HomeMy WebLinkAboutE-102 - ELECTRICAL FIRST FLOOR PLANTV
DRESSING
DRESSING
STOR.
LINEN
PATIENT
BIO RESTROOM
SOIL
IM-4
EXAM RO
CHECK-IN
PATIENT
RESTROOM
IM-3
STAIR EXAM RO
MECH
TABLE PARK
1
A
T
LF/30/42
T
BBF
T
BBF
T
F F3
J
SO
OH
OH
OH
OH
OH
OH
F3
F
PC
SO
F3
CR
J
A
2
2
2
2
1
WP
USB
USB
USB USB
EX
EX
EX EX
EX
EX
L22
L24
L24 L24
L22
L22
L6
L6
L6
L6 L6
L6 L6
3
X1
X1
X2
EX
EX
4
6
5
A
A
WAITING
102
VESTIBULE
101
REG.
103A
PUBLIC TLT
104
OFFICE
105
X-RAY
108
CHANGE
126
CHANGE
125
MRI COMPUTER
127
WORK AREA
103B
SUB WAITING
106
RECEPTION
109
CIRC.
110
CIRC.
111
CIRC
107
OFFICE
112
CIRC
113
CIRC
116
CIRC
115
L22 L22
LW6
LW6 LW6
LW6
7
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
L6
L6
4
8
80"
ETR
6
9
ETR
ETR
10
A. LIGHT FIXTURES TO BE ORDERED THROUGH
GRAINGER.
B. RECEPTACLES TO BE ORDERED THROUGH GRAINGER,
HUBBELL TYPE 8300TR.
C. TIE NEW FIRE ALARM DEVICES TO EXISTING FIRE
ALARM PANEL. PROGRAM AS REQUIRED.
GENERAL SHEET NOTES:
Drawing Name:
Plot Time/Date:
DRAWING CONTENTS:
ISSUE DATE:
DRAWING NO.
PROJECT NO.
ST. VINCENT
MICHIGAN ROAD
HOPD
IMAGING POS22
COMPLIANCE
10801 N MICHIGAN RD,
ZIONSVILLE, IN 46077
MKM:
ASCENSION:
Certification:
Key Plan:
Consultant Logo:
119 West Wayne Street
Fort Wayne, Indiana 46802
p 260.422.0783
f 260.426.4561
www.MKMdesign.com
30329
2/1 3/201 8 8:54:22 AM
02/01/2018 17088
E-102
Template.rte
ELECTRICAL FIRST
FLOOR PLAN
NORTH
1/4" = 1'-0"
ELECTRICAL FIRST FLOOR PLAN
1. WHIP CONNECTION FOR SYSTEMS FURNITURE.
PROVIDE NEW 20A/120V CONNECTION FROM PANEL
SERVING EXISTING AREA.
2. REUSE EXISTING LIGHTING CIRCUIT IN EACH SPACE.
3. X-RAY IS FED WITH (4) #1, #6G., 1-1/2" C. FROM 480V
PANEL IN MRI EQUIPMENT ROOM. PROVIDE 100A
CIRCUIT BREAKER IN MRI EQUIPMENT ROOM PANEL
AND IN X-RAY ROOM PANEL.
4. PROVIDE DEDICATED 20A, 120V CIRCUIT FROM PANEL
FEEDING EXISTING AREA. CIRCUIT WITH 2#12, #12 G. IN
1/2" C.
5. REUSE EXISTING CIRCUIT IN ROOM FOR NEW DUPLEX
USB RECEPTACLES.
6. CIRCUIT RECEPTACLES TOGETHER TO 20A, 120V
CIRCUIT FROM PANEL FEEDING EXISTING AREA.
CIRCUIT WITH 2#12, #12 G. IN 1/2" C.
7. CIRCUIT LIGHTS IN CANOPY TO INTERIOR VESTIBULE
LIGHTING CIRCUIT THROUGH CONTACTOR TIED TO
PHOTOCELL. SET PHOTOCELL TO 5 FC.
8. RELOCATE FIRE ALARM DEVICE TO NEW LOCATION.
UPDATE AND PROGRAM AS REQUIRED.
9. NEW CABINET UNIT HEATER . CIRCUIT TO PANEL IN MRI
COMPUTER ROOM. CIRCUIT WITH 3#10, #10G IN 3/4" C.
PROVIDE 25 A, 208 V, 3-PHASE CIRCUIT BREAKER.
10. RELOCATE EXISTING PANIC BUTTON FROM
REGISTRATION TO NEW REGISTRATION. CONNECT AND
PROGRAM AS REQUIRED.
# SHEET KEYNOTES
15. PROVIDE AND INSTALL ALL LAMP TYPES INDICATED IN LUMINAIRE SCHEDULE. LEDS SHALL HAVE A MINIMUM COLOR RENDERING INDEX (CRI) OF 85 AND SHALL HAVE COLOR TEMPERATURE OF 3500K, U.O.N.
14. VERIFY COMPATIBILITY OF ALL DIMMING BALLASTS WITH SPECIFIED DIMMING CONTROLS PRIOR TO ORDERING AND PROVIDE APPROPRIATE COMPONENTS TO CREATE A COMPLETE AND FULLY FUNCTIONAL INSTALLATION.
13. WHEN VARYING FROM BASIS-OF-DESIGN LUMINAIRE, PROVIDE A LUMINAIRE UTILIZING ±10% OF THE LED LUMENS INDICATED IN LUMINAIRE SCHEDULE.
12. COMPLETE CATALOG NUMBER MAY NOT BE LISTED. ORDER LUMINAIRE BASED ON DESCRIPTION, PARTIAL CATALOG NUMBER AND SPECIFICATIONS. THE FIRST MANUFACTURER LISTED IS THE BASIS-OF-DESIGN.
11. REFER TO SPECIFICATION SECTION 265100 LIGHTING FOR ADDITIONAL INFORMATION CONCERNING LUMINAIRES, FINISHES, BALLASTS, LAMPS, ETC.
10. WHEN LUMINAIRES ARE INSTALLED IN CONTINUOUS ROWS TWO (2) OR MORE, LUMINAIRES SHALL BE APPROVED FOR USE AS WIREWAY.
9. ALL LUMINAIRES SHALL OPERATE AT 120 OR 277 VOLTS OR OTHER VOLTAGE AS REQUIRED BY THE CIRCUITS AND/OR PANELS TO WHICH THEY ARE CONNECTED.
8. FOR LUMINAIRES TYPES WITH PARABOLIC LOUVERS: FOR LUMINAIRES WITH BALLAST COMPARTMENTS PROTRUDING INTO LUMINAIRE, MOUNT COMPARTMENT OVER LOUVERS.
7. IN ALL MECHANICAL ELECTRICAL EQUIPMENT AREAS, CONTRACTOR TO COORDINATE LUMINAIRE LOCATIONS SUCH THAT LIGHT LUMINAIRES RUN PARALLEL TO THE FACE OF THE EQUIPMENT AND OVER AISLES BETWEEN
EQUIPMENT. INSTALL AT EXACT
LOCATIONS AND AT EXACT HEIGHT TO ILLUMINATE ALL GAGES, PANELS, CONTROLS, VALVES, ETC. CHAIN HANGING, STEM HANGING, UNISTRUT HANGING, ETC. ARE ACCEPTABLE METHODS.
6. ALL LUMINAIRES SHALL HAVE A U.L. LABEL.
5. ALL RECESSED DOWNLIGHTS SHALL HAVE SELF-FLANGED REFLECTORS U.O.N. AND SHALL BE INSTALLED SO THAT THE BOTTOM OF THE THROAT IS EVEN WITH THE FINISHED CEILING PLANE. THE OVERLAPPING
FLANGE MUST THEN FIT FLUSH TO THE CEILING
PLANE/THROAT. NO LIGHT LEAK MUST BE VISIBLE. ALL MISCELLANEOUS HARDWARE ABOVE THE CEILING PLANE TO ACCOMPLISH THE ABOVE SHALL BE INCLUDED IN THE BASE BID.
4. WHEN INSTALLING LUMINAIRES, THE CONTRACTOR SHALL USE THE LUMINAIRE MANUFACTURER'S MOUNTING HARDWARE AND FOLLOW ALL MANUFACTURER'S INSTALLATION DIRECTIONS.
3. REFER TO ARCHITECTURAL DOCUMENTS FOR EXACT MOUNTING LOCATIONS OF LUMINAIRES AND CEILING TYPES.
2. CONTRACTOR IS RESPONSIBLE FOR ALL MISCELLANEOUS HARDWARE, CLIPS, ANGLES, FRAMES, ETC. AS REQUIRED TO MOUNT THE LUMINAIRES IN OR ON THE SURFACES THEY ARE TO BE INSTALLED.
1. ALL LUMINAIRES SHOWN ON THIS SCHEDULE MAY NOT BE USED ON THE VARIOUS PLANS. ALSO, THE USE OF ONLY CERTAIN NUMERICAL SUBSCRIPTS FOR LUMINAIRE TYPES (e.g. H2, H3, A2, A3, etc.) ON THIS
PROJECT DOES NOT NECESSARILY MEAN THAT ON . . .
LUMINAIRE SCHEDULE GENERAL NOTES:
LUMINAIRE SCHEDULE
PLAN MARK DESCRIPTION MANUFACTURER # OF LAMPS LAMP TYPE LED LUMENS WATTAGE
L6 6" OPEN LED DOWNLIGHT, SELF-FLANGED REFLECTOR, ACRYLIC LENS, CLEAR TRIM, MEDIUM WIDE DISTRIBUTION, SEMI-SPECULAR FINISH, 0-10V DIMMING, 3500K, BATTERY
PACK AS REQUIRED.
GOTHAM EVO 1 LED 1500 24 W
L22 2'x2' SMOOTH ACRYLIC LENS, 85+ CRI, 0-10V DIMMING, PROVIDE BATTERY PACKS AS SHOWN ON DRAWINGS LITHONIA 2TL 1 LED 2500 45 W
L24 2'X4' VOLUMETRIC RECESSED STATIC LENSED TROFFER, CURVED LINEAR PRISM DIFFUSER, 82 CRI, 3500K, 0-10V DIMMING LITHONIA 2BLT 1 LED 4800 49 W
LW6 6" LED DOWNLIGHT, SELF-FLANGED REFLECTOR, FROSTED LENS, ELECTRONIC DRIVER, WET LOCATION LISTED GOTHAM EVO 1 LED 1000 10 W
X1 EDGE LIT EXIT SIGN. PROVIDE WITH BATTERY BACKUP. LITHONIA LRP SERIES 1 LED -- 5 W
X2 DOUBLE SIDED X1 LITHONIA LRP SERIES 1 LED -- 5 W
REVISION
No. Date Revision
1905-23 2/12/2018
04/12/18
Nick Mishler
04/12/18
Nick Mishler