TENANT BUILD-OUT FOR:
PROFILE BY SANFORD
ϭϭϱϬϯ ^WZ/E' D/>> Z͕ ^h/d ϳϬϬ භ ZD>͕ /E ϰϲϬϯϮ
NOT FOR CONSTRUCTION
PRELIMINARY DATES
H4.0
SCHEDULES
JAN. 31, 2018
DUCTWORK AND DUCTWORK INSULATION SCHEDULE
N.R. = NOT REQUIRED
EXPOSED = VISIBLE FROM OCCUPIED SPACE, DOES NOT INCLUDE DUCTWORK ABOVE WALK-ON CEILINGS AND IN MECHANICAL ROOMS.
CONCEALED = HIDDEN FROM VIEW BY WALLS AND CEILINGS. INCLUDES DUCTWORK ABOVE WALK-ON CEILINGS AND IN MECHANICAL ROOMS.
MATERIALS:
- ALL JOINTS, LONGITUDINAL AND TRANSVERSE SEAMS AND CONNECTIONS IN DUCTWORK SHALL BE SEALED PER IECC 503.2.7.
(1) DUCT DIMENSIONS ARE SHEET METAL DIMENSIONS AND INCLUDE LINING.
(2) INSULATE FROM 18" UPSTREAM OF THE BACKDRAFT OR MOTOR OPERATED DAMPER TO THE POINT WHERE THE DUCT EXITS THE BUILDING.
(10) A.L.D. WHERE NOTED ON PLAN.
SUPPLY
SUPPLY
RETURN
EXHAUST
GALV. STEEL: ASTM A653, LOCK FORMING QUALITY, 1.25 OUNCES/ S.F. ZINC COATING (G90 IN ACCORDANCE WITH ASTM A90 BOTH SIDES).
ALUMINUM: ASTM B209, ALLOY 3003H-14 CAPABLE OF DOUBLE SEAMING WTHOUT FRACTURE.
SERVICE
SINGLE ZONE RTAC
SINGLE ZONE RTAC
UPSTREAM OF FAN
UPSTREAM OF FAN
LOCATION
EXPOSED IN ROOM SERVED
CONCEALED
CONCEALED AND EXPOSED
CONCEALED
DUCT
MAT'L
GALV. ST.
GALV. ST.
GALV. ST.
GALV. ST.
SMACNA
PRESS.
CLASS
+1"
+1"
-1"
-1"
INSULATION
RECTANGULAR
DUCT
N.R.
1.5" FLEX F.G.
1" A.L.D. (1) (10)
1.5" FLEX. F.G. (2)
ROUND
DUCT
N.R.
1.5" FLEX. F.G.
N.R.
1.5" FLEX. F.G. (2)
INSUL.
JACKET
N.R.
N.R.
N.R.
N.R.
ELECTRICAL/STARTER/DISCONNECT SCHEDULE
SYM.
RTAC-1
RTAC-2
CEF-1
CEF-2
STARTER TYPE:
INTEG.= INTEGRAL: PROVIDED INTEGRAL WITH EQUIPMENT.
FURNISHED BY:
EM = EQUIPMENT MANUFACTURER
HC = HEATING CONTRACTOR
EC = ELECTRICAL CONTRACTOR
- VERIFY VOLTAGE AND PHASE WITH ELECTRICAL CONTRACTOR BEFORE ORDERING EQUIPMENT.
(1) WALL OCCUPANCY SENSOR PROVIDED BY E.C. TO TURN ON ROOM LIGHTS AND FAN.
LOCATION
ROOF
ROOF
TOILET RM
TOILET RM
ELECTRICAL DATA
HP
-
-
-
-
KW
-
-
0.08
0.08
MCA
20.0
31.0
-
-
MOP
30
45
-
-
DISCONNECT:
NR= NOT REQUIRED
R = REQUIRED
WP= WEATHERPROOF
VOLT
208
208
120
120
PH.
3
3
1
1
TYPE
INTEG.
INTEG.
(1)
(1)
STARTER
LOCATION
INTEGRAL
INTEGRAL
(1)
(1)
REMARKS:
H.W.= HARD WIRED
REC.=RECEPTACLE
FURN.
BY
EM
EM
EC
EC
AUX.
CONTACT
-
-
-
-
ACCESS-
ORIES
-
-
-
-
DISCONNECT
DIS-
CONNECT
R, WP
R, WP
R
R
FURN.
BY
EM
EM
EM
EM
REMARKS
-
-
-
-
CABINET EXHAUST FAN SCHEDULE (C.E.F.)
NO.
1
2
- ACCEPTABLE MANUFACTURERS: GREENHECK, COOK, PENN, CARNES.
- SUPPORT FROM STRUCTURE, ISOLATE FAN AND ASSOCIATED DUCTWORK.
- PROVIDE SPEED CONTROL MOUNTED ON FAN HOUSING, INTERNAL PLUG-IN DISCONNECT
AND BACKDRAFT DAMPER
- PROVIDE WITH WHITE ALUMINUM GRILLE
AREA
SERVED
TOILET RM
TOILET RM
TYPE
CEILING
CEILING
CFM
100
100
S.P.
" W.C.
0.38
0.38
RPM
950
950
MOTOR
WATTS
80
80
MAX.
SONES
2.7
2.7
DUCT
COLLAR
SIZE
6"
6"
MODEL
SP-B110
SP-B110
REMARKS
"GREENHECK"
"GREENHECK"
ROOF CAP SCHEDULE
NO.
1
- ACCEPTABLE MANUFACTURERS: GREENHECK, CARNES
(1) PROVIDE ROOF CURB.
SERVICE
EXHAUST
TYPE
FLAT
THROAT
6
CFM
200
APD.
0.05
SCREEN
BIRD
DAMPER
NO
MODEL
RCC-7 (1)
REMARKS
"GREENHECK"
SUPPLY GRILLE SCHEDULE (S.G.)
NO.
1-6
1-8
1-10
1-12
1-14
2S
- ACCEPTABLE MANUFACTURERS: TITUS, PRICE, CARNES, METALAIRE, ANEMOSTAT, KRUEGER.
- NOT ALL SUPPLY GRILLES SCHEDULED ARE USED ON THE PROJECT.
(1) DAMPER AT THE GRILLE INDICATED BY A "D" AFTER THE GRILLE DESIGNATION. EXAMPLE: SG1SD-6 IS SG1S-6 WITH A DAMPER.
(2) NECK SIZE INDICATED ON PLAN AT GRILLE IDENTIFICATION.
(4) FRONT BLADES IN THE HORIZONTAL DIRECTION.
TYPE
LOUVER
LOUVER
LOUVER
LOUVER
LOUVER
DBL DEFL.
CFM
RANGE
0-75
76-275
276-375
375-550
551-750
SEE DWG
NECK/
FACE
SIZE
24 X 24
24 X 24
24 X 24
24 X 24
24 X 24
(2)
INLET
DUCT
DIA.
6"
8"
10"
12"
14"
-
MAT'L
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
DAMPER
(1)
(1)
(1)
(1)
(1)
(1)
FINISH
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
FRAME
LAY-IN
LAY-IN
LAY-IN
LAY-IN
LAY-IN
SURFACE MOUNT
THROW
4-WAY
4-WAY
4-WAY
4-WAY
4-WAY
DBL DEFL. (4)
MODEL
SCD
SCD
SCD
SCD
SCD
520
REMARKS
"PRICE"
"PRICE"
"PRICE"
"PRICE"
"PRICE"
"PRICE"
RETURN GRILLE SCHEDULE (R.G.)
NO.
1-6
1-8
1-10
1-12
1-14
1-16
2S
- ACCEPTABLE MANUFACTURERS: TITUS, KRUEGER, CARNES, SHOEMAKER.
- BRANCH DUCT SIZE TO GRILLE SHALL BE SAME SIZE AS NECK UNLESS OTHERWISE NOTED.
(2) COORDINATE MOUNTING WITH ARCH. PLANS. PROVIDE PLASTER RINGS WHERE REQD FOR INSTALLATION.
(3) 1/2 X 1/2 / 1/2 CORE
(4) DAMPER AT THE GRILLE INDICATED BY A "D" AFTER THE GRILLE DESIGNATION.
EXAMPLE: RG1SD-6 IS RG1S-6 WITH A DAMPER.
(5) NECK SIZE INDICATED ON PLAN AT GRILLE IDENTIFICATION.
(6) BLADES IN HORIZONTAL DIRECTION
TYPE
EGG CRATE
EGG CRATE
EGG CRATE
EGG CRATE
EGG CRATE
EGG CRATE
LOUVERED
MAX
CFM
75
275
450
750
1,100
1,600
SEE DWG.
NECK
SIZE
24 x 12
24 x 12
24 x 12
24 x 12
24 x 24
24 x 24
(5)
FLEX.
DUCT.
DIA.
6"
8"
10"
12"
14"
16"
-
MAT'L
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
STEEL
DAMPER
(4)
(4)
(4)
(4)
(4)
(4)
(4)
FINISH
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
FRAME
LAY-IN (2)
LAY-IN (2)
LAY-IN (2)
LAY-IN (2)
LAY-IN (2)
LAY-IN (2)
SURFACE MOUNT
MODEL
50F (3)
50F (3)
50F (3)
50F (3)
50F (3)
50F (3)
530 (6)
REMARKS
"TITUS"
"TITUS"
"TITUS"
"TITUS"
"TITUS"
"TITUS"
"PRICE"
ROOFTOP AIR CONDITIONING UNIT SCHEDULE (RTAC)
- ROOFTOP UNITS TO BE FURNISHED BY OWNER, INSTALLED BY CONTRACTOR.
- SEE MOTOR SPECIFICATIONS FOR MOTOR REQUIREMENTS.
- PROVIDE PRE-INSULATED ROOF CURB.
- PROVIDE WITH 2" ASHRAE STD 52.2 MERV 8 T.A. FILTERS .
- RTAC DESIGNED TO PREVENT RAIN INTRUSION INTO THE AIRSTREAM WHEN TESTED AT DESIGN AND NO AIRFLOW PER SECTION 58 OF UL 1995.
- PROVIDE UNIT WITH INTEGRAL MANUFACTURER INSTALLED WATER-LEVEL MONITORING DEVICE IN THE PRIMARY DRAIN PAN TO SHUT OFF THE EQUIPMENT PER IMC 307.2.3.1.
- PROVIDE WITH HAIL GUARD FOR CONDENSING COILS.
(1) PROVIDE UNIT MOUNTED NEMA 3R DISCONNECT.
(5) PROVIDE MODULATING ECONOMIZER DAMPERS AND ACTUATOR WITH DIFFERENTIAL ENTHALPY CONTROL.
(6) PROVIDE MULTI-STAGE AIR VOLUME UNITS WITH TWO SPEED BELT DRIVE FAN MOTORS WITH VFDS AND 2-STAGE COMPRESSORS.
NO.
1
2
NOM.
TONS
3
5
CFM
1,200
1,600
OA
CFM
175
375
SUPPLY FAN
EXT.
SP
1.0
1.0
DRIVE
TYPE
BELT(6)
BELT(6)
MOTOR
HP
1
1
MOD.
TYPE
VFD (6)
VFD (6)
RELIEF
BAR.
X
-
FAN
-
X
EAT
DB / WB
78.2/66.0
79.5/67.2
MBH
CAP.
32.4
55.7
COOLING
AMB.
TEMP F
110
110
NO.
COMPR.
1
1
NO.
STAGES
2 (6)
2 (6)
KW
-
-
HEATING
MBH
IN
65
65
MBH
OUT
52
52
NO.
STAGES
1
1
OUTSIDE
AIR
(5)
(5)
SMOKE
DETECTOR
NO
NO
CURB
HEIGHT
BY MFR.
18"
18"
TYPE
STANDARD
STANDARD
MCA
20.0
31.0
MOP
30
45
VOLT/
PHASE
208/3
208/3
MIN.
CODE
13.0 SEER
13.0 SEER
EFFICIENCY
UNIT
RATING
15.0 SEER
15.5 SEER
TEST
PROC.
ARI 210/240
ARI 210/240
WEIGHT
(LBS.)
850
950
MODEL
LGH
LGH
REMARKS
LENNOX (1)
LENNOX (1)
03/29/18