HomeMy WebLinkAboutME 1.1 Mechanical Electrical PlanCOMMON
SUITE 100
38'-10" x 76'-5"
SUITE 101
38'-10" x 76'-5"
PROGRAMMING
DESKS
15'-10" x 32'-1"
QC DESKS
17'-3" x 16'-0"
OFFICE
9'-0" x 12'-0" OFFICE
8'-6" x 12'-0"
OFFICE
12'-7" x 9'-8"
OFFICE
11'-3" x 9'-8"
KITCHEN
14'-4" x 15'-8"
OFFICE
10'-3" x 10'-0"
OFFICE
13'-10" x 10'-0"
RECEPTION
23'-10" x 14'-5"
OFFICE
9'-8" x 14'-4"
OFFICE
9'-11" x 16'-0"
OFFICE
9'-7" x 16'-0"
OFFICE
OFFICE 17'-7" x 10'-0"
10'-3" x 10'-0"
HALLWAY
17'-10" x 26'-0"
OFFICE
10'-10" x 11'-8"
OFFICE
12'-2" x 11'-8"
OFFICE
9'-4" x 16'-1"
OFFICE
10'-3" x 15'-8"
HALLWAY
28'-7" x 16'-11"
OFFICE
13'-10" x 10'-0"
OPEN
18'-8" x 23'-7"
CONFERENCE
ROOM
9'-11" x 16'-1"
TRAINING
ROOM
24'-2" x 26'-5"
N
S
W E
MECHANICAL ELECTRICAL PLAN
AG
AEM/ SA
DED Dedicated circuit
GFCI
Wall Receptacle: 120V, duplex - Install w/ ground pin
Wall Receptacle: 120V, duplex on Ground Fault Circuit
Interrupter
ELECTRICAL LEGEND
Wall Receptacle: telephone
N NEW Receptacle, all others shown are existing
ELECTRICAL NOTES
VERIFY LOCATIONS AND NUMBER OF LIGHT SWITCHES WITH TENANT PRIOR TO INSTALLATION.
VERIFY DEDICATED OUTLETS AND CIRCUITRY REQUIREMENTS WITH TENANT.
F.
I.
J.
L.
D.
E.
C.
B.
A.
G.
H.
K.
M.
N.
O.
P.
ELECTRICAL/DATA OUTLET LOCATIONS TO BE COORDINATED WITH TENANT PRIOR TO ROUGH-IN.
CONTRACTOR TO VERIFY ALL LOCATIONS WITH FURNITURE & EQUIPMENT PLACEMENT.
THESE ELECTRICAL DRAWINGS REFLECT LOCATIONS ONLY. CONSULT WITH GC FURTHER TECHNICAL
INFORMATION.
DO NOT SCALE DRAWINGS. ALL DIMENSIONS GIVEN ARE TO BE ADHERED TO, UNLESS FIELD CONDITIONS
DEEM OTHERWISE. ANY CONFLICTS THAT MAY EXIST W/ NEW CONSTRUCTION MUST BE REVIEWED BY THE
ARCHITECT/ DESIGNER PRIOR TO CONSTRUCTION OF WORK. DO NOT CIRCUMVENT DIMENSIONS BY
ATTACHING RECEPTACLES TO NEAREST STUD.
PROVIDE EMERGENCY STROBES AND HORNS AS REQUIRED BY STATE AND LOCAL BUILDING CODES. FA
CONTRACTOR TO COORDINATE ANY REQUISITE ALTERATIONS W/ OWNER.
ADJACENT OUTLETS SHALL BE GANGED WHEN POSSIBLE. IF THEY CANNOT BE GANGED, THEY SHALL BE
INSTALLED WITH A MINIMUM DISTANCE BETWEEN UNITS.
ALL DIMENSIONS SHOWN ARE TO CENTERLINE OF OUTLETS OR GROUPS OF OUTLETS, UNLESS NOTED
OTHERWISE.
SWITCH PLATES, MONUMENTS, AND ELECTRICAL COVER PLATES SHALL BE WHITE COLOR.
ALL WALL MOUNTED OUTLETS ARE TO BE MOUNTED 18" A.F.F. TO CENTERLINE OF OUTLET, UNLESS NOTED
OTHERWISE.
ELECTRICAL CONTRACTOR SHALL COORDINATE ANY ELECTRICAL OR LIGHTING REQUIREMENTS OF
MILLWORK WITH ARCHITECTURAL WOODWORK CONTRACTOR AS NECESSARY.
ELECTRICAL CONTRACTOR TO PROVIDE JUNCTION BOXES AT TELEPHONE/DATA LOCATIONS AS
INDICATED ON PLANS. COMPLETE TELEPHONE/DATA SYSTEMS (MATERIAL AND LABOR) ARE PROVIDED
BY THE TENANT UNLESS NOTED OTHERWISE.
ELECTRICAL CONTRACTOR TO COORDINATE SPECIAL ELECTRICAL EQUIPMENT REQUIREMENTS OF
TENANT'S AS SPECIFICALLY INDICATED ON DRAWINGS. VERIFY ACTUAL REQUIREMENTS WITH
ARCHITECT/DESIGNER PRIOR TO INSTALLATION.
THE ELECTRICAL CONTRACTOR SHALL NOTIFY THE ARCHITECT/DESIGNER OF ANY DISCREPANCIES
BETWEEN THE CONTRACT DOCUMENTS AND APPLICABLE CODES PRIOR TO CONSTRUCTION.
ALL MATERIAL AND WORKMANSHIP SHALL MEET ALL APPLICABLE STATE AND LOCAL CODES,
ORDINANCES, UTILITY COMPANY REGULATIONS AND NATIONALLY ACCEPTED CODES AND STANDARDS.
THE ELECTRICAL CONTRACTOR WILL BEAR ALL COSTS ARISING IN CORRECTING ANY NONCOMPLIANCE
WITH THE REQUIREMENTS OF APPLICABLE CODES.
THE ELECTRICAL CONTRACTOR IS TO PROVIDE ALL REQUIRED LABOR, MATERIAL, EQUIPMENT, AND
CONTRACTORS SERVICES NECESSARY TO COMPLETE INSTALLATION OF SYSTEMS REQUIRED IN FULL
CONFORMITY WITH APPLICABLE CODES AND ORDINANCES. THE FINISHED JOB SHALL BE FUNCTIONAL
AND COMPLETE IN EVERY DETAIL INCLUDING ANY AND ALL SUCH ITEMS FOR A COMPLETE SYSTEM.
New Electrical Panel:
A: Emergency Lighting 100A 120V Single Phase
B: Heating/ Cooling 225A 120/ 208V 3-Phase
C: Unit 300 Service 225A 120/ 208V 3-Phase
J Junction Box
# KEYED LIGHTING NOTES
1
2
NO NEW SERVICE OR PANEL- RECONFIGURE OF EXISTING BRANCH CTS ONLY.
New Emergency Light: Evenlite Inc., TLM2W
Wall Receptacle: 240V, duplex - Install w/ ground pin
FEC Fire Extinguisher Cabinet
ILLUMINATED EXIT SIGN WITH BATTERY BACKUP
PLUMBING NOTES
A.
NO PLUMBING IN SUITES.
Existing 4plex wall outlet
Switching Intent
S Single Pole Switch
F5: New Can Light Recessed: TBD
S
3 3-Way Switch
LIGHTING LEGEND
+ XX" Mounting height to center above finished floor
Provide GFCI protection for all 125-volt, single-phase, 15 and 20 ampere receptacles located within 6 feet of all
sinks. For GFCI receptacles located behind appliances that are that are not readily accessible to test/reset GFCI,
consider using GFCI breakers in the panel board which would be more readily accessible.
Q.
Support fixtures at each corner independent of the suspended ceiling; or alternatively, use suspended (and
supported) ceiling suitable for supporting fixtures and provide rated grid clips at each fixture corner. Use ceiling tie
wire same as ceiling.
R.
Wall Sconces to be ADA compliant so that objects projecting from walls with their leading edges between 27" and 80"
above the finished floor shall protrude no more than 4" into walks, halls, corridors, passageways or aisles.
S.
Exit Sign w/ Emergency Egress Light Twin Head LED w/ Battery Backup 90 min
Provide exterior, egress light at exit discharge doorway with battery backup suitable for 90 minutes of operation.
Consider the use of a remote head connected to the interior exit light with battery backup.
T.
Provide not less than one (1) foot-candle average of illumination along means of egress at the walking surface level
with a minimum at any point of 0.1 foot-candle. Provide egress lights where necessary. Provide with power backup
suitable for 90 minutes of operation.
U.
V. All electrical wiring will be done with MC cables passed and anchored appropriately through metal studs.
Lighting for all exterior applications not excepted in Section 9.1 shall have automatic controls capable of turning off
exterior lighting when sufficient daylight is available or when the light is not required during nighttime hours. Lighting
not designated for dusk-to-dawn operation shall be controlled by either a) a combination of a photo sensor and a time
switch or b) an astronomical time switch.
W.
Exterior Emergency Egress Light
THE INFORMATION CONTAINED HEREIN IS THE EXCLUSIVE PROPERTY OF
H.C.O., INC., AND IS THEREBY PROTECTED UNDER COPYRIGHT LAWS. THE
ORIGINAL IDEAS REPRESENTED HERE BY THIS INFORMATION SHALL NOT
BE USED, ALTERED, OR REPRODUCED IN ANY MANNER WITHOUT THE
EXPRESSED WRITTEN CONSENT OF H.C.O., INC.
SHEET NO:
DRAWN BY:
CHECKED BY:
PROJECT NO:
DATE:
REVISIONS:
CONSTRUCTION DOCUMENTS
COMPASS
RESIDENTIAL
OFFICE LAYOUT
9660 COMMERCE DR SUITE 100 & 101
CARMEL, INDIANA 46032
02.09.2018
P:\AE INTERIOR DESIGN\PROJECTS\2017-8 J Benzal\Drawings\ARCHITECTURAL\steve's stamp.jpg
AE DESIGNS
INTERIOR DESIGN
(317) 974-9328
Info@
TheAeExperience.com
GFCI
GFCI
2X4 RECESSED FLUORESCENT FIXTURE
S 4 4-Way Switch
03/16/18
Nick Mishler