HomeMy WebLinkAboutEncore on Penn_First Floor Bui10 & 120_CONSTRUCTION DRAWI... 12A.0 B.0 C.0 D.0 E.0 F.0 G.0 H.0 I.0
2.0
1.0
3.0
4.0
5.0
6.0
CONFERENCE ROOM
111
OFFICE
112
OFFICE
119
IT CLOSET
118
OFFICE
117
UNISEX RR
116
KITCHENETTE
SUITE 120 ENTRY
120
SMALL CONFERENCE
122
LARGE CONFERENCE
123
WAITING
121
FUTURE TENANT SUITE
100
100
OPEN OFFICE
113
ST101
STAIR 1
102
VESTIBULE
ST102
EV100
ELEVATOR
STAIR 2
101
UTILITY
ALTERNATE
BID
'W1'
'C1'
'E1'
'C1'
'C1'
'C1'
'E1'
'
UNISEX RR
115
'X1'
'X1'
'L1' 'L1'
'L1' 'L1'
'L1'
'
'X1'
'C2'
'C2'
'E1' 'E1'
'E1'
'E1'
'L1'
114
'W1'
'C2' 'C2' 'C2'
'C2' 'C2' 'C2' 'C2'
'P2'
'P2'
'C2'
'C2'
'C2'
'C2' 'C2'
'C2'
'C2'
'C2'
'P2'
'C2'
'C2'
'C2'
'C2'
'X1'
'P3'
'P3'
'P4' 'P4' 'P4'
'P-12'
'P-12'
'P-16'
'P-16'
'P-16'
'P-16'
'L1' 'L1'
'L1'
'L1'
'L1'
'L1'
'P-16'
'E1'
'C2' 'C2'
'C2'
'C2'
'C2'
'L2' 'L2'
8
LD1-12
via "LC1"
LD1-14
LD1-28
Note:
Unless otherwise noted on plan, connect all exit
signs (fixture type 'X1') and emergency lighting
units (fixture type 'E1') to the room lighting circuit
the sign and/or the emergency lighting unit is
serving (ahead of any local switching means).
)GPGTCN 0QVGU
All 120 volt, 20 amp circuits over 60' in length shall be
#10 AWG, over 95' shall be #8, over 145' shall be #6.
Contractor shall coordinate with all other trades to avoid
conflicts of space.
Contractor shall coordinate the exact location of all
devices with all other trades prior to rough-in. Exact
location to be determined in the field.
Contractor shall coordinate with the mechanical and
plumbing contractors for exact locations of equipment
prior to rough-in.
Refer to sheet EI701 for details and symbols.
Refer to sheet EI601 electrical riser diagram.
Refer to sheets EI601 and EI602 for electrical schedules.
Shared neutrals shall not be permitted.
Note "H" clips are not acceptable for junction box
supporting.
Switches shall be a maximum +48" A.F.F. to the top of
the device unless otherwise noted.
Receptacles, telephone outlets, and television outlets
shall be a minimum of +18" A.F.F. to the bottom of the
device unless otherwise noted.
Where devices are installed in fire walls, the boxes shall
be rated and sealed for installation in a fire wall.
Provide HACR circuit breakers for all HVAC and
refrigeration equipment.
All light fixtures marked '/ (Emergency) shall be on a
switched circuit and have an emergency battery pack.
All light fixtures marked 0. (Night Light) shall be on a
non-switched circuit.
All light fixtures marked '/0. (Emergency/Night Light)
shall be on a non-switched circuit and have an
emergency battery pack.
Provide plenum rated cable/wire/conduit as required.
Coordinate with mechanical contractor.
A.
B.
C.
D.
E.
F.
G.
H.
J.
K.
L.
M.
N.
P.
Q.
R.
Note:
E.C. shall comply with the IBC in regards
to fire rated membrane penetrations.
Utilize means of fire rated junction boxes,
"putty pads", fire blocking and offsetting.
2NCP 0QVGU
Contractor shall provide and install a 2-pole contactor
"LC1" for general lighting in the Owner's specified
location. Contactor "LC1" shall be controlled by digital
time switch 1P and 1HH. Digital time switch shall have
integral manual override control.
8
S.
ALL INFORMATION CONTAINED IN THIS
DOCUMENT IS CONSIDERED TO BE BOTH
CONFIDENTIAL AND PROPRIETARY
INTELLECTUAL PROPERTY OF BLACKLINE
STUDIO AND SHALL NOT BE COPIED,
REPRODUCED, DISTRIBUTED OR ASSIGNED TO
A THIRD PARTY WITHOUT PRIOR WRITTEN
CONSENT OF BLACKLINE STUDIO.
UNAUTHORIZED USE OF THESE DOCUMENTS IS
NOT PERMITTED.
c 2018 BLACKLINE STUDIO
ARCHITECT
BLACKLINE
1 N MERIDIAN ST, SUITE 4 00
INDIANAPOLIS, INDIANA 4 6204
BLACKLINESTUDIO.NET
317.803.7900
CERTIFICATION:
CHECKED BY:
DRAWN BY:
MEP ENGINEER
THE ENGINEERING COLLABORATIVE
24 10 EXECUTIVE DRIVE, SUITE 100
INDIANAPOLIS, INDIANA 4 624 1
WWW.TEC-MEP.COM
317.636.3941
# Date Description
P
R
O
F
E
S
S
I
O
N
A
L
E
N
G
N
I
E
E
R
S
A
M
U
E
L
L.
H
U
R
T
I
N
D
I
A
N
A
0
N
P E 1 6
o .
10 0 87
S T A T E O F
R
E
T
E
G
I
S
D
E
R
12411 Pennsylvania St.
Carmel, Indiana 46032
Permit Set
JANUARY 17, 2018
Encore on Penn - Permit Set 01.17.18
First Floor Office Build-Out: Suites
E101
FIRST FLOOR LIGHTING PLAN
SLH
ALB
3/16" = 1'-0"
1 FIRST FLOOR LIGHTING PLAN
03/07/18
Nick Mishler