HomeMy WebLinkAboutE-001 - ELECTRICAL SYMBOLS & ABBREVIATIONSF HF HR SD PLAN NORT H TV TV DL DL PS J MCC COMBINATION AUDIO/VISUAL ALARM AUDIBLE ALARM ONLY TELEVISION OUTLET: WALL MOUNTED DOUBLE GANG BOX WITH SINGLE GANG RING (VERTICAL) MOUNTED AT 84" A.F.F. U.O.N. PROVIDE ONE (1) 3/4" EMPTY CONDUIT STUB INTO ACCESSIBLE CEILING, WITH J-HOOK SUPPORT PATHWAY TO TELECOM CLOSET. CARD READER WITH PIN PAD WALL MOUNT AT +48" A.F.F. ELECTRIC DOOR STRIKE (FURNISHED BY G.C., INSTALLED BY E.C.) OH ND NS N2 N1 CB DZ MAS PC NB NC NCEQ NCEQ F# F# A 1a LUMINAIRES ABBREVIATIONS POWER EQUIPMENT LINE TYPE LEGEND WIRING PLANS DRAWING REFERENCES WIRING DEVICES, RECEPTACLES - MISC. SWITCHES AND LIGHTING CONTROL DEVICES FIRE ALARM SYSTEMS SECURITY ALARM SYSTEMS ELECTRICAL GENERAL NOTES NURSE CALL SYSTEMS GENERAL DEMOLITION NOTES DISTRIBUTED TELEVISION TELECOMMUNICATIONS JUNCTION AND PULL BOXES ACCESS CONTROL SYSTEMS PULL BOX HEAT DETECTOR : FIXED TEMPERATURE SPRINKLER SYSTEM WATER FLOW SWITCH SPRINKLER SYSTEM TAMPER (SUPERVISORY) SWITCH SPRINKLER SYSTEM ELECTRICAL SOLENOID VALVE EXTINGUISHING SYSTEM PRESSURE SWITCH SMOKE DETECTOR : PHOTOELECTRIC TYPE. END OF LINE RESISTOR ADDRESSABLE CONTROL RELAY ADDRESSABLE MONITOR MODULE SMOKE DAMPER FIRE ALARM ELECTROMAGNETIC DOOR HOLDER SINGLE STATION SMOKE DETECTOR WITH SOUNDER BASE WALL MOUNTED [HORN/BELL/SPEAKER/CHIME] WITH STROBE WALL MOUNTED STROBE CEILING MOUNTED WITH STROBE HEAT DETECTOR : RATE OF RISE DUCT MOUNTED SMOKE DETECTOR : PHOTOELECTRIC TYPE CEILING MOUNTED [HORN/BELL/SPEAKER/CHIME] WITH STROBE CEILING MOUNTED [HORN/BELL/SPEAKER/CHIME] SHADING INDICATES EMERGENCY POWER WALL MOUNTED [HORN/BELL/SPEAKER/CHIME] FIRE ALARM MANUAL STATION: +48" A.F.F. TO CENTER LINE CONTACT IN KITCHEN EXTINGUISHING SYSTEM PANEL FOR CONNECTION INTO FIRE ALARM SYSTEM NEW WORK BY THIS CONTRACTOR (DARK, SOLID LINE) EXISTING TO REMAIN OR NEW WORK BY OTHERS (LIGHT, SOLID LINE) EXISTING TO BE REMOVED BY THIS CONTRACTOR (DARK, DASHED LINE, DEMOLITION PLANS) NEW WORK BY THIS CONTRACTOR TO BE INSTALLED UNDERGROUND, OR BELOW FLOOR (DARK, LONG DASHED LINE) CONDUIT TURNING UP CONDUIT TURNING DOWN CONDUIT CAPPED FOR FUTURE. CABLE TRAY : TYPE AS NOTED BUSWAY HOMERUN TO PANEL OR DESTINATION NOTED ISOLATED GROUND GROUND NEUTRAL PHASE CONDUCTOR HACHURES INDICATE NUMBER OF CONDUCTORS IN CONDUIT NOTE: LONG HACHURE - NEUTRAL CONDUCTOR NORTH ARROW PLAN DETAIL REFERENCE TITLE # KEYED NOTE DESIGNATION AHU 1 PLAN MARK EQUIPMENT NUMBER EQUIPMENT DESIGNATION REFER TO MEP SCHEDULE FOR CIRCUITING AND DEVICE REQUIREMENTS AND FLOOR PLANS FOR LOCATIONS # E100 ENLARGED PLAN REFERENCE 1 PLAN MARK SHEET NUMBER MOTOR CONTROL CENTER SWITCHBOARD PANELBOARD (SURFACE) ELECTRIC HEATING EQUIPMENT HANDHOLE MANHOLE ELECTRICAL SERVICE METER PANELBOARD (FLUSH) VARIABLE FREQUENCY DRIVE TRANSFORMER MOTOR : SEE EQUIPMENT DATA SCHEDULE FOR HORSEPOWER MAGNETIC STARTER UNFUSED DISCONNECT SWITCH FUSED DISCONNECT SWITCH MAGNETIC STARTER WITH DISCONNECT PIPE WITH ELECTRIC HEAT TRACING UNINTERRUPTIBLE POWER SUPPLY SYSTEM FLOOR BOX : ROUGH IN ONLY WITH BLANK COVER FLOOR BOX : SYMBOL DESIGNATES TYPE OF SERVICE DUPLEX RECEPTACLE OUTLET DUPLEX RECEPTACLE OUTLET : GROUND FAULT TYPE SPECIAL PURPOSE OUTLET AS NOTED SINGLE RECEPTACLE OUTLET DUPLEX RECEPTACLE OUTLET WITH ISOLATED GROUND DOUBLE DUPLEX RECEPTACLE OUTLET M ELECTRICAL CONNECTION: CEILING MOUNTED SHADING INDICATES EMERGENCY POWER COMBINATION DUPLEX RECEPTACLE AND TV OUTLET (SEE TV SYMBOL UNDER "DISTRIBUTED TELEVISION"). TYPICAL MOUNTING HEIGHT: +18" A.F.F. SUBSCRIPT LEGEND: A: ABOVE COUNTER: MOUNT +6" ABOVE BACKSPLASH OR WORK SURFACE. C: CEILING: MOUNT FLUSH WITHIN CEILING TILE OR GYPSUM BOARD. CR: COMPUTER RECEPTACLE: PROVIDE LABEL TO READ: 'COMPUTER'. S: SWITCHED: PROVIDE ONE OUTLET CONTROLLED BY TOGGLE SWITCH. U: UNDER COUNTER: WITHIN CABINETRY OR CASEWORK. A SLASH BETWEEN TWO SUBSCRIPTS INDICATES MULTIPLE PARAMETERS (EXAMPLE: A/3 DENOTES ABOVE COUNTER MOUNTING, CIRCUIT 3). 1. 2. 3. 4. REFER TO LUMINAIRE SCHEDULE FOR LUMINAIRE DESCRIPTIONS. "NL" INDICATES UNSWITCHED LUMINAIRE "SE" DESIGNATION INDICATES LUMINAIRE IS SWITCHED DURING NORMAL OPERATION, BUT UPON LOSS OF POWER, LUMINAIRE REVERTS TO 100% OUTPUT VIA BATTERY BALLAST, REGARDLESS OF THE ON/OFF STATUS OF THE LOCAL LIGHTING CONTROL DEVICE. EXTEND AN UNSWITCHED PORTION OF THE LIGHTING CIRCUIT SERVING AREA, AHEAD OF ALL LIGHTING CONTACTORS, TO THIS DEVICE. SHADING LEGEND (APPLICABLE TO LUMINAIRE SYMBOLS): NO SHADING: NORMAL POWER HALF-SHADING: LIFE SAFETY OR BATTERY BACKUP FULL-SHADING: CRITICAL POWER A: LUMINAIRE TYPE 1: CIRCUIT NUMBER a: CONTROLLING SWITCH SWITCH - TYPE AS INDICATED BY SUBSCRIPT CEILING OCCUPANCY DETECTOR : INFRARED SENSOR TYPE. 1. 2. 3. 4. TYPICAL MOUNTING HEIGHT : 48" A.F.F. TO CENTER U.O.N. WHERE TWO OR MORE SWITCHES ARE SHOWN ADJACENT TO EACH OTHER, PROVIDE A COMMON GANG BOX WITH A SINGLE, SEAMLESS FACEPLATE. SUBSCRIPT LEGEND: 2 : TWO-POLE SWITCH 3 : THREE-WAY SWITCH 4 : FOUR-WAY SWITCH K : KEY SWITCH D : DIMMER - COORDINATE REQUIREMENTS FOR LUMINAIRE COMPATIBILITY P : PILOT LIGHT SWITCH C : MOMENTARY CONTACT SWITCH LV : LOW VOLTAGE CONTROL MASTER STATION L : LOW VOLTAGE LOCAL SINGLE/PUSH BUTTON STATION -A LOWERCASE SUBSCRIPT INDICATES THE SWITCHLEG THE DEVICE CONTROLS. REFER TO SPECIFICATION SECTION 26 09 23 FOR ADDITIONAL INFORMATION. BUZZER MOUNT AS NOTED BELL MOUNT AS NOTED CHIME MOUNT AS NOTED DOOR ALARM JAMB SWITCH MOUNT AS NOTED SECURITY CAMERA SINGLE BED STATION : +48" A.F.F. U.O.N. DOUBLE BED STATION : +48" A.F.F. U.O.N. STAFF STATION : +48" A.F.F. U.O.N. DUTY STATION : +48" A.F.F. U.O.N. EMERGENCY PUSHBUTTON STATION : +48" A.F.F. U.O.N. CODE BLUE STATION : +48" A.F.F. U.O.N. NURSE CALL MASTER STATION : DESK MOUNTED CEILING MOUNTED ZONE LIGHT. EMERGENCY PULL CORD STATION: +48" A.F.F. AT TOILETS, +78" AT SHOWER STATIONS. CORD LENGTH SHALL EXTEND TO +6" A.F.F. CEILING MOUNTED DOME LIGHT: CENTERED AT DOOR OPENING NURSE CALL EQUIPMENT CABINET WITH POWER SUPPLY: SURFACE MOUNTED NURSE CALL EQUIPMENT CABINET WITH POWER SUPPLY: FLUSH MOUNTED WALL MOUNTED DOME LIGHT: MOUNT ABOVE DOOR JAMB, CENTERED BETWEEN TOP OF DOOR FRAME AND CEILING PUSHBUTTON : +48" A.F.F. OR AS NOTED KEYSWITCH : WALL MOUNT AT +48" A.F.F. PASSIVE INFRA-RED DETECTOR BALANCED MAGNETIC SWITCH ELECTRO-MAGNETIC LOCK CARD READER : WALL MOUNT AT +48" A.F.F. POWER SUPPLY REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT MOUNTING HEIGHTS AND LOCATIONS. WHERE ELEVATIONS DO NOT SPECIFY, MOUNT DEVICES AS INDICATED. MANUAL MOTOR STARTER WITH PILOT LIGHT (+48" A.F.F.) JUNCTION BOX : CEILING OR FLOOR MOUNTED. SIZE PER N.E.C. REQUIREMENTS. JUNCTION BOX : WALL MOUNTED. SIZE PER N.E.C. REQUIREMENTS. CEILING PHOTOCELL POWER POLE ELECTRICAL CONNECTION: WALL MOUNTED 1. 2. 3. 4. 5. 6. REFER TO SPECIFICATIONS SECTION 283111 FOR ADDITIONAL INFORMATION PERTAINING TO THE FIRE ALARM SYSTEM. SIGNALING LINE CIRCUITS SHALL BE ROUTED IN A CLASS [A] [B] CONFIGURATION. NOTIFICATION APPLIANCE CIRCUITS SHALL BE ROUTED IN A CLASS [A] [B] CONFIGURATION. FIRE ALARM CIRCUITS SHALL BE ROUTED IN CONDUIT WHERE INACCESSIBLE. WHERE ROUTED ABOVE ACCESSIBLE CEILINGS, FIRE ALARM CIRCUITS SHALL CONSIST OF [PLENUM RATED CABLE SUPPORTED EVERY 4'-0"][WIRING WITHIN CONDUIT] BETWEEN DEVICES. FOR VISUAL DEVICES, THE '#' WITHIN THE SYMBOL CORRESPONDS TO THE CANDELA RATING OF THE DEVICE: 1=15cd, 3=30cd, 5=75cd, 7=177cd. WALL MOUNTED NOTIFICATION DEVICES SHALL BE MOUNTED WITH THE TOP OF THE DEVICE +90" A.F.F. OR 6" BELOW THE CEILING, WHICHEVER IS LOWER. RESPONSIBILITIES: RESPONSIBILITIES: 1. 2. 3. TYPICAL MOUNTING HEIGHT: +18" A.F.F. UNLESS OTHERWISE NOTED. PROVIDE 4 11/16" SQUARE BOX WITH SINGLE GANG PLASTER RING (VERTICAL) ALL TELECOMMUNICATION CONDUIT SHALL BE A MINIMUM OF 1" IN DIAMETER STUBBED TO ACCESSIBLE CORRIDOR CEILING SPACE, UNLESS OTHERWISE NOTED. SUBSCRIPT LEGEND: A: ABOVE COUNTER - MOUNT +6" ABOVE BACKSPLASH OR WORK SURFACE WITH BOX ORIENTED HORIZONTALLY. C: CEILING MOUNTED - MOUNT FLUSH WITHIN CEILING TILE OR GYPSUM CEILING. W: WALL PHONE - MOUNT +48" A.F.F. OR 6" ABOVE WORK SURFACE. PROVIDE MOUNTING LUGS FOR TELEPHONE. WAP: WIRELESS ACCESS POINT DATA OUTLET - FURNISH AND INSTALL A [CAT 6] CABLE WITH RJ-45 JACK AND 10-'0" OF SLACK CABLE COILED ABOVE ACCESSIBLE CEILING FROM [TELECOM ROOM]. WIRELESS ACCESS POINTS ARE [OWNER FURNISHED], [OWNER INSTALLED]. - A SLASH BETWEEN TWO SUBSCRIPTS INDICATES MULTIPLE PARAMETERS (EXAMPLE: A/3 DENOTES ABOVE COUNTER MOUNTING, 3 CABLES.) RESPONSIBILITIES: RESPONSIBILITIES: RESPONSIBILITIES: RACEWAY AND BOXES: CONTRACTOR FURNISHED, INSTALLED WIRING: CONTRACTOR FURNISHED, INSTALLED DEVICES: CONTRACTOR FURNISHED, INSTALLED F F F# DS FW FT SD DH FK FR FM SD FV FP F# J P M UPS VFD HH MH T E D A V BMS PIR ES CR MAG KS CRP PP E MAKE ALL INSTALLATIONS IN ACCORDANCE WITH THE [AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES (ADAAG)] AND/OR [ARCHITECTURAL BARRIERS ACT (ABA)]. MOUNTING HEIGHTS INDICATED WITHIN PLANS AND SCHEDULES ARE DIMENSIONED TO THE CENTER LINE OF THE DEVICE, EQUIPMENT, LUMINAIRE, ETC. UNLESS OTHERWISE NOTED. COORDINATE EXACT EQUIPMENT LOCATIONS WITH OTHER TRADES. EQUIPMENT LOCATIONS SHOWN ON ELECTRICAL PLANS ARE DIAGRAMMATICAL ONLY AND MIGHT NOT BE EXACT. CIRCUIT IDENTIFICATION NUMBERS BESIDE ELECTRICAL DEVICES AND CONNECTION POINTS ON PLANS CORRESPOND TO AN OVERCURRENT DEVICE IN THE DESIGNATED PANELBOARD. NOTE ALL CIRCUIT NUMBER CHANGES MADE IN THE FIELD AT EACH ELECTRICAL DEVICE AND CONNECTION POINT. ALSO CORRECT THE DIRECTORIES AND DEVICE MARKINGS AT PANELBOARDS, SWITCHBOARDS AND SWITCHGEAR TO ACCURATELY REFLECT THE AS-BUILT CONDITIONS. INSTALL EMERGENCY AND EXIT LUMINAIRE WIRING IN A SEPARATE RACEWAY FROM THAT OF ANY NORMAL POWER DEVICE. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILINGS, OR BELOW FLOOR SLABS, ETC. UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT ROUTED IN MECHANICAL ROOMS, ELECTRICAL ROOMS, AND STORAGE ROOMS WITHOUT CEILINGS MAY BE ROUTED EXPOSED. COORDINATE VERTICAL CONDUIT ROUTING TO WALL MOUNTED DEVICES TO ENSURE DEVICES LOCATED WITHIN AN 18-INCH HORIZONTAL DIMENSION WILL BE CENTER- ALIGNED VERTICALLY. CONCEAL ELECTRICAL CONNECTIONS FOR ELECTRIC WATER COOLERS (EWC) BEHIND WATER COOLER ACCESS PLATE OR DIRECTLY BELOW AND CENTERED ON WALL. FIELD COORDINATE ALL ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT MOUNTING LOCATIONS TO AVOID ENCROACHMENT OF OPERATION AND ACCESS TO EQUIPMENT FROM OTHER TRADES. COORDINATE THE APPROPRIATE MOUNTING LOCATION WITH THE AFFECTED DISCIPLINES WHEN EQUIPMENT IS SPECIFIED TO BE MOUNTED ONTO THE SURFACE OF ANOTHER DISCIPLINE'S EQUIPMENT. REPAIR ALL OPENINGS MADE IN EXISTING WALLS, PARTITIONS, ETC TO ACCOMMODATE WORK OF THIS DISCIPLINE TO MATCH THE SURROUNDING CONDITIONS, USING WORKERS QUALIFIED IN THE APPROPRIATE TRADE. APPROPRIATELY GROUT OR SEAL ALL CONDUITS THROUGH WALLS. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS MUST HAVE BEEN TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. INSTALL A PERMANENT DIRECTORY ACCORDING TO THE NATIONAL ELECTRICAL CODE, ARTICLE 230 AT EACH SERVICE ENTRANCE AND POWER SOURCE. PERFORM ALL WELDING ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS. FURNISH CERTIFICATES QUALIFYING EACH WELDER TO THE ARCHITECT OR ENGINEER PRIOR TO START OF WORK. THE ARCHITECT OR ENGINEER RESERVES THE RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT NO ADDITIONAL EXPENSE, OF ANY WELDERS ASSIGNED TO THE JOB. REPLACE OR REINSTALL ALL PORTIONS OF THE BUILDING (CEILING TILES, WALLS, ETC) REMOVED TO ACCOMMODATE THE INSTALLATION OF ANY ELECTRICAL DEVICE, EQUIPMENT, ETC., USING WORKERS QUALIFIED IN THE APPROPRIATE TRADE. COORDINATE LUMINAIRE LOCATIONS SUCH THAT LUMINAIRES RUN PARALLEL TO THE FACE OF THE EQUIPMENT AND OVER AISLES BETWEEN EQUIPMENT IN ALL MECHANICAL AND ELECTRICAL EQUIPMENT AREAS. INSTALL AT PROPER LOCATIONS AND HEIGHTS TO PROPERLY ILLUMINATE ALL GAGES, PANELS, ELECTRICAL EQUIPMENT, CONTROLS, VALVES, ETC. CHAIN HANGING, STEM HANGING, CHANNEL HANGING, ETC. ARE ACCEPTABLE METHODS. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. REMOVE, CAP AND RELOCATE EQUIPMENT, OUTLETS, CONDUIT, WIRE, ETC., AS SHOWN AND SPECIFIED ON DRAWINGS, AND AS MAY BECOME NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. VISIBLY EXAMINE ALL EXISTING WALLS DESIGNATED FOR REMOVAL TO DETERMINE THE CONDUIT AND THE WIRING THAT WILL REQUIRE CAPPING AND REMOVAL, WHETHER OR NOT SUCH CONDITIONS ARE INDICATED ON THE DRAWINGS. FAILURE TO VISIT THE SITE AND TO TAKE ALL EXISTING CONDITIONS INTO ACCOUNT WILL NOT ALLOW FOR CHANGES TO THE SCOPE OF WORK. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING FIXTURES, EQUIPMENT, OUTLETS, ETC., TO REMAIN IN USE WHETHER NOTED ON THE PLANS OR NOT. FIELD VERIFY EXISTING ITEMS TO REMAIN IN USE. RECONNECT RACEWAYS AND WIRING FOR EXISTING CIRCUITS WHICH MUST BE RE-ROUTED OR WHICH ARE PARTIALLY ABANDONED TO POWER THE REMAINING OUTLETS ON THE CIRCUIT. REMOVE ALL UNUSED WIRING AND CABLES BACK TO THEIR SOURCE. REMOVE ALL UNUSED CONDUIT THAT IS EXPOSED OR ABOVE ACCESSIBLE CEILINGS WHICH IS AFFECTED BY OR IS IN THE AREA OF THE DEMOLITION WORK. THE INTENTION OF THE ELECTRICAL DEMOLITION DRAWINGS IS TO DISCONNECT AND REMOVE ALL ELECTRICAL WORK MADE VOID BY THE SCOPE OF THE CONSTRUCTION AND ALTERATION. FIELD VERIFY EXACT MATERIAL QUANTITIES REQUIRED TO BE REMOVED. DISCONNECT AND REMOVE ALL EXISTING ELECTRICAL EQUIPMENT, DEVICES, ASSOCIATED RACEWAYS, SUPPORTING HARDWARE, AND WIRING, WHICH HAVE BEEN MADE OBSOLETE BY THE WORK OR IS SHOWN DASHED ON THE ELECTRICAL DEMOLITION DRAWINGS, UNLESS OTHERWISE NOTED. ALTHOUGH AN ATTEMPT HAS BEEN MADE TO INDICATE ALL OF THIS WORK, TOTAL ACCURACY IS NOT GUARANTEED. VISIBLY EXAMINE ALL AREAS AND WALLS AND CEILINGS SCHEDULED FOR REMOVAL TO DETERMINE EXISTING ELECTRICAL ITEMS TO REMAIN. WHERE ELECTRICAL EQUIPMENT, CONDUIT, BOXES, AND SUPPORTING HARDWARE ARE REMOVED, PATCH AND FINISH THE SURFACE AS REQUIRED TO MATCH THE EXISTING, USING WORKERS QUALIFIED IN THE APPROPRIATE TRADE. WHERE BURIED CONDUITS EXTENDING OUT OF A CONCRETE SLAB BECOME ABANDONED, CUT AND GRIND THE CONDUITS OFF FLUSH WITH TOP OF SLAB AND PLUG WITH NON-SHRINK WATERPROOF GROUT FILL. TAKE ALL REMOVED MATERIALS FROM THE PROJECT SITE, EXCEPT FOR THOSE TO BE RELOCATED, STORED, OR TURNED OVER TO THE OWNER. ACCEPTANCE OF CONTRACT MEANS INSTALLER ACCEPTS EXISTING CONDITIONS. COORDINATE ALL DEMOLITION WORK WITH ALL OTHER TRADES. PROVIDE A BLANK COVER OVER THE OUTLET WHERE A FLUSH DEVICE IS BEING REMOVED FROM FLOORS AND WALLS THAT ARE TO REMAIN. MATCH THE COLOR AND MATERIAL TO THE EXISTING REMAINING COVERS IN THE ROOM OR SPACE. LEGALLY DISPOSE OF HAZARDOUS MATERIALS AND BALLASTS OR OTHER EQUIPMENT CONTAINING PCBS AND LAMPS CONTAINING MERCURY. COMPLY WITH ALL FEDERAL, STATE, AND LOCAL LAWS. MODIFY EXISTING PANEL DIRECTORIES (OR REPLACE) FOR PANELBOARDS WHICH HAVE HAD ALTERATIONS TO THE CIRCUITS ORIGINATING THEREIN. DESCRIBE THE LOAD AND LOCATION. TYPE, DO NOT HAND LETTER NEW PANELBOARD DIRECTORIES. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. A.F.F : ABOVE FINISHED FLOOR C : CONDUIT E.C. : ELECTRICAL CONTRACTOR ER : EXISTING RELOCATED ETR : EXISTING TO REMAIN EWC : ELECTRIC WATER COOLER G.C. : GENERAL CONTRACTOR GND : GROUND TYP. : TYPICAL U.O.N. : UNLESS OTHERWISE NOTED PROVIDE WIRING REQUIRED BY THE CIRCUITING AND SWITCHING REQUIREMENTS FOR THE PARTICULAR CIRCUITS INVOLVED. TYPICAL 120V HOMERUNS SHALL CONSIST OF #12 AWG CONDUCTORS IN 3/4" CONDUIT MINIMUM UNLESS INDICATED OTHERWISE. NO SHARED NEUTRALS SHALL BE ALLOWED. A MAXIMUM OF NINE CURRENT- CARRYING CONDUCTORS ARE ALLOWED IN A RACEWAY. NEUTRAL CONDUCTORS ARE ALSO CONSIDERED CURRENT-CARRYING CONDUCTORS. FOR CIRCUITS EXCEEDING 75'-0" IN LENGTH, PROVIDE THE NEXT LARGER WIRE SIZE FOR THE CIRCUIT AMPACITY. WHERE NUMBER OF CURRENT-CARRYING CONDUCTORS IN A RACEWAY EXCEEDS THREE, THE ALLOWABLE AMPACITY OF EACH CONDUCTOR SHALL BE REDUCED AS SHOWN IN THE ADJUSTMENT FACTOR TABLE IN THE NATIONAL ELECTRIC CODE. LOAD DIVERSITY FACTORS SHALL NOT BE USED IN SIZING CONDUCTORS. NEUTRAL CONDUCTORS SHALL BE COUNTED AS CURRENT-CARRYING CONDUCTORS. 1. 2. RACEWAY AND BOXES: CONTRACTOR FURNISHED, INSTALLED WIRING: CONTRACTOR FURNISHED, INSTALLED DEVICES: CONTRACTOR FURNISHED, INSTALLED 1. 2. 5. LUMAINAIRE DESIGNATION KEY: RACEWAY AND BOXES: CONTRACTOR FURNISHED, INSTALLED WIRING: CONTRACTOR FURNISHED, INSTALLED DEVICES: CONTRACTOR FURNISHED, INSTALLED RACEWAY AND BOXES: CONTRACTOR FURNISHED, INSTALLED WIRING: CONTRACTOR FURNISHED, INSTALLED DEVICES: CONTRACTOR FURNISHED, INSTALLED 1. RACEWAY AND BOXES: CONTRACTOR FURNISHED, INSTALLED WIRING: CONTRACTOR FURNISHED, INSTALLED DEVICES: CONTRACTOR FURNISHED, INSTALLED DATA OUTLET WITH 4 POSITION FACEPLATE & TOTAL OF [(2)] ACTIVE JACKS AND [(2)] [CAT 6e CABLES]. TELEPHONE OUTLET WITH SINGLE POSITION FACEPLATE & TOTAL OF [(1)] ACTIVE JACK AND [(1)] [CAT 6e] CABLE. COMBINATION VOICE/DATA OUTLET WITH 4 POSITION FACEPLATE & TOTAL OF [(2)] ACTIVE DATA JACKS, [(1)] ACTIVE VOICE JACK AND [(3)] [CAT 6e CABLES]. DUPLEX RECEPTACLE OUTLET : INTELLIGENTLY CONTROLLED SO WALL MOUNTED SINGLE SWITCH OCCUPANCY SENSOR Drawing Name: Plot Time/Date: DRAWING CONTENTS: ISSUE DATE: DRAWING NO. PROJECT NO. ST. VINCENT MICHIGAN ROAD HOPD IMAGING POS22 COMPLIANCE 10801 N MICHIGAN RD, ZIONSVILLE, IN 46077 MKM: ASCENSION: Certification: Key Plan: Consultant Logo: 119 West Wayne Street Fort Wayne, Indiana 46802 p 260.422.0783 f 260.426.4561 www.MKMdesign.com 30329 2/1 3/201 8 8:54:1 9 AM 02/01/2018 17088 E-001 Template.rte ELECTRICAL SYMBOLS & ABBREVIATIONS REVISION No. Date Revision 1905-23 2/12/2018 04/12/18 Nick Mishler 04/12/18 Nick Mishler