HomeMy WebLinkAboutL100x
OFFICE
207
10'-0" 12'-0"
x
WORK
ROOM
204
9'-4" 16'-11"
x
ENTRY
201
13'-4" 26'-3"
REFRIG
BY
TENANT
OPEN OFFICE
210
x
CONF
203
12'-0" 17'-0"
MICRO
x
CONF
202
13'-0" 16'-11"
x
OFFICE
211
14'-9" 14'-9"
x
OFFICE
208
10'-0" 12'-0" x
OFFICE
206
10'-0" 12'-0"
x
OFFICE
215
x 10'-0" 12'-0"
OFFICE
214
x 9'-8" 12'-0"
OFFICE
213
x 10'-5 " 12'-0"
OFFICE
212
12'-6" 12'-0"
x
OFFICE
205
13'-11" 9'-9"
x
IT/STG.
209
12'-3" 8'-0"
DN
DN
UP
UP
UP
NLEL
NLEL
NLEL
FE
LIFE SAFETY
L100
LIFE SAFETY PLAN
DATE DESCRIPTION
ISSUE
02.09.18 REVIEW SET
02.13.18 PERMIT SET
REVISIONS
MARK DATE DB DESCRIPTION
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.
PROJECT NUMBER
PROJ. MGR DRAWN BY
450 E. 96th Street
Indianapolis, IN 46240
p: 317.387.1700
www.schottdesign.com
FOUR QUADRANTS
11939 N. MERIDIAN ST.- 2ND FLOOR
CARMEL, IN 46032
AS KV
2017.272
2ND FLOOR
N
0 4' 8' 16'
AREA NOT IN CONTRACT
AREA OF WORK
LIFE SAFETY NOTES GENERAL NOTES
SCOPE OF WORK OFFICE REMODEL OF PREVIOUSLY BUILT-OUT OFFICE SPACE
TOTAL BUILDING AREA
TOTAL PROJECT AREA
CHANGE OF OCCUPANCY CLASS?
OCCUPANCY CALCULATIONS SPACE TYPE AREA SF PER OCCUPANT OCCUP LOAD
NO
OCCUPANCY CLASSIFICATION B(USINESS)
GEN. OFFICE SF 100
SPRINKLER SYSTEM (YES/NO) YES - EXISTING TO REMAIN
TOTAL AREA OF ACCESSORY USES 0
TOTAL AREA ON THE FLOOR
SF
SF/FLOOR X STORIES SF
SF
20,519 SF
ACCESSORY AREA EXCEEDS 10% NO
FIRE WALLS, AND/OR OCCUPANCY
SEPARATIONS (IF REQUIRED)
N/A
=
TOTAL OCCUPANTS IN PROJECT AREA 39
CODE SUMMARY
PREVIOUS USE OF SPACE B(USINESS)
ASHRAE 90.1 SUMMARY REQUIREMENTS WILL BE MET (SEE REFLECTED CEILING PLAN)
BUILT BEFORE 1978? NO
3,829
3,829
20,519 3 61,557
39
BUILDING CONSTRUCTION TYPE II-B
1. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY.
2. PROVIDE ALARM NOTIFICATION APPLIANCES (HORNS/STROBES),
EMERGENCY SPEAKERS, SMOKE DETECTORS, FIRE PULLS, AND ANY
OTHER REQUIRED ALARM & DETECTION SYSTEMS AS NECESSARY TO
MEET ALL APPLICABLE CODES (INTERNATIONAL BUILDING CODE,
INTERNATIONAL FIRE CODE, NFPA). IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN SUITE,
ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI OR
TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT IN
CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE.
3. FIRE PROTECTION WORK IS TO BE PROVIDED BY DESIGN/BUILD
SERVICES UNDER THE GENERAL CONTRACT. PROVIDE A COMPLETE,
WORKING SYSTEM. SCHOTT DESIGN, INC., IS NOT RESPONSIBLE FOR
THE DESIGN, INSTALLATION, OR RENOVATION OF THE FIRE SPRINKLER
SYSTEM.
4. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL REQUIRED
DRAWINGS, AND SHALL FILE THOSE DRAWINGS, AND RELATED
DOCUMENTS, WITH THE STATE AND LOCAL AUTHORITIES HAVING
JURISDICTION OVER THE PROJECT.
5. FIRE EXTINGUISHERS: CONTRACTOR TO ENSURE ALL NEW AND
EXISTING FIRE EXTINGUISHERS ARE INSTALLED ACCORDING TO NFPA
10. COORDINATE WITH OWNER/LANDLORD ON EXTINGUISHER TYPE
AND HOUSING. MAXIMUM TRAVEL DISTANCE OF 75 FEET FROM ANY
POINT TO A VISIBLE EXTINGUISHER.
L1. REFER TO ARCHITECTURAL PLAN FOR WALL TYPE AND CONSTRUCTION
DETAILS.
L2. EXISTING COMMON CORRIDOR TO REMAIN. EXISTING EXIT SIGNS, FIRE
PULLS, FIRE EXTINGUISHERS, ALARM NOTIFICATION APPLIANCES TO
REMAIN. RELOCATE EXISTING EXIT SIGNS, FIRE PULLS, FIRE
EXTINGUISHERS AND ALARM NOTIFICATIONS AS REQUIRED TO MEET
ALL LOCAL AND STATE CODES.
EXISTING ELECTRICAL PANEL LOCATION
EXISTING EXIT
EP
EX
LEGEND
FIRE EXTINGUISHER
EXIT SIGN
FE FE
- BUILDING STAIR LOCATION
TRAVEL DISTANCE
NUMBER OF EXITS REQUIRED: 1 PROVIDED: 2
TRAVEL DISTANCE = 134'
BUSINESS
BUSINESS
EX
EX
EP
NIGHT LIGHT/EMERGENCY LIGHTING
NLEL
03/12/18
Nick Mishler