HomeMy WebLinkAboutE000-Electrical Notes Symbols & SchedulesLIGHTING SYMBOL SCHEDULE
SYMBOL DESCRIPTION
SWITCH, a = SWITCH LEG, 48" AFF (TYP)
3-WAY SWITCH
SLIDE DIMMER SWITCH
OCCUPANCY SENSOR SWITCH, WALL MOUNTED
OCCUPANCY SENSOR SWITCH, CEILING MOUNTED
PHOTOCELL
TIME CLOCK
2' x 4' LED LIGHT FIXTURE - XX DENOTES TYPE, a
SIGNIFIES SWITCH LEG, # DENOTES CIRCUIT
EMERGENCY BATTERY PACK
EXIT SIGN, WALL MOUNTED
EXIT SIGN, CEILING MOUNTED
EGRESS LIGHTING REMOTE HEAD
EXTERIOR WALL PACK
PENDANT LIGHT FIXTURE
a
ELECTRICAL SHEET INDEX
E000 ELECTRICAL NOTES, SYMBOLS, AND SCHEDULES
E001 SITE ELECTRICAL PLAN
E101 1ST FLOOR LIGHTING PLAN
E201 1ST FLOOR POWER & SYSTEMS PLAN
E102 2ND FLOOR LIGHTING PLAN
E202 2ND FLOOR POWER & SYSTEMS PLAN
E203 ROOF POWER PLAN
E501 ONE-LINE DIAGRAM
E502 PANEL SCHEDULES
FIRE ALARM SYMBOL SCHEDULE
SYMBOL DESCRIPTION
MANUAL PULL STATION, 48" AFF (TYP)
SMOKE DETECTOR
SMOKE DETECTOR-DUCT MTD
HEAT DETECTOR
TAMPER SWITCH
FLOW SWITCH
HORN/STROBE NOTIFICATION DEVICE, 80" AFF (TYP)
HORN/STROBE NOTIFICATION DEVICE
WEATHERPROOF
STROBE ONLY NOTIFICATION DEVICE
SPEAKER NOTIFICATION DEVICE
FIRE ALARM CONTROL PANEL
FIRE ALARM REMOTE ANNUNCIATOR
WP
S
NL
GENERAL NOTES
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED LABOR,
MATERIAL, EQUIPMENT AND SERVICES NECESSARY TO COMPLETE THE
INSTALLATION OF ALL SYSTEMS INDICATED. THE FINISHED JOB SHALL BE
FUNCTIONAL AND COMPLETE IN EVERY DETAIL INCLUDING ANY AND ALL
ITEMS REQUIRED FOR A FULLY FUNCTIONING SYSTEM.
2. ALL MATERIALS AND WORKMANSHIP SHALL MEET ALL APPLICABLE STATE AND
LOCAL CODES, ORDINANCES, UTILITY COMPANY REGULATIONS AND NATIONALLY
RECOGNIZED CODES AND STANDARDS.
3. DO NOT LOCATE BOXES BACK TO BACK IN WALL PARTITIONS. STAGGER AS
REQUIRED TO MINIMIZE SOUND TRANSMISSION.
4. COORDINATE THE SERVICE INSTALLATION WITH THE UTILITY COMPANY. INSTALL
METER CABINET PROVIDED BY THE UTILITY COMPANY IN ACCORDANCE WITH THE
UTILITY COMPANY'S STANDARDS.
5. PROVIDE ALL GROUNDING AS REQUIRED TO MEET THE UTILITY AND NEC SECTION
250 REQUIREMENTS.
6. ALL ELECTRICAL EQUIPMENT SHALL BE UL LISTED AND LABELED.
7. ALL EQUIPMENT AND DEVICES SHALL BE INSTALLED IN A PROFESSIONAL AND
WORKMANSHIP MANNER AND IN COMPLIANCE WITH NATIONAL ELECTRICAL
CONTRACTORS ASSOCIATION (NECA) RECOMMENDED STANDARDS.
8. MATERIALS SHALL BE RECEIVED AND STORED IN A MANNER TO BEST PROTECT THE
MATERIALS PRIOR TO INSTALLATION. PROTECTIVE COVERS SHALL REMAIN IN
PLACE AS MUCH AS POSSIBLE.
9. HANGERS AND SUPPORTS SHALL BE USED AS REQUIRED TO PROPERLY AND FULLY
SUPPORT ALL ELECTRICAL MATERIALS AND EQUIPMENT IN A PERMANENT
MANNER.
10. ALL MATERIALS AND EQUIPMENT USED SHALL BE OF THE TYPE DESIGNED AND
SUITABLE FOR THE MANNER IN WHICH THEY ARE INSTALLED.
11. EQUIPMENT SHALL BE INSTALLED LEVEL, PLUMB AND TRUE WITH THE STRUCTURE
AND OTHER EQUIPMENT AND INSTALLED IN A HORIZONTAL OR VERTICAL POSITION
AS INTENDED.
12. ROUTE RACEWAYS PARALLEL OR PERPENDICULAR TO BUILDING SURFACES OR
EXPOSED STRUCTURAL MEMBERS AND FOLLOW SURFACE CONTOURS IN ORDER TO
PRESENT A NEAT APPEARANCE.
13. GROUP RACEWAYS WHERE POSSIBLE AND COMPLY WITH RECOMMENDED
SPACING STANDARDS.
14. BENDS AND OFFSETS IN PARALLEL RACEWAYS SHALL BE MADE FROM THE SAME
CENTER LINE SO THE BENDS AND OFFSETS REMAIN PARALLEL.
15. TAKE ALL NECESSARY PRECAUTIONS TO PREVENT FOREIGN MATTER FROM
ENTERING RACEWAYS. IF NECESSARY, CLEAN OUT RACEWAYS PRIOR TO PULLING
IN THE CONDUCTORS.
16. ALL WIRE AND CABLE SHALL BE SUITABLE FOR THE TEMPERATURE, CONDITIONS,
AND LOCATIONS WHERE THEY ARE INSTALLED.
17. TAKE ALL NECESSARY PRECAUTIONS WHEN PULLING WIRE AND CABLES TO
PREVENT DAMAGE TO THE INSULATION.
18. ALL CONDUCTORS TO BE PULLED IN A RACEWAY SHALL BE PULLED TOGETHER.
19. KEEP CONDUCTOR SPLICES TO A MINIMUM.
20. TYPICAL DEVICE MOUNTING HEIGHTS (ABOVE THE FINISHED FLOOR) ARE AS
FOLLOWS:
a. WALL SWITCHES 48”
b. RECEPTACLES 18”
c. COUNTERTOP RECEPTACLES 42” OR 6” ABOVE THE COUNTERTOP
d. DISCONNECTS 72” TO THE TOP OF THE HANDLE
e. PANELBOARDS 72” TO THE TOP
f. TELECOM OUTLETS 18”
g. THERMOSTATS 48”
h. PULL STATIONS 48”
i. VISUAL STROBES 80”
NOTE: ALL SYMBOLS INDICATED ARE NOT NECESSARILY USED ON
THE PROJECT.
NOTE: ALL SYMBOLS INDICATED ARE NOT NECESSARILY USED ON
THE PROJECT.
a
MANUAL STARTER SHALL BE HORSEPOWER RATED, THERMAL OVERLOAD TYPE WITH
PILOT LIGHT. MOUNT AT +72" A.F.F. TO TOP. SQUARE D 2500 OR EQUAL.
HEAVY DUTY TYPE, FUSIBLE OR NON FUSIBLE AS INDICATED ON DRAWINGS,
QUICK-MAKE QUICK-BREAK TYPE, HINGE LOCKABLE COVER, OPERATING LEVER.
MOUNTING AT +72" A.F.F. TO TOP. SQUARE D HEAVY DUTY OR EQUAL.
BOXES USING BLACK MARKER.
600VOLTS, 98% CONDUCTIVITY, STRANDED ALUMINUM, CLASS B, THHN/THWN
RECEPTACLES: (NEMA 5-20R), DUPLEX, 20 AMP, 125 VAC, GROUNDING TYPE,
WHITE COLOR, HUBBELL 5352 OR EQUAL. MOUNT AT 18" A.F.F. UNLESS
GFCI TYPE RECEPTACLE: (NEMA 5-20RGFI), DUPLEX, 20 AMP, 125 VAC, DUPLEX 5
ML AMP SENSITIVITY TRIP TYPE, HUBBELL GF-5362 OR EQUAL. MOUNT AT 18" A.F.F.
OCCUPANCY SENSORS (WALL MOUNTED): REFER TO DRAWINGS FOR MODEL NUMBER.
COVERPLATES: SMOOTH NYLON SCRATCH RESISTANT TYPE, WHITE FINISH.
UNLESS OTHERWISE NOTED.
MOUNT AT 48" A.F.F. UNLESS NOTED OTHERWISE.
INSULATION, MINIMUM #12AWG. USE EMT CONDUITS FOR #8AWG AND LARGER.
CONDUCTORS:
WIRING DEVICES:
PROVIDE NAME PLATE LABEL (IDENTIFICATION) TO SERVICE EQUIPMENT, PANELBOARDS,
DISCONNECT SWITCHES AND SIMILAR EQUIPMENT.
PROVIDE LABEL TO IDENTIFY CIRCUIT NUMBER AT JUNCTION BOXES AND DEVICE
SPECIFICATIONS
LABELING AND IDENTIFICATION:
WITH EVERY BRANCH CIRCUIT. TEST IN ACCORDANCE WITH NEC ARTICLE 250.
CABLE TO MAIN SERVICE DISTRIBUTION BUS. PROVIDE A SEPARATE GROUND WIRE
CLAD GROUND ROD 3/4"D x 10'L, AND CONNECT WITH #2/0 AWG BARE COPPER
WATER PIPE, BUILDING STRUCTURE, AND 25' OF BARE COPPER WIRE, COPPER
GROUNDING SYSTEM SHALL MEET REQUIREMENTS OF NEC ARTICLE 250. BOND
GROUNDING:
OTHERWISE NOTED.
WEATHERPROOF: BELL BOX WITH WEATHERPROOF COVER.
ALL EQUIPMENT AND WIRING INSTALLED ABOVE CEILING SHALL BE RATED FOR USE
IN ENVIRONMENTAL AIR PLENUM.
BOND COMMUNICATION EQUIPMENT TO THE GROUNDING ELECTRODE SYSTEM.
POWER AND SYSTEMS SYMBOL
SCHEDULE
SYMBOL DESCRIPTION
PLAN NOTE
ELECTRICAL PANEL
DUPLEX RECEPTACLE, 18" A.F.F. CENTER OF BOX
DUPLEX RECEPTACLE, EXISTING TO REMAIN
DUPLEX RECEPTACLE, GROUND FAULT INTERRUPTER
DUPLEX RECEPTACLE, GROUND FAULT INTERRUPTER,
WEATHERPROOF, WITH "WHILE-IN-USE" COVER
DUPLEX RECEPTACLE W/USB PORTS
TAMPER RESISTANT DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SPECIALTY RECEPTACLE
FLOORBOX
FLOOR POKE THRU
TELECOMMUNICATIONS OUTLET
PHONE OUTLET, WALL MOUNTED AT 48"
TV TV CABLE OUTLET
PUSHBUTTON
START/STOP STATION
JUNCTION BOX, WALL MOUNTED
JUNCTION BOX, CEILING MOUNTED
MOTOR
MOTOR RATED SWITCH
NON-FUSED DISCONNECT SWITCH
4'x8' PLYWOOD TELEPHONE BACKBOARD
SPEAKER-CEILING MOUNTED
F
FF
CR
MS
REX
NOTE: ALL SYMBOLS INDICATED ARE NOT NECESSARILY USED ON
THE PROJECT.