HomeMy WebLinkAbout1757840H-01DIVISION 23 HVAC
00 72 00 GENERAL CONDITIONS
A. THE AIA GENERAL CONDITIONS A201 LATEST EDITION IS A PART OF THESE DOCUMENTS.
COPIES ARE ON FILE AT THE OFFICE OF EXCEL ENGINEERING, INC.
01 11 00 GENERAL REQUIREMENTS
A. SEE SHEET T2.0.
B. PROJECT CLOSEOUT
1. PROVIDE HVAC EQUIPMENT OPERATING AND MAINTENANCE MANUALS TO THE OWNER
PER IMC 364.0313(3).
2. AS-BUILT DRAWINGS SHALL BE MARKED ON A FINAL SET OF DRAWINGS WHICH INCLUDES
ALL REVISIONS.
23 05 00 BASIC HVAC REQUIREMENTS
A. HVAC CONTRACTOR SHALL VERIFY REQUIREMENTS FOR TEMPORARY HEATING WITH
GENERAL CONTRACTOR AND INCLUDE IN HIS SCOPE OF WORK WHEN DIRECTED BY G.C..
INSTALL IN ACCORDANCE WITH ALL CODE AND OSHA REQUIREMENTS FOR CONSTRUCTION
PROJECTS.
B. DETAILS AND SCHEDULES ARE SHOWN TO AID THE CONTRACTOR AND ARE NOT MEANT TO BE
INCLUSIVE OF ALL DEVICES. PROVIDE REQUIRED EQUIPMENT AND ACCESSORIES FOR A
COMPLETE INSTALLATION.
C. INSTALL ALL EQUIPMENT PER MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
REQUIREMENTS. PROVIDE ADDITIONAL WORK AND MATERIALS AS REQUIRED.
D. COORDINATE INSTALLATION OF HVAC WORK WITH THE OTHER CONTRACTORS TO AVOID
CONFLICTS WITH OTHER WORK.
E. PROVIDE ALL CUTTING AND PATCHING NECESSARY FOR HVAC WORK INSTALLATION UNLESS
THIS WORK IS IDENTIFIED TO BE THE WORK OF OTHER CONTRACTORS. PATCHING SHALL
MATCH ADJACENT SURFACES. CORE DRILL OR SAW-CUT OPENINGS THROUGH EXISTING
CONCRETE.
F. REMOVE HVAC DUCTWORK, PIPING, EQUIPMENT, ETC. INDICATED BY THE DRAWINGS TO BE
DEMOLISHED FROM THE JOB SITE, UNLESS INDICATED TO BE TURNED OVER TO THE OWNER.
G. PROJECT COMPLETION
1. INSTALL CLEAN SET OF FILTERS IN ALL UNITS AT TIME OF TESTING AND BALANCING.
2. CLEAN GRILLES AND EQUIPMENT AND LEAVE IN PROPER WORKING CONDITION AT THE
TIME OF FINAL CLEAN-UP.
23 07 00 INSULATION
A. GENERAL
1. SEE INSULATION SCHEDULES ON PLANS FOR ADDITIONAL INFORMATION.
2. INSULATION, INSULATION SYSTEM AND JACKETS SHALL MEET UL-723/ASTM E84
REQUIREMENTS OF MAX. FIRE HAZARD CLASSIFICATIONS OF 25, AND MAX. FLAME SPREAD,
FUEL CONTRIBUTED, AND SMOKE DEVELOPED OF 50 WHEN INSTALLED IN A RETURN AIR
PLENUM.
3. INSTALL MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND MICA
PUBLICATION "NATIONAL COMMERCIAL AND INDUSTRIAL STANDARDS", 2011 SEVENTH
EDITION.
4. CONTINUE INSULATION WITHOUT INTERRUPTIONS THROUGH WALLS AND FLOOR
PENETRATIONS AND HANGERS.
B. FIBERGLASS (F.G.) INSULATION
1. FLEX. F.G.:
a. O.C. SOFTR DUCT WRAP, KNAUF FRIENDLY FEEL DUCT WRAP, CERTAINTEED
SOFTTOUCH, JOHNS MANVILLE MICROLITE EQ FSK DUCT WRAP.
b. GLASS FIBER INSULATION FACTORY LAMINATED TO FRK/FSK VAPOR RETARDER.
LISTED THICKNESS IS NOMINAL.
c. 0.75 LB/CU. FT., R=3.3 / NOMINAL INCH AT 75 DEG F.
d. MAX 250 DEG F, JACKET MAX 150 DEG F, 0.02 PERM.
C. DUCT INSULATION REQUIREMENTS
1. INSULATE FITTINGS, JOINTS, FLANGES, FLEXIBLE CONNECTIONS, DAMPERS, AND IN-LINE
ACCESSORIES WITHOUT INTERNAL LINING/INSULATION WITH SAME MATERIAL AND
THICKNESS AS SPECIFIED FOR THE DUCT SYSTEM. STOP AND POINT INSULATION AROUND
ACCESS DOORS AND DAMPER OPERATORS TO ALLOW OPERATION WITHOUT DISTURBING
WRAPPING.
23 31 13 DUCTWORK
A. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS OF SMACNA - HVAC DUCT
CONSTRUCTION STANDARDS, NFPA 90A.
B. GENERAL
1. PAINT THE INSIDE OF ALL DUCTS VISIBLE THROUGH GRILLES IN ROOMS WITH CEILINGS
WITH DULL BLACK PAINT.
2. CERTAIN VERTICAL AND HORIZONTAL OFFSETS ARE INDICATED IN DUCTS TO INDICATE
THE GENERAL POSITION RELATIONSHIP OF THE DUCTWORK SYSTEMS; PROVIDE
ADDITIONAL OFFSETS AS REQUIRED TO COORDINATE WITH THE INSTALLATION OF OTHER
SYSTEMS, CEILINGS AND STRUCTURE. THE DRAWINGS SHALL NOT BE SCALED TO
DETERMINE EXACT LOCATION OF DUCTWORK.
3. PROVIDE TEMPORARY CLOSURES OF METAL OR TAPED POLYETHYLENE ON OPEN
DUCTWORK TO PREVENT CONSTRUCTION DUST FROM ENTERING DUCTWORK SYSTEM.
4. LOCATE DUCTS WITH SUFFICIENT SPACE AROUND EQUIPMENT TO ALLOW NORMAL
OPERATING AND MAINTENANCE ACTIVITIES.
5. INCREASE DUCT SIZES GRADUALLY, NOT EXCEEDING 15 DEGREES WHENEVER POSSIBLE.
30 DEGREE MAXIMUM.
6. ROUND DUCTS MAY BE SUBSTITUTED FOR RECTANGULAR IF SIZED IN ACCORDANCE WITH
ASHRAE TABLES OF EQUIVALENT RECTANGULAR AND ROUND DUCTS.
C. ROUND DUCTWORK
1. CONCEALED BRANCH DUCTWORK TO GRILLES AND DIFFUSERS MAY BE LONGITUDINAL
LOCKSEAM. ALL OTHER ROUND DUCTWORK SHALL BE SPIRAL LOCKSEAM WITH FITTINGS
AND COUPLINGS MINIMUM 2 GAUGES HEAVIER THAN DUCT.
D. FLEXIBLE DUCTWORK
1. MANUFACTURERS: THERMAFLEX, FLEXMASTER, CLEVAFLEX.
2. U.L. 181 LISTED CLASS 1 FACTORY FABRICATED FLEXIBLE AIR DUCT, COMPLY WITH NFPA
90A, FLAME SPREAD OF 25 OR LESS, SMOKE DEVELOPED RATING OF 50 OR LESS.
3. MINIMUM PRESSURE RANGE -1/2" TO 4" W.C., TEMPERATURE RANGE 0-200 DEG F.
4. ACOUSTIC: THERMAFLEX M-KE OR G-KM, FLEXMASTER TYPE 1 OR 6
a. POLYETHYLENE, SPUNBOUND NYLON OR CHLORINATED POLYETHYLENE LINER.
b. DUCTWORK TO HAVE TESTED ACOUSTICAL PERFORMANCE NOT LESS THAN 2 DB LESS
THAN THE TYPES SPECIFIED.
5. SEMI-RIGID FLEXIBLE ALUMINUM DUCTWORK NOT PERMITTED.
6. SUPPLY DUCTWORK SHALL BE INSULATED WITH FIBERGLASS INSULATION, MINIMUM R
VALUE 4, WITH VAPOR BARRIER JACKET WITH MAXIMUM 0.10 PERM RATING
7. CONNECT TO SUPPLY DUCTWORK BY SLIDING CORE OVER COLLAR, TAPE JOINT WITH
MINIMUM 3 WRAPS OF TAPE, AND APPLY METAL BAND CLAMP OR PANDUIT. FOR
INSULATED DUCTWORK, PULL INSULATION AND OUTER JACKET BACK INTO POSITION, AND
TAPE WITH MINIMUM 3 WRAPS OF TAPE BETWEEN FLEX DUCT AND DUCT INSULATION.
8. CONNECT TO GRILLES AND RETURN AND TRANSFER DUCTWORK WITH METAL BAND
CLAMP OR PANDUIT.
9. MAXIMUM LENGTH FROM DUCTWORK TO GRILLES OR SLOTS 8'-0" WITH ONE 90 DEG ELBOW.
10. MAXIMUM LENGTH UPSTREAM OF VAV BOXES PER DETAIL.
11. DO NOT RUN THROUGH WALLS OR PARTITIONS.
E. DUCTWORK SEALANTS
1. MANUFACTURERS: HARDCAST SURE-GRIP 404 SOLVENT BASED DUCT SEALANT OR
EQUIVALENT.
a. SYNTHETIC RUBBER RESIN BASE.
b. -20 TO 200 DEG F.
c. PRESSURE CLASSES UP TO 10" W.C., MEETING SEAL CLASS A.
d. MAXIMUM FLAME SPREAD OF 25, SMOKE DEVELOPED OF 50.
e. APPLY MINIMUM 20-MIL THICK WET FILM AT TEMPERATURES BETWEEN 35-100 DEG F.
2. HARDCAST ALUMA-GRIP 701 OR EQUIVALENT PRESSURE SENSITIVE DUCT JOINT ROLLED
SEALANT MAY BE USED IN PLACE OF MASTIC. SEALANT SHALL COMPLY WITH THE
FOLLOWING:
a. MILL FINISH ALUMINUM SUSTRATE WITH GRAY ADHESIVE.
b. MINIMUM 30 MIL THICK
c. MIN. 17 LB PER LINEAR INCH PEEL STRENGTH
d. MAX FLAME SPREAD OF 25, MAX SMOKE DEVELOPED OF 50 WHEN TESTED IN
ACCORDANCE WITH ASTM G-53.
e. VOC: 0 G/L, COMPLIANT WITH LEED SCAQMD RULE 1168.
f. PRESSURE CLASSES UP TO 10" W.C.
F. ADDITIONAL REQUIREMENTS FOR GALVANIZED DUCTWORK EXPOSED IN FINISHED SPACES
1. ROUND DUCTS EXPOSED IN FINISHED SPACES SHALL BE SPIRAL LOCKSEAM.
2. STANDING SEAM GORED OR PLEATED ELBOWS.
3. WHERE REQUIRED, SEAL ROUND DUCTWORK BY PLACING A BEAD OF SEALER AROUND
THE INSIDE OF THE DUCT BEFORE JOINING SECTIONS.
4. PROVIDE STRAP HANGERS AT JOINTS SYMMETRICALLY SPACED.
5. CLEAN DUCTWORK WITH A VINEGAR AND WATER SOLUTION AFTER INSTALLATION TO
PREPARE FOR PAINTING.
G. DUCT CLEANING
1. PROTECT DUCTWORK AGAINST ENTRY OF FOREIGN MATTER DURING CONSTRUCTION.
PROVIDE TEMPORARY END CAPS AND SEALS. PROVIDE TEMPORARY FILTERS OVER
RETURN OR EXHAUST AIR INLETS IF DUCTWORK IS USED DURING CONSTRUCTION.
2. REMOVE ALL DIRT AND FOREIGN MATTER AND CLEAN DIFFUSERS, REGISTERS, AND
GRILLES BEFORE OPERATING FANS.
H. SEALING DUCT PENETRATIONS
1. THRU NON-RATED WALLS WHERE DRYWALL, CONCRETE, OR MASONRY EXTENDS TO
STRUCTURE, FILL VOID BETWEEN DUCT AND WALL WITH MINERAL WOOL AND CAULK BOTH
SIDES WITH NON-HARDENING CAULK.
23 33 00 DUCTWORK ACCESSORIES
A. GENERAL - ALL DUCT ACCESSORIES SHALL BE CONSTRUCTED OF SAME MATERIAL AS
DUCTWORK BEING INSTALLED IN.
B. TURNING VANES
1. MANUFACTURERS: AERO/DYNE CO. H.E.P., HART & COOLEY, UNITED MCGILL, SEMCO.
2. RECTANGULAR DUCTWORK: AIRFOIL TURNING VANES IN ACCORDANCE WITH SMACNA FIG.
2-3 AND 2-4. VANE RADIUS AS PROVIDED BY AERO/DYNE H.E.P. OR 4-1/2 INCHES WITH A
3-1/2 INCH SPACING.
3. ROUND DUCTWORK: TWO-PIECE MITERED, MINIMUM 20 GAUGE.
C. MANUAL VOLUME DAMPERS
1. MANUFACTURERS: RUSKIN, VENT PRODUCTS, UNITED MCGILL.
2. DAMPERS WITH EXTENDED SHAFTS AND QUADRANTS, OPERATOR WITH LOCKING DEVICE,
POSITION INDICATOR, AND ELEVATED PLATFORM FOR EXTERNALLY INSULATED
DUCTWORK.
3. EVERY SUPPLY, RETURN AND EXHAUST GRILLE SHALL HAVE EITHER A VOLUME DAMPER IN
THE BRANCH DUCT OR AT THE GRILLE WHERE SHOWN. IF ONE IS NOT SHOWN,
CONTRACTOR SHALL PROVIDE VOLUME DAMPER IN DUCT IF DUCT IS ACCESSIBLE,
OTHERWISE AT THE GRILLE.
4. RECTANGULAR DAMPERS WHICH DO NOT EXCEED 12" HIGH OR 36" WIDE: BUTTERFLY
DAMPER, MINIMUM 22 GAUGE. SHAFT ALONG ENTIRE LENGTH OF DAMPER FOR DAMPERS
EXCEEDING 18" IN WIDTH.
5. RECTANGULAR DAMPERS GREATER THAN 12" HIGH OR 36" WIDE: MULTI-BLADE DAMPER
WITH CONNECTING LINKAGE TO CONTROL FROM A SINGLE POINT. BLADES MINIMUM 16
GAUGE WITH OPPOSED BLADE ACTION.
6. ROUND DAMPERS: MINIMUM 20 GAUGE BUTTERFLY DAMPER.
D. TAKE-OFF FITTINGS
1. MANUFACTURERS: FLEXMASTER, UNITED MCGILL.
2. ROUND BRANCH TAKE-OFFS TO MULTIPLE GRILLES SHALL BE CONICAL.
3. RECTANGULAR BRANCH TAKE-OFFS TO MULTIPLE GRILLES SHALL PER DUCT FITTING
DETAIL ON PLANS.
4. ROUND TAKE-OFFS TO INDIVIDUAL GRILLES AND SLOT DIFFUSERS: ONE PIECE SPIN-IN
WITH INTEGRAL FACTORY INSTALLED LOCKING TYPE BALANCING DAMPERS.
E. DUCT ACCESS DOORS
1. MANUFACTURERS: CESCO, FLEXMASTER, VENT PRODUCTS, KEES, UNITED MCGILL,
SEMCO, DUCTMATE.
2. HINGE, LATCHES, HANDLES, AND RUBBER GASKET IN FRAME. 1" INSULATED DOUBLE WALL
CONSTRUCTION FOR DOORS IN LINED OR EXTERNALLY INSULATED DUCTWORK.
ATTACHMENT CABLES FOR SPIN-IN UNITS. DOOR SUITABLE FOR DUCT STATIC PRESSURE
CLASS.
3. DOOR SIZE 2" LESS THAN THE WIDTH OF THE DUCT (MAX. DOOR SIZE 24"X 24" (24" DIA.).
4. ROUND DUCTWORK: 16 GAUGE ROLLED SHEET METAL HINGED ACCESS DOOR WITH
BUCKLE LOCKS.
5. PROVIDE AT:
a. MOTOR OPERATED AND BACKDRAFT DAMPERS
b. UPSTREAM SIDE OF TURNING VANES IN RETURN AND EXHAUST DUCTWORK
c. DRAIN PANS
d. AT ANY DEVICE IN THE DUCT WHICH REQUIRES MAINTENANCE, SERVICE OR
CLEANING.
6. USE HINGED ACCESS DOORS WHERE POSSIBLE. USE CAM OPERATED REMOVABLE
DOORS WHERE SPACE PREVENTS THE OPENING OF A HINGED MODEL.
F. FLEXIBLE CONNECTIONS
1. MANUFACTURERS: VENTFABRICS, DURO-DYNE.
2. MATERIAL BOLTED SECURELY TO THE EQUIPMENT AND CONNECTING DUCTWORK WITH
#16 GAUGE GALVANIZED IRON BAND (LOOP) CLAMPS BOLTED TIGHT TO MAKE AN AIRTIGHT
CONNECTION, MINIMUM 6" WIDE.
3. PROVIDE AT INLET AND OUTLET OF ALL AIR HANDLING UNITS AND FANS IN ACCORDANCE
WITH SMACNA FIGURE 2-19.
4. CONVENTIONAL INTERIOR: VENTGLAS, -20 TO 200 DEG F., 30 OZ. PER SQUARE YARD
GLASS FABRIC DOUBLE COATED WITH NEOPRENE, UL 214 APPROVED.
23 90 10 SEQUENCE OF OPERATION
A. ROOFTOP AIR CONDITIONING UNIT
1. PROVIDE A HONEYWELL VISION PRO 8000 SEVEN DAY PROGRAMMABLE HEATING/COOLING
THERMOSTAT CAPABLE OF 1 STAGE OF HEATING AND 1 STAGE OF COOLING.
a. SET FAN SETTING TO "ON" FOR FAN TO RUN CONTINUOUSLY IN OCCUPIED PERIODS,
AND TO RUN WITH EQUIPMENT OPERATION DURING UNOCCUPIED PERIODS.
b. SET INSTALLER SETUP NUMBERS TO MATCH INSTALLED SYSTEM IN ADDITION TO THE
FOLLOWING (CONTACT ENGINEER WITH ANY QUESTIONS REGARDING ANY SETUP
NUMBERS):
1). 101 APPLICATION: COMMERCIAL
2). 326 EXTENDED FAN RUN TIME IN HEAT: 60 SECONDS.
2. MOUNT AND WIRE ALL CONTROL WIRING ASSOCIATED WITH THE ROOFTOP AND PROVIDE
ANY ADDITIONAL DEVICES NECESSARY FOR A COMPLETE OPERATIONAL SYSTEM.
23 95 00 TESTING, ADJUSTING AND BALANCING
A. QUALITY ASSURANCE
1. PERFORM TOTAL SYSTEM BALANCE IN ACCORDANCE WITH AABC NATIONAL STANDARDS
FOR FIELD MEASUREMENT AND INSTRUMENTATION, TOTAL SYSTEM BALANCE OR NEBB
PROCEDURAL STANDARDS FOR TESTING, BALANCING AND ADJUSTING OF
ENVIRONMENTAL SYSTEMS, AND ASHRAE STANDARD 111.
2. THE TESTING, ADJUSTING AND BALANCING (TAB) CONTRACTOR SHALL BE AN
INDEPENDENT COMPANY SPECIALIZING IN THE TESTING, ADJUSTING, AND BALANCING OF
SYSTEMS WITH MINIMUM THREE YEARS EXPERIENCE AND NOT ASSOCIATED WITH THE
SUPPLIERS OF EQUIPMENT OR THE INSTALLING CONTRACTOR.
3. PERFORM WORK UNDER SUPERVISION OF AABC CERTIFIED TEST AND BALANCE ENGINEER
OR NEBB CERTIFIED TESTING, BALANCING AND ADJUSTING SUPERVISOR.
B. SUBMITTALS
1. CONTRACTOR SHALL SUBMIT THE FINAL TESTING AND BALANCING REPORT PRIOR TO
PROJECT COMPLETION AND IN ADVANCE OF DATE OF OCCUPANCY. THE FINAL TESTING
AND BALANCING REPORT SHALL COMPLY WITH DEPT. OF COMM. 64.0313. SUBMIT
REPORTS ON AABC NATIONAL STANDARDS FOR TOTAL SYSTEM BALANCE OR NEBB
FORMS.
2. SUBMIT THE DESIGN AND ACTUAL DATA FOR EACH SCHEDULED PIECE OF EQUIPMENT:
MODEL; SUPPLY, RETURN, AND OUTSIDE AIR FLOWS; STATIC PRESSURE PROFILES OF AIR
HANDLING UNIT COMPONENTS AND ALL FANS; FAN RPM, BHP, AMPERAGE; FAN AND
MOTOR SHEAVE, DIAMETER, BORE AND MAKE; BELT SIZE AND QUANTITY; MOTOR SHEAVE
CENTER LINE AND OPERATOR DISTANCE; ROOM AIR FLOW; TERMINAL UNIT MAXIMUM AND
MINIMUM AIRFLOWS; EQUIPMENT FLOW RATES AND PRESSURE DROPS.
C. INSTALLATION TOLERANCES
1. AIR HANDLING SYSTEMS: ADJUST SUPPLY SYSTEMS TO WITHIN PLUS OR MINUS 5
PERCENT OF DESIGN AND RETURN AND EXHAUST SYSTEMS TO PLUS OR MINUS 10
PERCENT OF DESIGN.
2. AIR OUTLETS AND INLETS: ADJUST TOTAL AIR FLOW TO SPACE TO WITHIN PLUS 10
PERCENT AND MINUS 5 PERCENT OF DESIGN.
3. ADJUST OUTLETS AND INLETS IN SPACE TO WITHIN PLUS OR MINUS 10 PERCENT OF DESIGN.
D. AIR SYSTEM BALANCE
1. VARY TOTAL SYSTEM AIR QUANTITIES BY ADJUSTING FAN SPEEDS. VARY BRANCH AIR
QUANTITIES BY DAMPER REGULATION.
2. ADJUST SETTINGS ON DIRECT DRIVE FANS WITH ECM MOTORS AS REQUIRED TO ACHIEVE
DESIGN AIRFLOW.
3. ADJUST OUTSIDE AIR, RETURN AIR, AND EXHAUST AIR AUTOMATIC DAMPERS FOR DESIGN
CONDITIONS.
4. TEST AIR HANDLING UNITS AT MINIMUM AND 100% OUTSIDE AIR.
E. FANS WITH FIXED MOTOR SHEAVES - TEST THE FAN EQUIPMENT. IF THE DESIGN CONDITIONS
ARE NOT OBTAINED, CALCULATE THE FINAL FIXED MOTOR SHEAVE AND/OR BELTS REQUIRED
TO OBTAIN DESIGN CONDITIONS. HEATING CONTRACTOR SHALL OBTAIN THE FINAL FIXED
MOTOR SHEAVE AND BELT(S) FROM THE FAN MANUFACTURER AND TURN THEM OVER TO THE
TAB CONTRACTOR FOR INSTALLATION.
2016 EXCEL ENGINEERING, INC.
SHEET INFORMATION
SHEET NUMBER
PROJECT INFORMATION
PROJECT NUMBER
PROFESSIONAL SEAL
1757840
TENANT BUILD-OUT FOR:
PROFILE BY SANFORD
ϭϭϱϬϯ ^WZ/E' D/>> Z͕ ^h/d ϳϬϬ භ ZD>͕ /E ϰϲϬϯϮ
NOT FOR CONSTRUCTION
PRELIMINARY DATES
H0.1
LEGEND & SPECIFICATIONS
JAN. 31, 2018
IDENTIFICATION SYM. ABBR. IDENTIFICATION SYM. ABBR. IDENTIFICATION
SYM. ABBR.
NOTE: ALL SYMBOLS SHOWN MAY NOT APPEAR ON DRAWINGS.
CONNECT TO EXISTING ABOVE FINISHED FLOOR
HEATING CONTRACTOR
AFF
HC
EC ELECTRICAL CONTRACTOR
GENERAL CONTRACTOR /
GC
X X=CENTERLINE OF PIPE
OR BOTTOM OF DUCT
X
HV-Y
X=SECTION NUMBER
SHOWN ON DWG HV-Y
COMBINATION STARTER
MS MANUAL STARTER
MISCELLANEOUS AND CONTROLS
CONTROL PANEL
TYP. TYPICAL
WWM
TTS TIGHT TO STRUCTURE
BJ
TJ
BETWEEN JOISTS
THRU JOISTS
WELDED WIRE MESH
RAO
VFD
RETURN AIR OPENING
VARIABLE FREQ. DRIVE
TCP
AP
NIC
TEMPERATURE
ACCESS PANEL
NOT IN CONTRACT
PC PLUMBING CONTRACTOR
HUMIDISTAT / HUMID. SENSOR
THERMOSTAT / TEMP. SENSOR
H
T
ECCENTRIC TRANSITION
CONCENTRIC TRANSITION
SQUARE TO ROUND TRANS.
DTG DOOR TRANSFER GRILLE
EG,RG
(T)RANSFER GRILLE
(E)XHAUST/(R)ETURN/
SUPPLY GRILLE
DS DSD DUCT SMOKE DETECTOR
BDD BACKDRAFT DAMPER
FS FSD FIRE/SMOKE DAMPER
AD
FIRE DAMPER
F
VD
FD
S
RC
UCD
TG
SD
SG
SMOKE DAMPER
UNDERCUT DOOR (BY GC)
VOLUME DAMPER
ACCESS DOOR
REHEAT COIL
DUCT CAP
EA
OA
RA
SA
MOD
FC FLEXIBLE CONNECTION
MOTOR OPERATED DAMPER
EXHAUST AIR DUCT UP
RETURN AIR DUCT UP
SUPPLY AIR DUCT UP
OUTSIDE AIR DUCT UP
ALD
ACOUSTICALLY LINED DUCT
(NOT ALWAYS SHOWN)
TEE WITH TURNING VANES
R
R
RADIUS ELBOW
BRANCH TAKEOFF
WITHOUT TURNING VANES
WITH TURNING VANES
SQUARE OR RECTANGULAR
SQUARE ELBOW
SQUARE ELBOW
DUCT (R)ISE/(D)ROP
DUCTWORK
SA OR OA
DUCT DOWN OR AWAY
EA DUCT
DOWN OR AWAY
TAO TRANSFER AIR OPENING
TV TURNING VANES
EQUIPMENT BY OTHERS,
CONNECTION BY HC
RECTANGULAR TO ROUND
TAKEOFF
S STATIC PRESS. SENSOR
BOL BOTTOM OF LINTEL
TCC TEMPERATURE CONTROL
S S SLAB SENSOR
ROUND TO ROUND
BRANCH TAKEOFF
TTB TIGHT TO BEAM
CONSTRUCTION MANAGER
,
RA DUCT
DOWN OR AWAY
HVAC SPECIFICATIONS
SHEET INDEX
NUMBER
HVAC
H0.1
H1.1
H3.0
H4.0
SHEET NAME
LEGEND & SPECIFICATIONS
FIRST FLOOR PLAN
DETAILS
SCHEDULES
PROJECT DESIGN CRITERIA
WINTER:
SUMMER:
MECHANICAL CODE
ENERGY CODE
SEISMIC DESIGN CATEGORY
NEAREST ASHRAE CITY
ELEVATION
INSIDE
DB
72
75
IMC 2012
IECC 2012
B
INDIANAPOLIS
807
% RH
N/A
50
OUTSIDE
DB
2
91
WB
N/A
78.2
03/29/18
Nick Mishler