HomeMy WebLinkAbout1757840 - Sheet - P3-0 - DETAILSMAX. SPACING BETWEEN PIPE SUPPORTS AND MIN. HANGER ROD SIZES PIPE SIZE WATER VAPOR PIPE CLAMP B-LINE B2000 SERIES STRUT SUPPORT SYSTEM PIPE CLAMP B-LINE B2000 SERIES COPPER FINISH FOR COPPER TUBING. 1/4"-1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 7 7' 7' 7' 9' 10' 11' 12' 12' 8' 9' 9' 9' 12' 12' 12' 12' 12' THREADED MILD STEEL BLACK OR ZINC PLATED FINISH, THREADED ROD. (TYP) 8" AND SMALLER : CARBON STEEL ADJUSTABLE BAND HANGER MSS SP-58 TYPE 10 (B-LINE FIG. 200). PLASTIC COATED FOR COPPER TUBNG (B- LINE FIG. 200C). ALL SIZES: CARBON STEEL STANDARD CLEVIS HANGER MSS SP-58 TYPE 1 (B-LINE FIG. B3100). PLASTIC COATED FOR COPPER TUBNG (B-LINE FIG. B3100C). 6" 8" 10" 12" 12' 12' 12' 12' 12' 12' MSS = MANUFACTURER'S STANDARDIZATION SOCIETY - INSTALL ADDITIONAL HANGERS WITHIN 12" OF ELBOWS AND TEES AND AT CONCENTRATED LOADS, INCLUDING VALVES, FLANGES AND STRAINERS 2 1/2" AND LARGER. CARBON STEEL STANDARD CLEVIS HANGER MSS SP-58 TYPE 1 (B-LINE FIG. B3100). PLASTIC COATED FOR COPPER TUBNG (B-LINE FIG. B3100C). CALCIUM SILICATE PRE-INSULATED SUPPORT (B-LINE FIG. B338* - INSULATION THICKNESS SAME AS ADJACENT INSULATION) WITH VAPOR BARRIER FOR COLD PIPING. CALCIUM SILICATE PRE-INSULATED SUPPORT (B-LINE FIG. B338* - INSULATION THICKNESS SAME AS ADJACENT INSULATION) WITH VAPOR BARRIER FOR COLD PIPING. INSULATION (THICKNESS AND TYPE PER SCHEDULE) (TYP) GALVANIZED CARBON STEEL SHIELD - MSS SP-58 TYPE 40 (B-LINE FIG. 3151) SECURE BOTH ENDS WITH ZESTON 5 MIL PVC Z-TAPE ll WITH 2" OVERLAP. - UNINSULATED PIPING APPLICATIONS - HOT AND COLD WATER PIPING APPLICATIONS - HOT AND COLD WATER PIPING APPLICATIONS HANG FROM BEAM CLAMPS, CONCRETE INSERTS, UNI-STRUT, STRUCTURAL STEEL OR WALL BRACKET. (TYP) 14" 16" MAX VERT. (1) 12' 12' 15' (1) SUPPORT AT MINIMUM EVERY FLOOR LEVEL OR SPACING LISTED. STEEL MIN. ROD 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" WATER VAPOR MIN. ROD 5' 5' 6' 7' 8' 8' 9' 10' 12' 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 12' - - - 3/8" - - 10' COPPER PVC PEX MIN. ROD 4' 4' 4' 4' 4' 4' 4' 4' 4' 32" 32" 32" 32" 32" - - - - 4' 4' 4' 4' - - 4' 4' 10' 12' 12' 12' 12' 15' - 1/2" 5/8" 5/8" 3/4" - 1/2" 6' 7' 8' 9' 10' 11' 12' 12' 12' 12' - - - - - 10' - - - - - - - - - - 10' 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" - CPVC 3' 3' 3' 4' 4' 4' 4' 4' 4' 4' 4' 4' 4' 4' 4' 10' CAST IRON (2) 5' 5' 5' 5' 5' 5' 5' 5' 5' 5' - - - - 5' (2) SPACING MAY BE INCREASED TO 10' FOR 10' PIPE LENGTHS. EXTERIOR OF PIPE OR INSULATION. NON-HARDENING SEALANT (PROVIDE BACKER ROD AS REQUIRED) DRYWALL WALL EXPOSED IN FINISHED ROOMS CHROME PLATED STEEL ESCUTCHEON PLATE CONCEALED SIDE OF WALL, EXPOSED IN MECH. EQUIP. ROOM, OR OUTDOORS 3/4" CW SHUTOFF VALVE DRAIN VALVE THERMOMETER HW UNION (TYP.) T & P RELIEF VALVE WATER HEATER WH-1 3/4" DRAIN PAN 1 1/2" LOCAL WASTE DN THRU WALL TO 6" A.F.F. OF 114 "BREAKROOM", NEAR SS-1 AND FD-1. WALL AIR GAP FOR T&P VALVE DISCHARGE. ET-1 PLATFORM BY G.C. CONCENTRIC JOIST HANGER THRU JOIST BOTTOM CHORD. -NO ANGLE BRACE REQ'D IF LOAD OCCURS WITHIN 4" OF A JOIST PANEL POINT CENTERLINE -DETAIL APPLIES TO LOADS ABOVE OR HUNG BELOW JOISTS IN EXCESS OF 100 LBS. L1 1/2 x 1 1/2 x 3/16 STEEL ANGLE EACH SIDE BY STRUCTURAL STEEL ERECTOR. -LOADS HUNG FROM BOTTOM CHORD SHALL BE CONCENTRICALLY LOADED. CLAMP STYLE THRU-ROD STYLE OR STEEL WASHER PLATE. PANEL POINT. TYP.EA.END 1" 3/16" L-1 SUPPLY STOP (TYP.) P-TRAP 24 VAC TO 9 VDC CONVERTER PROVIDED BY P.C. INSIDE J-BOX. PROVIDE RUBBER GROMMET THRU COVER FOR WIRE. CONCEAL EXCESS WIRE WITHIN J-BOX. 4"x4" J-BOX PROVIDED BY E.C. WITH COVER PLATE. CONNECTOR PLUG PROVIDED W/ FAUCET. P.C. SHALL PROVIDE SPLICE IN LOW VOLTAGE WIRE BETWEEN CONVERTER PIGTAIL AND WIRING FROM TRANSFORMER. CONDUIT & WIRE TO ADDITIONAL FAUCET. 24 VAC WIRING THRU CONDUIT BY P.C. 1/2" CONDUIT IN WALL PROVIDED BY E.C. 120 VAC BY E.C. BOX MOUNT TRANSFORMER FURNISHED BY P.C. INSTALLED ON J-BOX BY E.C. FLOOR CEILING COUNTER BY G.C. TW HW TMV-1 CW FURNISHED BY SYPATECO, INSTALLED BY P.C.. 2017 © EXCEL ENGINEERING, INC. SHEET INFORMATION SHEET NUMBER PROJECT INFORMATION PROJECT NUMBER PROFESSIONAL SEAL PRELIMINARY DATES NOT FOR CONSTRUCTION 100 CAMELOT DRIVE FOND DU LAC, WI 54935 PHONE: (920) 926-9800 WWW.EXCELENGINEER.COM ARCHITECTS ● ENGINEERS ● SURVEYORS 2/1/2018 3:34 :43 PM C:\Users\TonyC\Documents\1757840_Plbg_Central_(rvt 2015)_tony.cGCK3T.rvt DETAILS 1757840 TENANT BUILD-OUT FOR: PROFILE BY SANFORD 11503 SPRING MILL RD, SUITE 700 ● CARMEL, IN 46032 JAN. 31, 2018 P3.0 P3.0 NOT TO SCALE 1 PIPE HANGER AND INSULATION DETAILS P3.0 NOT TO SCALE 4 PIPE PENETRATION THRU STUD WALL P3.0 NOT TO SCALE 5 WATER HEATER PIPING DETAIL P3.0 NOT TO SCALE 3 JOIST HANGER CONNECTION DETAIL P3.0 NOT TO SCALE 7 FAUCET WIRING DETAIL 03/29/18 Nick Mishler