HomeMy WebLinkAboutEncore on Penn_First Floor Bui10 & 120_CONSTRUCTION DRAWI... 2PF
DW REF.
TRAVEL DISTANCE: 64'-0"
TRAVEL DISTANCE: 40'-0"
FEC
EXIT AT GRADE
EXIT AT
GRADE
EXIT AT
GRADE
FUTURE TENANT
NOT IN SCOPE OF
WORK
EXIT AT GRADE
TRAVEL DISTANCE: 71'-0"
TRAVEL DISTANCE: 36'-6"
TRAVEL
DISTANCE: 19'-4"
SUITE 120 SUITE 110
(ALT. BID)
EXISTING
ELEVATOR
EXISTING
UTILITY
EXISTING
LOBBY
EXIST.
JANITOR
EXISTING
RESTROOM
FEC
SYMBOL/LINETYPE DESCRIPTION
1 HR FIRE BARRIER
2 HR SMOKE/FIRE BARRIER
SMOKE RESISTANT CORRIDOR
NON-RATED INCIDENTAL USE SEPARATION
LIFE SAFETY PLAN LEGEND
3 HR SMOKE/FIRE BARRIER
F.E.C
.
FIRE EXTINGUISHER CABINET
CODE SUMMARY
APPLICABLE CODES:
2014 INDIANA BUILDING CODE
2014 INDIANA FIRE CODE
2014 INDIANA PLUMBING CODE
2014 INDIANA ELECTRICAL CODE
SCOPE OF PROJECT:
EXISTING SHELL: 19,085 GSF
LEVEL 1 - SUITE 110: 2,838 GSF
LEVEL 1 - SUITE 120 (ALT. BID): 564 GSF
OCCUPANCY CLASSIFICATION:
B-BUSINESS 100 GROSS
LEVEL 1 - SUITE 110: 2,838/100 = 29 OCC.
LEVEL 1 - SUITE 120 (ALT. BID): 564/100 = 6 OCC.
TOTAL: 35 OCC.
CHAPTER 10 MEANS OF EGRESS:
TABLE 1014.3 - COMMON PATH OF TRAVEL:
- 'B' OCCUPANCY W/SPRINKLER SYSTEM = 100'
TABLE 1015.1 - SPACES W/ ONE EXIT:
- 'B' OCCUPANCY = 49 MAX.
- TRAVEL DISTANCE LIMITED TO 75'
TABLE 1016.2 - EXIT ACCESS TRAVEL DISTANCE:
- 'B' OCCUPANCY W/SPRINKLER SYSTEM = 300'
TABLE 1018.1 - CORRIDOR FIRE RESISTANCE RATING:
- 'B' OCCUPANCY W/SPRINKLER SYSTEM = 0 HRS
TABLE 1016.2 - WHERE TWO EXITS ARE REQUIRED, THE EXIT DOORS SHALL NOT BE SEPARATED
LESS THAN ONE-THIRD OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL OF THE AREA
SERVED. (COMPLIES)
TABLE 1005.3 - MINIMUM REQUIRED EGRESS WIDTH:
- STAIRWAYS WIDTH = 57 * .3in = 17.1in (COMPLIES)
- OTHER MEANS = 57 * .2in = 11.4in (COMPLIES)
TABLE 1008.1.1 - 48" MAX. WIDTH, 32" CLEAR MIN. WIDTH
TABLE 1008.1.2 - EXIT DOOR SWING IN THE DIRECTION OF EGRESS WHEN SERVING
OCCUPANTS LOAD OF 50 PERSONS OR MORE.
TABLE 1011.1 - EXITS SHALL BE MARKED BY AN EXIT SIGN READILY VISIBLE FROM ANY
DIRECTION OF EGRESS TRAVEL. THEY SHALL BE PLACED SO THAT NO POINT IN A CORRIDOR IS
MORE THAN 100 FEET APART IN VIEW DISTANCE.
TABLE 1011.6.3 - EMERGENCY POWER REQUIRED. POWER SUPPLY NEEDED TO EMERGENCY
LIGHTING/EQUIPMENT DURIGN A POWER OUTAGE.
TABLE 1006.2 - EGRESS ILLUMINATION SHALL NOT BE LESS THAN ONE FOOT CANDLE AT THE
WALKING SURFACE.
TABLE 1027.1 - EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR OF THE BUILDING. THE EXIT
DISCHARGE SHALL BE AT GRADE OR SHALL PROVIDE DIRECT ACCESS AT GRADE.
CHAPTER 9: FIRE PROTECTION SYSTEMS
PROJECT HAS AUTOMATIC SPRINKLER SYSTEMS INSTALLED
CHAPTER 29: PLUMBING SYSTEMS
'B' OCCUPANCY"
- WATER CLOSETS:
MALE/FEMALE: 35/2 = 17.5 TOTAL OCC. = 2 REQUIRED
- LAVATORIES: 35/2 = 17.5 TOTAL OCC. = 1 REQUIRED
- DRINKING FOUNTAINS 35 TOTAL OCC. = 1 REQUIRED
- SERVICE SINK 1 REQUIRED
OCCUPANCY TABULATION PER 2012 IBC TABLE 1004.1 .1
REFLECTIVE SURFACE
3' - 4" MAX TO B.O. OF
TO T.O. TOWEL SLOT
RE: TABLE 603.6
MIRROR
(PUBLIC)
ICC A117.1 -2009
SECTION 603
PAPER TOWEL DISPENSER
(PUBLIC)
ICC A117.1 -2009
SECTION 603
SOAP DISPENSER
(PUBLIC)
ICC A117.1-2009
SECTION 603
T.O. PUSH BUTTON
48" MAX TO
T.O. SEAT
17" - 19"
18" MIN
MIN
1 1/2"
12" MAX
54" MIN
33" - 36" TO TOP
39" - 41"
39" - 41" 18" MIN
GRAB BARS & TOILET TISSUE DISPENSER
(PUBLIC)
ICC A117.1-2009
SECTION 604
17" - 19" AMBULATORY
24" MIN* 12" MIN
REAR GRAB BAR
(NOT REQD @
AMBULATORY)
SIDEWALL GRAB BARS.
PROVIDE ON EACH SIDE OF
AMBULATORY STALL
6"
3' - 6"
3' - 2"
LIGHT
SWITCH
DOOR
LEVER
6'-8" - 8'-0"
4' - 0" MAX
DOOR & DEVICES
(PUBLIC)
ICC A117.1-2009
SECTIONS 703 & 308
TYP WALL OUTLET
THERMOSTAT, PHONE,
FIRE ALARM PULL STATION,
HC DOOR BUTTON OR
CARD READER,
IF NOT OBSTRUCTED
FIRE ALARM
SPEAKER/STROBE
MIN
1' - 3"
ROOM SIGN
(PUBLIC)
ICC A117.1-2009
SECTION 703
FIRE EXTINGUISHER CABINET
(PUBLIC)
ICC A117.1-2009
SECTION 308
9" MIN
4' - 0"
4' - 0" MIN
5' - 0" MAX
TACTILE AREA OF
REFUGE SIGN
9" MIN 9" MIN
9" MIN
40" MIN
70" MAX
24" MIN
42" MAX
16" - 18" ACCESSIBLE
MAXIMUM REACH DEPTH 0.5 INCH 2 INCHES 5 INCHES 6 INCHES 9 INCHES 11 INCHES
(13 MM) (51MM) (125MM) (150 MM) (230MM) (288 MM)
MAXIMUM REACH HEIGHT 48 INCHES 46 INCHES 42 INCHES 40 INCHES 36 INCHES 34 INCHES
(1220 MM) (1170 MM) (1065 MM) (1015 MM) (915 MM) (865 MM)
ICC/ANSI A117.1 -2009 TABLE 603.6
MAXIMUM REACH DEPTH AND HEIGHT
CL
GENERAL NOTES
*12" MIN WHERE 24"
NOT POSSIBLE
CL
TO T.O. CONTROLS
RE: TABLE 603.6
HAND DRYER
(PUBLIC)
ICC A117.1-2009
SECTION 603
HANDLE AT
OPEN SIDE
CL
60" MIN CLEARANCE
MIN
9"
11" MIN 6" MAX
MIN
8"
2' - 3" MIN
2' - 10" MAX
17" - 25"
INSULATE ALL
EXPOSED PIPING
LAVATORY
(PUBLIC)
ICC A117.1-2009
SECTION 306
OUTLET AT COUNTER- PARALLEL APROACH
(PUBLIC)
ICC A117.1-2009
SECTION 308
46" MAX @ 24" MAX CAB DEPTH
48" MAX @ 10" MAX CAB DEPTH
2' - 10" MAX
FLUSH COUNTER
REQUIRED
MIN
9"
6" MAX
MIN
8"
2' - 3" MIN
2' - 10" MAX
24" MAX
INSULATE ALL
EXPOSED PIPING
KITCHEN SINK
(PUBLIC)
ICC A117.1-2009
SECTION 606 & 1003.12.4
NOTE:
CLEARANCE REQUIRED
AT ONLY ONE BOWL OF
MULTI-BOWL SINK
1. DIMENSIONS ARE COMPLIANT WITH ICC A117.1-2009.
2. NOT ALL FIXTURES AND DEVICES INDICATED MAY BE USED IN THE PROJECT.
3. MOUNTING HEIGHTS INDICATED MAY BE SUPERCEDED BY MORE SPECIFIC INFORMATION
ELSEWHERE IN THE DOCUMENTS.
4. "PUBLIC" INDICATES ELEMENTS TO COMPLY IN PUBLIC AREAS.
5. PROVIDE BLOCKING / REINFORCEMENT FOR ALL ACCESSORIES PER MANUFACTURER'S
INSTRUCTIONS.
6. GRAB BARS SHALL NOT ROTATE WITHIN THEIR FITTINGS & SHALL WITHSTAND A VERTICAL OR
HORIZONTAL FORCE OF 250 LBS APPLIED TO ANY POINT ON THE GRAB BAR, FASTENEER,
MOUNT, OR SUPPORT.
7. ALL APPLIANCES & PLUMBING FIXTURES MUST COMPLY WITH APPLICABLE ANSI & ADA
REQUIREMENTS. OPERABLE PARTS SHALL: 1) BE 34" - 48" AFF.; 2) BE OPERABLE WITH ONE HAND,
3) NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST, AND 4) BE
ACTIVATED BY NO MORE THAN 5 LBS OF FORCE.
8. DOOR THRESHOLDS MUST HAVE A MAXIMUM HEIGHT OF 1/2" WITH A 1:2 BEVEL.
BRAILLE TO BE
LOCATED DIRECTLY
UNDER SIGNAGE
INFORMATION
WOMEN MEN 1" TEXT
R
T
AR19900111
A
C
R
H
C
E
T
I
STATE OF
B
T
T
O
C
S
No.
T
S
I
G
E
R
E
R
E
D
N
E
T
R
A
E
P
K
S
N
I
I
A
N
A
D
N
I
ALL INFORMATION CONTAINED IN THIS
DOCUMENT IS CONSIDERED TO BE BOTH
CONFIDENTIAL AND PROPRIETARY
INTELLECTUAL PROPERTY OF BLACKLINE
STUDIO AND SHALL NOT BE COPIED,
REPRODUCED, DISTRIBUTED OR ASSIGNED TO
A THIRD PARTY WITHOUT PRIOR WRITTEN
CONSENT OF BLACKLINE STUDIO.
UNAUTHORIZED USE OF THESE DOCUMENTS IS
NOT PERMITTED.
c 2018 BLACKLINE STUDIO
ARCHITECT
BLACKLINE
1 N MERIDIAN ST, SUITE 400
INDIANAPOLIS, INDIANA 46204
BLACKLINESTUDIO.NET
317.803.79 00
CERTIFICATION:
CHECKED BY:
DRAWN BY:
MEP ENGINEER
THE ENGINEERING COLLABORATIVE
2410 EXECUTIVE DRIVE, SUITE 100
INDIANAPOLIS, INDIANA 46241
TEC-MEP.COM
317.636.39 41
1/18/2018 3:14:39 PM C:\Users\emaher\Documents\Encore Sotheby's Build-Out_maher@blacklinestudio.net.rvt
LS101
LIFE SAFETY PLAN
Encore on Penn - Permit Set 01.17.18
First Floor Office Build-Out: Suites
12411 Pennsylvania St.
Carmel, Indiana 46032
COPYRIGHT 2014
Permit Set
January 17, 2018
SBP
ERM
# Date Description
1/8" = 1'-0"
1 LIFE SAFETY PLAN - FIRST FLOOR
1/2" = 1'-0"
2 STANDARD MOUNTING HEIGHTS
1 1/2" = 1'-0"
3 TOILET ROOM SIGNS
03/07/18
Nick Mishler