HomeMy WebLinkAboutFS-102CURBS AND PROVIDE CHASE WORK REQUIRED BY NFPA 96
- TO SET, FLASH, & CUT OPENINGS FOR EXHAUST & SUPPLY
AS NEEDED
- TOTAL CFM OF EXHAUSTED AIR TO BE 5450
TOTAL SUPPLY AIR TO BE 4450 CFM PROVIDED THRU TEMPERED MAKE-UP
AIR PLENUM ON HOODS #7 & #23
CONTRACTOR
BUILDING NEGATIVE OF 1000 CFM TO BE MADE UP BY MECHANICAL
E.C.- TO PROVIDE SWITCH AND MOTOR STARTER WITH AUTOMATIC THERMAL
FAN UPON FIRE SYSTEM DISCHARGE AS DIRECTED AS BY K.E.C.
TO TERMINATE POWER TO SUPPLY FAN AND MAINTAIN POWER TO EXHAUST
AND INTERCONNECT MOTOR STARTERS WITH FIRE SUPPRESSION SYSTEM
PROTECTION DEVICE. E.C. TO INTER-WIRE FANS TO OPERATE TOGETHER
- TO PROVIDE 360,450 BTU FOR DIRECT GAS FIRED HEATED MAKE
UP AIR UNIT. (VERIFY LOCATION)
- TO PROVIDE 208-V, 3-PH, 7-1/2 H.P., 22.3 AMPS TO (1) EXHAUST
FAN AND 208-V, 3-PH, 5-H.P., 15.0 AMPS TO (1) SUPPLY FAN
HOOD #7 & #23:
SHARED WITH HOOD #23
04/05/18
Nick Mishler