1757840 - Sheet - T2-1 - GENERAL BUILDING SPECIFICATIONS
F. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION. FURNISH AND INSTALL ALL HARDWARE AS INDICATED ON THE PLAN. 08 80 00 GLAZING A. COMPLY WITH COMBINED WRITTEN INSTRUCTIONS OF MANUFACTURERS OF GLASS, SEALANTS, GASKETS, AND OTHER GLAZING MATERIALS, UNLESS MORE STRINGENT REQUIREMENTS ARE INDICATED, INCLUDING THOSE IN REFERENCED GLAZING PUBLICATIONS. B. PROTECT GLASS EDGES FROM DAMAGE DURING HANDLING AND INSTALLATION. REMOVE DAMAGED GLASS FROM PROJECT SITE AND LEGALLY DISPOSE OF OFF PROJECT SITE. DAMAGED GLASS IS GLASS WITH EDGE DAMAGE OR OTHER IMPERFECTIONS THAT, WHEN INSTALLED, COULD WEAKEN GLASS AND IMPAIR PERFORMANCE AND APPEARANCE. C. PROVIDE SAFETY GLASS IN ALL GLAZING AS LISTED BELOW UNLESS NOTED OTHERWISE: 1. WHERE REQUIRED BY FEDERAL, STATE AND LOCAL CODES. D. SAFETY GLASS REQUIREMENTS 1. SAFETY GLASS SHALL BE, BUT NOT LIMITED TO a.) TEMPERED GLASS b.) LAMINATED GLASS c.) SAFETY PLASTIC d.) SAFETY INSULATING UNITS WHICH MEET THE TEST REQUIREMENTS OF ANSI Z97.1, AND WHICH ARE CONSTRUCTED, TREATED, OR COMBINED WITH OTHER MATERIALS SO AS TO MINIMIZE THE LIKELIHOOD OF CUTTING AND PIERCING INJURIES RESULTING FROM HUMAN IMPACT WITH THE GLAZING MATERIAL. 2. ALL SAFETY GLAZING MATERIAL SHALL BE LABELED PER LOCAL, STATE, AND FEDERAL REQUIREMENTS. E. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION. FURNISH AND INSTALL THE GLAZING AS INDICATED ON THE PLAN. DIVISION 09 FINISHES 09 01 00 FINISHES A. REQUIREMENTS 1. PROVIDE AND INSTALL ALL FINISHES AS INDICATED ON PLANS. 2. INSTALL ALL MATERIALS PER MANUFACTURER'S RECOMMENDATIONS AND SPECIFICATIONS. 3. "FINISH" INSTALLER INSPECT SUBSURFACE AND PREPARE AS PER MANUFACTURER'S SPECIFICATIONS PRIOR TO INSTALLATION OF PRODUCT. 4. ALL FINISHES TO MEET ALL CODE REQUIREMENTS AND REGULATIONS INCLUDING FLAME SPREAD AND SMOKE DEVELOPMENT. B. EXTRA MATERIAL 1. PROVIDE NEW, EXTRA MATERIAL OF EACH FINISH TYPE AND COLOR TO BE TURNED OVER TO OWNER AT JOB COMPLETION FOR THE FOLLOWING ITEMS: a.) PAINT: PROVIDE 1 GALLON FOR FIELD COLORS AND 1 QUART FOR ACCENT COLORS APPLIED b.) RESILIENT FLOOR TILE: PROVIDE 1 BOX FOR EVERY 50 BOXES OR FRACTION THEREOF INSTALLED c.) ACOUSTICAL CEILING TILE: PROVIDE FULL-SIZE UNITS EQUAL TO 2% OF QUANTITY INSTALLED, BUT NOT LESS THAN 1 BOX d.) WOOD FLOORING: PROVIDE FULL-SIZE UNITS EQUAL TO 3% OF QUANTITY INSTALLED, BUT NOT LESS THAN 50 S.F. e.) LAMINATE FLOORING: CERAMIC, QUARRY AND PORCELAIN TILE: PROVIDE FULL-SIZE UNITS EQUAL TO 3% OF QUANTITY INSTALLED, BUT NOT LESS THAN 50 S.F. f.) RESILIENT SHEET FLOORING: PROVIDE NOT LESS THAN 10 LINEAR FEET FOR EACH 500 LINEAR FEET OR FRACTION THEREOF INSTALLED g.) WALL COVERING MATERIAL: PROVIDE FULL-SIZE UNITS EQUAL TO 5 PERCENT INSTALLED h.) TILE CARPET: PROVIDE FULL-SIZE UNITS EQUAL TO 5 PERCENT OF THE AMOUNT INSTALLED, BUT NOT LESS THAN 10 SQ. YD. i.)SHEET CARPET: PROVIDE FULL-WIDTH ROLLS EQUAL TO 5 PERCENT OF THE AMOUNT INSTALLED, BUT NOT LESS THAN 10 SQ. YD. j.)CERAMIC, QUARRY AND PORCELAIN TILE: PROVIDE FULL-SIZE UNITS EQUAL TO 3% OF QUANTITY INSTALLED, BUT NOT LESS THAN 50 S.F. 09 22 16 DRYWALL STUDS (INTERIOR NON-BEARING) A. REQUIREMENTS 1. STUDS SHALL BE SECURED TO TOP AND BOTTOM TRACK WITH (1) #8ML SCREW IN EACH FLANGE (UNLESS A SLIP TRACK IS REQUIRED AT THE TOP OF THE WALL). 2. PROVIDE SLIP TRACK AT TOP OF FULL HEIGHT PARTITIONS. 3. STUDS SHALL BE INSTALLED PER "GYPSUM CONSTRUCTION HANDBOOK" AS PUBLISHED BY UNITED STATES GYPSUM COMPANY LATEST EDITION. 4. DRYWALL STUDS SHALL BE ACCORDING TO THE LIST BELOW OR AS INDICATED ON THE PLANS (THESE HEIGHTS ARE BASED ON THE STUDS HAVING (1) LAYER OF DRYWALL EACH FACE). STUD SIZE - GUAGE - LIMITING HEIGHT WITH STUD SPACING 3 5/8" - 25 GA. - 13'-6" AT 16" O.C. - 11'-9" AT 24" O.C. 3 5/8" - 22 GA. - 15'-3" AT 16" O.C. - 13'-4" AT 24" O.C. 3 5/8" - 20 GA. - 15'-11" AT 16" O.C. - 13'-11" AT 24" O.C. 6" - 25 GA. - 20'-0" AT 16" O.C. - 17'-6" AT 24" O.C. 6" - 22 GA. - 22'-9" AT 16" O.C. - 19'-11" AT 24" O.C. 6" - 20 GA. - 23'-9" AT 16" O.C. - 20'-9" AT 24" O.C. 09 29 00 GYPSUM BOARD (GYP) A. DRYWALL SHALL BE INSTALLED PER THE LATEST EDITIONS OF "RECOMMENDED SPECIFICATIONS FOR THE APPLICATION AND FINISHING OF GYPSUM BOARD" GA-216 AS PUBLISHED BY THE GYPSUM ASSOCIATION AND THE "GYPSUM CONSTRUCTION HANDBOOK" AS PUBLISHED BY UNITED STATES GYPSUM COMPANY. 1. PROVIDE CONTROL JOINTS PER THESE REQUIREMENTS. B. COMPLY WITH ASTM C36 OR ASTM C 1396 AS APPLICABLE TO THE TYPE OF GYPSUM BOARD INDICATED. C. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, MANUFACTURES OFFERING PRODUCTS THAT MAY BE INCORPORATED INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING. 1. AMERICAN GYPSUM CO. 2. BPB AMERICAN INC. 3. G-P GYPSUM 4. LAFARGE NORTH AMERICA INC. 5. NATIONAL GYPSUM COMPANY 6. USG CORPORATION D. AT ALL TOILET ROOMS, LOCKERS ROOMS, COOLER/FREEZER ROOMS, UNDER FRP PANELS OR OTHER DAMP/WET LOCATIONS PROVIDE 1. MOLD TOUGH GYPSUM BY USG CORPORATION OR EQUAL. E. UNDER CERAMIC AND PORCELAIN TILE IN TOILET ROOMS, LOCKER ROOMS OR OTHER DAMP/WET LOCATIONS 1. FIBEROCK AQUA-TOUGH TILE BACKER BOARD BY USG CORPORATION OR EQUAL. F. UNDER CERAMIC AND PORCELAIN TILE IN SHOWERS, TUBS, KITCHEN WASH DOWN AREAS OR OTHER HIGH-MOISTURE AREAS. 1. DUROCK CEMENT BOARD BY USG CORPORATION OR EQUAL G. DRYWALL FINISHES SHALL BE INSTALLED PER THE LATEST EDITION OF "RECOMMENDED LEVELS OF GYPSUM BOARD FINISH" GA-214 AS PUBLISHED BY THE AWCI, PAINTING AND DECORATING CONTRACTORS OF AMERICA, GYPSUM ASSOCIATION AND CISCA. PROVIDE A LEVEL 1 FINISH AT ALL CONCEALED AND ABOVE CEILING AREAS AND A LEVEL 4 FINISH ON ALL EXPOSED BELOW CEILING AREAS OR AS NOTED ON PLANS. H. LEVELS OF FINISH: 1. LEVEL 0 - NO TAPING, FINISHING OR ACCESSORIES REQUIRED. 2. LEVEL 1 - JOINTS AND INTERIOR ANGLES HAVE TAPE SET IN JOINT COMPOUND; SURFACE IS FREE OF EXCESS JOINT COMPOUND; TOOL MARKS AND RIDGES ARE ACCEPTABLE; TAPE AND FASTENERS ARE NOT COVERED WITH JOINT COMPOUND. 3. LEVEL 2 - JOINTS AND INTERIOR ANGLES HAVE TAPE EMBEDDED IN JOINT COMPOUND AND HAVE A THIN COAT OF JOINT COMPOUND OVER JOINTS AND INTERIOR ANGLES; FASTENER HEADS AND ACCESSORIES ARE COVERED WITH JOINT COMPOUND; SURFACE IS FREE OF EXCESS JOINT COMPOUND; TOOL MARKS AND RIDGES ARE ACCEPTABLE. 4. LEVEL 3 - JOINTS AND INTERIOR ANGLES HAVE TAPE EMBEDDED IN JOINT COMPOUND AND ONE ADDITIONAL COAT OF JOINT COMPOUND OVER ALL JOINTS AND INTERIOR ANGLES; FASTENER HEADS AND ACCESSORIES COVERED WITH TWO (2) COATS OF JOINT COMPOUND; NO TOOL MARKS OR RIDGES. 5. LEVEL 4 - JOINTS AND INTERIOR ANGLES HAVE TAPE EMBEDDED IN JOINT COMPOUND AND TWO SEPARATE COATS OF JOINT COMPOUND APPLIED OVER ALL FLAT JOINTS AND ONE SEPARATE COAT APPLIED OVER INTERIOR ANGLES; FASTENER HEADS AND ACCESSORIES ARE COVERED WITH THREE (3) SEPARATE COATS OF JOINT COMPOUND; NO TOOL MARKS OR RIDGES. 6. LEVEL 5 - IN ADDITION TO REQUIREMENTS OF LEVEL 4, A THIN SKIM COAT OF JOINT COMPOUND OR EQUAL SHALL BE APPLIED TO THE ENTIRE SURFACE; NO TOOL MARKS OR RIDGES ON THIS SURFACE. 09 30 00 TILING A. COMPLY WITH TCA'S "HANDBOOK FOR CERAMIC TILE INSTALLATION" FOR TCA INSTALLATION METHODS SPECIFIED IN TILE INSTALLATION SCHEDULES B. JOINTS IN TILE SURFACE TO BE LOCATED DIRECTLY ABOVE JOINTS IN CONCRETE SUBSTRATES - BRIDGE CRACKS OR JOINTS WITH 'NOBLESEAL CIS' COMPOSITE SHEET MEMBRANE OVER ALL SAWCUT JOINTS IN CONCRETE SLABS WHERE BRIDGED BY PORCELAIN / CERAMIC TILE - INSTALL JOINT BRIDGING MATERAL PER MANUF. SPEC'S AND DETAILS C. PROVIDE MANUFACTURER'S STANDARD PORCELAIN / CERAMIC TILE AS SPECIFIED COMPLYING WITH STANDARD GRADE REQUIREMENTS OF ANSI A137.1 STATIC COEFFICIENT OF FRICTION TO BE 0.60 MIN AND A DYNAMIC COEFFICIENT OF FRICTION OF 0.42 MIN. D. PROVIDE COLORED GROUT AT ALL INTERIOR TILE SURFACES -COLOR TO BE SELECTED BY ARCHITECT/OWNER E. EXTEND TILE WORK INTO RECESSES AND UNDER OR BEHIND EQUIPMENT AND FIXTURES TO FORM COMPLETE COVERING WITHOUT INTERRUPTIONS UNLESS OTHERWISE INDICATED. TERMINATE WORK NEATLY AT OBSTRUCTIONS, EDGES, AND CORNERS WITHOUT DISRUPTING PATTERN OR JOINT ALIGNMENTS. F. ACCURATELY FORM INTERSECTIONS AND RETURNS. PERFORM CUTTING AND DRILLING OF TILE WITHOUT MARRING VISIBLE SURFACES. CAREFULLY GRIND CUT EDGES OF TILE ABUTTING TRIM, FINISH, OR BUILT-IN ITEMS FOR STRAIGHT ALIGNED JOINTS. FIT TILE CLOSELY TO ELECTRICAL OUTLETS, PIPING, FIXTURES, AND OTHER PENETRATIONS SO PLATES, COLLARS, OR COVERS OVERLAP TILE. G. JOINTING PATTERN: LAY TILE IN GRID PATTERN UNLESS OTHERWISE INDICATED. LAY OUT TILE WORK AND CENTER TILE FIELDS IN BOTH DIRECTIONS IN EACH SPACE OR ON EACH WALL AREA. LAY OUT TILE WORK TO MINIMIZE THE USE OF PIECES THAT ARE LESS THAN HALF OF A TILE. PROVIDE UNIFORM JOINT WIDTHS UNLESS OTHERWISE INDICATED. H. METAL EDGE STRIPS: INSTALL WHERE EXPOSED EDGE OF TILE FLOORING MEETS CARPET, WOOD, OR OTHER FLOORING THAT FINISHES FLUSH WITH OR BELOW TOP OF TILE AND NO THRESHOLD IS INDICATED. I. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION 09 51 13 ACOUSTICAL PANEL CEILINGS A. COMPLY WITH ASTM C636 (STANDARD PRACTICE FOR INSTALLATION OF METAL CEILING SUSPENSION SYSTEMS FOR ACOUSTICAL TILE AND LAY-IN PANELS), ASTM C635 (STANDARD SPECIFICATION FOR THE MANUFACTURE, PERFORMANCE AND TESTING OF METAL SUSPENSION SYSTEMS FOR ACOUSTICAL TILE AND LAY-IN PANEL CEILINGS) AND SEISMIC DESIGN REQUIREMENTS INDICATED, PER MANUFACTURER'S WRITTEN INSTRUCTIONS AND CISCA'S "CEILING SYSTEMS HANDBOOK." B. SUSPEND CEILING HANGERS FROM BUILDING'S STRUCTURAL MEMBERS, PLUMB AND FREE FROM CONTACT WITH INSULATION OR OTHER OBJECTS WITHIN CEILING PLENUM. SPLAY HANGERS ONLY WHERE REQUIRED?AND, IF PERMITTED WITH FIRE-RESISTANCE-RATED CEILINGS, TO MISS OBSTRUCTIONS; OFFSET RESULTING HORIZONTAL FORCES BY BRACING, COUNTERSPLAYING, OR OTHER EQUALLY EFFECTIVE MEANS. WHERE WIDTH OF DUCTS AND OTHER CONSTRUCTION WITHIN CEILING PLENUM PRODUCES HANGER SPACINGS THAT INTERFERE WITH LOCATION OF HANGERS, USE TRAPEZES OR EQUIVALENT DEVICES. WHEN STEEL FRAMING DOES NOT PERMIT INSTALLATION OF HANGER WIRES AT SPACING REQUIRED, INSTALL CARRYING CHANNELS OR OTHER SUPPLEMENTAL SUPPORT FOR ATTACHMENT OF HANGER WIRES. WIRE HANGERS TO BE ZINC-COATED CARBON STEEL WIRE COMPLYING WITH ASTM A641 STANDARDS, SIZED TO WITHSTAND 5X THE HANGER DESIGN LOAD BUT NOT LESS THAN .106" C. INSTALL EDGE MOLDINGS AND TRIM AT PERIMETER OF ACOUSTICAL CEILING AREA AND WHERE NECESSARY TO CONCEAL EDGES OF ACOUSTICAL PANELS. SCREW ATTACH MOLDINGS TO SUBSTRATE, LEVELING WITH CEILING SUSPENSION SYSTEM. MITER CORNERS ACCURATELY AND CONNECT SECURELY D. INSTALL SUSPENSION SYSTEM RUNNERS SO THEY ARE SQUARE AND SECURELY INTERLOCKED WITH ONE ANOTHER. REMOVE AND REPLACE DENTED, BENT, OR KINKED MEMBERS. SUSPENSION SYSTEM AS REQUIRED FOR THE SPECIFIED TILE-INTERMEDIATE DUTY CLASSIFICATION. PROVIDE CORROSION RESISTANT GRID IN SHOWER AND EXTREME ENVIRONMENT AREAS. E. INSTALL ACOUSTICAL PANELS WITH UNDAMAGED EDGES AND FIT ACCURATELY INTO SUSPENSION SYSTEM RUNNERS AND EDGE MOLDINGS. SCRIBE AND CUT PANELS AT BORDERS AND PENETRATIONS TO PROVIDE A NEAT, PRECISE FIT. F. PROVIDE HOLD-DOWN CLIPS AT ENTRY VESTIBULE(S) AND FOR FIRST 12' OF CORRIDOR(S) IN FRONT OF EACH EXTERIOR DOOR. G. PROVIDE APPROVED FIRE RATED GRID SYSTEM FOR FIRE RATED CEILINGS H. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION 09 64 00 WOOD FLOORING (WF) A. COMPLY WITH FLOORING MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS, BUT NOT LESS THAN APPLICABLE RECOMMENDATIONS IN NWFA'S "INSTALLATION GUIDELINES: WOOD FLOORING." B. PROVIDE EXPANSION SPACE AT WALLS AND OTHER OBSTRUCTIONS AND TERMINATIONS OF FLOORING C. SOLID-WOOD FLOORING: BLIND NAIL OR STAPLE FLOORING TO SUBSTRATE D. PROTECT INSTALLED WOOD FLOORING DURING REMAINDER OF CONSTRUCTION PERIOD WITH COVERING OF HEAVY KRAFT PAPER OR OTHER SUITABLE MATERIAL. DO NOT USE PLASTIC SHEET OR FILM THAT MIGHT CAUSE CONDENSATION. E. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION 09 65 13 RESILIENT BASE AND ACCESSORIES A. PROVIDE MANUFACTURES STANDARD VINYL WAS BASE AS SPECIFIED THAT COMPLIES WITH ASTM F1861 TYPE TV. B. PROVIDE MANUFACTURES STANDARD VINYL ACCESSORIES AS SPECIFIED THAT COMPLIES WITH ASTM F2169 TYPE TV C. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLING RESILIENT BASE AND ACCESSORIES. D. PREPARE SUBSTRATES ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS TO ENSURE ADHESION OF BASE AND ACCESSORIES. E. APPLY RESILIENT BASE TO WALLS, COLUMNS, PILASTERS, CASEWORK AND CABINETS IN TOE SPACES AND OTHER PERMANENT FIXTURES IN ROOMS AND AREAS WHERE BASE IS SPECIFIED. F. INSTALL RESILIENT BASE IN LENGTHS AS LONG AS PRACTICAL WITHOUT GAPS AT SEAMS AND WITH TOPS OF ADJACENT PIECES ALIGNED. G. TIGHTLY ADHERE RESILIENT BASE OR ACCESSORY TO SUBSTRATE THROUGHOUT LENGTH OF EACH PIECE, WITH BASE OR ACCESSORY IN CONTINUOUS CONTACT WITH HORIZONTAL AND VERTICAL SUBSTRATES. H. DO NOT STRETCH RESILIENT BASE DURING INSTALLATION. I. ON MASONRY SURFACES OR OTHER SIMILAR IRREGULARS SUBSTRATES, FILL VOIDS ALONG TOP EDGE OF RESILIENT BASE WITH MANUFACTURER'S RECOMMENDED ADHESIVE FILLER MATERIAL. J. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION 09 65 16 RESILIENT SHEET FLOORING (RSF) K. PREPARE SUBSTRATES ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS TO ENSURE ADHESION OF FLOOR COVERINGS. 1. MOISTURE TESTING: PERFORM TESTS RECOMMENDED BY MANUFACTURER. PROCEED WITH INSTALLATION ONLY AFTER SUBSTRATES PASS TESTING. L. FILL CRACKS, HOLES, AND DEPRESSIONS IN SUBSTRATES WITH TROWELABLE LEVELING AND PATCHING COMPOUND AND REMOVE BUMPS AND RIDGES TO PRODUCE A UNIFORM AND SMOOTH SUBSTRATE. M. DO NOT INSTALL FLOOR COVERINGS UNTIL THEY ARE SAME TEMPERATURE AS SPACE WHERE THEY ARE TO BE INSTALLED. N. SWEEP AND VACUUM CLEAN SUBSTRATES TO BE COVERED BY FLOOR COVERINGS IMMEDIATELY BEFORE INSTALLATION. O. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLING FLOOR COVERINGS. P. UNROLL FLOOR COVERINGS AND ALLOW THEM TO STABILIZE BEFORE CUTTING AND FITTING. Q. SCRIBE AND CUT FLOOR COVERINGS TO BUTT NEATLY AND TIGHTLY TO VERTICAL SURFACES, PERMANENT FIXTURES, AND BUILT-IN FURNITURE INCLUDING CABINETS, PIPES, OUTLETS, AND DOOR FRAMES. R. ADHERE FLOOR COVERINGS TO SUBSTRATES USING A FULL SPREAD OF ADHESIVE APPLIED TO SUBSTRATE TO PRODUCE A COMPLETED INSTALLATION WITHOUT OPEN CRACKS, VOIDS, RAISING AND PUCKERING AT JOINTS, TELEGRAPHING OF ADHESIVE SPREADER MARKS, AND OTHER SURFACE IMPERFECTIONS. S. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR CLEANING AND PROTECTION OF FLOOR COVERING. T. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION. 09 65 19 RESILIENT TILE FLOORING (RTF) A. PROVIDE MANUFACTURES STANDARD VINYL COMPOSITE FLOOR TILE AS SPECIFIED COMPLYING WITH ASTM F1066 CLASSIFICATIONS. B. PREPARE SUBSTRATES ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS TO ENSURE ADHESION OF FLOOR COVERINGS. 1. MOISTURE TESTING: PERFORM TESTS RECOMMENDED BY MANUFACTURER. PROCEED WITH INSTALLATION ONLY AFTER SUBSTRATES PASS TESTING. C. FILL CRACKS, HOLES, AND DEPRESSIONS IN SUBSTRATES WITH TROWELABLE LEVELING AND PATCHING COMPOUND AND REMOVE BUMPS AND RIDGES TO PRODUCE A UNIFORM AND SMOOTH SUBSTRATE. D. DO NOT INSTALL FLOOR COVERINGS UNTIL THEY ARE SAME TEMPERATURE AS SPACE WHERE THEY ARE TO BE INSTALLED. E. SWEEP AND VACUUM CLEAN SUBSTRATES TO BE COVERED BY FLOOR COVERINGS IMMEDIATELY BEFORE INSTALLATION. F. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLING FLOOR TILE. G. LAY OUT FLOOR TILES FROM CENTER MARKS ESTABLISHED WITH PRINCIPAL WALLS, DISCOUNTING MINOR OFFSETS, SO TILES AT OPPOSITE EDGES OF ROOM ARE OF EQUAL WIDTH. ADJUST AS NECESSARY TO AVOID USING CUT WIDTHS THAT EQUAL LESS THAN ONE-HALF TILE AT PERIMETER. MATCH TILES FOR COLOR/PATTERN AND LAY TILE WITH GRAIN DIRECTION ALTERNATING IN ADJACENT TILES H. SCRIBE, CUT, AND FIT FLOOR TILES TO BUTT NEATLY AND TIGHTLY TO VERTICAL SURFACES AND PERMANENT FIXTURES INCLUDING BUILT-IN FURNITURE, CABINETS, PIPES, OUTLETS, AND DOOR FRAMES. I. EXTEND FLOOR TILES INTO TOE SPACES, DOOR REVEALS, CLOSETS, AND SIMILAR OPENINGS. EXTEND FLOOR TILES TO CENTER OF DOOR OPENINGS. J. ADHERE FLOOR TILES TO FLOORING SUBSTRATES USING A FULL SPREAD OF ADHESIVE APPLIED TO SUBSTRATE TO PRODUCE A COMPLETED INSTALLATION WITHOUT OPEN CRACKS, VOIDS, RAISING AND PUCKERING AT JOINTS, TELEGRAPHING OF ADHESIVE SPREADER MARKS, AND OTHER SURFACE IMPERFECTIONS. K. FLOORING CONTRACTOR SHALL STRIP AND FINISH ALL VCT FLOORING AS RECOMMENDED PER MANUFACTURERS SPECIFICATIONS PRIOR TO OCCUPANCY. L. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR CLEANING AND PROTECTION OF FLOOR TILE. M. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION. 09 68 13 TILE CARPETING (TC) A. GENERAL: COMPLY WITH CRI 104, SECTION 14, "CARPET MODULES," AND WITH CARPET TILE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS. B. PREPARE FLOOR SURFACES RECEIVING NEW FLOORING AS REQUIRED FOR A SMOOTH AND LEVEL SURFACE PRIOR TO INSTALLING NEW FLOORING. C. INSTALLATION METHOD: AS RECOMMENDED IN WRITING BY CARPET TILE MANUFACTURER. D. EXTEND CARPET TILE INTO TOE SPACES, DOOR REVEALS, CLOSETS, OPEN-BOTTOMED OBSTRUCTIONS, REMOVABLE FLANGES, ALCOVES, AND SIMILAR OPENINGS. E. INSTALL PATTERN PARALLEL TO WALLS AND BORDERS. F. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION. 09 68 16 SHEET CARPET (SC) A. COMPLY WITH CRI 104 AND CARPET MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS. B. PREPARE FLOOR SURFACES RECEIVING NEW FLOORING AS REQUIRED FOR A SMOOTH AND LEVEL SURFACE PRIOR TO INSTALLING NEW FLOORING. C. COMPLY WITH CARPET MANUFACTURER'S WRITTEN RECOMMENDATIONS AND SHOP DRAWINGS FOR SEAM LOCATIONS AND DIRECTION OF CARPET; MAINTAIN UNIFORMITY OF CARPET DIRECTION AND LAY OF PILE. AT DOORWAYS, CENTER SEAMS UNDER THE DOOR IN CLOSED POSITION D. EXTEND CARPET INTO TOE SPACES, DOOR REVEALS, CLOSETS, OPEN-BOTTOMED OBSTRUCTIONS, REMOVABLE FLANGES, ALCOVES, AND SIMILAR OPENINGS. E. INSTALL PATTERN PARALLEL TO WALLS AND BORDERS. F. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION. 09 72 00 WALL COVERING A. CLEAN SUBSTRATES OF SUBSTANCES THAT COULD IMPAIR BOND OF WALL COVERING, INCLUDING DIRT, OIL, GREASE, MOLD, MILDEW, AND INCOMPATIBLE PRIMERS. B. PREPARE SUBSTRATES TO ACHIEVE A SMOOTH, DRY, CLEAN, STRUCTURALLY SOUND SURFACE FREE OF FLAKING, UNSOUND COATINGS, CRACKS, AND DEFECTS. C. ACCLIMATIZE WALL-COVERING MATERIALS BY REMOVING THEM FROM PACKAGING IN THE INSTALLATION AREAS NOT LESS THAN 24 HOURS BEFORE INSTALLATION. D. CUT WALL-COVERING STRIPS IN ROLL NUMBER SEQUENCE. CHANGE ROLL NUMBERS AT PARTITION BREAKS AND CORNERS. E. INSTALL WALL COVERING WITH NO GAPS OR OVERLAPS, NO LIFTED OR CURLING EDGES, AND NO VISIBLE SHRINKAGE. F. MATCH PATTERN AT 72" ABOVE FINISHED FLOOR. G. EXTEND WALL COVERING A MIN. OF 6" BEHIND PERMANENT CASEWORK AND EQUIPMENT. H. INSTALL SEAMS VERTICAL AND PLUMB AT LEAST 6 INCHES (150 MM) FROM OUTSIDE CORNERS AND 3 INCHES (75 MM) FROM INSIDE CORNERS UNLESS A CHANGE OF PATTERN OR COLOR EXISTS AT CORNER. NO HORIZONTAL SEAMS ARE PERMITTED. I. FULLY BOND WALL COVERING TO SUBSTRATE. REMOVE AIR BUBBLES, WRINKLES, BLISTERS, AND OTHER DEFECTS. J. REMOVE EXCESS ADHESIVE AT FINISHED SEAMS, PERIMETER EDGES, AND ADJACENT SURFACES. K. ADHESIVE TO BE MILDEW RESISTANT, NON-STAINING AS RECOMMENDED BY THE WALL COVERING MANUFACTURER. L. SEE PLAN FOR PRODUCT SPECIFICATION AND LOCATION. 09 91 00 PAINTING A. REMOVE AND/OR PROTECT ALL HARDWARE, HARDWARE ACCESSORIES, MACHINED SURFACES, PLATES, LIGHTING FIXTURES, SPRINKLER HEADS AND SIMILAR ITEMS THAT ARE NOT TO BE PAINTED, BUT REQUIRE PROTECTION FROM THE PAINTING PROCESS. RE-INSTALL SAME AFTER COMPLETION OF PAINTING. MASK OFF ALL NAMEPLATES, EQUIPMENT IDENTIFICATION AND SIMILAR ITEMS. REMOVAL AND REINSTALL OF ITEMS IS TO BE DONE BY CONTRACTOR SKILLED IN SUCH WORK. B. SEAL TOPS, BOTTOMS AND CUTOUTS OF UNPRIMED WOOD DOORS WITH A HEAVY COAT OF SEALER IMMEDIATELY UPON DELIVERY TO THE PROJECT. C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER PREPARATION OF ALL SURFACES PRIOR TO THE PAINTING INSTALLATION D. GALVANIZED METAL: CLEAN PER SSPC-SP1 USING DETERGENT AND WATER OR A DEGREASING CLEANER TO REMOVE GREASES AND OILS. APPLY A TEST AREA, PRIMING AS REQUIRED. ALLOW THE COATING TO DRY AT LEAST ONE WEEK BEFORE TESTING. IF ADHESION IS POOR, BRUSH BLAST PER SSPC-SP7 IS NECESSARY TO REMOVE THESE TREATMENTS. E. THE FINISH PRODUCT SHALL HAVE A CONSISTENT, SMOOTH APPEARANCE OF THE SPECIFIED LUSTER. F. APPLY PAINT PER MANUFACTURER'S TEMPERATURE AND HUMIDITY REQUIREMENTS. G. COMPLETED WORK SHALL BE FREE FROM DEFECTS AND FLAWS. H. FURNISH ALL LABOR, MATERIALS, TOOLS, EQUIPMENT AND SCAFFOLDING REQUIRED FOR COMPLETING SURFACE PREPARATION, PAINTING, FINISHING AND RELATED ITEMS. I. EXCESS MATERIALS, CONTAINERS AND OTHER ITEMS NECESSARY FOR THE COMPLETION OF THE WORK MUST BE DISPOSED OF IN A MANNER THAT MEETS OR EXCEEDS THE STRICTEST LAWS GOVERNING THE PROJECT'S MUNICIPALITY AND/OR STATE. THE PAINTING CONTRACTOR IS RESPONSIBLE FOR COMPLETE ADHERENCE TO ALL DISPOSAL REGULATIONS. J. PAINT ALL EXPOSED MISCELLANOUS ITEMS, FINISHED OR UNFINISHED (EXCLUDING H.V.A.C. RETURN AIR GRILLES, CONDUIT, ETC.) TO MATCH ADJOINING WALL SURFACES. K. CONTRACTOR TO VERIFY THAT PAINT IS COMPATIBLE WITH PRIMER OF SHOP PRIMED SURFACES. NOTIFY EXCEL ENGINEERING IF THERE ARE ANY COMPATIBILITY ISSUES. L. THE CONTRACTOR SHALL KEEP EMPTY CONTAINERS ON THE PROJECT SITE UNTIL ALL PRODUCTS ARE VERIFIED AS TO COLOR AND/OR SHEEN. THE CONTRACTOR SHALL LEAVE WITH THE OWNER ALL OPENED PAINT CONTAINERS. M. ALL PAINT COLORS, STAIN COLORS, AND VARNISH TO BE SELECTED BY ARCHITECT/OWNER FROM A FULL RANGE OF AVAILABE COLORS. N. ALL EXPOSED EXTERIOR& INTERIOR METAL SURFACES SHALL BE PAINTED, U.N.O. O. EXTERIOR ITEMS: 1. FERROUS METAL (PRIMED): STRUCTURAL STEEL, MISCELLANEOUS IRON, HANDRAILS, HOLLOW METAL DOORS AND FRAMES, ROOF STRUCTURE, EXPOSED ROOF PIPING, ETC.: a.) ALKYD SHOP PRIMER ON METAL OR 1 COAT S-W KEM BOND HS UNIVERSAL METAL PRIMER B50 SERIES b.) 2 COATS S-W PRO INDUSTRIAL ACRYLIC SEMIGLOSS, B66-650 @ 2.5-4.0 MILS DFT/COAT. 2. GALVANIZED, ALUMINUM, ZINC-COATED AND NON FERROUS METALS: a.) 1 COAT S-W PRO INDUSTRIAL PRO-CRYL UNIVERSAL PRIMER, B66-310 SERIES, @ 2.0-4.0 MILS DFT. b.) 2 COATS S-W PRO INDUSTRIAL ACRYLIC SEMIGLOSS, B66-650 @ 2.5-4.0 MILS DFT/COAT. 3. CONCRETE: a.) 1 COAT S-W LOXON CONCRETE MASONRY PRIMER A24W8300 @ 2.0-3.5 MILS DFT b.) 2 COAT S-W A-100 EXTERIOR LATEX SATIN A82 SERIES @ 1.5-2.0 MILS DFT/COAT P. INTERIOR ITEMS: 1. GYPSUM DRYWALL FINISH: EG-SHEL a.) 1 COAT S-W PROMAR 200 ZERO VOC INTERIOR LATEX PRIMER B28W2600 @ 1.2-1.5 MILS DFT. b.) 2 COATS S-W PROMAR 200 ZERO VOC INTERIOR LATEX EG-SHEL B20-2600 @ 1.6-2.2 MILS DFT/COAT. 2. GYPSUM DRYWALL FINISH: FLAT a.) 1 COAT S-W PROMAR 200 ZERO VOC INTERIOR LATEX PRIMER B28W2600 @ 1.2-1.5 MILS DFT b.) 2 COATS S-W PROMAR 200 ZERO VOC INTERIOR LATEX FLAT B30W2600 @ 1.6-2.2 MILS DFT/COAT. 3. GYPSUM DRYWALL FINISH: SEMI-GLOSS a.) 1 COAT S-W PROMAR 200 ZERO VOC INTERIOR LATEX PRIMER B28W2600 @ 1.2-1.5 MILS DFT. b.) 2 COATS S-W PROMAR 200 ZERO VOC INTERIOR LATEX SEMI-GLOSS B31W2600 @ 1.6-2.2 MILS DFT/COAT. 4. GYPSUM DRYWALL FINISH: EPOXY SYSTEM SEMI-GLOSS a.) 1 COAT S-W PROMAR 200 ZERO VOC INTERIOR LATEX PRIMER B28W2600 @ 1.2-1.5 MILS DFT. b.) 2 COATS S-W PRO INDUSTRIAL WATER BASED CATALYZED EPOXY B73 SERIES @ 2.0-4.0 MILS DFT/COAT. 5. NEW WOOD, STAINED: a.) 1 COAT S-W WOOD CLASSICS 250 INTERIOR OIL STAIN A49-800 SERIES. b.) 1 COAT S-W WOOD CLASSICS WATERBORNE POLYURETHANE GLOSS VARNISH A68. c.) 1 COAT S-W WOOD CLASSICS WATERBORNE POLYURETHANE SATIN VARNISH A68 d.) 0.8-1.2 MILS DTF/COAT. 6. NEW WOOD, PAINTED: a.) 1 COAT S-W PREMIUM WALL AND WOOD PRIMER B28W8111 @ 1.8-2.1 MILS DFT. b.) 2 COATS S-W PRO INDUSTRIAL ACRYLIC SEMIGLOSS B-66-650 @ 2.5-4.0 MILS DFT/COAT. 7. FERROUS METAL (PRIMED, BRUSH/ROLLER) - DOORS, FRAMES, HANDRAILS, MISC. METALS, ETC.: ACRYLIC a.) 1 COAT S-W PRO INDUSTRIAL PRO-CRYL UNIVERSAL PRIMER B66-310 @ 2.0-4.0 MILS DFT. b.) 2 COATS S-W PRO INDUSTRIAL ACRYLIC SEMIGLOSS B-66-650 @ 2.5 - 4 MILS DFT/COAT. 8. FERROUS METAL (PRIMER, SPRAYED), ALL EXPOSED STRUCTURAL STEEL AND EXPOSED MECHANICAL/ELECTRICAL ITEMS: FINISH IS ALKYD a.) SPOT PRIME AS NEEDED: S-W KEM BOND HS UNIVERSAL METAL PRIMER B50 SERIES @ 2.0-5.0 MILS DFT. b.) FINISH COAT S-W SUPER SAVE-LITE HI-TEC DRY FALL, EGGSHEL B48 SERIES @ 3.0-3.5 MILS DFT. 9. FERROUS METAL-ACRYLIC SYSTEM (PRIMER, SPRAYED), ALL EXPOSED STRUCTURAL STEEL AND EXPOSED MECHANICAL/ELECTRICAL ITEMS. NORMAL EXPOSURE, CONFIRM COMPATABILITY WITH SHOP APPLIED PRIMERS a.) SPOT PRIME AS NEEDED: S-W PRO INDUSTRIAL PRO-CRYL UNIVERSAL PRIMER @ 2.0-4.0 MILS DFT b.) -FINISH COAT S-W PRO INDUSTRIAL WATERBORNE ACRYLIC DRY FALL, EG-SHEL, B 42W2 @ 3.0-4.5 MILS DFT 1). CONTRACTOR SHALL MAINTAIN A DAILY LOG OF TEMPERATURE (50F-110F) AND RELATIVE HUMIDITY 2). AMBIENT TEMPERATURE AND SUBSTRATE TEMPERATURE SHALL BE 50 DEGREES F TO 110 DEGREES F. 3). RELATIVE HUMIDITY SHALL NOT EXCEED 75%. 10. GALVANIZED: INTERIOR CEILING DECKING: a.) SPRAYED: 1). FINISH COAT S-W PRO INDUSTRIAL WATERBORNE ACRYLIC DRYFALL, EG-SHEL, B42W2 @ 3.0-4.5 MILS DFT. 11. ALUMINUM,ZIC-COATED AND NON FERROUS METALS: a.) 1 COAT S-W PRO INDUSTRIAL PRO-CRYL UNIVERSAL PRIMER B66-310 @ 2.0 - 4.0 MILS DFT b.) 2 COATS S-W PRO INDUSTRIAL ACRYLIC SEMIGLOSS B66-650 @ 2.5-4.0 MILS DFT/COAT. 12. CONCRETE MASONRY UNITS: ACRYLIC FINISH: SEMI-GLOSS a.) 1 COAT S-W PREPRITE BLOCK FILLER B25W25- WHITE. b.) 2 COATS S-W PROMAR 200 ZERO VOC INTERIOR LATEX SEMI-GLOSS B31W2600 @ 1.6 -2.2 MILS DFT/COAT. 13. CONCRETE MASONRY UNITS EPOXY FINISH: SEMI-GLOSS a.) 1 COAT S-W HEAVY DUTY BLOCKFILLER B42W46-WHITE. b.) 2 COATS S-W PRO INDUSTRIAL WATER BASED CATALYZED EPOXY B73 SERIES @ 2.0-4.0 MILS DFT/COAT. 14. PRECAST CONCRETE: EG-SHELL a.) 1 COAT S-W LOXON CONCRETE MASONRY PRIMER A24W8300 @ 2.0-3.5 MILS DFT b.) 2 COAT S-W PROMAR 200 ZERO VOC INTERIOR LATEX EG-SHELL B20 SERIES @ 1.5-2.0 MILS DFT/COAT 15. FERROUS METAL (PRIMER, SPRAYED), ALL EXPOSED STRUCTURAL STEEL EPOXY/URETHANE a.) PREPARATION SSPC-SP-6 COMMERCIAL BLAST b.) 1 COAT DUPONT CORLAR 2.1 - LF63225P WHITE (4.0 - 6.0 DFT) MIX 1:1 WITH VF525 ACTIVATOR. (IF ROLLER APPLIED USE 5% RT001P ROLLING THINNER PER MIXED GALLON OF EPOXY). c.) 1 COAT DUPONT IMRON 3.5 HG -33M24861 WHITES (2.0 MILS DFT) MIX 4:1 WITH VG-M6005 ACTIVATOR. (IF ROLLER APPLIED USE 1OZ OF RT002P ROLLING ADDITIVE PER MIXED GALLON OF IMRON). Q. PROVIDE A YELLOW STRIPED AREA, 3' DEEP BY THE WIDTH OF THE ELECTRICAL PANELS, ON THE CONCRETE FLOOR IN FRONT OF THE ELECTRICAL PANELS AND SWITCHGEAR IN THE RECEIVING AREA. AT THE SWITCHGEAR, PAINT THE EXPOSED PORTION OF THE CONCRETE HOUSEKEEPING PAD YELLOW. DIVISION 10 SPECIALTIES 10 14 00 SIGNAGE A. REQUIREMENTS 1. CONTRACTOR TO FURNISH AND INSTALL SIGNAGE PER LOCAL, STATE, AND FEDERAL CODES AND PER ROOM FINISH SCHEDULE. 2. ALL SIGNAGE SHALL MEET THE REQUIREMENTS OF THE A.D.A. AND ANSI. 3. WHERE PERMANENT IDENTIFICATION IS PROVIDED FOR ROOMS AND SPACES, SIGNS SHALL BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. WHERE THERE IS NO WALL SPACE TO THE LATCH SIDE OF THE DOOR, INCLUDING AT DOUBLE LEAF DOORS, SIGNS SHALL BE PLACED ON THE NEAREST ADJACENT WALL. 4. MOUNTING HEIGHT SHALL BE 60" ABOVE FINISH FLOOR TO THE CENTERLINE OF THE SIGN UNLESS INDICATED OTHERWISE. 5. PROVIDE HANDICAP PARKING SIGNS AS INDICATED ON PLANS AND AS REQUIRED BY LOCAL, STATE, AND FEDERAL CODES. 10 44 00 FIRE EXTINGUISHERS A. REQUIREMENTS 1. FURNISH AND INSTALL EXTINGUISHERS PER LOCAL, STATE, AND FEDERAL CODES, AND N.F.P.A. NO.10-1978. 2. MOUNT FIRE EXTINGUISHER NOT HIGHER THAN 48" ABOVE FINISH FLOOR UNLESS LOCAL REGULATIONS REQUIRE DIFFERENT HEIGHT. 3. ALL FIRE EXTINGUISHERS AND CABINETS TO MEET THE REQUIREMENTS OF THE A.D.A. AND ANSI A117.1. DIVISION 21 FIRE SUPPRESSION 21 10 00 FIRE PROTECTION WORK A. SEE FIRE PROTECTION PLANS FOR SPECIFICATIONS. DIVISION 22 PLUMBING 22 05 00 PLUMBING WORK A. SEE PLUMBING PLANS FOR SPECIFICATIONS DIVISION 23 HEATING AND VENTILATING AND AIR CONDITIONING 23 05 00 HEATING AND VENTILATION WORK A. SEE HVAC PLANS FOR SPECIFICATIONS. DIVISION 26 ELECTRICAL 26 05 00 ELECTRICAL WORK A. SEE ELECTRICAL PLANS FOR SPECIFICATIONS. 2017 © EXCEL ENGINEERING, INC. SHEET INFORMATION SHEET NUMBER PROJECT INFORMATION PROJECT NUMBER PROFESSIONAL SEAL PRELIMINARY DATES NOT FOR CONSTRUCTION 100 CAMELOT DRIVE FOND DU LAC, WI 54935 PHONE: (920) 926-9800 WWW.EXCELENGINEER.COM ARCHITECTS ● ENGINEERS ● SURVEYORS GENERAL BUILDING SPECIFICATIONS 1757840 TENANT BUILD-OUT FOR: PROFILE BY SANFORD 11503 SPRING MILL RD, SUITE 700 ● CARMEL, IN 46032 JAN. 31, 2018 T2.1 GENERAL BUILDING SPECIFICATIONS (CONT) 03/29/18 Nick Mishler