FAN AND MOTOR BEARINGS.
6. INSPECT FAN -WHEEL ROTATION FOR MOVEMENT INCORRECT DIRECTION WITHOUT VIBRATION AND BINDING.
7. ADJUST FAN BELTS TO PROPER ALIGNMENT AND TENSION.
8. START UNIT ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS.
a. INSPECT AND RECORD PERFORMANCE OF INTERLOCKS AND PROTECTIVE DEVICES; VERIFY SEQUENCES.
10. OPERATE UNIT FOR AN INITIAL PERIOD AS RECOMMENDED OR REQUIRED BY MANUFACTURER.
11. PERFORM THE FOLLOWING OPERATIONS FOR BOTH MINIMUM AND MAXIMUM FIRING. ADJUST BURNER FOR
PEAK EFFICIENCY.
a. MEASURE GAS PRESSURE ON MANIFOLD.
b. INSPECT OPERATION OF POWER VENTS.
c. MEASURE SUPPLY -AIR TEMPERATURE AND VOLUME WHEN BURNER IS AT MAXIMUM FIRING RATE AND WHEN
BURNER IS OFF. CALCULATE USEFUL HEAT TO SUPPLY AIR.
20. ADJUST AND INSPECT HIGH -TEMPERATURE LIMITS.
21. INSPECT OUTDOOR -AIR DAMPERS FOR PROPER STROKE AND INTERLOCK WITH RETURN -AIR DAMPERS.
22. INSPECT CONTROLS FOR CORRECT SEQUENCING OF HEATING, MIXING DAMPERS, REFRIGERATION, AND
NORMAL AND EMERGENCY SHUTDOWN.
23. SIMULATE MAXIMUM COOLING DEMAND AND INSPECT THE FOLLOWING:
a. COMPRESSOR REFRIGERANT SUCTION AND HOT -GAS PRESSURES.
b. SHORT CIRCUITING OF AIR THROUGH CONDENSER COIL OR FROM CONDENSER FANS TO OUTDOOR -AIR
INTAKE.
27. VERIFY OPERATION OF REMOTE PANEL INCLUDING PILOT -LIGHT OPERATION AND FAILURE MODES. INSPECT THE
FOLLOWING:
a. HIGH -TEMPERATURE LIMIT ON HEAT EXCHANGER.
b. LOW -TEMPERATURE SAFETY OPERATION.
c. FILTER HIGH-PRESSURE DIFFERENTIAL ALARM.
d.ECONOMIZER TO MINIMUM OUTDOOR -AIR CHANGEOVER.
e. RELIEF -AIR FAN OPERATION.
f. SMOKE ALARMS.
28. AFTER STARTUP AND PERFORMANCE TESTING AND PRIOR TO SUBSTANTIAL COMPLETION, REPLACE EXISTING
FILTERS WITH NEW FILTERS.
3.7 CLEANING AND ADJUSTING
A. OCCUPANCY ADJUSTMENTS: WHEN REQUESTED WITHIN 12 MONTHS OF DATE OF SUBSTANTIAL COMPLETION,
PROVIDE ON -SITE ASSISTANCE IN ADJUSTING SYSTEM TO SUIT ACTUAL OCCUPIED CONDITIONS. PROVIDE UP TO
TWO VISITS TO SITE DURING OTHER -THAN -NORMAL OCCUPANCY HOURS FOR THIS PURPOSE.
B. AFTER COMPLETING SYSTEM INSTALLATION AND TESTING, ADJUSTING, AND BALANCING RTU AND AIR -DISTRIBUTION
SYSTEMS, CLEAN FILTER HOUSINGS AND INSTALL NEW FILTERS.
19
a
v
0
� 0)
M 00 00
n rl_
> N •—
C: TH T__l
10
ta vi l0 l0
qp =5
Ln
Ln
00 :3
0
U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE+ PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
5W
G
L.ii
W
N
\
O
=
0
5�
G
Z)
0
Sm
Oo
Z)0
J
Q
zm0
J
N
M
�w
W
J
U
'
QQ
�z
�o
V)
Q
0
LU
�_
Q
z
00
M
�
Q
z
�
Co
W
J
z
UocWc
Q
al
G
=a
cn
W
�
�<
<o
rl
U L
rl
PROJECT NUMBER:
WPGO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
SPECIFICATIONS
MECHANICAL
610: 15
M33
RELEASED IFCR CONSTRUCTION
5uuh;ezttn cnmiplanum with 311l1regwlmu ma _
m95tate and lmeal Endles
0tp at Cairemal
ntro
DATE: 03/07/18
Nick Mishler
a
N
O
V1
r-
o
r
RELEASED IFCR CONSTRUCTION
5uud9ezttn cnmplanum with 311l1ru9ulmtima _
n9 State and lmeal Endes
ntro
DATE: 03/07/18
Nick Mishler
LUMINAIRE SCHEDULE
TYPE
DESCRIPTION
MANUFACTURER
MODEL
HOUSING /
MOUNTING
LAMP TYPE
BALLAST / DRIVER
COMMENTS
VOLTS
INPUT WATTS
R1
COMBO LIGHT/FAN
NUTONE
769RL
RECESSED
INCANDESCENT
ELECTRONIC
-
120
100
R2
LED TROFFER
CREE
ZR22-32L-40K-1 OV
RECESSED
LED ENGINE
LED DRIVER
-
120
40
EX1
COMBINATION EMERGENCY EXIT SIGN
LITHONIA
LHQM-SW 3R-HO
UNIVERSAL
WITH UNIT
N/A
WITH EMERGENCY BATTERY PACK
120
3.3
EM1
EMERGENCY BATTERY PACK WITH DUAL HEADS
NAVILITE
N1 W H
W ALL
WITH UNIT
N/A
WITH EMERGENCY BATTERY PACK
120
10.8
NOTES:
1.) ELECTRICAL CONTRACTOR SHALL PROVIDE LIGHTING FIXTURES ABOVE. ANY LIGHTING EQUALS SHALL BE SUBMITTED TO ARCHITECT FOR REVIEW AND APPROVAL.
PANEL NAME
A (EXISTING)
I VOLTAGE
1 208
1 PHASE
3
1 WIRE
4
LOCATION: REAR
SOURCE: (E) TENANT DISCONNECI
I
1200AMCB
#
K
L
R
M
X
H
C
BREAKER
DESCRIPTION
KVA/PHASE
DESCRIPTION
BREAKER
K
L
R
M
X
H
C#
AMP
POLE
A
B
C
AMP
POLE
1
30
2
SPARE
6.1
1hlllllllllllll
RTU -1 (HACR RATED BREAKER)
60
3
6.1
2
3
6.1
6.1
4
5
0.2
20
1
RESTROOM LIGHTING
................................
6.3
6.1
6
7
0.3
2 0
1
TENANT SPACE - LIGHTING
0.3
.,.,.,
S PARE
2 0
1
8
9
0.4
2 0
1
SHOW WINDOW RECEPTACLES
.4
0.
S PARE
2 0
1
1 0
11
1.1
15
3
EWH-1 - ELECTRIC WATER HEATER
1.1
SPARE
20
1
12
13
1.1
1...1
SPARE
40
2
14
15
1.1
1.,.,1
16
17
1 0.2
1
1
L20
1
NIGHT LIGHTING EMERG FIXTURES
/
O .2
S PARE
2 0
1
1 8
19
0.4
20
1
RECEPTACLES
0.4
SPARE
20
1
20
21
20
1
SPARE
0.0))
SPARE
20
1
22
23
20
1
SPARE
................................
0.0
SPARE
20
1
24
25
20
1
SPARE
0.0
SPARE
20
1
26
27
20
1
SPARE
0.0
)))))))))))))))
SPARE
20
1
28
29
20
1
SPARE
0.0
SPARE
20
1
30
3 1
0.8
2 0
1
EX. AD RE PT. BELOW PNL'A'
QUAD C O
0.8
S PARE
2 0
1
3 2
33
20
1
SPARE
0.0
)))))))))))))))
SPARE
20
1
34
35
20
1
SPARE
0.0
SPARE
20
1
36
37
20
1
SPARE
0.0
SPARE
20
1
38
391
1
1
1
1
1
1
1 20
1 1
ISPARE
0.0
ii iiiiii
SPARE
20
1
I40
411
1
1
1
1
1
1
1 20
1 1
ISPARE
0.0
SPARE
1 20
1 1
1
1
42
TOTAL CONNECTED LOAD/PH
8.7
7.6
7.6
BREAKER NOTES
H = PROVIDE HID RATED BREAKER.
L = PROVIDE A BREAKER LOCK ON DEVICE
T = PROVIDE ASHUNT TRIP BREAKER.
G = PROVIDE A GFI BREAKER.
A= PROVIDE AN ARC FAULT CIRCUIT INTERRUPTER BREAKER.
0.01 0.71 1.61 0.01 3.31 0.01 18.31 TOTAL CONNECTED
LOAD
23.90
K = KITCHEN
DEMAND 65%
0.0
KVA
L = LITE
DEMAND 125%
0.9
KVA
R = RCPT
FIRST IOKVAAT 100% AND REMAINING AT 50%
1.6
KVA
M = MOTOR
DEMAND 100%
0.0
KVA
X = MISC
DEMAND 100%
3.3
KVA
COMMENTS
1. PROVIDE (2)#12,(1)#12GND,3/4"C FOR ALL BRANCH CCTS UNLESS STATED OTHERWISE.
2. PROVIDE HACR RATED BREAKERS ON ALL MOTOR LOADS.
3. PROVIDE LOCKING TYPE BREAKER FOR ALL LIFE SAFETY AND
NIGHT LIGHTING BRANCH CIRCUITS.
H = HEAT
I
IDEMAND 100% IF H>C, 0% IF H<C
0.0
KVA
C = COOL
I
IDEMAND 100% IF C>H, 0% IF C<H
18.3
KVA
TOTAL PANEL DEMAND =
TOTAL PANEL AMPS =
24.1
KVA
669
AMPS
ELECTRICAL - LIGHTING
1 /4" = Y-O"
ELECTRICAL - POWER
1 /4" = Y-0"
ELECTRICAL LEGEND
DETAIL
DESCRIPTION
DUPLEX RECEPTACLE
GFI
DUPLEX RECEPTACLE - GFCI
'OLGFI
DUPLEX RECEPTACLE - GFCI, ABOVE COUNTER
A-1
BRANCH CIRCUIT HOME -RUN WITH CIRCUIT NUMBER
Q
JUNCTION BOX
ELECTRICAL PANEL
DISCONNECT - NON FUSED
DISCONNECT - FUSED
O
2X2 LAY -IN TROFFER
El2X2
NIGHT LIGHT
❑❑
CEILING MOUNTED LIGHT/FAN COMBO FIXTURE
EMERGENCY BATTERY PACK AND DUAL HEADS
EXIT/EMERGENCY LIGHT
W/ BATTERY PACK AND DUAL HEADS
Q
WALL MOUNTED OCCUPANCY SENSOR
TOGGLE SWITCH
SINGLE POLE SWITCH WITH COVER PLATE
I GENERAL NOTES: I
A. ALL WORK TO COMPLY TO ALLSTATE, LOCAL, NEC, & NFPA CODES.
B. ELECTRICAL CONTRACTOR TO VISIT THE SITE PRIOR TO SUBMITTING A BID & INCLUDE IN THEIR BID ANY
ITEM ANY ITEMS NECESSARY FOR A COMPLETE & OPERATIONAL SYSTEM.
C. DRAWINGS ARE SCHEMATIC IN NATURE. ELECTRICAL CONTRACTOR IS TO ADD ANY ITEMS THAT ARE
REQUIRED FOR A COMPLETE & OPERATIONAL SYSTEM IN THEIR PROPOSAL.
D. ELECTRICAL CONTRACTOR IS TO COORDINATE THEIR INSTALLATION WITH THE OTHER TRADES. IF A
CONFLICT OCCURS AND IT IS DUE TO THE ELECTRICAL CONTRACTOR'S LACK OF COORDINATION, ALL
WORK INVOLVED IN RESOLVING THE CONFLICT WILL BE AT THE EXPENSE OF THE ELECTRICAL
CONTRACTOR.
E. ELECTRICAL CONTRACTOR TO FURNISH A TYPE WRITTEN PANEL SCHEDULE DESCRIBING EACH CIRCUIT
AND WHAT LOCATION IT CONTROLS PER NEC 408.4
CODED NOTES: O
1. PROVIDE SHOW WINDOW DUPLEX RECEPTACLE AT NO MORE THAN 18'' ABOVE WINDOW.
2. LANDLORD TO PROVIDE 2" PVC EMPTY CONDUIT STUBBED HIGH ON WALL INTO SPACE FOR
TELECOMMUNICATIONS WIRING FOR FUTURE TENANT.
3. EWH-1: 9.7 AMPS, 208V, 30 ELECTRIC WATER HEATER SUPPLIED BY PLUMBING CONTRACTOR. WIRED BY
EC. EC SHALL PROVIDE SWITCH FOR DISCONNECT MEANS. PROVIDE (3) # 12, # 12G IN 3/4" CONDUIT
FROM 15A/3P BREAKER IN PANEL'A'. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH
PLUMBING CONTRACTOR PRIOR TO ROUGH -IN. MAKE FINAL CONNECTIONS
4. EC SHALL INSTALL OCCUPANCY SENSOR WALL SWITCH TO CONTROL RESTROOM LIGHT/FAN COMBO
FIXTURE. SEE #3 DIAGRAM ON THIS DRAWING FOR WIRING. (LEVITON #OSS10-IDW OR EQUAL PROVIDE
FACE PLATE).
5. NEW RTU-1 TO REPLACE OLD ROOFTOP UNIT. EC SHALL COORDINATE WITH MECHANICAL
CONTRACTOR DEMOLITION OF OLD RTU. EC SHALL DE -ENERGIZE OLD UNIT AND REMOVE CONDUIT
AND CONDUCTORS BACK TO SOURCE. NEW RTU-1: 51 MCA, 208V/3PH. PROVIDE (3) # 6, # 1 OG IN 1"
CONDUIT FROM NEW 60/3P HACR BREAKER THROUGH FACTORY SUPPLIED DISC SWITCH TO UNIT. MAKE
FINAL CONNECTION.
ABBREVIATIONS
(A)
EXISTING TO BE ABANDONED
HPC
HIGH PRESSURE CONTACT SWITCH
(D)
EXISTING TO BE DEMOLISHED
HZ
HERTZ
(E)
EXISTING TO REMAIN
IG
ISOLATED GROUND
(R)
EXISTING TO BE RELOCATED
IMC
INTERMEDIATE METAL CONDUIT
A
AMPERE
KVA
KILOVOLT AMPERE
AF
AMP FUSED
KW
KILOWATT
AS
AMP SWITCH
LTG
LIGHTING OR LIGHT
AFF
ABOVE FINISHED FLOOR
MCA
MAXIMUM CURRENT AMPACITY
AWG
AMERICAN WIRE GAUGE
MCB
MAIN CIRCUIT BREAKER
C
CONDUIT
MDP
MAIN DISTRIBUTION PANEL
CB
CIRCUIT BREAKER
MLO
MAIN LUGS ONLY
CKT
CIRCUIT
MOCP
MAXIMUM OVERCURRENT PROTECTION
CM
CONSTRUCTION MANAGER
MH
METAL HALIDE
DP
DISTRIBUTION PANELBOARD
MTS
MANUAL TRANSFER SWITCH
EB
ELECTRONIC BALLAST
NL
NIGHTLIGHTING
EC
ELECTRICAL CONTRACTOR
OCC
OCCUPANCY
EM
EMERGENCY
PB
PULL BOX OR PUSH BUTTON
EWC
ELECTRIC WATER COOLER
RECPT
RECEPTACLE
FA
FIRE ALARM
TC
TIME CLOCK
FLA
FULL LOAD AMPS
TYP
TYPICAL
G
GROUND
UNO
UNLESS NOTED OTHERWISE
GC
GENERAL TRADES CONTRACTOR
V
VOLT
GFCI
GROUND FAULT CIRCUIT INTERRUPTER
W
WATT
GEN
GENERATOR
WP
WEATHERPROOF, NEMA 3R UNO
HP
IHORSEPOWER
IXFMR
ITRANSFORMIER
L
O
A
NEUTRAL WHT r RED I D
POWER
HOT BILK I T RED
I
PACK T
o
Lu J J
ll:� Co m
r ISOLATED RELAY
DT-200 OCCUPANCY SENSOR WITH
MANUAL -ON STANDARD SCHEMATIC
RED
RLY COM.'
ORG
N.O.
BRN
L-----------------LGT.LEVEL
N.C.
BLU
OCCUPANCY
YLW
SENSORS USING
-0 GRIN
CTRL OUT.
EIGHT WIRES
MAN. SW
WITH MANUAL -ON
VIO
+24V
GRA
COMMON
*MOMENTARY SWITCH DT-200
WIRES
NOTE:
THE MANUAL ON FEATURE VIA A MOMENTARY
SWITCH IS OPTIONAL. REFER TO THE INSTALLATION
INSTRUCTION FOR ADDITIONAL INFORMATION.
OCCUPANCY SENSOR WIRING DIAGRAM
N.T.S.
rn IN r, rl-
ro N N !`_� rl_
�m0000
It n r.
. .� =3 O 00 00
>
�O
L vi lfl lD
4A Z3
Ln a) ro
Ln E 4--
00 =5
O
1 U
COPYRIGHT2018. ALLDRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE+ PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
z
W
5
G
Ln
W
N
\
O
=
0
5�
G
Z)
Co
0
2
Oo
Z)o
J
Q
zm0
J
N
M
Il�
(Dw
�
L1J
JUG
2�
'
QQ
�z
�o
V)
O'�'a
C)
zo
LL_�z
�m
W
WV)
Q
U
J
Lu
Z
~
<<q
�
�
�
w
PROJECT NUMBER:
W P GO07
ISSUE
DATE
PERMIT
FEB. 01, 2018
I.171:111:11115
ELECTRICAL PLANS
E 1 a 1
00
00
N
SPECIFICATIONS - DIVISION 26 - ELECTRICAL
GENERAL REQUIREMENTS
208Y/120V SYSTEM: BLACK, RED, BLUE & WHITE (NEUTRAL)
20 AMPERE #12 #12 #12
PROVIDE LUMINAIRES AND/OR LUMINAIRE OUTLET BOXES WITH HANGERS TO PROPERLY SUPPORT LUMINAIRE WEIGHT.
EQUIPMENT GROUNDING: GREEN
25 AMPERE #10 #10 #10
ALL LUMINAIRES INSTALLED IN OR ON SUSPENDED CEILING SYSTEMS SHALL BE ANCHORED DIRECTLY TO THE BUILDING
THE GENERAL PROVISIONS OF THE CONTRACT INCLUDING THE GENERAL AND SUPPLEMENTAL CONDITIONS AND
ALL EQUIPMENT & SYSTEM IDENTIFICATION NOMENCLATURE SHOWN ON DRAWINGS OR LISTED HEREIN IS SHOWN FOR
30 AMPERE #10 #10 #10
STRUCTURAL SYSTEM ABOVE (ANCHORED PER NEC). SUCH ANCHORING SHALL BE INDEPENDENT OF THE CEILING
GENERAL REQUIREMENTS APPLY TO THE WORK IN THIS SECTION. BEFORE SUBMITTING A BID, EXAMINE DOCUMENTS
GENERAL DESIGN AND INSTALLATION REFERENCE ONLY. THE ACTUAL NAMEPLATE, ETC. NOMENCLATURE FOR THIS
35 AMPERE # 8 # 8 #10
SUPPORTSYSTEM. ALL LUMINAIRES SHALL BE INSTALLED PLUMB AND LEVEL. SUPPORT SURFACE MOUNTED LUMINAIRES
OF ALL OTHER TRADES, VISIT THE SITE AND GET ACQUAINTED WITH ALL CONDITIONS THAT MAY IN ANY WAY
PROJECT SHALL BE VERIFIED BY ELECTRICAL CONTRACTOR IN FIELD PRIOR TO FABRICATION AND WHERE APPLICABLE,
40 AMPERE # 8 # 8 #10
GREATER THAN 2 FEET IN LENGTH AT A POINT IN ADDITION TO THE OUTLET BOX LUMINAIRE STUD.
WHATSOEVER AFFECT THE EXECUTION OF THIS CONTRACT. TAKE MEASUREMENTS AND BE RESPONSIBLE FOR EXACT
SHALL BE AN EXTENSION OF EXISTING NOMENCLATURE USED ON THE SITE AS DETERMINED IN FIELD BY ELECTRICAL
SIZE AND LOCATIONS OF ALL OPENINGS REQUIRED FOR THE INSTALLATION OF WORK. FIGURED DIMENSIONS ARE
CONTRACTOR.
MECHANICAL EQUIPMENT
REASONABLY ACCURATE AND SHOULD GOVERN IN SETTING OUT WORK. WHERE DETAILED METHOD OF
CONDUIT AND FITTINGS
OUTLETS SHALL BE LOCATED APPROXIMATELY AS SHOWN ON THE PLANS AND SHALL BE WIRED TO PROVIDE
INSTALLATION IS NOT INDICATED OR WHERE VARIATIONS EXIST BETWEEN DESCRIBED WORK AND APPROVED
CONTROL OF OUTLETS INDICATED. ALL WIRES OF ANY ONE CIRCUIT SHALL BE RUN IN THE SAME CONDUIT.
PRACTICE, DIRECTION OF THE OWNERS REPRESENTATIVE ON JOB SITE SHALL BE FOLLOWED.
PROVIDE ALL CONDUIT AND OUTLET BOXES AS REQUIRED FOR ALL CONTROL WIRING AND THERMOSTATS. FURNISH
NORMAL SYSTEM BRANCH CIRCUITS SHALL BE INSTALLED IN SEPARATE RACEWAYS FROM EMERGENCY SYSTEM
TYPE AC/MC CABLE MAY BE UTILIZED ONLY IF NEC APPROVED AND IF APPROVED BY LOCAL AUTHORITY HAVING
AND INSTALL POWER WIRING AND MAKE LINE CONNECTIONS TO ALL HEATING, VENTILATING AND AIR
THE CONTRACT INCLUDES ALL ITEMS OF MATERIAL AND LABOR REQUIRED FOR THE COMPLETE INSTALLATION AND
POWER.
JURISDICTION AND IF INCLUDED IN THE APPLICATIONS DEFINED BELOW.
CONDITIONING EQUIPMENT. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY DISCONNECTS TO
FULL OPERATION OF THE ELECTRICAL WORK AS SHOWN ON THE DRAWINGS AND HEREINAFTER SPECIFIED. ALL
OPERATE THE HEATING, VENTILATING AND AIR CONDITIONING SYSTEM AS DESCRIBED ON DRAWINGS OF ALL OTHER
MATERIALS AND METHODS SHALL BE IN ACCORDANCE WITH APPLICABLE CODES, REGULATIONS AND/OR
ALL WIRING FOR DIFFERENT POWER VOLTAGES SHALL BE INSTALLED IN RACEWAY SYSTEMS SEPARATE FROM EACH
15 THROUGH 30 AMPERE BRANCH CIRCUIT WORK. THIS SHALL APPLY ONLY UNDER ALL OF THE FOLLOWING
TRADES. THE ELECTRICAL CONTRACTOR SHALL PROVIDE CONTROL AND INTERLOCK WIRING AS SPECIFICALLY
INDICATED ON THE DRAWINGS. ALL OTHER CONTROL WIRING REQUIRED FOR OPERATION OF THE SYSTEMS SHALL BE
ORDINANCES AND MEET THE APPROVAL OF LOCAL INSPECTION AUTHORITY HAVING JURISDICTION. THE LATEST
OTHER.
CIRCUMSTANCES AND CONDITIONS.
PROVIDED BY THE HEATING CONTRACTOR.
EDITION OF THE NATIONAL ELECTRIC CODE SHALL BE THE MINIMUM REQUIREMENT FOR ALL WORK. EXAMINE THE
DRAWINGS AND SPECIFICATIONS FOR COMPLIANCE WITH THE ABOVE CODES, REGULATIONS AND ORDINANCES
AND BASE BID AND WORK ACCORDINGLY. OBTAIN AND PAY FOR ALL PERMITS AND INSPECTIONS RELATED TO THIS
ALL WIRING FOR THE VARIOUS ELECTRICAL SYSTEMS SHALL BE INSTALLED IN RACEWAY SYSTEMS SEPARATE FROM
ONLY WHERE CONCEALED (ALL EXPOSED WIRING SHALL BE INSTALLED IN CONDUIT).
ELECTRICAL CONTRACTOR SHALL EXAMINE THE APPROVED DRAWINGS OF ALL BRANCHES AND SHALL WIRE AND
EACH OTHER.
WORK. A CERTIFICATE OF APPROVAL FOR WORK FROM INSPECTION AUTHORITY SHALL BE GIVEN TO THE OWNER
CONNECT ALL MOTORS, DISCONNECTS, CONTROL DEVICES AND OTHER ITEMS REQUIRING ELECTRICITY FOR
BEFORE FINAL ACCEPTANCE WILL BE GIVEN BY OWNERS REPRESENTATIVE.
ROUTE ALL CABLES PERPENDICULAR AND PARALLEL TO THE BUILDING ARCHITECTURAL
OPERATION. THIS CONTRACTOR SHALL MAKE THE NECESSARY ELECTRICAL CONNECTIONS BETWEEN THE SPECIFIED
ALL CONDUIT INSTALLED INDOORS SHALL BE GALVANIZED STEEL EMT MINIMUM ALL FITTINGS FOR SAME SHALL
LINES/SURFACES/STRUCTURAL MEMBERS, KEEPING OFFSETS TO A MINIMUM AND FOLLOWING SURFACE
EQUIPMENT AND THE JUNCTION BOX NEAR EQUIPMENT WITH FLEXIBLE METALLIC CONDUIT AND MATCHED
ALL WORK, MATERIALS, AND EQUIPMENT SHALL HAVE A WARRANTY FOR THE DURATION OF THE INSTALLATION OR A
BESET -SCREW COMPRESSION TYPE STEEL, WITH INSULATED THROATTS.S. UNLESS INDICATED OTHERWISE ON
CONTOURS WHERE POSSIBLE. MAINTAIN A UNIFORM ELEVATION FOR ALL CABLE RUNS WHEREVER POSSIBLE. ALL
CONNECTORS. NO FLEXIBLE CONDUIT SHALL BE EXPOSED IN FINISHED ROOMS.
PERIOD OF 1 YEAR, WHICHEVER IS LESS, AFTER ACCEPTANCE OF THE WORK BY THE OWNER. ANY DEFECTIVE ITEMS
IN
DRAWINGS OR N OTHER PARTS OF THE ELECTRICAL SPECIFICATIONS.
CABLES SHALL BE SUPPORTED/ANCHORED AT MAXIMUM 4 FOOT INTERVALS AND WITHIN 12" OF BOX OR OUTLET
SHALL BE REMOVED AND REPLACED AT THE ELECTRICAL SUB -CONTRACTORS EXPENSE AND TO THE SATISFACTION OF
AND SHALL NOT SAG. INSTALL CABLES IN A MANNER THAT PREVENTS OVERHEATING. CABLES SHALL BE
THE OWNER.
CONDUIT SHALL BE CLEANED INSIDE BEFORE ANY WIRES ARE PULLED. CONDUIT ENDS SHALL BE CAPPED AND
FASTENED DIRECTLY TO THE STRUCTURE USING FACTORY CLAMPS/CLIPS SPECIFICALLY DESIGNED FOR THE
PLUGGED WITH STANDARD ACCESSORIES AS SOON AS CONDUIT HAS BEEN PERMANENTLY INSTALLED. CONDUIT
RESPECTIVE CABLE (CADDY OR EQUAL).
PERFORM WORK UNDER THIS CONTRACT IN CLOSE HARMONY WITH OTHER CONTRACTORS SO COMPLETED WORK
INSTALLED WITHOUT CONDUCTORS SHALL BE PROVIDED WITH SWEEP BENDS AND BALING WIRE FOR PULLING.
SHALL PRESENT A NEAT AND WORKMANLIKE INSTALLATION. EXPOSED FINISHED MATERIALS AND EQUIPMENT SHALL BE
OUTLET, JUNCTION AND SWITCHBOXES
MISCELLANEOUS SPECIALTIES
CAREFULLY CLEANED AND WIPED TO REMOVE GREASE, SMUDGES, DUST AND OTHER SPOTS AND LEFT SMOOTH AND
ALL JOINTS SHALL BE MADE TIGHT WITH WATERTIGHT COUPLINGS MATCHING CONDUIT AND ALL CORNERS SHALL BE
CLEAN. DURING THE PROGRESS OF THE WORK, THE ELECTRICAL SUB -CONTRACTOR SHALL CAREFULLY CLEAN UP
MAKE WITH LONG RADIUS. THE ENDS OF ALL CONDUITS SHALL BE CUT SQUARE AND REAMED AND ALL JOINTS
PROVIDE A COMPLETE WIRING SYSTEM TO KITCHEN EQUIPMENT. DETERMINE EXACT LOCATION, MOUNTING HEIGHT
AFTER HIS MEN AND SHALL LEAVE THE PREMISES AND ALL PORTIONS OF THE BUILDING IN WHICH HE IS WORKING FREE
BROUGHT TO A SHOULDER. CONDUIT SHALL BE CONTINUOUS BETWEEN OUTLETS TO MAKE A COMPLETE
IN GENERAL, GANG TYPE OUTLET BOXES SHALL NOT BE USED. THE OUTLET BOX LOCATIONS INDICATED ON
AND TERMINATION REQUIREMENTS FROM MANUFACTURERS EQUIPMENT SUBMITTALS. PROVIDE EITHER DIRECT
OF DEBRIS AND IN A CLEAN AND SAFE CONDITION.
INSTALLATION AND TO EFFECT A CONTINUOUS GROUND. SUITABLE SUPPORTS AND FASTENING SHALL BE PROVIDED
DRAWINGS SHALL BE CONSIDERED APPROXIMATE, AND THEREFORE, IT SHALL BE INCUMBENT UPON THIS
CONNECTIONS OR CORD & PLUG CONNECTIONS (INCLUDING CORDS, PLUGS AND RECEPTACLES) AS DETERMINED
FOR CONDUIT.
CONTRACTOR TO STUDY THE GENERAL CONSTRUCTION WITH RELATION TO SPACES AND EQUIPMENT SURROUNDING
IN FIELD; VERIFY CASE BY CASE PRIOR TO ROUGH -IN. VERIFY ELECTRICAL RATINGS IN FIELD PRIOR TO ROUGH -IN.
WHENEVER THE WORDS "CONTRACTOR", "THIS CONTRACTOR", ETC. APPEAR ON DRAWINGS OR IN THESE
EACH OUTLET. ALL OUTLET, SWITCH AND JUNCTION BOXES SHALL BE MADE OF CODE GALVANIZED STEEL COMPLETE
MAKE FINAL CONNECTIONS TO EQUIPMENT.
SPECIFICATIONS FOR THE ELECTRICAL WORK, IT SHALL REFER TO THE ELECTRICAL SUB -CONTRACTOR. WHENEVER THE
WITH RINGS AND SCREW COVER PLATES AND LOCATED WHERE SHOWN AND NOTED ON DRAWINGS. WHERE
WORD "PROVIDE" APPEARS IN THESE DOCUMENTS, IT SHALL BE INTERPRETED TO MEAN "FURNISH & INSTALL".
CONDUIT SHALL BE SUPPORTED BY APPROVED STRAPS, FASTENERS AND HANGERS. HANGERS SHALL BE SUSPENDED
CONDUIT IS CONCEALED, BOXES SHALL NOT BE LESS THAN 4" SQUARE X 1-1/2" DEEP. ALL BOXES SHALL BE EQUIPPED
FROM RODS. PERFORATED STRAPS WILL NOT BE ACCEPTABLE. FASTENERS SHALL BE LEAD EXPANSION SHIELDS IN
WITH PROPER COVERS TO BRING FLUSH WITH FINISHED WALL SURFACE.
BLOCK OR CONCRETE, TOGGLE BOLTS IN HOLLOW WALLS, MACHINE SCREWS ON METAL SURFACES AND WOOD
THE EXACT MOUNTING HEIGHT OF OUTLETS SHALL BE DETERMINED IN THE FIELD WITH RELATION TO ARCHITECTURAL
SCREWS ON WOOD CONSTRUCTION. ALL CONDUIT SHALL BE SUPPORTED INDEPENDENTLY FROM ALL OTHER
DETAILS AND EQUIPMENT BEING SERVED. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE
BUILDING SYSTEMS AND SHALL BE SUPPORTED DIRECTLY FROM STRUCTURAL COMPONENTS. WHERE DEFLECTION IS
WHERE OUTLET BOXES OCCUR IN FACING TILE OR OTHER MATERIAL WHERE SUCH MATERIALS FORM THE FINISHED
OUTLET LOCATION WITH EQUIPMENT. THE OWNERS REPRESENTATIVE SHALL BE PERMITTED TO RELOCATE ANY OUTLET
EXPECTED, CONDUITS SHALL BE PROVIDED WITH EXPANSION FITTINGS WITH BONDING JUMPERS. CONDUITS PASSING
WALL SURFACE, THE OPENING FOR THE BOX SHALL BE CUT NEATLY AND OF THE SIZE THAT THE COVER PLATE WILL
PRIOR TO INSTALLATION WITHIN A 15 FOOT LIMIT AT NO ADDITIONAL CHARGE IN CONTRACT PRICE. ALL FASTENERS,
THROUGH STRUCTURAL MEMBERS SHALL BE PROVIDED WITH STUB AND COUPLING OR SLEEVE IN THE MEMBER.
COVER ALL PARTS OF THE OPENING. CONDULETS SHALL BE USED ON EXPOSED RACEWAYS. IN GENERAL, JUNCTION
HANGERS AND METHODS OF HANGING EXPOSED WORK IN FINISHED AREAS SHALL BE SUBMITTED TO THE OWNERS
BOXES SHALL BE FURNISHED AND REQUIRED BY THE NATIONAL ELECTRIC CODE, OF THE PROPER SIZES, AND SHALL BE
REPRESENTATIVE FOR APPROVAL BEFORE INSTALLATION.
CONSTRUCTED OF #12 GAUGE STEEL WITH REMOVABLE FRONT FASTENED ON WITH COUNTER SUNK HEAD SCREWS
ALL RACEWAYS SHALL BE ENTIRELY FREE OF PLASTER, MORTAR, WATER AND OTHER FOREIGN MATTER.
OR OTHER APPROVED MEANS. FOR SPECIAL APPLICATION, JUNCTION BOXES SHALL BE NOTED, DETAILED AND/OR
THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER INSTRUCTION OF EACH SYSTEM TO THE SATISFACTION OF
SIZED ON THE DRAWINGS OR IN THE FIELD AS REQUIRED.
THE OWNERS REPRESENTATIVE.
PROVIDE RIGID STEEL, HEAVY WALL, FULL WEIGHT, ZINC -COATED, THREADED TYPE CONDUITS (GROUNDED) THAT
TURN UP FROM BELOW GRADE OR BELOW SLAB, EXCLUDING THE 90 DEGREE FITTINGS THAT CONNECT TO
HEIGHT OF BOXES
THE ELECTRICAL CONTRACTOR SHALL CONSULT THE PLUMBING, HEATING AND ARCHITECTURAL PLANS IN ALL
HORIZONTAL CONDUITS BELOW GRADE OR SLAB.
INSTANCES BEFORE INSTALLING HIS WORK SO THAT HIS PIPING WILL NOT INTERFERE WITH THOSE BRANCHES. IN THE
PRIOR TO ROUGH -IN, VERIFY ALL BOX/DEVICE MOUNTING HEIGHTS AND LOCATIONS IN FIELD WITH OWNERS
EVENT OF A CONFLICT, THIS CONTRACTOR SHALL REPORT TO THE OWNERS REPRESENTATIVE AT ONCE AND DO NO
BOXES AND FITTINGS
REPRESENTATIVE. IN GENERAL, WHERE NOT LOCATED AT COUNTER AREAS, THE HEIGHT OF BOXES FROM FINISHED
FURTHER WORK UNTIL A SATISFACTORY ARRANGEMENT IS DECIDED UPON. ANY WORK DONE, OR EQUIPMENT
FLOOR TO CENTER OF BOXES SHALL BE AS FOLLOWS, UNLESS OTHERWISE NOTED ON PLANS:
PLACED IN POSITION BY THIS CONTRACTOR, CREATING A CONFLICT IN VIOLATION HEREOF, SHALL BE READJUSTED TO
THE SATISFACTION OF THE OWNERS REPRESENTATIVE AT THE EXPENSE OF THE CONTRACTOR. THE DECISION OF THE
PROVIDE MINIMUM SIZE OF 4 INCHES SQUARE BY 1-1/2 INCHES DEEP FOR OUTLET BOXES AND JUNCTION BOXES.
OWNERS REPRESENTATIVE SHALL BE FINAL IN REGARD TO CHANGES DUE TO CONFLICTING CONDITIONS.
PROVIDE OUTLET BOX ACCESSORIES AS REQUIRED FOR EACH INSTALLATION, INCLUDING BOX SUPPORTS, MOUNTING
SWITCHES: 48"
CONTRACTOR SHALL COMPLETE HIS WORK OR ANY PART THEREOF AT SUCH TIME AS MAY BE DESIGNATED BY THE
EARS AND BRACKETS, WALLBOARD HANGERS, BOX EXTENSION RINGS, FIXTURE STUDS, CABLE CLAMPS, AND METAL
DEVICES AT SPECIAL HEIGHTS: AS DIRECTED INFIELD.
OWNER, SO THAT IT CAN BE USED FOR TEMPORARY OR PERMANENT USE AND SUCH USE OF THE SYSTEM SHALL NOT BE
STRAPS FOR SUPPORTING OUTLET BOXES, WHICH ARE COMPATIBLE WITH OUTLET BOXES BEING USED TO FULFILL
RECEPTACLES: 18" (UNLESS COUNTER HEIGHT)
CONSTRUED AS AN ACCEPTANCE OF SAME BY OWNER.
INSTALLATION REQUIREMENTS FOR INDIVIDUAL WIRING SITUATIONS. PROVIDE WITH STAINLESS STEEL NUTS, BOLTS,
TELEPHONE OUTLETS (DESK PHONE): 18"
SCREWS AND WASHERS.
TELEPHONE OUTLETS (WALL PHONE): 48"
EXISTING CONDITIONS
WIRE AND CABLE
DATA CABLE OUTLETS: 18"CONTROL STATIONS: 48"
WHERE THE TERM "DEMOLITION" IS USED HEREIN, INTERPRET IT TO MEAN "DEMOLITION" OR "SELECTIVE
DEMOLITION" AS APPLICABLE.
FURNISH AND INSTALL ALL NECESSARY CABLE OF THE SIZE AND TYPE INDICATED ON THE DRAWINGS OR SPECIFIED
WIRING DEVICES
PERFORM A DETAILED PRE -BID WALK-THROUGH FIELD INSPECTION TO REVIEW THE EXISTING STRUCTURES AND
HEREINAFTER. ALL WIRE SHALL BE COPPER. ALL WIRING SHALL BE NEW. NO WIRE SMALLER THAN #12 AWG SHALL BE
PREMISES, TO DETERMINE EXISTING CONDITIONS, AND TO DETERMINE SCOPE OF REQUIRED ELECTRICALLY RELATED
INSTALLED UNLESS SPECIFICALLY DESIGNATED. USE OF #14 COLOR CODED WIRE WILL BE ALLOWED FOR CONTROL
PROVIDE WALL SWITCHES THAT ARE FLUSH SELF -GROUNDING WITH GREEN GROUND SCREW AND COLOR CODED
DEMOLITION WORK. INCLUDE APPLICABLE ACCESSIBLE CEILING CAVITY AREAS IN THIS INSPECTION.
CIRCUITS ONLY. ALL CONDUCTORS SHALL BE COPPER. PROVIDE STRANDED CONDUCTORS FOR ALL SIZES UNLESS
COVER, SNAP TOGGLE TYPE, BACK AND SIDE WIRED, SPECIFICATION GRADE. PROVIDE WALL SWITCHES RATED 20A,
INDICATED OTHERWISE.
120/277 VOLTS, 1 HP AT 120V, A.C. QUIET TYPE. SINGLE POLE SWITCHES SHALL BE EQUAL TO LEVITON #1221-2 SERIES.
IT IS NOT THE INTENT OF THESE THIS SECTION, OR OF DRAWINGS, THAT EXISTING CONDITIONS BE ACCURATELY
DOUBLE -POLE SWITCHES SHALL BE EQUAL TO LEVITON #1222-2 SERIES.
SHOWN. EXISTING ELECTRICAL WORK IS SHOWN TO A VERY LIMITED EXTENT ON DRAWINGS AND IS SHOWN FOR
GENERAL PLANNING REFERENCE ONLY. LOCATIONS AND INFORMATION WERE DERIVED FROM CURSORY VISUAL
PROVIDE THHN/THWN INSULATION FOR ALL CONDUCTORS NO. 8 AWG AND SMALLER. FOR ALL OTHER SIZES
OBSERVATIONS OR FROM PORTIONS OF DOCUMENTS THAT WERE PREPARED FOR PREVIOUSLY INSTALLED WORK (NOT
PROVIDE THW OR THHN/THWN INSULATION AS APPROPRIATE FOR THE LOCATIONS WHERE INSTALLED. PROVIDE
PROVIDE DUPLEX AND SINGLE SPECIFICATION GRADE RECEPTACLES, 2-POLE, 3-WIRE GROUNDING,
FROM RECORD DRAWINGS OR "AS-BUILTS").
COLOR CODED INSULATION/JACKET FOR PHASE IDENTIFICATION. ALL WIRES SHALL BE RATED AT 600 VOLTS.
SELF -GROUNDING, GREEN GROUNDING SCREW, GROUND TERMINALS AND POLES INTERNALLY CONNECTED TO
MOUNTING YOKE, COLOR CODED BASE, 20-AMPERES, 125-VOLTS, WITH METAL PLASTER EARS, BACK & SIDE WIRING,
DO NOT REUSE REMOVED ELECTRICAL MATERIALS UNLESS SPECIFICALLY INDICATED IN PROJECT MANUAL OR ON
TYPE AC AND MC CABLE SHALL BE FORMED FROM CONTINUOUS LENGTH OF SPIRALLY WOUND, INTERLOCKED
NEMA CONFIGURATION 5-20R. PROVIDE DUPLEX RECEPTACLES EQUAL TO LEVITON #5362 SERIES. FOR RECEPTACLE
DRAWINGS. EXISTING WIRING SYSTEMS MAY BE UTILIZED ONLY TO THE EXTENT INDICATED IN PROJECT MANUAL, OR
ZINC -COATED OR GALVANIZED (INSIDE & OUTSIDE) STRIP STEEL. ALL CONDUCTORS SHALL BE RATED FOR 90 DEG. C.
CIRCUITS PROTECTED WITH 15A BREAKERS, PROVIDE NEMA 5-15R EQUIVALENTS.
ON DRAWINGS, OR AS DIRECTED BY OWNER'S REPRESENTATIVE IN FIELD.
MINIMUM. PROVIDE WITH FULL PARITY SIZED GREEN INSULATED EQUIPMENT GROUND CONDUCTOR. PROVIDE
LOCATE, IDENTIFY, AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREAS AND SERVING
COMPATIBLE STEEL FITTINGS WITH INTEGRAL RED PLASTIC INSULATED THROAT BUSHINGS, COMPLIANT WITH NEC 350-5.
PROVIDE SELF -GROUNDING COMMERCIAL SPECIFICATION GRADE, DUPLEX RECEPTACLES, GROUND -FAULT CIRCUIT
OTHER AREAS OUTSIDE THE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE DEMOLITION LIMITS. WHEN
CABLES SHALL BE 90 DEG. C. RATED WITH ALL COMPONENTS AND FITTINGS LISTED FOR GROUNDING AND
INTERRUPTERS; FEED-THRU TYPE, CAPABLE OF PROTECTING CONNECTED DOWNSTREAM RECEPTACLES ON SINGLE
SERVICES MUST BE INTERRUPTED, INSTALL TEMPORARY SERVICES FOR AFFECTED AREAS.
COMPLIANT WITH THE FOLLOWING.
CIRCUIT, GROUNDING TYPE UL-RATED 943, CLASS A, GROUP 1, SPECIFICATION GRADE, 20-AMPERES RATING (DEVICE
& FEED-THRU), 125-VOLTS, 60 HZ; WITH SOLID-STATE GROUND -FAULT SENSING AND SIGNALING (MAXIMUM
PROVIDE ELECTRICAL DEMOLITION WORK AS REQUIRED TO ACCOMMODATE PROJECT DEMOLITION AND AS
UL STD.4 AND UL STD. 83.
THRESHOLD OF 5MA AT 0.025 SECONDS MAXIMUM); EQUIP WITH 20-AMPERE PLUG CONFIGURATION, NEMA 5-20R.
REQUIRED TO ACCOMMODATE NEW CONSTRUCTION.
ANSI E119 AND E814.
PROVIDE GROUND FAULT CIRCUIT INTERRUPTER DUPLEX RECEPTACLES EQUAL TO LEVITON #8898 SERIES.
REFER TO OWNER'S REPRESENTATIVE FOR DISPOSAL INSTRUCTIONS FOR ABANDONED ELECTRICAL MATERIALS
NEC ARTICLES 250 AND 333.
REMOVED DURING DEMOLITION AND THEREAFTER. NEATLY STORE ELECTRICAL MATERIALS THAT THE OWNER ELECTS
SPECIAL PURPOSE RECEPTACLES SHALL BE OF THE SIZE, TYPE AND MANUFACTURER AS INDICATED ON THE PLANS OR
TO RETAIN AT THE SITE AS DESIGNATED BY THE OWNER'S REPRESENTATIVE. LEGALLY DISPOSE OF MATERIALS THAT THE
METHOD OF WIRING -POWER
AS DETERMINED IN FIELD. REFER TO GROUNDING SECTION FOR SPECIAL RECEPTACLE GROUNDING REQUIREMENTS.
OWNER ELECTS NOT TO RETAIN.
AFFECTED EQUIPMENT/MATERIALS AREAS FOLLOWS.
NEATLY DRESS ALL WORK. INSTALL ALL WORK PARALLEL AND PERPENDICULAR TO SURFACES OR EXPOSED
ALL DEVICE WALLPLATES SHALL BE STANDARD SIZE; "MIDWAY", "OVERSIZED" ("JUMBO") OR "EXTRA DEEP" WALLPLATES
SHALL NOT BE ACCEPTABLE. CONSTRUCT WITH METAL SCREWS FOR SECURING PLATES TO DEVICES; SCREW HEADS
LUMINAIRES.
STRUCTURAL MEMBERS, AND FOLLOW SURFACE CONTOURS, WHERE POSSIBLE. KEEP CONDUCTOR SPLICES TO
COLORED TO MATCH FINISH OF PLATES. WALLPLATES IN FINISHED AREAS SHALL BE COMMERCIAL SPECIFICATION
MINIMUM. INSTALL SPLICE AND TAP CONNECTORS WHICH POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH
GRADE.
WIRING DEVICES.
AND INSULATION RATING THAN CONDUCTORS BEING SPLICED. USE SPLICE AND TAP CONNECTORS WHICH ARE
COMPATIBLE WITH CONDUCTOR MATERIAL. ALL WIRES SHALL BE RUN CONTINUOUS FROM OUTLET TO
DATA/COMMUNICATIONS DEVICES 8 EQUIPMENT.
OUTLET/LUMINAIRE TO LUMINAIRE. INSULATION VALUE OF JOINTS TO BE 100% IN EXCESS OF WIRE. PROVIDE
SUPPORTS, INSERTS, CUTTING AND PATCHING
ADEQUATE LENGTH OF CONDUCTORS WITHIN ELECTRICAL ENCLOSURES AND TRAIN THE CONDUCTORS TO TERMINAL
INTERIM AIR QUALITY (IAQ) WORK
POINTS WITH NO EXCESS. BUNDLE MULTIPLE CONDUCTORS, WITH CONDUCTORS LARGER THAN NO 10 AWG CABLED
THIS CONTRACTOR SHALL DO ALL CUTTING AND PATCHING REQUIRED FOR THE ADMISSION OF HIS WORK. ANY
PREVENT AIRBORNE DUST AND PARTICULATE MATTER RESULTING FROM ELECTRICAL WORK FROM ENTERING
IN INDIVIDUAL CIRCUITS. MAKE TERMINATIONS SO THERE IS NO BARE CONDUCTOR AT THE TERMINAL.
DAMAGE DONE BY THIS CONTRACTOR TO THE BUILDING DURING THE PROGRESS OF HIS WORK SHALL BE MADE
OCCUPIED SPACES, AND FROM ENTERING AIR INTAKES TO OPERATING HVAC SYSTEMS.
GOOD AT HIS OWN EXPENSE. ALL PATCHING SHALL BE DONE BY A SKILLED CRAFTSMAN IN THAT RESPECTIVE TRADE.
KEEP CONDUCTOR SPLICES TO MINIMUM. PULL CONDUCTORS SIMULTANEOUSLY WHERE MORE THAN ONE IS BEING
IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO SUPERVISE THE INSTALLATION OF, AND PAY FOR ALL
MAKE REQUIRED ELECTRICAL OPENINGS THROUGH WALLS AND FLOORS IMMEDIATELY PRIOR TO INSTALLATION OF
INSTALLED IN SAME RACEWAY. USE UL LISTED PULLING COMPOUND OR LUBRICANT, WHERE NECESSARY. INSTALL
ADDITIONAL MEMBERS, WOOD OR METAL AND LABOR WHICH MAY BE REQUIRED TO SUPPORT ANY TYPE OF
WORK. PROPERLY AND PERMANENTLY SEAL ELECTRICAL OPENINGS IMMEDIATELY AFTER INSTALLATION OF WORK.
SPLICE AND TAP CONNECTORS WHICH POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION
PERMANENT OR TEMPORARY ELECTRICAL APPARATUS EMPLOYED IN THE EXECUTION OF THIS CONTRACTORS WORK.
PROVIDE TEMPORARY SEALS FOR APPLICATIONS WHERE PENETRATIONS ARE MADE BUT CAN NOT BE PERMANENTLY
RATING THAN CONDUCTORS BEING SPLICED. USE SPLICE AND TAP CONNECTORS WHICH ARE COMPATIBLE WITH
SEALED WITHIN FOUR HOURS.
CONDUCTOR MATERIAL. INCREASE WIRE SIZES PER NEC TO OFFSET VOLTAGE DROP AS/IF REQUIRED.
SEAL ALL NEW FLOOR, CEILING, WALL, SLAB, ETC. PENETRATIONS TO MATCH OR EXCEED EXISTING ASSEMBLY FIRE
RATINGS. PROVIDE SLEEVE SEALS FOR ALL SLEEVES, PROVIDE SLEEVES FOR ALL PENETRATIONS. ALL PENETRATIONS OF
MATERIALS AND EQUIPMENT
NO WIRE SIZE SMALLER THAN NO. 12 SHALL BE USED FOR ANY BRANCH CIRCUIT UNLESS OTHERWISE NOTED ON PLANS
FIRE -RATED OR SMOKE -RATED WALL, FLOORS CEILINGS, ETC. SHALL BE SEALED IMMEDIATELY AFTER RACEWAYS ARE
FOR CONTROL CIRCUITS. LARGER SIZES SHALL BE USED WHERE REQUIRED AND/OR INDICATED ON THE PLANS.
INSTALLED. ALL NEW ELECTRICALLY RELATED WORK SHALL BE SUPPORTED DIRECTLY FROM BUILDING STRUCTURAL
ALL MATERIALS AND EQUIPMENT SHALL BE NEW. ALL MATERIALS, APPARATUS AND EQUIPMENT SHALL BEAR THE
MEMBERS. NEW ELECTRICALLY RELATED WORK SHALL NOT BE SUPPORTED FROM DUCTWORK, DUCTWORK HANGER,
UNDERWRITERS LABORATORIES INC., LABEL WHERE REGULARLY SUPPLIED. CERTAIN MANUFACTURERS OF MATERIAL
PROVIDE THE FOLLOWING MINIMUM WIRE SIZES BASED ON DISTANCES FROM PANEL TO FIRST DEVICE OF A 15 OR 20
CEILING SUPPORTS, EXISTING CONDUIT SUPPORT, ETC. ALL CONDUITS (AND CABLE ASSEMBLIES, WHERE APPLICABLE)
AND EQUIPMENT ARE SPECIFIED AND PLANS ARE DETAILED ACCORDING TO THIS MATERIAL. THIS CONTRACTOR
AMPERE GENERAL LIGHTING OR RECEPTACLE BRANCH CIRCUIT. IN ADDITION TO UPSIZING CONDUCTORS AS
SHALL BE ROUTED PARALLEL TO BUILDING STRUCTURAL MEMBERS. ANY AND ALL NONCOMPLYING WORK INSTALLED
SHALL BASE HIS BID ON FURNISHING AND INSTALLING THIS MAKE OF MATERIAL AND EQUIPMENT.
REQUIRED FOR VOLTAGE DROP, PROVIDE MINIMUM #10 AWG CONDUCTORS TO THE LAST DEVICE FOR BRANCH
BY THE ELECTRICAL CONTRACTOR SHALL BE REMOVED AND REINSTALLED TO THE SATISFACTION OF THE OWNER'S
CIRCUITS MORE THAN 150 FEET IN LENGTH.
REPRESENTATIVE AND THE ENGINEER, AT THE EXPENSE OF THE ELECTRICAL CONTRACTOR.
WHERE MORE THAN ONE MAKE OF MATERIAL OR EQUIPMENT IS SPECIFIED, THE CONTRACTOR SHALL STATE IN HIS BID
WHICH MAKE HE PROPOSES TO FURNISH. SHOP DRAWINGS SHALL BE SUBMITTED ON MATERIAL AND EQUIPMENT TO
DISTANCE AWG WIRE SIZES
BE FURNISHED BY THE CONTRACTOR FOR ENGINEERS APPROVAL. THIS APPROVAL TO BE OBTAINED PRIOR TO
UP TO 60 FEET #12
LUMINAIRES
SHIPMENT OF EQUIPMENT.
61 TO 90 FEET #10
91 TO 150 FEET # 8
ALL RECESSED LUMINAIRES SHALL BE EQUIPPED WITH NECESSARY PLASTER FRAMES AND SURFACE TRIM. ALL
ELECTRICAL IDENTIFICATION
151 TO 240 FEET # 6
RECESSED FLUORESCENT LUMINAIRES SHALL BE EQUIPPED AND SUITABLY CONSTRUCTED TO OPERATE WITH "P" RATED
BALLASTS. ALL RECESS MOUNTED INCANDESCENT AND H.I.D. LUMINAIRESSHALL HAVE UL APPROVED THERMAL
PROVIDE MANUFACTURERS STANDARD SELF-ADHESIVE VINYL TAPE NOT LESS THAN 3 MILS THICK BY 1-1/2" WIDE.
PROTECTION PER LATEST EDITION OF NFPA/NEC. ALL JUNCTION BOXES AND SERVICEABLE COMPONENTS (BALLASTS,
WHERE APPLICABLE, INSTALL ON ALL CONCEALED RACEWAYS AT CONNECTION TO ALL JUNCTION BOXES, PULL
THERMAL PROTECTION DEVICES, FUSES, ETC.) FOR RECESSED LUMINAIRES SHALL BE READILY ACCESSIBLE FOR SERVICE
BOXES, EQUIPMENT, WALL/FLOOR/ROOF PENETRATIONS, ETC. UNLESS OTHERWISE INDICATED OR REQUIRED BY
PROVIDE THE FOLLOWING MINIMUM AWG CONDUCTOR SIZES FOR GENERAL BRANCH CIRCUITING THAT ARE NOT
OR REPLACEMENT FROM BELOW THE CEILING, WITHOUT REMOVING ANY CEILING COMPONENTS (OTHER THAN TILES).
GOVERNING REGULATIONS, PROVIDE ORANGE TAPE WITH BLACK LETTERS. PROVIDE CIRCUIT IDENTIFICATION BANDS
INDICATED ON DRAWINGS, BASED ON USING COPPER CONDUCTORS. WHERE APPLICABLE INCREASE AS REQUIRED
FOR ALL CABLES AND CONDUCTORS. PROVIDE MANUFACTURERS STANDARD COLOR CODING FOR
TO ACCOMMODATE VOLTAGE DROP AND TO ACCOMMODATE SPECIAL CONDITIONS. DO NOT DERATE ANY
PROVIDE LOW ENERGY SOLID STATE RAPID START ELECTRONIC FLUORESCENT LAMP BALLASTS SPECIFICALLY
CABLE/CONDUCTOR JACKET AND/OR INSULATION FOR ALL CABLES AND CONDUCTORS OF ALL SYSTEMS. MATCH
GROUNDED (NEUTRAL) CONDUCTORS. TEMPERATURE RATINGS LISTED BELOW PERTAIN TO BOTH WIRE AND
DESIGNED FOR OPERATING LAMP TYPES INDICATED UNLESS NOTED OTHERWISE. FLUORESCENT BALLASTS SHALL BE
IDENTIFICATION WITH MARKING SYSTEM USED IN EXISTING SYSTEMS SHOP DRAWINGS, CONTRACT DOCUMENTS, AND
TERMINATIONS.
MOTOROLA OR ADVANCE EQUAL (LESS THAN OR EQUAL TO 20% THD). ALL LUMINAIRES MAY CONTAIN EITHER
SIMILAR PREVIOUSLY ESTABLISHED IDENTIFICATION FOR PROJECTS ELECTRICAL WORK. PROVIDE ON ALL
SINGLE BALLASTS OR MULTIPLE BALLASTS AS REQUIRED TO FULFILL REQUIRED FUNCTION AND AS REQUIRED TO
CONDUCTORS OF ALL SYSTEMS.
COMPLY WITH CONSTRUCTION SCHEDULE.
THE FOLLOWING INSULATION COLOR CODE SHALL BE USED FOR SYSTEM AND VOLTAGE IDENTIFICATION. THIS SHALL
60 DEG. C RATING 75 DEG. C RATING EQUIPT. GROUNDING
FLUORESCENT LAMP COLOR TEMPERATURE SHALL BE AS INDICATED ON DRAWINGS OR AS DIRECTED IN FIELD.
SOURCE BREAKER/FUSE AWG WIRE SIZE AWG WIRE SIZE AWG WIRE SIZE
APPLY TO BOTH FEEDER AND BRANCH CIRCUIT WIRING. INTERCHANGE OF COLORS SHALL NOT BE PERMITTED.
15 AMPERE # #12 #12
• . L0 Ln •
ro Ol r—I n
ro N N �
N M N
>
O
ro
�u
on
L
00 Z3
O
1 U
n
COPYRIGHT 2018. ALLDRAWII
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RE
ARCHITECTURE + PLANNING L
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSE
OF THE ARCHITECT.
z
uj
Lu
O
�NN
Oo
112L I
ZI
O
z
J
co
N
m
a
Lu
C:)
Lu
J
U
a
z
� I
a
a
O
rin
w
F_
C)I
z
��
>_z
wUw
z�
U
a
void
�i
a
m
o
<
to
rl
U LL
PROJECT NUMBER:
W PGO07
SHEET:
SPECIFICATIONS
ELECTRICAL
E791
RELEASED IFCR CONSTRUCTION
at State and Ilmeail Endlen
0tp at Caimal
DATE: 03/07/18
Nick Mishler