HomeMy WebLinkAboutEncore on Penn_First Floor Bui10 & 120_CONSTRUCTION DRAWI... 116GTOKPCN 1WVNGVU
Mark Function
Price
Model
Airflow
Range
(CFM)
Face Size
(in.)
Neck Size
(in.) Color Remarks
PD-1 Plaque Diffuser SPD 50-180 24 x 24 6Ø White 1,2,3
PD-2 Plaque Diffuser SPD 181-300 24 x 24 8Ø White 1,2,3
SDG-1 Spiral Duct Grille SDGE 50-175 10 x 4 N/A White 4
ER-1 Exhaust Register 530 0-100 7
3
4 x 7
3
4 6 x 6 White 1,2,3
ECR-1 Eggcrate Return 80 501-1500 24 x 12 22 x 10 White 1,2,3
LS-1 Linear Slot Diffuser SDS75 - 1 slot 1-100 24" 5"Ø By Architect 3
LS-2 Linear Slot Diffuser SDS75 - 1 slot 1-100 48" 5"Ø By Architect 3
LS-3 Linear Slot Diffuser SDS75 - 2 slot 101-180 48" 7"Ø By Architect 3
LS-4 Linear Slot Diffuser SDS100 - 2 slot 181-240 48" 8"Ø By Architect 3
LS-5 Linear Slot Diffuser SDS100 - 3 slot 241-310 48" 10"Ø By Architect 3
Notes:
1. Provide factory extended panel for any diffuser which is smaller than the grid in which it is installed.
2. Sound baffle by Sheet Metal Contractor.
3. Provide plaster frame for diffusers, registers and grilles installed in gypsum board.
4. Provide optional air scoop.
&WEVNGUU 5RNKV #KT %QPFKVKQPGT
Mark
Area
Served
Model
Cooling
Capacity
(BTU/hr)
Heating
Capacity
(BTU/hr)
Airflow
(CFM)
Electrical Connection
Disconnect Remarks
Outdoor Indoor Outdoor Indoor
Voltage
(V)
Phase
(Ø)
MCA
(Amps)
DSAC-118 DSFC-118 IT Closet
Mitsubishi
MUy-GL12NA-U1
Mitsubishi
MSY-GL12NA-U1
12,000 N/A 360 208 1 7.00 Manufacturer See Notes
Notes:
1. Provide integral drain pan mounted condensate pump.
2. Provide flooded drain pan interlock.
3. Line voltage to outdoor unit.
4. Provide locking disconnect.
1-1/2"
Round Flexible Connection
1" x 1/8" Band iron
Washer
1/2"
1" x 1/8" Draw band
1/2"
5/16" Flange
Bolt 4" on centers
Rectangular Flexible Connection
1" Flange and hem
Bolt 4" on centers
1" x 1/8" Band iron
Washer
Rivet 4" on centers
Ductwork
1-1/2" Pocket slip
Ductwork
Flexible material
as specified
1-1/2" Minimum to 3" maximum
installed. 6" nominal with material taut
Sheet metal as specified for ductwork
Flanged connection
on fan side
Sheet metal as specified for ductwork
Alternate position of bolt
1-1/2" Minimum to 3" maximum
installed. 6" nominal with material taut
Flanged connection
on fan side
Flexible material as specified
1" x 1/8" Draw band
D (NGZKDNG %QPPGEVKQP
M-XX Scale: None
X
Sheet metal box
1-1/2" duct wrap
1-1/2" duct wrap
Sheet metal elbow
Supply diffuser
Application NOT Acceptable
12" x 12" supply diffuser Ceiling
24" x 24" supply diffuser
Low pressure
supply branch duct
Collar with manual
volume damper & lock Insulated flexible
duct to supply
diffuser
Notes:
Provide a 45 degree entry square-to-round fitting from low pressure
supply branch duct when the supply diffuser branch size equals or
exceeds the depth of the supply branch duct. Width shall equal round
diffuser branch size, depth shall equal supply branch duct depth.
Refer to supply diffuser plenum connection detail if guidelines of this
detail can not be met due to physical limitations.
A maximum length of 25'-0" of flexible duct is allowed in a single run.
Secure flexible duct to
supply diffuser elbow
fitting with drawband
Lay-in panel
where required
Secure flexible duct to
supply diffuser elbow
fitting with drawband
Insulated flexible duct
to supply diffuser
Provide shoe 8" Min.
tap fitting
Ceiling
D 5WRRN[ &KHHWUGT CPF (NGZKDNG &WEV %QPPGEVKQP
M-XX Scale: None
X
Full size
Cleanout plug
Draw Through Coil
Blow Through Coil
Full size
Cleanout plug
Cleanout plug
Route full size condensate drain pipe to
nearest floor drain. Refer to plumbing
drawings for floor drain locations.
Unit manufacturers threaded
drain pipe connection (typ)
Cooling coil
drain pan
Drain line (bottom
connection only)
1" greater than
fan static pressure
1" greater than half of
fan static pressure
1" greater than
half of fan
static pressure
1" greater than fan
static pressure
D %QPFGPUCVG &TCKP $NQY&TCYÄ6JTW %QKN
M-XX Scale: None
X
Drain line (bottom
connection only)
Cooling coil
drain pan
Full size
Full size
Unit manufacturers threaded
drain pipe connection (typ)
Cleanout plug
Route full size condensate drain pipe to
nearest floor drain. Refer to plumbing
drawings for floor drain locations.
Fiber cap
Fiber cant
Stainless steel
adjustable clamps
Heavy gauge galvanized steel with
continuous welded corner seams
1 1/2" rigid
fiberglass insulation
1 1/2" wood nailer
Stepped polyvinyl boot
D 2KRG %WTD
M-XX Scale: None
X
More than 30°
30° or less
V.D.
45° Boottap fitting
Duct offset
Use radius for more than 30°
Use mitered for 30° or less
Duct offset
90° Square Elbow Branch off main
Turning vanes
90° Radiused Elbow
H H
2H
D .QY 8GNQEKV[ 5JGGV /GVCN (KVVKPIU
M-XX Scale: None
X
Minimum 1" wide clamp.
Detail 2
Maximum flexible
duct length shall be
5'-0".
Wire support.
Detail 1
Detail 3
Notes:
1. Metallic flexible ductwork shall be attached using a minimum of three (3) #8 sheet
metal screws equally spaced around the ductwork circumference. Ductwork larger
than 12" shall have a minimum of five (5) #8 sheet metal crews. Screws shall be
located at least 1/2" from the ductwork end.
2. Non-metallic flexible ductwork shall be secured to the sleeve or collar using a
draw band. If the ductwork collar exceeds 12", the draw band must be positioned
behind a bead on the metal collar.
3. Insulation and vapor barriers present on factory-fabricated ductwork shall be fitted
over the core connection and shall be supplementally secured with a draw band.
4. Flexible ductwork sealing shall be a class "B" seal for low pressure ductwork.
5. Support system shall not damage or cause out-of-round shape.
6. Flexible ductwork shall be a maximum of 5'-0" in length and shall NOT be used as
an elbow.
Maximum sag shall be
1/2" per foot of support
spacing.
Strap bracing shall be
provided at a maximum
of 3'-0" on centers.
1" Band clamp with
wire. (Optional)
D +PUWNCVGF (NGZKDNG &WEVYQTM
M-XX Scale: None
X
Ceiling
Washer with
black neoprene
pad on underside
1" Black rigid
insulation board
Wire support attached
to structure
8" min.
Eggcrate type
return grille
12" all
4 sides
D 1RGP 2NGPWO 4GVWTP )TKNNG
M-XX Scale: None
D *KIJÄ9CNN &WEVNGUU 5RNKV X
M-XX Scale: None
X
Condensate drain up thru wall
cavity. Refer to "P" Series drawings.
Provide integral, drain pan mounted,
condensate pump detection unit.
Refrigerant piping up
thru wall cavity.
High-Wall type
ductless split FCU.
Mount FCU high on wall.
Condensate drain down
thru wall cavity. Refer to
"P" Series drawings.
Notes:
1. Install all components per Manufacturer's installation
instructions.
2. Fan coils shall have a flooded drain pan interlock.
3. Refrigerant lines and condensate drains shall be
insulated.
Refrigerant lineset and
condensate drain in wall
cavity
Provide piston type condensate
pump like Sauerman SI3100 with
detection unit located in FCU drain
pan.
ALL INFORMATION CONTAINED IN THIS
DOCUMENT IS CONSIDERED TO BE BOTH
CONFIDENTIAL AND PROPRIETARY
INTELLECTUAL PROPERTY OF BLACKLINE
STUDIO AND SHALL NOT BE COPIED,
REPRODUCED, DISTRIBUTED OR ASSIGNED TO
A THIRD PARTY WITHOUT PRIOR WRITTEN
CONSENT OF BLACKLINE STUDIO.
UNAUTHORIZED USE OF THESE DOCUMENTS IS
NOT PERMITTED.
c 2018 BLACKLINE STUDIO
ARCHITECT
BLACKLINE
1 N MERIDIAN ST, SUITE 4 00
INDIANAPOLIS, INDIANA 4 6204
BLACKLINESTUDIO.NET
317.803.7900
CERTIFICATION:
CHECKED BY:
DRAWN BY:
MEP ENGINEER
THE ENGINEERING COLLABORATIVE
24 10 EXECUTIVE DRIVE, SUITE 100
INDIANAPOLIS, INDIANA 4 624 1
WWW.TEC-MEP.COM
317.636.3941
# Date Description
P
R
O
F
E
S
S
I
O
N
A
L
E
N
G
N
I
E
E
R
S
A
M
U
E
L
L.
H
U
R
T
I
N
D
I
A
N
A
0
N
P E 1 6
o .
10 0 87
S T A T E O F
R
E
T
E
G
I
S
D
E
R
12411 Pennsylvania St.
Carmel, Indiana 46032
Permit Set
JANUARY 17, 2018
Encore on Penn - Permit Set 01.17.18
First Floor Office Build-Out: Suites
M601
HVAC SCHEDULES & DETAILS
XXX
XXX
03/07/18
Nick Mishler