Loading...
HomeMy WebLinkAboutE-502-ELECTRICAL-DETAILS-Rev.0SHEET PROJECT INFO SEAL REVISIONS DRAWING TITLE PROJECT CLIENT ARCHITECT 17105 NOVEMBER 15, 2017 CONSTRUCTION SET MERCHANTS CORPORATE CENTER CARMEL, IN E-502 ELECTRICAL DETAILS EMERGENCY GENERATOR G GENERATOR 400F 300AT MINIMUM RATED CAPACITY: 175 KW 219 SKVA BASIS OF DESIGN: MANUF: GENERAC MODEL: SG175 RATED VOLTAGE: 480/277 V 3-PHASE/ 4 WIRE ENCLOSURE RATING: 72dBA @ 7M FUEL TYPE: NATURAL GAS SEE SPECIFICATIONS FOR ADDITIONAL FEATURES LOAD BREAKERS INSTALL ON REINFORCED CONCRETE PAD. CONNECT TO SERVICE GROUNDING SYSTEM #4/0 CU TWO(2) 1"C. TO TRANSFER SWITCH (CONTROLS) REMOTE ANNUNCIATOR LOCATED IN MED ROOM REMOTE STOP EPO INSTALLED ADJACENT TO TRANSFER SWITCH BATTERY CHARGER CRP-1 (3) #10, 3/4"C LIGHTING RECEP. CRP-2 (3) #10, 3/4"C BLOCK HEATER CRP-3 (3) #10, 3/4"C TRANSFER SWITCH #1 NOTES N L E TRANSFER SWITCH SEE ATTACHED NOTES TO GENERATOR TO PANELBOARD, SWITCHBOARD OR UTILITY TRANSFER SWITCH TYPE: AUTOMATIC CURRENT RATING: 60 A RATED VOLTAGE: 480/277 V 3-PHASE/ 3 WIRE # OF POLES: 4 NEUTRAL CONFIGURATION: SWITCHED IN-SYNC TRANSFER: Y MAIN CIRCUIT BREAKER: N GROUND FAULT ON MAIN: N SERVICE ENTRANCE RATED: Y REMOTE ANNUNCIATION: Y BY-PASS/ISOLATION: N NEC LOAD BRANCH: 701 KAIC: 42 SEE SPECIFICATIONS FOR ADDITIONAL FEATURES NEMA RATING: 1 CYCLE RATING: TRANSFER SWITCH #2 NOTES 700 - LIFE SAFETY SYSTEMS 701 - LEGALLY REQUIRED STANDBY SYSTEMS 702 - OPTIONAL STANDBY SYSTEMS 517 - HOSPITAL CRITICAL BRANCH SYSTEMS NEC LOAD BRANCH OPTIONS: N L E TRANSFER SWITCH SEE ATTACHED NOTES TO GENERATOR TO PANELBOARD, SWITCHBOARD OR UTILITY TRANSFER SWITCH TYPE: AUTOMATIC CURRENT RATING: 200 A RATED VOLTAGE: 480/277 V 3-PHASE/ 4 WIRE # OF POLES: 4 NEUTRAL CONFIGURATION: SWITCHED IN-SYNC TRANSFER: Y MAIN CIRCUIT BREAKER: N GROUND FAULT ON MAIN: N SERVICE ENTRANCE RATED: Y REMOTE ANNUNCIATION: Y BY-PASS/ISOLATION: Y NEC LOAD BRANCH: 701 KAIC: 42 SEE SPECIFICATIONS FOR ADDITIONAL FEATURES NEMA RATING: 1 CYCLE RATING: REFER TO SINGLE LINE DIAGRAM 05/01/18 Nick Mishler