FLEX CONNECTION
FLEX CONNECTION
-STRIP MALL
2016 EXCEL ENGINEERING, INC.
SHEET INFORMATION
SHEET NUMBER
PROJECT INFORMATION
PROJECT NUMBER
PROFESSIONAL SEAL
1757840
TENANT BUILD-OUT FOR:
PROFILE BY SANFORD
ϭϭϱϬϯ ^WZ/E' D/>> Z͕ ^h/d ϳϬϬ භ ZD>͕ /E ϰϲϬϯϮ
NOT FOR CONSTRUCTION
PRELIMINARY DATES
H3.0
DETAILS
JAN. 31, 2018
r
w
MIN. r = 1.0
w
TURNING
VANES
AIRFLOW
ACCESS PANEL FOR
RETURN, EXHAUST,
AND OUTSIDE AIR
NOT PERMITTED
DUCT FITTING DETAILS
NO SCALE
d= bxa
b+c
e= cxa
b+c
d e
b c
a
TEE WITH
TURNING VANES
SQUARE TO
ROUND TRANSITION
w+h
2
wxh
DUCT
SQUARE OR RECTANGULAR
BRANCH TAKEOFF
a
a
4
NOT PERMITTED WHERE TEE
WITH TURNING VANES IS
SHOWN ON PLANS
DUCT ELBOW
NO SCALE
GRILLE PLENUM BOX DETAIL
24 GA. SHEET METAL
PLENUM BOX. PAINT
INTERIOR BLACK.
ACOUSTICALLY LINE AT
TRANSFER AND RETURN
GRILLES AND PAINT
FASTENERS BLACK.
MINIMUM 6" DEPTH
GRILLE NECK SIZE
RETURN, EXHAUST OR
TRANSFER GRILLE
FLEXIBLE DUCT
(# AS SCHEDULED -
EITHER LOCATION)
INSULATION PER DUCT SCHEDULE
ROOF DECK
ROOF
INSULATION
ROOF CAP
AND CURB DETAIL
NOTE:
- H.C. SHALL BLOCK CURB SO TOP OF CURB IS LEVEL.
ROOFING AND
FLASHING BY
LANDLORD
ROOF OPENING & ANGLE REINFORCING
BY OTHERS
14" HIGH INSULATED
PREFAB CURB.
FURNISHED BY MFR.,
INSTALLED BY H.C.
ROOF CAP
BASE
NO SCALE
BLOCKING UNDER CURB BY H.C. AS REQ'D
TO RAISE TOP OF CURB HEIGHT ABOVE
INSULATION TO ROOFING MFR MINIMUM
REQUIREMENTS.
WEIGHTED GRAVITY
BACK DRAFT DAMPER
SEE PLAN
FOR SIZE
18" MIN.
4 1/2"
3 1/4"
NOTES:
- FILL TRAP MANUALLY ON INITIAL START-UP.
- TRAP EACH COMPONENT DRAIN CONNECTION.
SQUARE HEAD
PLUG (TYP.)
PIPE SIZE NOT LESS THAN
DRAIN PAN CONNECTION SIZE,
PITCH AT 1/4" PER FOOT
CONNECTION
AT RTAC
ROOF
PIPE TO WITHIN 6" OF ROOF.
EXTEND PIPING SO IT DOES
NOT DISCHARGE WHERE ROOF
IS PITCHED TO CURB.
NO SCALE
RTAC CONDENSATE DRAIN TRAP PIPING DETAIL
R.T.A.C. BASE, NEOPRENE
NO SCALE
RTAC AND CURB
ATTACHMENT DETAIL
RTAC
16 GAUGE MINIMUM
PRE-MANUFACTURED
CURB FURNISHED BY
MFR. INSTALLED BY H.C.
SEE SCHED. FOR TYPE
AND HEIGHT.
BLOCKING UNDER CURB BY
G.C. AS REQ'D TO RAISE TOP OF
CURB HEIGHT ABOVE
INSULATION TO ROOFING MFR
MINIMUM REQUIREMENTS.
BLOCKING ON TOP OF
INSULATION
ROOFING AND FLASHING BY
LANDLORD
NEOPRENE GASKET
#12-14 TEK SCREWS 24" O/C -
MIN. (6) IN LONG DIMENSION OF
UNIT - MIN. (3) IN SHORT
DIMENSION OF UNIT
#12-14 TEK SCREWS 24" O/C -
MIN. (6) IN LONG DIMENSION OF
UNIT - MIN. (3) IN SHORT
DIMENSION OF UNIT
SEE STRUCTURAL PLAN
FOR ADDITIONAL ROOF
SUPPORT
NOTE:
VERIFY THICKNESS OF ROOF
DECK. NOTIFY EXCEL
ENGINEERING IF LESS THAN 22
GAUGE.
NON-HURRICANE
NO SCALE
TYPICAL RTAC AND CURB DETAIL
NOTE:
- G.C. SHALL BLOCK CURB SO TOP OF CURB IS LEVEL.
SUPPLY AIR DUCT - SEE
PLAN FOR SIZE AND
CONTINUATION
RETURN AIR DUCT - SEE
PLAN FOR SIZE AND
CONTINUATION
ROOF INSULATION
ROOF DECK
ROOFING AND FLASHING
BY ROOFING CONTRACTOR
FILL VOID BETWEEN DECK
AND DUCT WITH MINERAL
WOOL INSUL.
NTS
R.T.A.C. BASE, NEOPRENE
GASKET, CURB BY UNIT MFR.
3/8" HARDBOARD (ON
METAL DECK ONLY)
2" RIGID 6 PCF
FIBERGLASS INSULATION.
INSULATION BY H.C.
RTAC
CURB FURNISHED BY MFR.
INSTALLED BY G.C. SEE SCHED. FOR
TYPE AND HEIGHT.
BLOCKING UNDER CURB BY G.C. AS
REQ'D TO RAISE TOP OF CURB
HEIGHT ABOVE INSULATION TO
ROOFING MFR MINIMUM
REQUIREMENTS.
(2) LAYERS OF 6" FIBERGLASS BATT
INSULATION.
03/29/18
Nick Mishler