HomeMy WebLinkAbout1757840 - Sheet - E0-1 - SYMBOLS LEGEND & FIXTURE SCHEDULE15A/1P OR 15A/2P (2) #12 #12 1/2" 20A/1P OR 20A/2P (2) #12 #12 1/2" 15A/3P OR 20A/3P (3) #12 #12 1/2" 25A/1P OR 25A/2P (2) #10 #10 3/4" 30A/1P OR 30A/2P (2) #10 #10 3/4" 25A/3P OR 30A/3P (3) #10 #10 3/4" 35A/1P OR 35A/2P (2) # 8 #10 3/4" 40A/1P OR 40A/2P (2) # 8 #10 3/4" 35A/3P OR 40A/3P (3) #8 #10 3/4" 45A/1P OR 45A/2P (2) #6 #10 1" 45A/3P OR 50A/3P (3) #6 #10 1" 50A/1P OR 50A/2P (2) #6 #10 1" 60A/1P OR 60A/2P (2) #4 #8 1" 60A/3P (3) #4 #8 1 1/4" 70A/3P OR 80A/3P (3) #4 #8 1 1/4" 90A/3P (3) #3 #8 1 1/4" 100A/3P OR 110A/3P (3) #2 #6 1 1/2" 125A/3P (3) #1 #6 1 1/2" - PROVIDE BRANCH CIRCUIT FEEDERS AS NOTED ABOVE, UNLESS NOTED OTHERWISE. BRANCH CIRCUIT FEEDER SCHEDULE AMP/POLE CONDUCT. GND. CONDUCT. CON. SS WIRING DEVICES DUPLEX RECEPTACLE SURFACE MOUNTED FLR = FLOOR MOUNTED CLG = CEILING/SOFFIT MOUNTED DUPLEX RECEPTACLE MOUNTED IN CABINET BEHIND MICROWAVE. FIELD VERIFY HEIGHT. COMBINATION FLOOR OUTLET/BLANK JUNCTION BOX PER SPECS - WIREMOLD - RESOURCE RFB / SERIES OR EQUIVALENT. PROVIDE 1" CONDUIT STUB TO NEAREST ACCESSIBLE SPACE. DUPLEX RECEPTACLE MOUNTED VERTICALLY 6" ABOVE BACKSPLASH TO CENTER. IF NO BACKSPLASH MOUNT 6" ABOVE COUNTER. BLANK BOX 4" EXTRA DEEP BOX, SINGLE GANG RING, BLANKPLATE, 1"C. STUBBED INTO ACCESSIBLE SPACE. MOUNTED @ 18" AFF TO CENTER JUNCTION BOX SPECIAL OUTLET POWER RECEPTACLE MTD @ 18" AFF TO CENTER SINGLE POLE SWITCH MOUNTED @ 46" AFF TO CENTER, 3 = 3 WAY, 4 = 4 WAY, P = PILOT, D = DIMMER, K = KEYED DUAL LEVEL SWITCHING MOUNTED @ 46" AFF TO CENTER SEE DETAIL DUPLEX RECEPTACLE MOUNTED @ 18" AFF TO CENTER DOUBLE DUPLEX RECEPTACLE MOUNTED @ 18" AFF TO CENTER ABOVE COUNTER BLANK BOX 4" EXTRA DEEP BOX, SINGLE GANG RING, BLANKPLATE, 1"C. STUBBED INTO ACCESSIBLE SPACE. MTD 6" ABOVE BACKSPLASH TO CENTER SWITCH BOTTOM HALF OF RECEPTACLE. TOP HALF UNSWITCHED. LOW VOLTAGE SWITCH MOUNT @ 46" AFF TO CENTER S MISC X CONDUIT STUB THROUGH WALL BUSHED EACH END CONDUIT WITH BUSHING ON END. REFERS TO NOTE WITH NUMBER "X" PUSHBUTTON PROVIDE JUNCTION BOX AND CONDUIT. MOUNT AT SWITCH HEIGHT. COMMUNICATION TV X CEILING MOUNTED SPEAKER TELEVISION OUTLET MOUNTED @ 18" AFF TO CENTER COMBINATION TELEPHONE/DATA WITH 1" C. STUBBED INTO AN ACCESSIBLE SPACE. MOUNTED @ 18" AFF TO CENTER. X = NUMBER OF DATA DROPS PER BOX. TELEPHONE OUTLET WITH 1" C. STUBBED INTO AN ACCESSIBLE SPACE. MOUNTED 18" AFF TO CENTER. W = WALL MOUNTED @ 52" AFF TO CENTER DATA OUTLET WITH 1" C. STUBBED INTO AN ACCESSIBLE SPACE. MOUNTED 18" AFF TO CENTER. PC LIGHTING OCCUPANCY SENSOR WALL MOUNTED OCCUPANCY SENSOR WITH SWITCH TWIN HEAD POLE MOUNTED FIXTURE SINGLE HEAD POLE RECESSED, SURFACE, OR PENDANT MOUNTED LIGHT FIXTURE RECESSED, SURFACE MOUNTED, OR CHAIN HUNG LIGHT FIXTURE. SEE LIGHTING FIXTURE LEGEND. EXIT LIGHT RECESSED EMERGENCY LIGHT PHOTO CONTROL EXTERIOR WALL MOUNTED FIXTURE OR INTERIOR WALL WASH FIXTURE EMERGENCY LIGHT. 11'-0" AFF TO TOP OR 8" BELOW CEILING WHICHEVER IS LOWER WALL MOUNTED LIGHT FIXTURE MOUNTED @ 7'-0" AFF OR 8" ABOVE MIRROR DUAL LEVEL/CIRCUIT OCCUPANCY SENSOR WITH SWITCH ABBREVIATIONS AC ABOVE COUNTER AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE BRD BOARD C CONDUIT C/T CURRENT TRANSFORMER DISC DISCONNECT DW DISHWASHER EC ELECTRICAL CONTRACTOR ELEV ELEVATION EM EMERGENCY ETR EXISTING TO REMAIN EWC ELECTRIC WATER COOLER FBO FURNISHED BY OTHERS FLA FULL LOAD AMPS FPC FIRE PROTECTION CONTRACTOR G.C. GENERAL CONTRACTOR GDSP GARBAGE DISPOSAL GFI GROUND FAULT CIRCUIT INTERRUPTED GND GROUND HC HVAC CONTRACTOR HP HORSE POWER IG ISOLATED GROUND LCP LIGHTING CONTROL PANEL MCA MINIMUM CIRCUIT AMPS MTD MOUNTED NL NIGHT LIGHT NTS NOT TO SCALE OC ON CENTER PC PLUMBING CONTRACTOR PH PHASE PNL PANELBOARD REF REFRIGERATOR SS STAINLESS STEEL UC UNDER COUNTER WP WEATHER PROOF XFMR TRANSFORMER WT WATER TIGHT WP/GFI WEATHER PROOF AND GROUND FAULT CIRCUIT INTERRUPTED SECURITY DC ES CR DOOR CONTACT ELECTRIC STRIKE CARD READER MOTOR CONTROL MS DISCONNECT FURNISHED BY E.C. F=FUSIBLE MOTOR CONNECTION COMBINATION STARTER MANUAL STARTER NON-COMBINATION STARTER FS TS FACP FAA F ARL ARM ARS FIRE ALARM / LIFE SAFETY S H S E M S D Co S SB ELEVATOR SMOKE DETECTOR SPRINKLER FLOW SWITCH MAGNETIC DOOR HOLDER SMOKE DETECTOR HEAT DETECTOR STROBE MOUNTED @ 84" AFF TO TOP OR 6" BELOW CEILING WHICHEVER IS LOWER HORN/STROBE MOUNTED @ 84" AFF TO TOP OR 6" BELOW CLG WHICHEVER IS LOWER. PULL STATION MOUNTED @ 46" AFF TO CENTER DUCT SMOKE DETECTOR SPRINKLER TAMPER SWITCH AREA OF REFUGE MASTER PANEL AREA OF REFUGE LIGHTING AREA OF REFUGE STATION DOOR BELL SPEAKER/STROBE MOUNTED @ 84" AFF TO TOP OR 6" BELOW CLG WHICHEVER IS LOWER. SPEAKER CEILING MOUNTED W = WALL MOUNTED FIRE ALARM CONTROL PANEL FIRE ALARM ANNUNCIATOR PANEL CARBON MONOXIDE DETECTOR HORN (SOUNDER) MOUNTED @ 84" AFF TO TOP OR 6" BELOW CLG WHICHEVER IS LOWER. SMOKE DETECTOR WITH SOUNDER BASE N P NURSE CALL DOME LIGHT GROUND ROD EXO-THERMIC WELD CONNECTION NURSE CALL PULL CORD FIRE RATED WALLS FIRE - 1 HOUR FIRE - 3 HOUR FIRE - 2 HOUR FIRE - 4 HOUR SYM. IDENTIFICATION SYM. NOTE: ALL SYMBOLS SHOWN MAY NOT APPEAR ON DRAWINGS. ALL MOUNTING HEIGHTS ARE TYPICAL UNLESS OTHERWISE NOTED. SYM. IDENTIFICATIONIDENTIFICATION S E J SYMBOLS LEGEND SHARED ELECTRICAL HOMERUN WHEN WIRE TAG HAS AN (*) ASTERISK PRECEDING PANEL- CIRCUIT INFO ELECTRICAL HOMERUN, CIRCUIT AS SHOWN *PNL-X ITEMS AND/OR DEVICES CIRCUITED TOGETHER ITEMS AND/OR DEVICES CIRCUITED TOGETHER, BUT SWITCHED SEPARATELY S WALL MOUNTED SPEAKER 2-LAMP FIXTURE CONNECTED TO NIGHT LIGHT CIRCUIT. 3 AND 4 LAMP FIXTURE CENTER LAMP(S) CONNECTED TO NIGHT LIGHT CIRCUIT. SEE LIGHTING FIXTURE LEGEND. MOTOR CONNECTION REQUIRING REMOTE STARTER/VFD. REFERENCE MOTOR CONNECTION SCHEDULE FOR ADDITIONAL INFORMATION. PENDANT FIXTURE MW K KEY PAD I INTERCOM CAMERA SIMPLEX RECEPTACLE MTD @ 18" AFF TO CENTER V LOCAL VOLUME CONTROL EQUIPMENT SURFACE MOUNTED RACEWAY EQUIPMENT CONNECTION RECESSED PANELBOARD SURFACE MOUNTED PANELBOARD ELM ELEVATOR LANDING MASTER PANEL. SEE ELEVATOR LANDING TWO-WAY COMMUNICATION DETAIL. ELS ELEVATOR LANDING STATION. SEE ELEVATOR LANDING TWO- WAY COMMUNICATION DETAIL. SM SOUND MASKING SPEAKER OFCI OWNER FURNISH CONTRACTOR INSTALL · SEE ARCHITECTURAL REFLECTED CEILING AND ELEVATION PLANS FOR LOCATION OF ALL LIGHTING FIXTURES. LOCATE FIXTURES IN ACCORDANCE WITH CEILING AND ELEVATION PLANS. · ONELINE DIAGRAMS AND RISER DIAGRAMS ARE A DIAGRAMMATIC REPRESENTATION TO AID THE CONTRACTOR IN UNDERSTANDING THE FUNCTION AND OPERATION OF THE SYSTEMS. E.C. SHALL REVIEW THE ONELINES, RISERS, AND FLOOR PLANS FOR THE EXACT QUANTITIES AND LOCATION OF ALL EQUIPMENT. E.C. SHALL FURNISH AND INSTALL ALL EQUIPMENT SHOWN ON ANY OR ALL OF THESE DIAGRAMS AND DRAWINGS. DETAILED WIRING DIAGRAMS SHOWING ACTUAL WIRING FOR THE SYSTEMS FURNISHED SHALL BE A PART OF THE SHOP DRAWING SUBMITTAL. · DEVICE LOCATIONS MAY BE DISTORTED FOR CLARITY. LOCATE DEVICES SYMMETRICALLY WITH THE ARCHITECTURAL ELEMENTS. · CONTRACTOR SHALL COORDINATE WITH THE OTHER TRADES TO VERIFY SPACES ARE CLEAR OF OBSTRUCTIONS. MAINTAIN MAXIMUM HEADROOM AND SPACE CONDITION AT ALL POINTS IN THE BUILDING. WHERE HEADROOM OR SPACE CONDITIONS APPEAR INADEQUATE, NOTIFY ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE INSTALLATION. · FURNISH OTHER TRADES ADVANCE INFORMATION ON LOCATIONS AND SIZES OF PIPING, DUCTWORK, EQUIPMENT, FRAMES, BOXES, SLEEVE AND OPENINGS NEEDED FOR WORK. FURNISH INFORMATION AND SHOP DRAWINGS TO PERMIT TRADES AFFECTED TO INSTALL THEIR WORK PROPERLY AND WITHOUT DELAY. · SEE HVAC AND PLUMBING PLANS FOR LOCATIONS OF HEATING, VENTILATING, AIR CONDITIONING AND PLUMBING EQUIPMENT. DO NOT REFERENCE ELECTRICAL DRAWINGS FOR EXACT LOCATION. · SCHEDULE REQUIRED POWER, TELEPHONE, OR DATA OUTAGES IN OCCUPIED AREAS OF THE BUILDING WITH THE OWNER. CONTRACTOR SHALL WORK UNTIL SERVICE IS RESTORED. OUTAGE WORK SHALL BE DONE AFTER OR BEFORE NORMAL WORKING HOURS, ON WEEKENDS OR HOLIDAYS. GENERAL ELECTRICAL NOTES REMARKS: (1) PROVIDE CABLE LENGTH TO MOUNT BOTTOM OF FIXTURE AT 8'-6" AFF. (2) PROVIDE STEM LENGTH TO MOUNT BOTTOM OF FIXTURE AT 9'-0" AFF (3) PROVIDE MINIMUM 12W LAMPHEADS FOR EMERGENCY LIGHTS. (4) PROVIDE MANUFACTURERS STANDARD LENGTHS OF TRACK TO MATCH LENGTHS SHOWN ON PLANS. PROVIDE ALL SUPPORTS, CONNECTORS AND POWER SUPPLIES FOR ACOMPLETE AND WORKING SYSTEM. SEE REFLECTED CEILING PLAN GENERAL NOTES · FIXTURE MODEL NUMBER MAY NOT REFLECT ALL MOUNTING HARDWARE. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY MOUNTING EQUIPMENT, LENSES, STEMS, SAFETY CHAINS, END PLATES, AND ALL OTHER HARDWARE NECESSARY FOR A COMPLETE FIXTURE INSTALLATION. SEE MOUNTING DETAILS WHEN APPLICABLE. (5) PROVIDE CABLE LENGTH TO MOUNT BOTTOM OF PENDANT AT 7'0" AFF. · ALL LIGHT FIXTURES ARE TO BE OWNER FURNISHED CONTRACTOR INSTALLED (6) TRACK MOUNTED AT 9'-0" CEILINGS SHALL HAVE 12" RIGID STANDOFFS. TRACKS MOUNTED AT EXPOSED STRUCTURE SHALL HAVE RIGID STANDOFFS EXTENDED FROM STRUCTURE ABOVE TO MOUNT BOTTOM OF TRACK HEAD AT 7'-6". FIELD VERIFY LENGTH. (7) PROVIDE CHAIN TO HANG FIXTURES 9'-0" AFF FROM BOTTOM OF FIXTURE. 2016 © EXCEL ENGINEERING, INC. SHEET INFORMATION SHEET NUMBER PROJECT INFORMATION PROJECT NUMBER PROFESSIONAL SEAL PRELIMINARY DATES NOT FOR CONSTRUCTION 100 CAMELOT DRIVE FOND DU LAC, WI 54935 PHONE: (920) 926‐9800 WWW.EXCELENGINEER.COM ARCHITECTS ● ENGINEERS ● SURVEYORS 2/1/2018 1:14:50 PM C:\Users\AndyL\Documents\Revit Local Files\1757840_Elec_Central_(rvt 2015)_AndyL.rvt SYMBOLS LEGEND & FIXTURE SCHEDULE 1757840 TENANT BUILD‐OUT FOR: PROFILE BY SANFORD 11503 SPRING MILL RD, SUITE 700 ● CARMEL, IN 46032 JAN. 31, 2018 E0.1 LIGHT FIXTURE SCHEDULE TYPE DESCRIPTION VOLTAGE LAMP QTY TYPE MANUF. / MODEL REMARKS TOTAL WATTAGE C16 6" DOWNLIGHT (OFCI) 120 V - W/FIXTURE 16 NORA LIGHTING / NLCBC-651-30K-DW / NHIC-17QAT EM1 WALL BATTERY EMERGENCY LIGHT WITH SELF-DIAGNOSTICS 120 V - W/FIXTURE - SURE-LITES / CC7NCSD (3) ID4 4' LINEAR DIRECT/INDIRECT (OFCI) 120 V 1 LED 61 PEERLESS / LDX-V1-DIN8-4-57-35-12-WM-60"-MV-D1 (1) L2 2X4 STEM MOUNTER TROFFER - ACRYLIC LENS (OFCI) 120 V 1 LED 49 PEERLESS / LACH3-24G-48-35K-12-MV-D1 (2) P1 PENDANT MOUNT (OFCI) 120 V 1 100W INC. 100 CONTEMPORARY LIGHTING / E20419-09 (5) R2 EXTERIOR REMOTE EMERGENCY HEAD (OFCI) 120 V - W/FIXTURE - EXITRONIX / TRL-EM-BR-CL S4 4' LED STRIP LIGHT (OFCI) 120 V - LED 32 TRACE LITE / BLCSLED4FT-32-4KMV-ET (7) T1 4' TRACK (OFCI) 120 V - - - NORA LIGHTIING / NRS0-P04 / NRS90-R39I / NRS0-N17-7-1/2 -11-1/2 / * / NRS0-P81 / * / * (4)(6) T2 LED TRACK HEAD (OFCI) 120 V 1 LED - NORA LIGHTING / NRS11-103LED-E10-S T3 6' DIAMETER TRACK (OFCI) 120 V - - - NORA LIGHTING / NRS0-P04 / NRS0-N17-7-1/2 -11-1/2 / * / NRS0-P81 / * / * (4)(6) XE COMBO SINGLE FACE EXIT W/REMOTE POWER EM HEADS - GREEN LETTERS 120 V - W/FIXTURE - SURELITE / APCH-7G NUMBER SHEET NAME ELECTRICAL E0.1 SYMBOLS LEGEND & FIXTURE SCHEDULE E0.2 SPECIFICATIONS E0.3 SPECIFICATIONS E1.1 FLOOR PLAN - ELECTRICAL E4.0 ONELINE DIAGRAMS, SCHEDULES & DETAILS SHEET INDEX 03/29/18 Nick Mishler