HomeMy WebLinkAboutE-501-ELECTRICAL-DETAILS-Rev.2SHEET PROJECT INFO SEAL REVISIONS DRAWING TITLE PROJECT CLIENT ARCHITECT
17105
NOVEMBER 15, 2017
CONSTRUCTION SET
MERCHANTS
CORPORATE
CENTER
CARMEL, IN
E-501
ELECTRICAL
DETAILS
W
96"
EXIT
96"
48"
48"
72"
48"
36"
20"
20"
20"
NOTE 2
20"
20"
96"
96"
72"
96"
48"
20"
48"
48"
84"
WC
NOTES:
1. EQUIPMENT MOUNTING HEIGHTS SHALL BE
INDICATED UNLESS OTHERWISE NOTED ON
THE DRAWINGS OR IN THE SPECIFICATIONS.
2. CONCEAL RECEPTACLE BEHIND WATER COOLER.
VERIFY EXACT MOUNTING HEIGHTS.
3. WHERE DEVICES ARE LOCATED IN MASONRY
WALLS LOCATE DEVICE WITHIN COARSING SO
THAT MOUNTING INDICATED HERE IN IS NOT
EXCEEDED.
4. ALL RECEPTACLES ABOVE KITCHEN COUNTER
AND NEAR BATH VANITIES SHALL BE INSTALLED
HORIZONTALLY AT +44" AFF TO TOP OF THE BOX.
SYMBOLS:
FLOOR
CEILING
SCALE:
ELECTRICAL ELEVATION
1 NONE
D
M
F
H
S
F S
J C S M
SCALE: NONE
LAY-IN FIXTURE SUPPORT
DETAIL
1. LIGHTING FIXTURES SHALL BE SUPPORTED INDEPENDENTLY OF CEILING SYSTEM. UPON WRITTEN
REQUEST TO THE ENGINEER, OTHER MEANS OF SUPPORT WILL BE CONSIDERED FOR APPROVAL.
NOTE:
FLEXIBLE
CONDUIT
DOUBLE LOOP SAFETY
CHAIN MIN. 2 PER FIXTURE
ANGLE IRON OR SLOTTED CHANNEL
AS REQUIRED SECURELY SUPPORTED
FROM STRUCTURE ABOVE
CADDY CLAMPS
OR EQUAL
OUTLET BOX &
SUPPORT ROD
CEILING T-BAR
CEILING
LAY-IN TYPE FIXTURE
STRUCTURE
2
4" OCTAGONAL JUNCTION BOX
(AT LEAST 1.5" DEEP). DO
NOT INSTALL SENSOR WITHOUT
JUNCTION BOX.
CEILING
DEPLUGGABLE
TERMINAL
SENSOR
(2) MOUNTING SCREWS
FRONT COVER
SCALE:
TYPICAL OCCUPANCY
SENSOR MOUNTING DETAIL
3 NONE
SCALE: NONE
LAY-IN CEILING EXIT SIGN
MOUNTING DETAIL
STEEL JOIST OR BEAMS
ADDITIONAL ROD
OR WIRE SUPPORT
1/FIXTURE.
ADJUSTABLE SUPPORT
BRACKET, 2/FIXTURE
(ATTACH TO CEILING
CHANNELS)
TIE WIRE
LAY-IN
CEILING
FIXTURE
LAY-IN
CEILING
CHANNELS
4
SCALE:
TYPICAL FLUSH MOUNTED
SYSTEMS OUTLET
5 NONE
CONDUIT STUBBED TO NEAREST
CABLE TRAY ON SAME FLOOR AS
OUTLET. SEE OUTLET DETAILS ON E501
FOR CONDUIT SIZES.
FACEPLATE.
FLUSH MOUNTED, 3" DEEP, 4" OR 4-11/16"
SQUARE BOX. PROVIDE WITH
SINGLE-GANG PLASTER RING IN GYPSUM
BOARD OR PLASTER FINISHED WALL.
PROVIDE 3-1/2 INCH DEEP MASONRY BOX
IN MASONRY WALL.
SCALE: NONE
FIRE/SMOKE DAMPER
WIRING DETAIL
1. SEE FIRE ALARM DRAWINGS AND POWER PLANS FOR LOCATIONS OF SMOKE DAMPER, DUCT
DETECTOR, AND PANEL/BRANCH CIRCUIT PANEL NUMBER.
2. ALL EQUIPMENT SHOWN DARK BY DIVISION 26 OR 28. ALL EQUIPMENT SHOWN SHADED BY OTHER
DIVISION.
NOTES:
BRANCH CIRCUIT
CONDUIT/WIRING
TO NEXT
FIRE/SMOKE
DAMPER BRANCH CIRCUIT
CONDUIT/WIRING
TO NEXT
ADDRESSABLE
DEVICE
4 WIRE FIRE ALARM
NETWORK CIRCUIT
FROM FACP
BRANCH CIRCUIT CONDUIT/WIRING
STANDBY POWER PANEL
FROM 208/120V LEGALLY-REQUIRED
DUCT
DETECTOR
FIRE/
SMOKE
DAMPER
DUCT OUTLINE
AIRFLOW
DIRECTION
DUCT OUTLINE
7
PER ONE LINE DIAGRAM
A SINGLE RACEWAY)
(MAY BE COMBINED IN
2#14, 3/4"C.
TELE. CABLE
NOTES:
TELE.
OUTLET
SECOND
LOBBY
FLOOR
IN HOISTWAY
IN ELEVATOR
PIT
FIRST
LOBBY
FLOOR
#18 SHIELDED
INDUSTRIAL
VAPORTITE
IN PIT
FIXTURE
RECEPTACLE
GFI
POWER FEED, SIZED
480V, 3Ø ELEVATOR
2#12,#12G., 3/4"C.
MANUFACTURER/
INSTALLER
CAB
CAB
HVAC
CONTROL
CAB LIGHTS
BY DIVISION 26
BY ELEVATOR
TO 480V PANEL
PER PLANS
CB CB
IN HOISTWAY
EQUIPMENT
ROOM
IN ELEVATOR
FIRST
FLOOR
LOBBY
BY DIV. 16
TWISTED PAIR
FLOOR
LOBBY
THIRD
SECOND
FLOOR
LOBBY
FOURTH
FLOOR
LOBBY
FLOOR
LOBBY
THIRD
FLOOR
LOBBY
FOURTH
SCALE:
TYPICAL ELEVATOR WIRING DIAGRAM
8 NOT TO SCALE
NOTES:
1. PROVIDE ENGRAVED PHOENELIC NAMEPLATE ON DISCONNECTS STATING MORE THAN ONE SOURCE SERVES THE
ELEVATOR CABINET.
2. SHOULD THE GENERAL CONTRACTOR UTILIZE AN ELEVATOR MANUFACTURER THAT REQUIRE MORE ELECTRICAL WORK
THAN SHOWN ON THIS DETAIL, THE COSTS SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR.
3. IF ELEVATOR CAN BE OPERATED FROM NEC 702 OPTIONAL POWER SYSTEM, ALL HVAC EQUIPMENT SERVING THE
ELEVATOR EQUIPMENT ROOM SHALL BE CONNECTED TO THE OPTIONAL POWER SYSTEM.
4. EQUIPMENT SHOWN SHADED IS BY ELEVATOR MANUFACTURER. ITEMS SHOWN DARK ARE BY DIVISION 26.
TO 208/120V PANEL
DEDICATED CIRCUIT
TO 208/120V PANEL
DEDICATED CIRCUIT
IN ELEVATOR
RECEPTACLE
GFI
2#12,#12G., 3/4"C.
TO 208/120V PANEL
DEDICATED CIRCUIT
TO 480/277V PANEL
DEDICATED CIRCUIT
MACHINE ROOM
LIGHT FIXTURES
IN ROOM
2#14,
3/4"C.
CB
480V 3P CIRCUIT BREAKER,
PER ONE LINE DIAGRAM
WITH AUXILIARY N.O.
CONTACT IN ELEVATOR
MACHINE ROOM
20A/1P
CIRCUIT BREAKER
IN ELEVATOR MACHINE ROOM
2#10, #10G., 3/4"C.
TO 208/120V PANEL
PER PLANS
FLOOR
LOBBY
FIFTH
DOOR POWER
SUPPLYCONTROLLER
ELECTRIC
STRIKE
READER ON
UNSECURED
SIDE
120V
TO SYSTEM
CONTROL
WIRING AND
CONNECTION IN
DOOR FRAME
MAGNETIC
DOORCONTACTS
NOTES:
1. DOOR HARDWARE AND POWER SUPPLY
FURNISHED BY OTHER
TRADE.
2. PROVIDE WIRING PER SYSTE
MANUFACTURING INSTRUCTIONS.
SCALE:
TYPICAL SECURE DOOR DETAIL
6 NONE
CU GRD. BAR
RACKS
#6 AWG INSULATED
GROUND CONDUCTOR
MDF & IDF'S
MAIN EQUIPMENT BONDING G
JUMPER (SIZE IN ACCORDANCE
WITH NEC ARTICLE 250)
TO MAIN SERVICE EQUIPMENT
SWITCHBOARD OR PANELBOARD
GROUND BUS AT SERVICE ENTRANCE
N
G
PANELBOARD
G
DISTRIBUTION PANELBOARD
N
N
G
PANELBOARD
EQUIPMENT
GROUND -
SIZE AS
SHOWN ON
DRAWINGS
TRANSFORMER
C
N
B A BONDING JUMPERS
(SIZE IN
ACCORDANCE WITH
NEC ARTICLE 250)
N
G
COMMUNICATIONS SYSTEMS
EQUIPMENT CABINET GROUND
COMMUNICATIONS PLYWOOD
BACKBOARD GROUND BAR
TELEPHONE SERVICE
DEMARK GROUND BAR
3/4"X10' CU GROUND
ROD AS REQUIRED
(SEE SECTION 260526)
#3/0 CU BONDING
JUMPER IF NOT
FACTORY INSTALLED
EQUIPMENT GROUND.
SIZE AS SHOWN ON
DRAWINGS
EQUIPMENT
GROUND -
SIZE AS
SHOWN ON
DRAWINGS
G
NEUTRAL BUS
GROUND BUS
BUILDING STEEL
(INDOOR) OR
GROUND ROD
(OUTDOOR)
GENERATOR FRAME
AND ENCLOSURE
N
C
GENERATOR
B A
#3/0 BARE CU GROUNDING
ELECTRODE CONDUCTOR
#3/0 CU EQUIPMENT
BONDING JUMPER
BONDING BUSHING (TYPICAL)
SERVICE EQUIPMENT ENCLOSURE
(MAIN SWITCHBOARD)
MAIN BONDING JUMPER
(SIZE IN ACCORDANCE
WITH NEC ARTICLE 250)
PANELBOARD
AUTOMATIC TRANSFER
SWITCH ENCLOSURE
(SWITCHED NTL)
NOT TO SCALE
TYPICAL GROUNDING DETAIL
BUILDING STEEL OR INTERIOR METAL WATER PIPE
AND GROUND ROD IF STEEL IS NOT AVAILABLE
#3/0 BARE CU GROUNDING
ELECTRODE CONDUCTOR
BUILDING
FOUNDATION
REBAR
#3/0 BARE CU
GROUND RING
INCOMING
METAL
WATER
SERVICE
INCOMING SERVICE
METAL CONDUITS
TRANSFORMER
ENCLOSURE
#3/0 BARE CU GROUNDING
ELECTRODE CONDUCTOR
IG
IG IG
TRANSFORMER
C
N
B A
NTL AS SHOWN
ON DRAWINGS
NO GROUND CABLE
TO NTL
UTILITY
TRANSFORMER
TO UTILITY
TRANSFORMER
ISOLATED GROUND-
SIZE AS SHOWN ON
DRAWINGS WHEN REQUIRED
3/4"X10' CU GROUND ROD
(TYP.)
BUILDING STEEL
(TYP.)
9
CONC. SLAB PER PLANS
FINISHED FLOOR
STEEL COLUMN PER PLANS
CL
3/4" x 10'-0" COPPER
CLAD STEEL GROUND ROD
FOOTINGS PER PLANS
BONDING PLATE OR
EXOTHERMIC WELD
TO STEEL COLUMN
EXOTHERMIC CONNECTION
TO GROUND ROD
CLASS II COPER
GROUNDING
CONDUCTOR
1" PVC CONDUIT
SLEEVE
SCALE:
COLUMN GROUNDING DETAIL
10 NONE
05/01/18
Nick Mishler