HomeMy WebLinkAboutE-901-ELECTRICAL-ONE-LINE-DIAGRAM-Rev.2SHEET PROJECT INFO SEAL REVISIONS DRAWING TITLE PROJECT CLIENT ARCHITECT
17105
NOVEMBER 15, 2017
CONSTRUCTION SET
MERCHANTS
CORPORATE
CENTER
CARMEL, IN
E-901
ELECTRICAL ONE
LINE DIAGRAM
2RPA
225A
208/120V
3Ø-4W
2RPA
225A
208/120V
3Ø-4W
3RPA
225A
208/120V
3Ø-4W
3RPA
225A
208/120V
3Ø-4W
4RPA
225A
208/120V
3Ø-4W
4RPA
225A
208/120V
3Ø-4W
5RPA
225A
208/120V
3Ø-4W
5RPA
225A
208/120V
3Ø-4W
2LPA
400A
480/277V
3Ø-4W
3LPA
400A
480/277V
3Ø-4W
4LPA
400A
480/277V
3Ø-4W
5LPA
400A
480/277V
3Ø-4W
ATS
#1
ATS
#2
2ERP
60A
208/120V
3Ø-4W
2ELP
60A
480/277V
3Ø-4W
3ERP
60A
208/120V
3Ø-4W
3ELP
60A
480/277V
3Ø-4W
4ERP
60A
208/120V
3Ø-4W
4ELP
60A
480/277V
3Ø-4W
5ERP
60A
208/120V
3Ø-4W
5ELP
60A
480/277V
3Ø-4W
G
ELEVATOR
#2
60A
ELEVATOR
#1
60A
MAIN
DIST. PANEL
2000A
480/277V
3Ø-4W
EMERGENCY
DIST. PANEL
200A
480/277V
3Ø-4W
RTU-2 RTU-1
75KVA
75KVA
75KVA
75KVA
1200A BUS RISER
480V, 3Ø-4W
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
FIFTH FLOOR
ROOF
SCALE:
ONE LINE DIAGRAM
1 NONE
GENERAL NOTES
A. REFER TO SHEET E-000 FOR SYMBOLS AND ABBREVIATIONS.
B. REFER TO SHEETS E-601 THROUGH E603 FOR PANEL SCHEDULES.
C. REFER TO SHEET EP100 THROUGH EP106 FOR EQUIPMENT LOCATIONS.
SHEET KEYNOTES
1. PROVIDED BY ELECTRICAL UTILITY. COORDINATE INSTALLATION WITH
UTILITY.
2. PROVIDE PANEL PLUG TO BUSWAY..
3. PROVIDE NORMAL AND EMERGENCY POWER FEEDS TO FIRE PUMP
CONTROLLER WITH INTEGRATED AUTOMATIC TRANSFER SWITCH.
4. BUS RISER SHALL BE SIMILAR TO GE "SPECTRA" SERIES BUSWAY.
5. REFER TO GROUNDING DETAILS ON SHEET E-501.
UTILITY
TRANSFORMER
FEEDER AND BRANCH CIRCUIT SCHEDULE
NOTE: SEE DRAWINGS FOR NUMBER OF WIRES IN HOMERUN
FEEDER/BRANCH CIRCUIT
DESIGNATION
CONDUCTOR SIZE TYPE CABLE CONDUIT
PHASE & NEUTRAL
EQUIPMENT
GROUND
ALUMINUM COPPER
F20 12 12 X MC
F30 10 10 X MC
F40-50 8 10 X MC
F60 6 10 X MC
F70-80 4 8 X MC
F90 3 8 X MC
F100 3 8 X MC
F125 1/0 4 X 2"
F150 3/0 4 X 2-1/2"
F175 4/0 4 X 2-1/2"
F200 250 4 X 3"
F225 300 2 X 3"
F250 350 2 X 3"
F300 500 2 X 3-1/2"
F350 2 RUNS OF 4/0 1 X 2-1/2"
F400 2 RUNS OF 250 1 X 3" EACH
F600 2 RUNS OF 500 2/0 X 3-1/2" EACH
F800 3 RUNS OF 400 3/0 X 3-1/2" EACH
F1000 3 RUNS OF 600 4/0 X 4" EACH
F1200 4 RUNS OF 500 250 X 3-1/2" EACH
F1600 5 RUNS OF 600 350 X 4" EACH
F2000 6 RUNS OF 600 400 X 4" EACH
F2500 7 RUNS OF 750 600 X 5" EACH
F3000 8 RUNS OF 750 600 X 5" EACH
NOTES:
1. ALL 20A CIRCUITS SHALL UTILIZE SEPARATE INDEPENDENT NEUTRAL CONDUCTORS. DO NOT COMBINE NEUTRAL
CONDUCTORS ON ANY BRANCH CIRCUITS.
2. ALL CIRCUITS CONNECTED TO "EXXX" PANELS SHALL HAVE CONDUCTORS INSTALLED IN SEPARATE CONDUITS OR
MC CABLE. DO NOT MIX NORMAL AND STANDBY CIRCUITS IN THE SAME RACEWAY.
400A 400A
15KVA
15KVA
15KVA
15KVA
100A
100A
100A
100A
60A
1
1RPA
225A
208/120V
3Ø-4W
1RPA
225A
208/120V
3Ø-4W
75KVA
2LPA
400A
480/277V
3Ø-4W
E
200A
E
175KW
STANDBY GENERATOR
480V, 3Ø-4W
F100
F225
F225
F60
F400
F400
F60 F30
F100
F225
F225
F60 F30
F100
F225
F225
F60 F30
F100
F225
F225
F60 F30
F400
N F100
F60
F60
F60
F60
N
F60
F60
F200
F2000
F60
1ERP
60A
208/120V
3Ø-4W
1ELP
60A
480/277V
3Ø-4W
15KVA
F60 F30
F60
FIRE
PUMP
60A
F60
2
2
2
3
E
F60
N
F200
4
TENANT METERS
RT #1
400A
RT #2
400A
GND
BAR
5
05/01/18
Nick Mishler