HomeMy WebLinkAboutEncore on Penn_First Floor Bui10 & 120_CONSTRUCTION DRAWI... 10ALTERNATE
BID
NOT IN
SCOPE
NOT IN
SCOPE
A.0 B.0 C.0 D.0 E.0 F.0 G.0 H.0 I.0
2.0
1.0
3.0
4.0
5.0
6.0
NOT IN
SCOPE
mech
chase
above
ALTERNATE
BID
NOT IN
SCOPE
FUTURE
COPIER
LOCATION
ST101
STAIR 1
EV100
ELEVATOR
102
VESTIBULE
ST102
STAIR 2
101
UTILITY
92 SF
CONFERENCE ROOM
111
OFFICE
112
OFFICE
119
IT CLOSET
118
OFFICE
117
UNISEX RESTROOM
115
UNISEX RESTROOM
116
KITCHENETTE
114
SUITE 120 ENTRY
120
SMALL CONFERENCE
122
LARGE CONFERENCE
123
WAITING
121
FUTURE TENANT SUITE 100
100
OPEN OFFICE
113
1
1
1
1
1
1
1
2
Xref Y:\2017\17116 - Loan Depot Suite at Encore on Penn\9.0 Drawings\Plans\Revit_temp\17116-MEPbase_NIELSEGO5173 - Reflected Ceiling Plan - A-FIRST FLOOR-16113-MEP_
18"x12"
18"x10"
Shell FCU-1-11
Shell FCU-1-12
Shell FCU-1-5
Shell FCU-1-4
Shell FCU-1-10
Shell FCU-1-1 Shell FCU-1-2
Shell FCU-1-7
Shell FCU-1-13
Shell FCU-1-8
8"ø 10"ø
12"ø
12"x10"
SDG-1
95
SDG-1
95
SDG-1
95
SDG-1
SDG-1 90
90
SDG-1
90
LS-1
100
LS-1
100
LS-1
50
PD-1
75
16"x10" 10"ø
6"ø
6"ø
6"ø
5"ø
16"x10" 24"x12"
LS-3
145
LS-3
LS-3 150
145
LS-3
145
LS-3
150
LS-3
145
SDG-1
75
SDG-1
75
SDG-1
70
SDG-1
70
SDG-1
70
SDG-1
75
10"ø 8"ø
PD-1
75
PD-1
75
6"ø 7"ø
6"ø
7" ø
12"ø
LS-3
145
LS-3
150
16"x10"
24"x12"
10"x10" 12"x10" 16"x10"
LS-1
50
LS-2
LS-2 90
80
LS-2
80
LS-2
80
LS-2
80
PD-1
150
PD-1
75
PD-1
110
PD-1
100
6"ø
6"ø
7"ø
6"ø
5"ø
7"ø
6"ø
24"x12"
LS-2
80
LS-2
80
LS-2
80
LS-2
80
8"ø 10"ø 12"ø
SDG-1
95
SDG-1
90
SDG-1
95
SDG-1
95
SDG-1
95
SDG-1
90
16"x10" 24"x12"
6"ø
6"ø
6"ø
6"ø
SDG-1
95
SDG-1
95
SDG-1
95
SDG-1
95
SDG-1
95
SDG-1
95
10"ø
8"ø
12"ø
16"x10"
12"x10"
8"ø
8"ø
8"ø
8"ø
8"ø
PD-1
150
PD-1
145
PD-1
150
PD-1
145
PD-1
145
PD-1
145
PD-1
175
PD-1
175
PD-1
175
PD-1
175
PD-1
180
Shell FCU-1-3
8"ø
16"x10"
6"ø
6"ø
6"ø
6" ø
5"ø
5"ø
LS-2
80
LS-2
80
PD-1
70
PD-1
40
PD-1
40
8"x4"
8"x4"
ER-1
75
ER-1
75
10"x4"
16"x10" 12"x10" 8"ø
8"ø
10"x4"
ECR-1
ECR-1
ECR-1
ECR-1
ECR-1
ECR-1
ECR-1
ECR-1
DSFC-118
Relocate shell fan coil unit to this location. Extend wiring
and piping as necessary.
Ductless split fan coil unit, mount FCU as high on wall as
possible. Route lineset thru plenum and up in chase to
roof. Mount outdoor unit on roof. Coordinate outdoor unit
location other equipment on roof.
2NCP 0QVGU
)GPGTCN 0QVGU
1. These plans are diagrammatic in nature, and do not
represent every necessary offset and fitting. Contractor
shall install his work in a manner that will conform with
the structure. Contractor shall avoid obstructions,
preserve head room and maintain maximum clearance
without additional cost to the owner.
2. Conceal all linesets, piping, power wiring, control wiring
and control components unless otherwise noted. If
concealment is not possible, contact Engineer for
alternatives prior to fabrication.
3. Insulate all interior linesets with
1
2" thick, flexible
elastomeric insulation. Insulate exterior linesets with 1"
thick flexible elastomeric insulation with external .020"
aluminum protective jacket.
4. Sheet metal supply ductwork in concealed spaces shall
be insulated with 11
2" thick, .75 PCF density, fiberglass
ductwrap. All ductwork in unconditioned spaces shall be
insulated with 2" thick, 1.0 PCF density, fiberglass
ductwrap. (Min R6)
5. Phenolic duct by Pal-Duct or Kool-Duct is an acceptable
alternative to sheetmetal duct and insulation in
concealed spaces. Use flanged joints.
6. Keep all ductwork, duct system and equipment openings
covered with adhesive duct protective wrap like
VentureTape 1512, until system start-up. This is to
prevent intrusion of construction dirt and debris into the
duct system, and HVAC equipment.
7. If any questions arise concerning the HVAC
requirements of these documents, please contact The
Engineering Collaborative at (317) 636-3941, prior to
bidding, fabrication or installation of equipment.
8. Sheet metal transitions by Sheet Metal Contractor.
9. Refer to detail sheets M600's for additional requirements
and information that applies to this project.
1
2
ALL INFORMATION CONTAINED IN THIS
DOCUMENT IS CONSIDERED TO BE BOTH
CONFIDENTIAL AND PROPRIETARY
INTELLECTUAL PROPERTY OF BLACKLINE
STUDIO AND SHALL NOT BE COPIED,
REPRODUCED, DISTRIBUTED OR ASSIGNED TO
A THIRD PARTY WITHOUT PRIOR WRITTEN
CONSENT OF BLACKLINE STUDIO.
UNAUTHORIZED USE OF THESE DOCUMENTS IS
NOT PERMITTED.
c 2018 BLACKLINE STUDIO
ARCHITECT
BLACKLINE
1 N MERIDIAN ST, SUITE 4 00
INDIANAPOLIS, INDIANA 4 6204
BLACKLINESTUDIO.NET
317.803.7900
CERTIFICATION:
CHECKED BY:
DRAWN BY:
MEP ENGINEER
THE ENGINEERING COLLABORATIVE
24 10 EXECUTIVE DRIVE, SUITE 100
INDIANAPOLIS, INDIANA 4 624 1
WWW.TEC-MEP.COM
317.636.3941
# Date Description
P
R
O
F
E
S
S
I
O
N
A
L
E
N
G
N
I
E
E
R
S
A
M
U
E
L
L.
H
U
R
T
I
N
D
I
A
N
A
0
N
P E 1 6
o .
10 0 87
S T A T E O F
R
E
T
E
G
I
S
D
E
R
12411 Pennsylvania St.
Carmel, Indiana 46032
Permit Set
JANUARY 17, 2018
Encore on Penn - Permit Set 01.17.18
First Floor Office Build-Out: Suites
M101
FIRST FLOOR HVAC PLAN
XXX
XXX
3/16" = 1'-0"
1 FIRST FLOOR HVAC PLAN
03/07/18
Nick Mishler