HomeMy WebLinkAboutE-502-ELECTRICAL-DETAILS-Rev.0SHEET PROJECT INFO SEAL REVISIONS DRAWING TITLE PROJECT CLIENT ARCHITECT
17105
NOVEMBER 15, 2017
CONSTRUCTION SET
MERCHANTS
CORPORATE
CENTER
CARMEL, IN
E-502
ELECTRICAL
DETAILS
EMERGENCY GENERATOR
G
GENERATOR
400F
300AT
MINIMUM RATED CAPACITY: 175 KW 219 SKVA
BASIS OF DESIGN: MANUF: GENERAC MODEL: SG175
RATED VOLTAGE: 480/277 V 3-PHASE/ 4 WIRE
ENCLOSURE RATING: 72dBA @ 7M FUEL TYPE: NATURAL GAS
SEE SPECIFICATIONS FOR ADDITIONAL FEATURES
LOAD BREAKERS
INSTALL ON REINFORCED
CONCRETE PAD.
CONNECT TO SERVICE
GROUNDING SYSTEM
#4/0 CU
TWO(2) 1"C. TO
TRANSFER
SWITCH
(CONTROLS)
REMOTE
ANNUNCIATOR
LOCATED IN
MED ROOM
REMOTE STOP
EPO INSTALLED
ADJACENT TO
TRANSFER SWITCH
BATTERY CHARGER
CRP-1
(3) #10, 3/4"C
LIGHTING RECEP.
CRP-2
(3) #10, 3/4"C
BLOCK HEATER
CRP-3
(3) #10, 3/4"C
TRANSFER SWITCH #1 NOTES
N
L
E
TRANSFER SWITCH
SEE ATTACHED NOTES
TO GENERATOR
TO PANELBOARD,
SWITCHBOARD OR
UTILITY
TRANSFER SWITCH TYPE: AUTOMATIC CURRENT RATING: 60 A
RATED VOLTAGE: 480/277 V 3-PHASE/ 3 WIRE # OF POLES: 4
NEUTRAL CONFIGURATION: SWITCHED IN-SYNC TRANSFER: Y
MAIN CIRCUIT BREAKER: N GROUND FAULT ON MAIN: N
SERVICE ENTRANCE RATED: Y REMOTE ANNUNCIATION: Y
BY-PASS/ISOLATION: N NEC LOAD BRANCH: 701 KAIC: 42
SEE SPECIFICATIONS FOR ADDITIONAL FEATURES
NEMA RATING: 1 CYCLE RATING:
TRANSFER SWITCH #2 NOTES
700 - LIFE SAFETY SYSTEMS
701 - LEGALLY REQUIRED STANDBY SYSTEMS
702 - OPTIONAL STANDBY SYSTEMS
517 - HOSPITAL CRITICAL BRANCH SYSTEMS
NEC LOAD BRANCH OPTIONS:
N
L
E
TRANSFER SWITCH
SEE ATTACHED NOTES
TO GENERATOR
TO PANELBOARD,
SWITCHBOARD OR
UTILITY
TRANSFER SWITCH TYPE: AUTOMATIC CURRENT RATING: 200 A
RATED VOLTAGE: 480/277 V 3-PHASE/ 4 WIRE # OF POLES: 4
NEUTRAL CONFIGURATION: SWITCHED IN-SYNC TRANSFER: Y
MAIN CIRCUIT BREAKER: N GROUND FAULT ON MAIN: N
SERVICE ENTRANCE RATED: Y REMOTE ANNUNCIATION: Y
BY-PASS/ISOLATION: Y NEC LOAD BRANCH: 701 KAIC: 42
SEE SPECIFICATIONS FOR ADDITIONAL FEATURES
NEMA RATING: 1 CYCLE RATING:
REFER TO SINGLE
LINE DIAGRAM
05/01/18
Nick Mishler