1757840 - Sheet - E0-2 - SPECIFICATIONS
2. KITCHEN AREAS: NEMA 250 TYPE 4X, STAINLESS STEEL. 1. OUTDOOR LOCATIONS: NEMA 250 TYPE 3R. D. ENCLOSURES: NEMA AB 1 AND NEMA KS 1 TO MEET ENVIRONMENTAL CONDITIONS OF INSTALLED LOCATION. C. FUSIBLE SWITCH: TYPE HD WITH CLIPS TO ACCOMMODATE FUSES. HANDLE LOCKABLE IN OPEN AND CLOSED POSITION. HANDLE INTERLOCKED WITH COVER IN CLOSED POSITION WITH INTERLOCK BYPASS. B. NONFUSIBLE SWITCH: TYPE GD WITH LOCKABLE HANDLE. A. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS DEFINED IN NFPA 70, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION, AND MARKED FOR INTENDED USE. 26 28 16 ENCLOSED DISCONNECT SWITCHES G. E.C. SHALL INCLUDE TIME IN HIS BID TO WORK WITH THE OWNER AND MANUFACTURER TO DETERMINE THE PROPER TIME AND SENSOR SETTING FOR EACH OF THE MOTION SWITCHES FOR THE TYPE OF SPACE IN WHICH THEY OPERATE. INCLUDE TIME IN BID TO HAVE THE MANUFACTURER'S REPRESENTATIVE ON SITE AND REVIEW THE JOB TO DETERMINE WHAT THE EXPECTED EQUIPMENT SETTINGS SHOULD BE. 6. PROVIDE MFR STANDARD LENS SUITABLE FOR APPLICATION. 5. LENS SHALL HAVE GROOVES FACING IN TO AVOID DUST AND RESIDUE BUILD UP. 4. FRESNEL LENS SHALL BE A POLY IR 4 BASED MATERIAL. 3. DAYLIGHT FILTER WHICH ENSURES THAT THE SENSOR IS INSENSITIVE TO SHORT-WAVELENGTH INFRARED WAVES SUCH AS THOSE EMITTED BY THE SUN. 2. DETECTION SHALL BE MAINTAINED WHEN A PERSON OF AVERAGE SIZE AND WEIGHT MOVES WITHIN A MAXIMUM DISTANCE OF 12" EITHER IN A HORIZONTAL OR VERTICAL MANNER AT THE APPROXIMATE SPEED OF 12" PER SECOND. 1. UTILIZE A TEMPERATURE COMPENSATED DUAL ELEMENT SENSOR AND A MULTI-ELEMENT FRESNEL LENS. UP TO 10 DIFFERENT PASSIVE INFRARED PATTERNS SHALL BE AVAILABLE BY LENS SELECTION. F. INFRARED SENSING 4. ULTRASONIC RECEIVERS: TEMPERATURE AND HUMIDITY RESISTANT WITH LESS THAN A 6 DB SHIFT IN THE HUMIDITY RANGE OF 10% TO 90% AND LESS THAN A 6 DB SHIFT IN THE TEMPERATURE RANGE OF -20 TO 60 DEGREES C. 3. ULTRASONIC FREQUENCY: 40 KHZ + .006%. 2. CIRCUIT SHALL BE SOLID STATE CONTROLLED WITH ADVANCED SIGNAL PROCESSING AND CRYSTAL ACCURACY. 1. VOLUMETRIC IN COVERAGE. E. ULTRASONIC SENSING 6. SENSOR SHALL HAVE STANDARD 5 YEAR WARRANTY AND BE UL LISTED. 5. POWER SUPPLY: UL LISTED POWER PACK THAT CONSISTS OF A TRANSFORMER AND CONTACT CLOSURE RELAY IN ONE PACKAGE. 4. TWO OUTPUTS: ONE OUTPUT IS BASED ON OCCUPANCY ONLY AND THE OTHER IS BASED ON OCCUPANCY WITH A HOLD OFF AND AN INTERNAL PHOTOCELL SETTING WHEN A MINIMUM LIGHT LEVEL IS PRESENT - ADJUSTABLE FROM 2.5 TO 430 FOOT-CANDLES. 3. SINGLE POLE, DOUBLE THROW ISOLATED RELAY WITH NORMALLY OPEN, NORMALLY CLOSED, AND COMMON OUTPUTS RATED AT 1 AMP FOR 24 VDC AND 1/2 AMP AT 120 VDC. THE ISOLATED RELAY IS FOR USE WITH HVAC CONTROL, DATA LOGGING, AND OTHER CONTROL OPTIONS. 2. INDEPENDENT SENSITIVITY ADJUSTMENTS AND LED DISPLAY FOR EACH SENSING TECHNOLOGY. 1. SENSORS SHALL BE SIZED FOR THE ROOM THEY SERVE BY MANUFACTURER'S VENDER OR COVER 1,500 SQUARE FEET WITH STANDARD LENS AND UP TO 90 LINEAR FEET WITH LONG RANGE LENS FOR WALKING MOTION WHEN MOUNTED AT A CEILING HEIGHT OF 12 FEET. D. SENSORS 3. RETRIGGER TIME DELAY: ONLY ONE MOTION IS NECESSARY TO TURN ON THE LIGHTS WITHIN 5 SECONDS AFTER TURNING OFF. 2. DETECTION BY EITHER TECHNOLOGY WILL HOLD LIGHTING ON FOR THE SET TIME PERIOD. 1. MOTION FROM BOTH TECHNOLOGIES MUST BE SENSED BEFORE TURNING LIGHTING ON. C. CONTROL STRATEGIES 2. PASSIVE INFRARED HEAT CHANGES. 1. DOPPLER SHIFTS IN TRANSMITTED ULTRASOUND. B. DUAL TECHNOLOGY CONTROL 3. POWER PACK: HUBBELL CPS-24 (SLAVE SL-20A). c) SINGLE STALL BATHROOM WALL SENSOR: HUBBELL LH-MT RATED FOR 1/6HP. b) DUAL LEVEL/CIRCUIT WALL SWITCH: HUBBELL LHMTD. a) SINGLE LEVEL WALL SWITCH: HUBBELL LH-MT SERIES 2. WALL SENSOR: b) LONG THROW FOR CORRIDORS OR OTHER LONG THROW SPACES: HUBBELL OMNI-US 2000. a) HUBBELL OMNI-DT. 1. CEILING SENSOR: A. MANUFACTURERS: HUBBELL, MYTECH, NOVITAS AND UNENCO, THE WATT STOPPER. 26 27 27 OCCUPANCY SENSORS G. BLANK, TELEVISION AND TELEPHONE OUTLETS: 4" SQUARE EXTRA DEEP BOX, SINGLE GANG RING AND BLANK COVER PLATE. PROVIDE CONDUIT FROM EACH BOX INTO AN ACCESSIBLE SPACE. TERMINATE CONDUIT WITH INSULATED CONNECTORS ON BOTH ENDS. 3. EXTERIOR: WEATHER-PROOF, GASKETED, LIFT COVER. RECEPTACLE COVER SHALL ALLOW CONTINUED USE WHEN COVER IS CLOSED. 2. MECHANICAL EQUIPMENT ROOM: STEEL. 1. INTERIOR: SMOOTH NYLON MATERIAL. F. COVER PLATES 7. MAKE CONNECTIONS THROUGH THE USE OF PIG-TAILS. 6. VERIFY ACTUAL LOCATION OF EQUIPMENT WITH OWNER PRIOR TO ROUGH-IN. 5. REVIEW RECEPTACLE LAYOUT WITH OWNER PRIOR TO ROUGH-IN. 4. SEE LEGEND FOR MOUNTING HEIGHTS. 3. EXTERIOR RECEPTACLES SHALL BE MARKED "WEATHER-RESISTANT" PER NEC. 2. GFCI RECEPTACLES: 20-AMPERE HUBBELL SPECIFICATION GRADE WITH LOCK OUT CAPABILITY UPON GFCI FAILURE. 1. DUPLEX GROUNDED RECEPTACLES, 20 AMPERE SPECIFICATION GRADE, HUBBELL 5362. E. RECEPTACLES: 2. PROVIDE 0-10V 3-WAY SLIDE DIMMER WITH ON/OFF SWITCH. EC SHALL VERIFY DIMMER IS COMPATIBLE WITH LED LIGHT FIXTURE. 1. PROVIDE 0-10V SLIDE DIMMER WITH ON/OFF SWITCH. EC SHALL VERIFY DIMMER IS COMPATIBLE WITH LED LIGHT FIXTURE. D. DIMMERS 3. PROVIDE PILOT LIGHT SWITCHES WHERE INDICATED. 2. SEE LEGEND FOR MOUNTING HEIGHTS. 1. 20-AMPERE HUBBELL 1221 SINGLE POLE, 1223 THREE-WAY AND 1224 FOUR-WAY. C. WALL SWITCHES: 2. COVER PLATE COLORS SHALL BE IVORY. 1. SWITCH AND RECEPTACLE COLORS SHALL BE IVORY. B. COLOR A. MANUFACTURERS: COOPER, HUBBELL, LEVITON AND PASS & SEYMOUR. 26 27 26 WIRING DEVICES A. EXISTING PANELBOARD (S) TO BE RE-USED 26 24 16 PANELBOARDS 1. PANELBOARDS B. PROVIDE TYPEWRITTEN DIRECTORY ACCURATELY INDICATING ROOMS AND/OR EQUIPMENT BEING SERVED AT THE FOLLOWING LOCATIONS: b. "FED FROM" LABEL. a. LABEL EQUIPMENT THAT IT SERVES. 3. DISCONNECTS: c. "FED FROM" LABEL b. LABEL EQUIPMENT THAT IT SERVES. a. TRANSFORMER IDENTIFICATION 2. TRANSFORMERS: c. "FED FROM" LABEL. b. FAULT CURRENT AMPERE RATING a. MOUNT IDENTIFICATION LABEL AT THE TOP OF THE FRONT COVER. MOUNT ON THE INSIDE OF DOOR FOR RECESSED PANELBOARDS. 1. PANELBOARDS: A. ENGRAVED LABELS: ENGRAVED 3-LAYER PHENOLIC LABEL WITH BLACK LETTERS ON WHITE MATERIAL, UNLESS OTHER COLORS ARE CALLED OUT ON THE DRAWINGS OR DETAILS. LABELS MINIMUM 3/4" HIGH AND 3" LONG. LABELS MAY BE ATTACHED WITH DOUBLE BACKED ADHESIVE TAPE UNLESS INDICATED OTHERWISE. LABELS REQUIRED AT: 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS F. SEAL ALL RACEWAY, CABLE AND CONDUIT PENETRATIONS THROUGH ALL WALLS IN THE ELECTRICAL ROOM(S). E. CONTRACTOR SHALL USE CAUTION PRIOR TO MAKING PENETRATIONS AS TO NOT DISTURB ANY EXISTING UTILITIES THAT MIGHT BE PRESENT IN EXISTING WALLS, CEILINGS OR FLOORS. THIS CONTRACTOR IS RESPONSIBLE FOR LOCATING EXISTING UTILITIES IN EXISTING WALLS, CEILINGS OR FLOORS. D. SMOKE WALL PENETRATIONS: CONDUITS OR CABLES PENETRATING PENETRATION SHALL NOT DESTROY THE BARRIER'S INTEGRITY. C. FIRE RATED INTERIOR WALL AND FLOOR PENETRATIONS: SEAL OPENING AROUND PIPE WITH A UL APPROVED FIRE-STOP SYSTEM HAVING AN F-RATING NOT LESS THAN THE HOURLY RATING OF THE ASSEMBLY BEING PENETRATED. B. NON-FIRE RATED INTERIOR WALL AND FLOOR PENETRATIONS: FILL VOID BETWEEN CONDUIT AND SLEEVE, CONCRETE, OR DRYWALL WITH EXPANDING POLYURETHANE FOAM. CAULK BETWEEN CONDUIT AND SLEEVE OR WALL WITH NON-HARDENING CAULK. 4. SLEEVE NOT REQUIRED FOR DRYWALL WALLS OR CORE DRILLED HOLE IN CONCRETE WALL. 3. FURNISH, INSTALL, AND GROUT SLEEVE IN EXISTING MASONRY AND NEW CONCRETE WALLS. 2. FURNISH SLEEVE TO MASON FOR NEW MASONRY WALLS. 1. FURNISH RIGID CONDUIT SLEEVES FOR CABLES PASSING THROUGH MASONRY, CONCRETE, OR OTHER SIMILAR CONSTRUCTION. A. SLEEVES F. 26 05 35 PENETRATIONS E. VERIFY LOCATION PRIOR TO ROUGH-IN. MATCH THE HEIGHT OF EXISTING DEVICES FOR INSTALLATIONS IN ADDITIONS TO EXISTING FACILITIES. D. OUTLET AND JUNCTION BOXES USED AS SURFACE METAL RACEWAY SHALL BE MANUFACTURED BY THE SURFACE METAL RACEWAY MANUFACTURER TO BE COMPATIBLE WITH THE RACEWAY USED. C. JUNCTION AND SPLICE BOXES SHALL HAVE GALVANIZED SCREW COVERS AND BE NOT LESS THAN CODE DIMENSIONS. THROUGH-WALL AND BACK-TO-BACK BOXES NOT ALLOWED. B. PROVIDE CAST BOXES FOR EXTERIOR USE DEVICES. NONMETALLIC BOXES MAY BE USED FOR EXTERIOR USE DEVICES WHERE PERMITTED BY STATE AND LOCAL CODES AND AUTHORITY HAVING JURISDICTION. PROVIDE COVERS WITH GASKETS. A. FLUSH INTERIOR 4" SQUARE STEEL BOXES WITH RAISED COVERS AND SQUARE CUT CORNERS. PROVIDE BOXES RATED FOR THROUGH FEED. 26 05 33 BOXES 8. PROVIDE UL LISTED FIRE-WALL PENETRATIONS WHEN CONDUIT PASS THROUGH A FIRE RATED WALL. 7. SECURE CONDUITS WITH AT LEAST ONE CORROSION PROOF MALLEABLE ALLOY STRAP OR HANGER EVERY 8 FT. DO NOT USE PERFORATED STRAPPING. 6. INSTALL FLEXIBLE STEEL CONDUIT DROPS FROM INDEPENDENT JUNCTION BOX MOUNTED ABOVE CEILING TO RECESSED LIGHT FIXTURES. 5. ROUTE CONDUIT ABOVE LAY-IN SUSPENDED CEILINGS SO AS NOT TO INTERFERE WITH TILE REMOVAL. 4. WHEN REQUIRED BY STATE AND LOCAL CODES AND ORDINANCES, PROVIDE SEPARATE CONDUIT/RACEWAY FOR FIRE ALARM AND TELECOMMUNICATION SYSTEMS. 3. INSTALL CONDUIT WITH ADEQUATE DRAINAGE. 2. INSTALL UL APPROVED EXPANSION FITTINGS COMPLETE WITH GROUNDING JUMPERS WHERE CONDUITS CROSS BUILDINGS EXPANSION JOINTS AND IN LONG CONDUIT RUNS WHERE DIFFERENTIAL EXPANSION OR CONTRACTION WOULD CAUSE BENDING OR SEPARATION. 1. DRAWINGS AND DIAGRAMS SHOW SIZE AND APPROXIMATE LOCATION OF CONDUIT. THE DRAWINGS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION. PROVIDE ADDITIONAL OFFSETS AS REQUIRED FOR FIELD CONDITIONS. ROUTE CONDUIT IN ORDERLY MANNER, PARALLEL TO BUILDING STRUCTURE. CONCEAL CONDUIT IN FINISHED AREAS. F. INSTALLATION 4. SCHEDULE 40 PVC. 3. MINIMUM SIZE 3/4". 2. ALLOWED FOR ABOVE GRADE CONDUIT WHEN CONDUIT IS UL LISTED FOR DIRECT SUNLIGHT EXPOSURE AND WHEN ALLOWED BY CODE AND LOCAL AUTHORITY HAVING JURISDICTION. 1. USE FOR CONDUIT IN CONCRETE, UNDER FLOOR SLABS, OR IN EARTH WHEN PERMITTED BY CODE AND LOCAL ORDINANCES. E. PVC 4. STEEL FITTINGS WITH INSULATED THROAT, UL LISTED. 3. MAXIMUM LENGTH 72" FOR CONNECTION TO FIXTURES IN TILE CEILINGS. 2. MAXIMUM LENGTH 36" FOR CONNECTION TO HVAC EQUIPMENT 1. MINIMUM SIZE 1/2". D. FLEXIBLE 3. SUPPORT MINIMUM EVERY TWO FEET. 2. ALLOWED FOR ABOVE GRADE CONDUIT WHICH IS CONCEALED INSIDE NON-RATED WALLS AND WHERE PERMITTED BY CODE AND LOCAL AUTHORITY HAVING JURISDICTION. 1. SIZES: MINIMUM 1/2", MAXIMUM 1". C. ENT 2. STEEL SET SCREW OR COMPRESSION TYPE FITTINGS WITH INSULATED THROAT. 1. ALLOWED FOR INSIDE ABOVE GRADE CONDUIT 2" AND SMALLER. B. EMT 4. GALVANIZED RIGID STEEL WITH GALVANIZED RIGID STEEL FITTINGS, THREADED WATERTIGHT. 3. GALVANIZED RIGID STEEL REQUIRED FOR ALL UNDERGROUND 90 DEGREE BENDS. 2. REQUIRED WHERE CALLED OUT ON PLANS. 1. ALLOWED FOR ALL SIZES BELOW GRADE AND INSIDE ABOVE GRADE. A. RMC 26 05 30 CONDUIT 1. PROVIDE FINAL INTERIOR EQUIPMENT CONCRETE PAD SIZE REQUIREMENTS TO CONCRETE CONTRACTOR. PADS SHALL EXTEND MINIMUM 2" BEYOND EQUIPMENT FOOTPRINT. C. CONCRETE PADS AND POLE BASES 2. SUPPORT WITH PAINTED OR GALVANIZED STEEL CHANNEL. 1. 3/4" PLYWOOD PAINTED ON BOTH SIDES AND EDGES WITH TWO COATS OF WHITE ENAMEL PAINT TO MOUNT EQUIPMENT WHERE SHOWN. B. BACKBOARDS 3. PROVIDE ANGLES, CHANNELS, AND BEAMS AS REQUIRED. 2. ATTACH TO STRUCTURAL COMPONENTS TO NOT JEOPARDIZE STRUCTURAL INTEGRITY. 1. PROVIDE PROPER FITTINGS AND SUPPORT SUITABLE FOR AMBIENT/ENVIRONMENTAL CONDITIONS AND SERVICE DUTY. A. CONDUIT HANGERS, ATTACHMENTS, AND SUPPORTS 26 05 29 HANGERS AND SUPPORTS I. TESTING: ALL CIRCUITS SHALL BE TESTED FOR PROPER OPERATION AND FUNCTION. REPARE ALL NON-WORKING, NEWLY INSTALLED, CIRCUITS. H. PROVIDE A SEPARATE NEUTRAL CONDUCTOR FOR EACH LIGHTING BRANCH CIRCUIT THAT SERVES HID, ELECTRONIC FLUORESCENT BALLASTS AND SOLID-STATE LED DRIVERS OR PROVIDE A NEUTRAL CONDUCTOR ONE SIZE LARGER THAN THE LARGEST SOURCE CONDUCTOR WHEN THE NEUTRAL IS SHARED. G. PROVIDE A SEPARATE GROUND CONDUCTOR AND A SEPARATE NEUTRAL CONDUCTOR WHEN AN INDIVIDUAL RECEPTACLE OR PIECE OF EQUIPMENT IS SHOWN WITH AN INDIVIDUAL HOMERUN. F. WHEN USING ALUMINUM CONDUCTORS: THE CONTRACTOR SHALL SEAL ALL EXPOSED ALUMINUM WHEN CONDUCTOR IS EXPOSED IN A LUG WITH AN ANTI-OXIDANT COMPOUND. THE CONDUCTORS SHALL BE COMPACT CONCENTRIC STRANDED PURE ALUMINUM CONDUCTORS. E. PROVIDE GROUND CONDUCTOR(S) WITH EVERY BRANCH CIRCUIT AND EVERY FEEDER. D. TWO PERCENT VOLTAGE DROP AT PANELBOARDS AND THREE PERCENT FOR BRANCH CIRCUITS FOR FIVE PERCENT VOLTAGE DROP PER NEC. 2. 277/480-VOLT SYSTEMS: PHASE-A (BROWN), PHASE-B (ORANGE), PHASE-C (YELLOW). 1. 120/208-VOLT AND 120/240-VOLT SYSTEM: PHASE-A (BLACK), PHASE-B (RED), PHASE-C (BLUE). C. WIRE COLORS B. NEUTRALS AND GROUNDS SHALL BE COLOR CODED PER NEC. 10. TYPE AC OR MC CABLE IS ACCEPTABLE WHERE ALLOWED BY STATE AND LOCAL CODES AND LOCAL AUTHORITY HAVING JURISDICTION. 9. UF CABLE IS ACCEPTABLE WHERE ALLOWED BY STATE AND LOCAL CODES AND LOCAL AUTHORITY HAVING JURISDICTION. 8. NM CABLE IS ACCEPTABLE WHERE ALLOWED BY STATE AND LOCAL CODES AND LOCAL AUTHORITY HAVING JURISDICTION. 7. GREEN INSULATION, COPPER STRANDED EQUIPMENT GROUND. 6. CONTROL WIRING: STRANDED COPPER, MINIMUM NO. 14. 5. MINIMUM BRANCH CIRCUIT WIRE SIZE NO. 12. 4. 250 KCMIL AND LARGER: STRANDED COPPER OR ALUMINUM, 600V, XHHW. 3. NO. 2 TO 250 KCMIL: STRANDED COPPER OR ALUMINUM, 600V, THHN/THWN. 2. NO. 8 TO 3: STRANDED COPPER, 600V, THHN/THWN. 1. NO. 10 & 12: SOLID OR STRANDED COPPER, 600V, THHN/THWN. A. TYPE AND SIZE 26 05 19 LOW VOLTAGE POWER CONDUCTORS AND CABLES (600V AND LESS) B. ASSIST THE OWNER IN APPLYING FOR ELECTRICAL SERVICE AND COORDINATE NEW SERVICE INSTALLATION WITH THE UTILITY COMPANY. PROVIDE METERING EQUIPMENT, TRANSFORMER PAD, AND CONDUIT ROUGH-IN AS REQUIRED BY THE UTILITY. A. EXISTING - PROVIDED BY LANDLOARD 26 05 02 ELECTRICAL SERVICE c. WIRE HOLDDOWN CLIPS ARE PROVIDED IN THE RACEWAY. b. RACEWAY HAS DIVIDERS BETWEEN THE LOW VOLTAGE AND LINE VOLTAGE COMPARTMENTS. a. EACH LINE VOLTAGE CIRCUIT IN THE RACEWAY IS PROVIDED WITH A SEPARATE GREEN GROUND WIRE. 2. WHERE IT IS IMPOSSIBLE TO CONCEAL CONDUIT AND WHEN APPROVED BY ARCHITECT, METAL SURFACE RACEWAY MAY BE USED FOR 110 VOLT OR GREATER POWER. PLASTIC SURFACE RACEWAY MAY BE USED UNDER THE FOLLOWING CIRCUMSTANCES: 1. CONCEAL CONDUIT IN WALLS, ABOVE CEILING, OR BELOW FLOORS. R. REMODELING IN EXISTING CONSTRUCTION 5. RESTORE EXISTING GROUND, LAWNS, PAVING, WALKS, ETC. TO ORIGINAL CONDITION. 4. BURY CONDUIT AND CABLE A MINIMUM 24" DEEP WITH 6" SAND BED ABOVE AND BELOW, AND WARNING MARKER TAPE MINIMUM 12" ABOVE. 3. CONDUIT PASSING UNDER FOOTINGS AND FOUNDATION WALLS ARE ALLOWED WHERE PERMITTED BY NEC. MAINTAIN MINIMUM 1-1/2" CLEARANCE UNDER FOOTINGS AND FOUNDATION WALLS. 2. EXCAVATE AND BACKFILL TRENCHES FOR ELECTRICAL WORK. BACKFILL AND COMPACTION SHALL MEET REQUIREMENTS SPECIFIED ELSEWHERE. 1. VERIFY ALL EXISTING UNDERGROUND ELECTRICAL FEEDERS, BRANCH CIRCUITS, LOW VOLTAGE CABLES AND FIBER OPTIC HAVE BEEN LOCATED BEFORE STARTING PRIOR TO EXCAVATION. CONTRACTOR SHALL NOT USE MACHINE EXCAVATORS AROUND EXISTING UNDERGROUND ELECTRICAL FEEDERS, BRANCH CIRCUITS, LOW VOLTAGE CABLES AND FIBER OPTIC CABLES. N. EXCAVATION AND BACKFILL. e) COORDINATE WITH THE OTHER CONTRACTORS AND WHEREVER PRACTICAL, GROUP DEVICES IN SUCH A MANNER SO AS TO MINIMIZE PANELS. d) ARCHITECT TO APPROVE ACCESS PANEL LOCATION PRIOR TO INSTALLATION OF EQUIPMENT REQUIRING ACCESS. c) TURN ACCESS PANEL OVER TO CONTRACTOR SKILLED IN THE CONSTRUCTION OF THE SURFACES INVOLVED FOR INSTALLATION. b) PANELS UL LISTED TO CONFORM TO THE FIRE RATING OF THE SURFACE INSTALLED IN. a) FURNISH ACCESS PANELS OF ADEQUATE SIZE TO PERMIT SERVICE OF CONCEALED DEVICES. PANELS SHALL BE SUITABLE FOR INSTALLATION IN THE MATERIAL FORMING THE FINISHED SURFACE, WITH FLUSH METAL FRAME, FLUSH HINGED STEEL DOOR, FLUSH SCREWDRIVER OPERATED LATCH. 2. ACCESS PANELS 1. INSTALL EQUIPMENT, JUNCTION BOXES, PULL BOXES AND ACCESSORIES TO PERMIT ACCESS WITHOUT RELOCATING INSTALLED OR YET TO BE INSTALLED EQUIPMENT. M. ACCESS 2. DO NOT LOCATE OUTLETS OR EQUIPMENT WHERE THE USEFULNESS AND/OR OPERATION WILL BE AFFECTED BY THE WORK OF OTHER TRADES, DOOR SWING, COUNTER, EQUIPMENT, ETC. 1. THE ARCHITECT SHALL RESERVE THE RIGHT TO MAKE OUTLET POSITION CHANGES UP TO 10' BEFORE INSTALLATION. L. LOCATION 3. PROVIDE RECORD DRAWINGS TO THE OWNER IN AUTOCAD FORMAT. 2. MARK RECORD DRAWINGS ON A FINAL SET OF DRAWINGS WHICH INCLUDES ALL REVISIONS. 1. CLEAN FIXTURES AND EQUIPMENT AND LEAVE IN PROPER WORKING CONDITION AT THE TIME OF FINAL CLEAN-UP. K. PROJECT COMPLETION J. REMOVE FROM THE JOB SITE ELECTRICAL CONDUIT, PANELS, CABLE, WIRE, EQUIPMENT, ETC. INDICATED BY THE DRAWINGS TO BE DEMOLISHED, UNLESS INDICATED TO BE TURNED OVER TO THE OWNER. I. PROVIDE ALL CUTTING AND PATCHING NECESSARY FOR ELECTRICAL WORK INSTALLATION UNLESS THIS WORK IS IDENTIFIED TO BE THE WORK OF OTHER CONTRACTORS. PATCHING SHALL MATCH ADJACENT SURFACES. CORE DRILL OR SAW-CUT OPENINGS THROUGH EXISTING CONCRETE. H. CONTRACTOR SHALL CALL LOCAL LOCATING SERVICE AND CONDUCT A PRIVATE UTILITY LOCATE TO INSURE THAT ALL ELECTRICAL FEEDERS, BRANCH CIRCUITS, LOW VOLTAGE CABLES AND FIBER OPTIC HAVE BEEN LOCATED BEFORE STARTING SITE DEMOLITION. DESIGN ENGINEER AND GENERAL CONTRACTOR SHALL BE NOTIFIED OF ANY DISCREPANCIES BETWEEN PLAN AND FIELD CONDITIONS PRIOR TO CONSTRUCTION. G. VERIFY ELECTRICAL SIZE AND CONNECTION REQUIREMENTS FOR EQUIPMENT FURNISHED BY OTHERS. F. INSTALL MOTOR STARTERS/VFDS FURNISHED BY HVAC AND PLUMBING CONTRACTORS, AND WIRE FROM THE POWER SOURCE TO THE STARTER/VFD AND FROM THE STARTER/VFD TO THE MOTOR. SEE HVAC AND PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION AND LOCATIONS. E. COORDINATE INSTALLATION OF ELECTRICAL WORK WITH THE OTHER CONTRACTORS TO AVOID CONFLICTS WITH OTHER WORK. D. MATERIAL SHALL BEAR U.L. AND/OR OTHER APPROVED AGENCY LISTING. C. COMPLY WITH THE REQUIREMENTS OF NFPA; NATIONAL, STATE AND LOCAL ELECTRICAL CODES AND LOCAL UTILITY REGULATIONS. B. ELECTRICAL CONTRACTOR SHALL VERIFY REQUIREMENTS FOR TEMPORARY LIGHTING AND POWER WITH GENERAL CONTRACTOR AND INCLUDE IN HIS SCOPE OF WORK WHEN DIRECTED BY G.C. INSTALL IN ACCORDANCE WITH ALL CODE AND OSHA REQUIREMENTS FOR CONSTRUCTION PROJECTS. A. THESE PLANS ARE SHOWN TO AID THE CONTRACTOR AND ARE NOT MEANT TO BE INCLUSIVE OF ALL DEVICES, DISCONNECTS AND ACCESSORIES. PROVIDE REQUIRED EQUIPMENT AND ACCESSORIES FOR A COMPLETE INSTALLATION. 26 05 01 BASIC ELECTRICAL REQUIREMENTS E. E.C. SHALL PROVIDE FINISH/PAINT WHERE SPECIFIED ELSEWHERE. D. WHERE THE ELECTRICAL CONTRACTOR IS REQUIRED TO PAINT, THE PAINTING SHALL BE DONE IN ACCORDANCE WITH THE PAINTING PORTION OF THE ARCHITECTURAL SPECIFICATION. C. IF FINISH BECOMES RUSTED, CORRODED, SCRATCHED, OR FLAKED DURING STORAGE OR INSTALLATION, REFINISH THE EQUIPMENT TO THE SATISFACTION OF THE OWNER. B. COORDINATE WORK WITH THE PAINTERS SO THAT ALL EQUIPMENT IS INSTALLED PRIOR TO PAINTING. E.C. SHALL PAINT ITEMS IF NOT IN PLACE PRIOR TO NORMAL ROUTINE PAINTING. A. E.C. SHALL PROVIDE A FACTORY OR FIELD APPLIED PRIME AND FINISH COAT OF COLOR SELECTED BY THE OWNER'S REPRESENTATIVE TO ALL ROOF MOUNTED EQUIPMENT AND OTHER EXTERIOR MATERIALS, INCLUDING SUPPORT HARDWARE. 09 91 00 FINISH AND PAINTING C. IN AS MUCH AS THE SPECIFICATIONS ARE BRIEF, THE CONTRACTOR SHALL PROVIDE WORKMANSHIP THAT IS OF THE BEST QUALITY WITH THE BEST POSSIBLE APPEARANCE AND UTILITY. FAULTY WORK SHALL BE REPAIRED OR REPLACED AT NO COST TO THE OWNER. INDUSTRY STANDARDS SHALL BE USED AS THE GUIDE FOR QUALITY OF MATERIALS AND WORKMANSHIP. 2. WHERE SUBSTITUTE EQUIPMENT REQUIRES REDESIGN OF ANY PART OF THE PROJECT, THE COST OF REDESIGN AND ADDITIONAL COSTS OF THE WORK SHALL BE PAID BY THE CONTRACTOR. REDESIGN SHALL BE SUBJECT TO THE APPROVAL OF ALL AUTHORITIES HAVING JURISDICTION OVER THE WORK INCLUDING THE ARCHITECT/ENGINEER. 1. WHERE "PRE-APPROVED EQUIVALENT" IS SCHEDULED, SUBMIT EQUIPMENT CUT SHEETS AND WRITTEN DESCRIPTION OF ANY DIFFERENCES BETWEEN THE SPECIFIED AND PROPOSED EQUIPMENT PRIOR TO BID TIME. B. SUBSTITUTIONS A. SEE SHEET T2.0. 01 11 00 GENERAL REQUIREMENT A. SEE SHEET T2.0. 00 72 00. GENERAL CONDITIONS DIVISION 26 ELECTRICAL 2016 © EXCEL ENGINEERING, INC. SHEET INFORMATION SHEET NUMBER PROJECT INFORMATION PROJECT NUMBER PROFESSIONAL SEAL PRELIMINARY DATES NOT FOR CONSTRUCTION 100 CAMELOT DRIVE FOND DU LAC, WI 54935 PHONE: (920) 926‐9800 WWW.EXCELENGINEER.COM ARCHITECTS ● ENGINEERS ● SURVEYORS 2/1/2018 1:14:52 PM C:\Users\AndyL\Documents\Revit Local Files\1757840_Elec_Central_(rvt 2015)_AndyL.rvt SPECIFICATIONS 1757840 TENANT BUILD‐OUT FOR: PROFILE BY SANFORD 11503 SPRING MILL RD, SUITE 700 ● CARMEL, IN 46032 JAN. 31, 2018 E0.2 ELECTRICAL SPECIFICATIONS 03/29/18 Nick Mishler