HomeMy WebLinkAboutMechanicalSECTION 15990 TESTING, START-UP, BALANCING, ETC. GENERAL: CONDUCT TESTS UPON COMPLETION OF THE HEATING AND VENTILATION INSTALLATIONS, AND AT TIMES AS DESIGNATED BY THE ARCHITECT. FURNISH ALL NECESSARY PERSONNEL AND TEST INSTRUMENTS. DUCTWORK: TEST ALL SUPPLY, RETURN AND EXHAUST DUCTS, PLENUMS, AND CASINGS AND MAKE SUBSTANTIALLY AIRTIGHT BEFORE COVERING WITH EXTERNAL INSULATION OR CONCEALING IN MASONRY. SUBSTANTIALLY AIRTIGHT SHALL BE CONSTRUED TO MEAN THAT NO AIR LEAKAGE IS NOTICEABLE THROUGH THE SENSES OF FEELING OR HEARING AT JOINTS. TEST SUPPLY DUCTWORK UNDER THE POSITIVE PRESSURE FOR THE RESPECTIVE SYSTEM. TEST RETURN AND EXHAUST DUCTS, PLENUM AND CASING UNDER A POSITIVE PRESSURE OF 2 INCH WG. VACUUM DEAN DUCTS, PLENUMS, CASING AND COILS. DEMONSTRATE OPERATION OF FIRE DAMPERS BEFORE INSTALLING FUSIBLE LINKS. CHECK THAT FLEXIBLE CONNECTIONS ARE LOOSE AND NOT TRANSMITTING VIBRATION. PERFORMANCE TESTS: AFTER CLEANING, BALANCING, AND TESTING ARE COMPLETED AS SPECIFIED, TEST EACH SYSTEM AS A WHOLE TO SEE THAT ALL ITEMS PERFORM AS INTEGRAL PARTS OF THE SYSTEM AND THAT TEMPERATURES AND CONDITIONS ARE EVENLY CONTROLLED THROUGHOUT THE BUILDING. MAKE CORRECTIONS AND ADJUSTMENTS AS NECESSARY TO PRODUCE THE INDICATED CONDITIONS. AFTER BUILDING IS OCCUPIED, MAKE MINOR ADJUSTMENTS AS REQUESTED BY THE OWNER. BALANCING: CHECK AIR FLOW AT SUPPLY, RETURN AND EXHAUST GRILLES AND DIFFUSERS AND OUTSIDE AIR INTAKES WITH A RECENTLY CALIBRATED DIRECT-READING VELOCITY INSTRUMENT; ADJUST SYSTEMS TO DELIVER, RETURN OR EXHAUST AIR QUANTITIES WITHIN 5 PERCENT OF THE INDICATED AMOUNTS. PROVIDE INSTRUMENTS AND OTHERWISE ASSIST ENGINEER IN CHECKING THE BALANCING AT FINAL INSPECTION. TEST DATA: ALL TEST AND BALANCE SHALL BE CONDUCTED BY A SEPARATE LICENSED AIR BALANCE CONTRACTOR RECOGNIZED BY THE ASSOCIATED AIR BALANCE COUNCIL. ALL TESTS SHALL BE CONDUCTED IN ACCORDANCE WITH AABC GUIDELINES. TWO WEEKS PRIOR TO FINAL INSPECTION, SUBMIT TYPEWRITTEN SCHEDULES OF READINGS TAKEN DURING THE BALANCING AND TESTING OPERATIONS INDICATING THE REQUIRED OR SPECIFIED READING, THE FIRST READING TAKEN, AND FINAL BALANCED READING FOR THE FOLLOWING ITEMS: (1). FANS -SIZE, TYPE, FAN SPEED IN RPM, EXTERNAL STATIC WATER PRESSURE, AIR QUANTITY CFM, AND MOTOR LOAD IN AMPERES. (2). AIR OUTLETS AND INLETS -SIZE, VELOCITY IN FPM, AND AIR QUANTITY IN CFM. (3). COILS OR HEAT EXCHANGERS -SIZE, FACE VELOCITY IN FPM; AIR TEMPERATURE ENTERING COIL AND AIR TEMPERATURE LEAVING COIL, WET-BULB AND DRY-BULB DEGREES F. (4). DUCTS: SIZE, VELOCITY IN FPM, STATIC PRESSURES, AND AIR QUANTITY IN CFM. END OF SECTION 15990 SECTION 15932 DIFFUSERS, REGISTERS & GRILLES PRODUCTS SHALL BE AS SCHEDULED ON THE DRAWINGS. SELECTIONS ARE BASED ON THE MANUFACTURERS SCHEDULED. UNITS BY OTHER MANUFACTURERS SHALL BE RE-SELECTED IN ACCORDANCE WITH PUBLISHED PERFORMANCE DATA TO PROVIDE THE AIR PATTERNS, VELOCITIES, PRESSURE DROPS, AND SOUND CHARACTERISTICS EQUAL TO THE UNIT SCHEDULED. THE RE-SELECTION SHALL BE CERTIFIED BY A LETTER SUBMITTED AS PART OF THE SHOP DRAWING SUBMITTAL. UNITS EQUIVALENT TO THOSE SCHEDULED BY TITUS, KRUEGER, HART & COOLEY OR OTHER PRIOR APPROVED MANUFACTURERS ARE ACCEPTABLE. COORDINATE EXACT LOCATION WITH LIGHTING FIXTURES, STRUCTURE AND OTHER OBSTRUCTIONS. IF IN DOUBT ABOUT EXACT LOCATION, COORDINATE WITH ARCHITECT. INSTALL IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS, PARALLEL TO THE LINES OF THE BUILDING, AND TIGHT AGAINST THE FINISHED SURFACE. MARGINS TO FULLY OVERLAP OPENINGS IN SURFACES SO THAT OPENINGS ARE NOT VISIBLE FROM THE FINISHED ROOM. UNITS SHALL BE ADEQUATELY SECURED TO PREVENT T-1 EF T RTU-1 197.5CFM 197.5CFM RTU-1 10"Ø 12"Ø 14"Ø 16"Ø 18"Ø 20"Ø 24"Ø 14"Ø 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM 197.5CFM DRAWING NUMBER CHECKED BY: WLW DRAWN BY: PROJECT: HF1802 REVISION: REVISION: E D R I S T E STATE OF No AR 1 1 1 01 08 G E R R N W A R L N N Y W E C R H T C E I T A A N N D I I A R E D E T S I G E R THIS DOCUMENT, THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF WARNER ARCHITECTURAL ASSOCIATES AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF WARNER ARCHITECTURAL ASSOCIATES, INC DATE: 02/15/2018 DATE: 02/15/2018 14598 CLAY TERRACE BLVD #160, CARMEL, IN 46032 WYNN L. WARNER, RA 1. CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING AND START OF CONSTRUCTION AND SHALL NOTIFY THE ARCHITECT OR ENGINEER OF ANY CONFLICTS OR DISCREPANCIES WITH THE DRAWINGS. ANY REQUIRED MODIFICATIONS NOT IDENTIFIED BEFORE START OF CONSTRUCTION SHALL BE MADE AT NO ADDITIONAL COST TO THE OWNER. 2. CONTRACTOR SHALL COORDINATE EXACT THERMOSTAT LOCATION WITH OWNER PRIOR TO INSTALLATION. 3. NEW RTU'S & ROUND DUCT TO BE INSTALLED TO MATCH NEW LAY-OUT. COORDINATION NOTES (APPLIES TO THIS SHEET ONLY) HVAC LEGEND FIXTURE SYMBOL FIXTURE DESCRIPTION THERMOSTAT (VERIFY LOCATION W/ OWNER) 2X2 HVAC SUPPLY DIFFUSER (MANUAL DAMPER WHERE REQUIRED) HVAC SUPPLY DIFFUSER (MANUAL DAMPER WHERE REQUIRED) RETURN AIR GRILLE EXHAUST FAN (MANUAL DAMPER WHERE REQUIRED) ROOFTOP UNIT (RTU) * PROVIDE DUCT INSULATION IN ALL DUCTWORK & REUSE ALL EXISTING DUCTWORK WHERE APPLICABLE. DISPOSE OF DUCT THAT IS NOT ABLE TO BE REUSED T EF AIR FLOW 4"Ø EXHAUST ALL DUCTWORK SHALL BE MINIMUM 26 GAUGE G-90 GALVANIZED SHEET METAL. CONTRACTOR SHALL REFER TO SMACNA 2" PRESSURE CLASS CONSTRUCTION DETAILS & METHODS FOR ALL LOW PRESSURE ROUND DUCTWORK BACK DRAFT ASSEMBLY FAN ASSEMBLY W/ INTERNAL VIBRATION ISOLATORS UNIT SHALL HAVE INTERNAL PLUG-IN DISCONNECT MOUNTING ANGLES ACT CEILING OFF WHITE METAL GRILLE 1" INSULATED BOX MANUAL VOLUME CEILING DAMPER EXHAUST GRILLE NEW EXHAUST DUCT THRU ROOF A.T.R. PIPE HANGER RING SUPPLY AIR SUPPLY DUCT-ROUND DOUBLE WALLED INSULATED DUCT AIR FLOW SCOOP MAIN SUPPLY DUCT DOUBLE DEFLECTION DIFFUSER DAMPER (WHERE REQUIRED) RMM MECHANICAL PLAN & DETAILS M2 SCALE: M2 1 MECHANICAL PLAN 1/4" = 1'-0" N PLAN NORTH M2 SCALE: 4 ROUND PIPE HANGER NTS M2 SCALE: 5 DIFFUSER DEFLECTION DETAIL M2 SCALE: NTS 3 EXHAUST THRU ROOF DETAIL M2 SCALE: NTS 2 EXHAUST FAN DETAIL NTS ALL DOCUMENTS ARE TO BE BUILT AND BID BASED ON THE MOST STRINGENT CODES. G.C. TO VERIFY THAT ALL CONSTRUCTION IS BUILT TO CODE AND THAT BIDS PROVIDED INCLUDE THE MOST RECENT CODE PER THE MUNICIPALITY. FAILURE TO DO SO WILL RESULT IN THE RELIEF OF LIABILITY OF THE OWNER, ARCHITECT, ENGINEER, AND DESIGNER. DRAWINGS ARE PROVIDED AS REFERENCE AND NOT ALL CONDITIONS ARE DETAILED. IF THERE ARE ANY DISCREPANCIES IN THE PLANS AND THE FIELD CONDITIONS THE CONTRACTOR MUST NOTIFY THE ARCHITECT OR ENGINEER OF RECORD. FAILURE TO DO SO WILL RESULT IN A DENIAL OF CHANGE ORDER REQUEST. THIS DESIGN IS A SUGGESTIVE DESIGN FOR OPTIMUM PERFORMANCE WITH THE EXISTING ROOF TOP UNIT. G.C. TO VERIFY NECESSARY CHANGES TO THE EXISTING DUCTWORK AND IF THERE IS A BETTER CONFIGURATION TO SAVE ON COSTS THEN WE ACCEPT AN ALTERNATE DESIGN FOR THIS TENANT SPACE. 04/12/18 Nick Mishler MOVEMENT WHEN DAMPERS ARE ADJUSTED. DAMPERS SHALL BE MOUNTED SO THAT DAMPER BINDING DOES NOT OCCUR. EXCEPT AS OTHERWISE APPROVED BY THE ARCHITECT OR REQUIRED BY FIELD CONDITIONS, UNITS SHALL BY SYMMETRICAL, EQUIDISTANT FROM WALLS OR OTHER MAJOR BUILDING LINES AND SYMMETRICAL IN CEILING GRIDS. COLOR OF LOUVERS, GRILLES, REGISTERS AND DIFFUSERS SHALL BE SELECTED BY THE ARCHITECT. ANY MATERIALS VISIBLE THROUGH A GRILLE, REGISTER, OR DIFFUSER SHALL BE PAINTED FLAT BLACK. FLEXIBLE DUCTS: SHALL BE EQUAL TO GENFLEX TYPE SFR-25A AND HAVE CONSTRUCTION CONFORMING TO UL-181 CLASS 1 AIR DUCT AND NFPA 90A AND 90B. THE DUCT SHALL HAVE A CONTINUOUS 2 PLY ALUMINUM LAMINATE FULL INTERNAL LINER; ENCAPSULATED, ZINC COATED, HIGH CARBON STEEL HELIX; A THICK BLANKET OF LASS FIBER INSULATION PROVIDING AN OVERALL THERMAL CONDUCTANCE OF 0.23 BTU/HR./SQ. FT./IN./DEGREE F; AND A DURABLE, SCUFF RESISTANT REINFORCED METALIZED COPOLYMER VAPOR BARRIER JACKET. FLEXIBLE DUCT SHALL BE FASTENED TO THE ROUND FITTINGS AND TAKEOFF FITTINGS WITH METAL SECTION 15010 CODES & STANDARDS ALL MATERIALS, EQUIPMENT, AND INSTALLATION SHALL COMPLY WITH APPLICABLE NFPA, ASME, OSHA, UMC, UBC, UPC AND SBCCI REQUIREMENTS, WITH LOCAL PLUMBING AND GAS CODES, AND OTHER LOCAL ORDINANCES AND CODES. WHERE CONFLICTS OCCUR BETWEEN A CODE AND CONTRACT DRAWINGS OR SPECIFICATIONS, MOST STRINGENT REQUIREMENTS SHALL APPLY. LICENSES, FEES & PERMITS PROVIDE ALL PERMITS, PAY ALL FEES, AND ARRANGE FOR INSPECTIONS AS REQUIRED BY LOCAL AND STATE AUTHORITIES. FURNISH ENGINEER, ARCHITECT AND OWNER CERTIFICATE OF FINAL INSPECTION AND APPROVAL FROM LOCAL BUILDING INSPECTORS. PRE-BID COORDINATION REVIEW THE REQUIREMENT OF OTHER SECTIONS OF THESE SPECIFICATIONS TO DETERMINE STRUCTURAL CONDITIONS, FINISH CONDITIONS, AND OTHER CONDITIONS WHICH MAY AFFECT WORK SPECIFIED HEREIN. BIDDERS SHALL VISIT SITE AND BECOME ACQUAINTED WITH ALL JOB CONDITIONS. NO CONSIDERATION WILL BE GIVEN AFTER CONTRACT FOR ALLEGED MISUNDERSTANDING REGARDING UTILITY CONNECTIONS PERMITS, FEES, ETC. POST-BID COORDINATION SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE GENERAL CONDITIONS. SHOP DRAWINGS SHALL BE CLEARLY IDENTIFIED, USING SAME NOMENCLATURE USED ON DESIGN DRAWINGS. SUBMITTALS SHALL BE BOUND IN COMPLETE SETS AND SHALL BE SUBMITTED AT ONE TIME. INCOMPLETE SUBMITTALS SHALL BE HELD WITHOUT REVIEW. CONTROL DIAGRAMS SHALL INCLUDE EQUIPMENT INTERNAL WIRING. ANCHOR BOLTS, SLEEVES, INSERTS, AND SUPPORTS REQUIRED FOR ITEMS SPECIFIED HEREIN AND NOT SPECIFICALLY INDICATED TO BE PROVIDED BY OTHER SHALL BE FURNISHED HEREIN, AND INSTALLED UNDER THE SECTION SPECIFYING THE MATERIAL IN WHICH THEY ARE LOCATED. PROVIDE EXACT LOCATIONS UNDER THIS SECTION.OFFSETS, TRANSITIONS, AND CHANGES IN DIRECTION IN PIPES AND DUCTS SHALL BE MADE AS REQUIRED TO MAINTAIN PROPER HEADROOM, CLEARANCES, AND SLOPE. PROVIDE TRAPS, VENTS, AND FITTINGS AS REQUIRED. INSTALLATION AND ARRANGEMENT OF WORK SHALL PERMIT REMOVAL OF PARTS REQUIRING PERIODIC REPLACEMENT OR MAINTENANCE AND ACCESS FOR INSPECTION AND SERVICING. ACCESS PANELS OR DOORS IN WALLS, FLOORS, CEILINGS, OR OTHER CONSTRUCTION SHALL BE FURNISHED HEREIN AND INSTALLED UNDER THE SECTION SPECIFYING THE MATERIAL IN WHICH THE PANELS ARE TO BE INSTALLED. WARRANTY GUARANTEE IN WRITING TO MAKE GOOD WITHOUT COST ANY DEFECTS IN MATERIALS AND WORKMANSHIP WITHIN ONE YEAR FROM THE DATE OF ACCEPTANCE OF PROJECT. PROVIDE FREE MAINTENANCE AND SERVICE DURING THE GUARANTEE PERIOD. SEE OTHER SECTIONS FOR SPECIAL GUARANTEE OF REFRIGERATION COMPRESSORS, WATER HEATERS, HEAT EXCHANGERS, ETC. THE CONTRACTOR SHALL, WITHOUT FURTHER INSTRUCTIONS, MAKE ONE "GOOD-WILL" SERVICE TRIP TO THE JOB 30 TO 45 DAYS AFTER COMPLETION FOR THE EXPRESS PURPOSE TO CHECK OPERATION OF ALL PLUMBING ITEMS AND REPLACE ALL LEAKING BIBB WASHERS AND CHECK ALL TRAPS FOR LEAKAGE. WORKMANSHIP: FIRST CLASS AND IN ACCORDANCE WITH BEST PRACTICE. PIPE SHALL BE CUT CLEAN, PROPERLY REAMED, THREADED OR SOLDERED, ERECTED PLUMB AND SECURE. MAKE CHANGES IN PIPE SIZE WITH REDUCING FITTINGS WITHOUT THE USE OF BUSHINGS. WORK SHALL BE EXECUTED BY EXPERIENCE MECHANICS AND SHALL PRESENT A NEAT APPEARANCE. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. AT ALL STAGES OF INSTALLATION, PROTECT PIPE OPENINGS, FIXTURES, DUCT WORK, AND EQUIPMENT AGAINST THE ENTRANCE OF FOREIGN MATERIALS, AND FROM DAMAGE BY THE ELEMENTS, MORTAR, PAINT, ETC. MAINTAIN A CLEAN WORK AREA AND REMOVE TRASH, DEBRIS, ETC. AS CONNECTED TO MECHANICAL WORK. FACTORY FINISHES: MANUFACTURER'S STANDARD UNLESS OTHERWISE STATED. SUBMIT COLOR CARDS FOR SELECTION WHERE CHOICE EXISTS. SECTION 15891 SHEET METAL DUCTWORK SIZES: TAKE MEASUREMENTS AT JOB AND FIT WORK INTO AVAILABLE SPACE; REPORT ANY UNWORKABLE CONDITIONS ENCOUNTERED. UNLESS OTHERWISE APPROVED, CONFORM TO DIMENSIONS INDICATED. DUCT DIMENSIONS SHOWN INDICATE NET FREE AREA AFTER INSTALLATION OF INDUCT LINER; INCREASE SIZES INDICATED TO ACCOUNT FOR THIS. GENERAL FABRICATION: CONSTRUCT AND ERECT IN A WORKMANLIKE MANNER, MEETING REQUIREMENTS OF THE LATEST SMACNA 'LOW VELOCITY AND DUCT CONSTRUCTION STANDARDS: AND NFPA CODE 90A. ASSEMBLE AND ANCHOR SO AS TO BE COMPLETELY FREE FROM VIBRATION AND DRUMMING UNDER ALL CONDITIONS OF OPERATION. EXPOSED DUCTWORK: INSTALL TIGHT AGAINST THE WALL AND/OR CEILING WITH DRIVE SLIP JOINTS. TURNS AND TRANSITIONS: FABRICATE TURNS WITH AN INSIDE RADIUS EQUAL TO WIDTH OF DUCT. AT 90 DEGREE TURNS CONTRACTOR MAY SUBSTITUTE SQUARE ELBOWS, WITH STANDARD FACTORY-MADE, MULTIPLE, DOUBLE-BLADE CONSTRUCTED VANES. AVOID ABRUPT CHANGES IN SHAPE, WITH A SLOPE OF 5:1 THE MINIMUM ALLOWED. UNAVOIDABLE OBSTRUCTIONS: WHERE STRUCTURAL ELEMENTS OR PIPES MUST PASS THROUGH A DUCT, PROVIDE TWO- PIECE STREAMLINERS, AND ENLARGE DUCT TO COMPENSATE FOR NET LOSS OF AREA. ROUND PIPES AND RODS SMALLER THAN 3 INCHES NEED NOT HAVE SPECIAL TREATMENT. NOTE: THIS PROVISION WILL NOT BE USED TO JUSTIFY OBSTRUCTIONS WHICH CAN BE AVOIDED. DUCT INSTRUMENT TEST HOLES: PROVIDE FOR EACH SYSTEM FOUR TEST HOLES (TWO IN SUPPLY DUCT AND TWO IN RETURN AIR PLENUM) AT OPPOSITE ENDS NEAR AIR HANDLING UNITS WITH SCREWED CAPS. SECTION 15250 DUCT INSULATION GENERAL: INTERNALLY INSULATE SUPPLY AIR, OUTSIDE AIR INTAKE AND RETURN AIR DUCTS AND PLENUMS, WITH 1.5 IB. DENSITY FLEXIBLE DUCT LINER, LINER SHALL BE IMPREGNATED GLASS FIBER, WATER REPELLENT, VERMIN PROOF, FIREPROOF AND MOLD RESISTANT, WITH SURFACE IN AIR STREAM VINYL OR NEOPRENE COATED. THERMAL CONDUCTIVITY SHALL BE .26 BTU PER HOUR, PER INCH THICKNESS, PER SQUARE FOOT, PER DEGREE F. TEMPERATURE DIFFERENCE AT 75 DEGREES F. MEAN TEMPERATURE. THICKNESS: 2.0 INCHES ON ALL SUPPLY AIR DUCTS ABOVE CEILINGS DIRECTLY BELOW ROOFS AND IN EQUIPMENT ROOMS. 2.0 INCHES ON ALL SUPPLY AIR DUCTS BELOW CONDITIONED FLOOR CEILINGS, IN CEILING RETURN AIR PLENUMS, ALL OUTSIDE AIR DUCTS AND ALL RETURN AIR DUCTS. APPLICATION: CEMENT INSULATION TO THE ENTIRE SURFACE OF THE SHEET METAL WITH BENJAMIN FOSTER NO. 81-99 ADHESIVE BEFORE THE METAL IS BROKEN, IN ADDITION, SECURE ALL SHEETS WIDER THAN 24 INCHES WITH SHEET METAL SCREWS AND WASHERS OR STUD PINS AND CLIPS 16 INCHES OCEW. JOINTS SHALL BE STRAIGHT AND SMOOTH AND SHALL BE BUTTERED WITH ADHESIVE TO PREVENT EROSION AND IMPROVE AIR FLOW. EXTERNAL DUCT INSULATION: INSULATE SHORT BRANCH DUCT COLLAR CONNECTIONS TO GRILLES AND HIGH PRESSURE SPIRAL DUCT EXTERNALLY WITH TWO-INCH THICK GLASS FIBER DUCT INSULATION, OWENS-COMING FRK-25, SERIES ED-150 WITH REINFORCED ALUMINUM FOIL AND PAPER VAPOR BARRIER IN LIEU OF INTERIOR DUCT LINER. ALL JOINTS SHALL BE STAPLED, SEALED AND TAPED AIR-TIGHT. APPROVALS: AH INSULATION MATERIALS AND MASTICS SHALL MEET REQUIREMENT OF NFPA PAMPHLET 90 AND SHALL BE UL LISTED. SECTION 15910 CONTROLS AND SUPPORTS THERMOSTATS, SUBBASES, AND OTHER NEEDED OPERATIONAL CONTROLS SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR ON ALL HVAC EQUIPMENT. EACH THERMOSTAT SHALL HAVE AN APPROVED LOCKING THERMOSTAT COVER. A SAMPLE COVER SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL PRIOR TO ORDERING OR INSTALLING SAME. FLEXIBLE CONNECTIONS: CONNECT ALL DUCTS TO FANS (EXCEPTING DOME TYPE FANS) WITH PREASSEMBLED FLEXIBLE CONNECTION OF FIRE-RESISTANT, NEOPRENE COATED GLASS FIBER CLOTH (3" FABRIC WIDTH), AS MANUFACTURED BY VENTFABRICS, WIREMOLD OR THERMOFLEX, INSTALL SO THAT CLOTH IS IN FOLDS (NOT DRAWN TIGHT). HANGERS AND SUPPORTS: SUPPORT SMALL HORIZONTAL DUCTS WITH 144" X 20 GA. BAND HANGERS (1- 112' X 16 GA, AT DUCTS LARGER THAN 70 UNITED INCHES). PROVIDE IN PAIRS CLOSE TO EACH TRANSVERSE JOIN! AND IN NO CASE MORE THAN SIX FEET APART. BANDS SHALL PASS COMPLETELY UNDER ROUND DUCTS. AT RECTANGULAR DUCTS BANDS SHALL BE TURNED UNDER THE LOWER COMER AND FASTENED WITH SELF-TAPPING SCREWS INTO THE BOTTOM SURFACE AND AT 6" INTERVALS UP THE SIDES, LOOP TOP ENDS OF HANGERS OVER STEEL STRUCTURAL MEMBERS ABOVE AND FASTEN WITH GALVANIZED BOLTS; WHERE CONCRETE JOISTS OCCUR OVERHEAD SECURE STRAPS TO SIDE OF JOIST WITH GALVANIZED EXPANSION OR RAMSET BOLTS; WHERE FLAT CONCRETE SURFACE OCCURS OVERHEAD SECURE WITH RAMSET OR EXPANSION BOLT FASTENERS. SUPPORT SMALL VERTICAL RUNS WITH 118" STEEL BANDS SCREWED TO 3 SIDES OF DUCT AND EXPANSION BOLTED TO ADJACENT STRUCTURAL ELEMENTS; SPACING SHALL NOT EXCEED 12 FEET. SUPPORT VERTICAL RUNS LARGER THAN 50 UNITED INCHES WITH STRUCTURAL BRACKETS WITH WELDED JOINTS. END OF SECTION 15910 DRAWING NUMBER CHECKED BY: WLW DRAWN BY: PROJECT: HF1802 REVISION: REVISION: E D R IS T E STATE OF No AR 1 1 1 01 08 G E R R N W A R L N N Y W E C R H T C E I T A A N N D I I A R E D E T S I G E R THIS DOCUMENT, THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF WARNER ARCHITECTURAL ASSOCIATES AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF WARNER ARCHITECTURAL ASSOCIATES, INC DATE: 02/15/2018 DATE: 02/15/2018 14598 CLAY TERRACE BLVD #160, CARMEL, IN 46032 WYNN L. WARNER, RA EXHAUST FAN SCHEDULE NAME MAKE/ MODEL DUTY VOLUME (CFM) SONES MOTOR SIZE WEIGHT (LB) DUCT AMPS VOLTAGE ACCESSORIES EF-1 EXISTING OR GREEN HECK SP--7 OR EQUIVALENT TOILET 75 0.25 3/4 HP 8 0'-4" 1 120 1, 2, 3, 6 ACCESSORIES: 1. GRAVITY BACK-DRAFT DAMPER 2. WIRE INTO DEDICATED WALL SWITCH. COORDINATE WITH ELECTRICAL 3. REMOTE MOUNTED SPEED CONTROL SWITCH 4. UNIT MOUNTED SPEED CONTROL SWITCH 5. ROOF MOUNTED 6. CEILING MOUNTED ALL DOCUMENTS ARE TO BE BUILT AND BID BASED ON THE MOST STRINGENT CODES. GC TO VERIFY THAT ALL CONSTRUCTION IS BUILT TO CODE AND THAT BIDS PROVIDED INCLUDE THE MOST RECENT CODE PER THE MUNICIPALITY. FAILURE TO DO SO WILL RESULT IN THE RELIEF OF LIABILITY OF THE OWNER, ARCHITECT, ENGINEER, AND DESIGNER. DRAWINGS ARE PROVIDED AS REFERENCE AND NOT ALL CONDITIONS ARE DETAILED. IF THERE ARE ANY DISCREPANCIES IN THE PLANS AND THE FIELD CONDITIONS THE CONTRACTOR MUST NOTIFY THE ARCHITECT OR ENGINEER OF RECORD. FAILURE TO DO SO WILL RESULT IN A DENIAL OF CHANGE ORDER REQUEST. AIR BALANCE UNIT NAME SUPPLY RETURN EXHAUST OUSIDE AIR BALANCE RTU-1 4000 3770 0.0 155.0 75.0 EF-1 0 0 75.0 0.0 -75.0 TOTAL 4000 3770 75.0 155.0 0.0 RTU SCHEDULE UNIT NAME MAKE/ MODEL HEATING (BTU/H) COOLING (BTU/H) VOLTAGE AMPS SEER IEER LOCATION CFM CAP. (HIGH/LOW) 8.5 TON RTU-1 (RTU-1) EXISITNG UNIT - - - - - - ROOF 4,000 RMM MECHANICAL NOTES & SCHEDULES M1 04/12/18 Nick Mishler