1. THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL INSPECTOR(S) TO PROVIDE INSPECTIONS DURING CONSTRUCTION
LISTED IN THIS SECTION. THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE
COMPETENCE TO THE INSPECTIONS BEING PERFORMED TO THE SATISFACTION OF THE ENGINEER OF RECORD AND THE
BUILDING OFFICIAL. THE SPECIAL INSPECTOR SHALL HAVE EXPERIENCE WITH AT LEAST FIVE OTHER PROJECTS SIMILAR
IN NATURE.
2. THE PURPOSE OF THE INSPECTIONS SHALL BE TO ENFORCE COMPLIANCE WITH THE CONSTRUCTION DRAWINGS,
SPECIFICATIONS, GEOTECHNICAL REPORT AND THE 200X XXXXX BUILDING CODE.
3. SPECIAL INSPECTORS SHALL KEEP RECORD OF INSPECTIONS. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION
REPORTS TO THE BUILDING OFFICIAL AND TO THE ENGINEER OF RECORD. REPORTS SHALL INDICATE THAT THE WORK
INSPECTED WAS PERFORMED IN CONFORMANCE TO THE APPROVED CONSTRUCTION DOCUMENTS. DISCREPANCIES
SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION. ANY CORRECTIONS THAT
WERE NOT COMPLETED BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL AND
THE ENGINEER OF RECORD. IF DISCREPANCIES ARE NOT CORRECTED BY THE CONTRACTOR, SPECIAL INSPECTOR SHALL
ISSUE A NOTIFICATION OF NON-COMPLIANCE (NNC) TO ENGINEER.
4. THE SPECIAL INSPECTOR SHALL VERIFY THAT THE FABRICATOR MAINTAINSDETAILED FABRICATION AND QUALITY
CONTROL PROCEDURES THAT PROVIDE A BASIS FOR INSPECTION CONTROL OF THE WORKMANSHIP. IF FABRICATOR IS
ENROLLED IN A NATIONALLY ACCEPTED INSPECTIONS PROGRAM (SATISFACTORY TO THE ENGINEER AND BUILDING
OFFICIAL), THIS IS NOT REQUIRED. ANY CORRECTIONS THAT WERE NOT COMPLETED BY THE CONTRACTOR SHALL BE
BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL AND THE ENGINEER OF RECORD.
5. EACH SPECIAL INSPECTOR IS RESPONSIBLE TO REVIEW THE PLANS THOROUGHLY AND SUFFICIENTLY AHEAD OF THE
CONSTRUCTION TO ESTABLISH IF HE CAN INSPECT THOSE ITEMS ENTRUSTED TO HIM. ALL AMBIGUITIES OR OMISSIONS IN
THE APPROVED PLANS THAT CREATE ANY FORM OF DOUBT FOR THE SPECIALINSPECTOR SHALL BE RESOLVED THROUGH
THE PROPER CHANNELS PRIOR TO CONSTRUCTION.
6. THE FOLLOWING ITEMS REQUIRE INSPECTION BY THE SPECIAL INSPECTOR:
STRUCTURAL/ REINFORCING STEEL
ITEMS TO BE INSPECTED: FREQUENCY: REFERENCED STANDARD
IDENTIFICATION MARKINGS TO CONFORM PERIODIC APPLICABLEASTM MATERIAL
TO ASTM STANDARDS SPECIFIED IN SPECS, AISC 360 SEC. A3.3
APPROVED CONSTRUCTION DOCUMENTS
MANUFACTURER'S CERTIFICATE OF PERIODIC
COMPLIANCE
INSPECTION OF HIGH STRENGTH BOLTING:
BEARING TYPE CONNECTIONS PERIODIC AISC 360, SEC. M2.5, IBC 1704.3.3
SLIP CRITICAL CONNECTIONS CONTINUOUS AISC 360, SEC. M2.5, IBC 1704.3.4
MATERIAL VERIFICATION OF STRUCTURAL STEEL
IDENTIFICATION OF MARKINGS TO ASTM A6/ A568. IBC 1708.4
CONFORM TO ASTM STANDARD SPECIFIED
IN APPROVED CONSTRUCTION DOCUMENTS
MANUFACTURER'S CERTIFIED MILL TEST ASTM A6/ A568. IBC 1708.4
REPORTS
MATERIAL VERIFICATION OF WELD FILLER MATERIALS.
IDENTIFICATION OF MARKINGS TO CONFORM AISC 360, SEC. A3.5
TO AWS SPECIFICATION IN APPROVED
CONSTRUCTION DOCUMENTS
MANUFACTURER CERTIFICATE OF COMPLIANCE AISC 360, SEC. A3.5
WELDING OF STRUCTURAL STEEL
FULL AND PARTIAL PENETRATION CONTINUOUS AWS-D1.1, IBC 1704.3.1
GROOVE WELDS
MULTI-PASS FILLET WELDS PERIODIC - 50% AWS-D1.1, IBC 1704.3.1
SINGLE-PASS FILLET WELDS > 5/16" PERIODIC - 50% AWS-D1.1, IBC 1704.3.2
SINGLE-PASS FILLET WELDS <= 5/16" PERIODIC - 25% AWS-D1.1, IBC 1704.3.1
FLARE BEVEL/ FLARE V PERIODIC - 25% AWS-D1.1, IBC 1704.3.1
INSPECTION OF STEEL FRAME JOINT DETAILS PERIODIC IBC 1704.3.2
FOR COMPLIANCE WITH APPROVED CONSTRUCTION
DOCUMENTS INCLUDING DETAILS SUCH AS
BRACING AND STIFFENING, MEMBER LOCATIONS,
AND APPLICATION OF JOINT DETAILS AT EACH
CONNECTION
CONCRETE CONSTRUCTION
ITEMS TO BE INSPECTED: FREQUENCY: REFERENCED STANDARD
REINFORCING STEEL PERIOIDIC ACI 318: 3.5, 7.1-7.7; IBC 1913.4
AWS D1.4, ACI 318: 3.5.2
REINFORCING STEEL WELDING CONTINUOUS IBC 1911.5
BOLTS INSTALLED IN CONCRETE
PRIOR TO AND DURING PLACEMENT
CONCRETE MIX DESIGN PERIODIC ACI 318: CH. 4, 5.2-5.4
EACH CONC. POUR IBC 1904.2.2, 1913.2, 1913.3
SAMPLING OF FRESH CONCRETE CONTINUOUS
PROVIDE A SET OF 4 FOR ACI 318: 5.6, 5.8
EVERY 50 CUBIC YARDS OF ASTM C172
CONCRETE BUT NOT LESS ASTM C31
THAN 1 FOR 5000 SF OF IBC 1913.10
SLAB OR WALL SURFACE AREA.
MONITOR SLUMP AND AIR
CONTENT OF CONCRETE &
NOTIFY DELIVERY DRIVER IF
SLUMP DEVIATES MORE THAN
1" FROM RECOMMENDED
VALUE.
DRILLED & POST-INSTALLED ANCHORS EACH APPLICATION
ALL DRILLED AND ADHESIVE
ANCHORS (REBAR, BOLTS,
THREADED RODS, ETC.)
SHALL BE PULL TESTED TO
133% OF THE ULTIMATE
BOND STRENGTH FOR NO
LESS THAN 3 MIN.
INSPECT FORMWORK FOR SHAPE, PERIODIC ACI 318: 6.1.1
LOCATION AND DIMENSIONS
MASONRY CONSTRUCTION
CONTINUOUS AND PERIODIC INSPECTIONS SHALL CONFORM TO
LEVEL 2 SPECIAL INSPECTION IN ACCORDANCE WITH IBC TABLE
1704.5.3. IN ADDITION, TESTING OF MASONRY MATERIALS
AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE
SPECIFICATIONS.
WOOD CONSTRUCTION
ITEMS TO BE INSPECTED: FREQUENCY: REFERENCED STANDARD
PREFAB'D. STRUCT'L. ELEMENTS/ PERIODIC IBC 1704.2
ASSEMBLIES
SITE BUILT ASSEMBLIES PERIODIC IBC 1704.1
DIAPHRAGMS PERIODIC IBC TABLE 2306.3.2
TRUSS BRACING PERIODIC PER TRUSS MFGR
RECOMMENDATIONS
SOILS - FOOTING BEARING AND BUILDING PAD SUBGRADE PREPARATION:
VERIFY MATERIALS BELOW FOOTINGS PERIODIC
ARE ADEQUATE TO ACHIEVE THE
DESIGN BEARING CAPACITY.
VERIFY EXCAVATIONS ARE EXTENDED PERIODIC
TO PROPER DEPTH AND HAVE REACHED
PROPER BEARING STRATA.
PERFORM CLASSIFICATION OF CONTROLLED PERIODIC
FILL MATERIALS
VERIFY USE OF PROPER MATERIALS, CONTINUOUS
DENSITIES, AND LIFT THICKNESS
DURING PLACEMENT AND COMPACTION
OF CONTROLLED FILL
PRIOR TO PLACEMENT OF CONTROLLED PERIODIC
FILL, OBSERVE SUBGRADE AND VERIFY
THAT SITE HAS BEEN PREPARED
PROPERLY
PROOFROLLING OBSERVATIONS CONTINUOUS GEOTECHNICAL REPORT &
FOUNDATION NOTES
1. PROJECT SHALL CONFORM TO ALL REQUIREMENTS OF ACI 423, AND ACI 301 CHAPTER 9, LATEST EDITION,
PUBLISHED BY THE AMERICAN CONCRETE INSTITUTE, FARMINGTON HILLS, MICHIGAN, EXCEPT AS MODIFIED BY
THESE CONTRACT DOCUMENTS.
2. THE POST-TENSIONING SUPPLIER SHALL BE RESPONSIBLE FOR THE DETAILED DESIGN OF THE POST-
TENSIONING SYSTEM, INCLUDING REQUIRED TENDONS, ANCHORAGE, COUPLING SYSTEMS, SPECIAL
REINFORCEMENT, TENDON SUPPORTS, AND TENDON STRESSING. THE POST-TENSIONING SUPPLIER SHALL
PROVIDE A MINIMUM NUMBER OF TENDONS EQUIVALENT TO THE EFFECTIVE FORCE SHOWN ON THE DRAWINGS
DIVIDED BY 26.7 AND ROUNDED TO THE NEAREST WHOLE TENDON.
3. FIELD FOREMAN: THE FIELD FOREMAN RESPONSIBLE FOR THE PLACEMENT OF ALL POST-TENSIONING SHALL
HAVE A MINIMUM OF THREE (3) YEARS IN THIS CAPACITY FOR THIS TYPE OF CONSTRUCTION.
4. PT STEEL QUALITY: ONE SAMPLE OF EACH REEL OR HEAT SHALL BE TESTED BY AN APPROVED LABORATORY.
TEST RESULTS OR MILL CERTIFICATES SHALL BE SUBMITTED TO THE ENGINEER BEFORE STRESSING OF
TENDONS. POST-TENSIONING TENDONS SHALL BE STRESS-RELIEVED OR BE OF LOW-RELAXATION QUALITY,
AND SHALL CONFORM TO THE FOLLOWING:
• SEVEN WIRE STRAND ASTM DESIGNATION.......A-416 1/2" DIAMETER TENDON
AREA..............0.153 IN SQ. ULTIMATE STRENGTH................................270 KSI
• TENDON STRESSES SHALL CONFORM TO THE FOLLOWING:
• MAXIMUM JACKING STRESS......................216 KSI MAXIMUM STRESS IMMEDIATELY
• AFTER PRESTRESS TRANSFER..................200 KSI
• MAXIMUM ANCHORAGE STRESS IMMEDIATELY
• AFTER PRESTRESS TRANSFER..................189 KSI
• POST-TENSION SYSTEM SHALL BE FULLY ENCAPSULATED PER PTI SPECIFICATIONS
U.N.O.
5. EFFECTIVE FORCE: EFFECTIVE FORCE SHALL BE 24 KIPS PER STRESS-RELIEVED, AND PER LOW-RELAXATION
TENDON, 26.8 KIPS WHEN TENDON LENGTH IS LESS THAN 100 FEET. FOR VARIANCE FROM THIS VALUE,
CONTRACTOR SHALL PROVIDE FRICTION AND LONG-TERM LOSS CALCULATIONS FOR THE ENGINEER'S
APPROVAL.
6. PT HARDWARE QUALITY: ALL ANCHORAGES, COUPLERS AND MISCELLANEOUS HARDWARE SHALL BE
STANDARD AND APPROVED BY GOVERNING AGENCIES AND THE ENGINEER.
7. TENDONS: UNBONDED STRANDS SHALL BE ENCASED IN SLIPPAGE SHEATHING WHICH SHALL CONSIST OF A
SEALED DURABLE WATERPROOF PLASTIC TUBING CAPABLE OF PREVENTING THE PENETRATION OF MOISTURE
AND CEMENT PASTE, AND WHICH WILL CONTAIN A RUST-INHIBITING GREASE COATING. TEARS IN THE
SHEATHING SHALL BE REPAIRED TO RESTORE THE WATERTIGHTNESS OF THE SHEATHING. HEAT-SEALED
SHEATHING SHALL NOT BE USED UNLESS THE WATERTIGHTNESS OF THE SHEATHING IS GUARANTEED BY THE
CONTRACTOR.
8. SHOP DRAWINGS: THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS SHOWING TENDON LAYOUT, DEAD-END
AND STRESSING- END LOCATIONS, AND TENDON SUPPORT LAYOUTS WITH DETAILS NECESSARY FOR
INSTALLATION FOR THE ENGINEER'S APPROVAL. A SET OF APPROVED SHOP DRAWINGS MUST BE FILED WITH
THE CITY ENGINEER BY THE CONTRACTOR.
9. REVIEW OF THE SHOP DRAWINGS AND CALCULATIONS BY THE STRUCTURAL ENGINEER DOES NOT RELIEVE THE
POST-TENSIONING SUPPLIER OF RESPONSIBILITY FOR DETAILED DESIGN AS SPECIFIED HEREIN.
10. TENDON PLACEMENT: CARE SHALL BE TAKEN THAT TENDONS ARE LOCATED AND HELD IN THEIR DESIGNED
POSITIONS. TOLERANCES FOR THE LOCATION OF THE PRESTRESSING STEEL SHALL NOT BE MORE THAN ± 1/8"
VERTICALLY, EXCEPT AS NOTED OR APPROVED BY THE ENGINEER. ACCESS TO STRESSING ENDS SHALL BE
MAINTAINED WHERE SHOWN.
11. TENDON ADJUSTMENTS: SLIGHT DEVIATIONS IN THE HORIZONTAL SPACING OF THE SLAB TENDONS WILL BE
PERMITTED WHEN REQUIRED TO AVOID OPENINGS, INSERTS, AND DOWELS WHICH ARE SPECIFICALLY
LOCATED. WHERE LOCATIONS OF TENDONS SEEM TO INTERFERE WITH EACH OTHER, ONE TENDON MAY BE
MOVED HORIZONTALLY IN ORDER TO AVOID THE INTERFERENCE.
12. TWISTING: TWISTING OR ENTWINING OF INDIVIDUAL WIRES OR STRANDS WITHIN A BUNDLE OR A BEAM SHALL
NOT BE PERMITTED UNLESS APPROVED BY THE ENGINEER.
13. STRAND BUNDLES: THE MAXIMUM ALLOWABLE NUMBER OF STRANDS PER BUNDLE IS FOUR (4) FOR SLABS,
U.N.O. AND SIX (6) FOR BEAMS.
14. PROFILES: PROFILES SHALL CONFORM TO CONTROLLING POINTS SHOWN ON THE DRAWINGS AND SHOULD BE
IN AN APPROXIMATE PARABOLIC DRAPE BETWEEN SUPPORTS, UNLESS NOTED OTHERWISE. LOW POINTS ARE
AT MIDSPAN UNLESS NOTED OTHERWISE. HARPED TENDONS SHALL BE STRAIGHT BETWEEN HIGH AND LOW
POINT CONTROLS.
15. PRESTRESS COVER: ALL DIMENSIONS SHOWING THE LOCATION OF PRESTRESSING TENDONS ARE TO THE
CENTER OF GRAVITY OF THE TENDON (CGS) UNLESS NOTED OTHERWISE.
16. MINIMUM CHAIRING: TENDONS SHALL BE SECURED TO A SUFFICIENT NUMBER OF POSITIONING DEVICES TO
ENSURE CORRECT LOCATION DURING AND AFTER THE PLACING OF THE CONCRETE, AND SHALL BE
SUPPORTED AT A MAXIMUM OF 3'-0" ON CENTER. CHAIRS GREATER THAN 2.5" IN SIZE SHALL BE STAPLED TO
THE FORMWORK.
17. ANCHORAGES SHALL BE RECESSED A MINIMUM OF TWO ANCHORS: (2) INCHES. PLACE TWO (2) CONTINUOUS #4
BARS BEHIND ALL ANCHORAGES, UNLESS NOTED OTHERWISE. REBAR SPLICES SHALL BE 24" MINIMUM AND
STAGGERED 5'-0" MINIMUM.
18. BLOCKOUTS: ALL POCKETS OR BLOCKOUTS REQUIRED FOR ANCHORAGE SHALL BE ADEQUATELY REINFORCED
SO AS NOT TO DECREASE THE STRENGTH OF THE STRUCTURE. ALL POCKETS SHOULD BE WATERPROOFED TO
ELIMINATE WATER LEAKAGE THROUGH OR INTO THE POCKET.
19. PIPES: PLASTIC OR METAL CONDUITS MAY BE EMBEDDED IN SLAB PROVIDING THAT THE FOLLOWING CRITERIA
ARE MET:
A. PIPES AND ELECTRICAL CONDUITS SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE
EXCEPT WHERE SPECIFICALLY APPROVED BY THE ENGINEER. MAXIMUM PIPE SIZE SHALL NOT
EXCEED THE LARGER OF ONE THIRD OF SLAB THICKNESS OR 2" DIA. LOCATE PIPES WITHIN THE
MIDDLE THIRD OF THE SLAB. MINIMUM SPACING SHALL BE SIX (6) TIMES THE PIPE DIAMETER.
PIPES SHALL NOT IMPAIR THE STRENGTH OF THE MEMBER. PROVIDE CONDUIT LAYOUT FOR
ENGINEER REVIEW AND APPROVAL.
B. CONDUITS MUST NOT INTERRUPT THE POST-TENSIONED CABLES.
C. COLUMN AREAS SHOULD BE AVOIDED.
D. IT IS UNDESIRABLE TO HAVE EXCESS AMOUNTS OF CONDUIT ENTERING THE SLAB FROM ONE
LOCATION. IF THIS CONDITION EXISTS, THE CONDUITS MUST BE FANNED OUT IMMEDIATELY.
20. PENETRATIONS: PENETRATIONS SHALL NOT BE PERMITTED IN BEAMS EXCEPT AS SHOWN IN P.T. DRAWINGS OR
TYPICAL DETAILS.
21. INSERTS: ALL INSERTS AND SLEEVES SHALL BE CAST IN PLACE WHENEVER POSSIBLE. DRILLED AND POWER-
DRIVEN FASTENERS WILL BE PERMITTED ONLY WHEN IT CAN BE SHOWN THAT THE INSERTS WILL NOT SPALL
THE CONCRETE AND ARE LOCATED TO AVOID THE TENDONS AND ANCHORAGES. THE CONTRACTOR MUST
LOCATE TENDONS ON THE SURFACE AND SOFFIT OF THE SLAB.
22. CHLORIDES: GROUT OR CONCRETE CONTAINING CHLORIDES SHALL NOT BE USED.
23. PUMPED CONCRETE: IF CONCRETE IS PLACED BY THE PUMP METHOD, THEN HORSES SHALL BE PROVIDED TO
SUPPORT THE HOSE. THE HOSE SHALL NOT BE ALLOWED TO RIDE ON THE TENDONS.
24. CONCRETE CONSOLIDATION: THE CONTRACTOR SHALL TAKE PRECAUTIONS TO ASSURE COMPLETE
CONSOLIDATION AND DENSIFICATION OF CONCRETE BEHIND ALL POST-TENSIONING ANCHORAGES.
25. AT TRANSFER OF CONCRETE STRENGTH AT STRESSING: PRESTRESS, CONCRETE SHALL BE 2,900 PSI MINIMUM
FOR ANY GIVEN CYLINDER COMPRESSION TEST. FOR MORE INFORMATION, SEE NOTES ON PLANS.
26. TENDON STRESSING: TENSIONING SHALL BE DONE BY JACKING UNDER IMMEDIATE CONTROL OF A PERSON
EXPERIENCED IN THIS TYPE OF WORK. CONTINUOUS INSPECTION AND RECORDING OF ELONGATIONS IS
REQUIRED DURING ALL STRESSING OPERATIONS.
27. CALIBRATION: THE RAM AND ATTENDANT GAUGE USED SHALL HAVE BEEN CALIBRATED WITHIN SIXTY (60) DAYS
OF THEIR USE.
28. STRESSING SEQUENCE: UNIFORMLY DISTRIBUTED TENDONS SHALL BE STRESSED BEFORE CONCENTRATED
BEAM STRIP (BANDED) TENDONS, AND SLAB TENDONS SHALL BE STRESSED BEFORE BEAM TENDONS.
29. ELONGATIONS: INDIVIDUAL TENDON FIELD READINGS OF ELONGATIONS AND/OR STRESSING FORCES SHALL
NOT VARY BY MORE THAN ±7% FROM CALCULATED REQUIRED VALUES SHOWN ON THE SHOP DRAWINGS. IF
THE MEASURED ELONGATIONS VARY FROM CALCULATED VALUES BY MORE THAN ±7%, THE CONTRACTOR
SHALL PROVIDE FRICTION CALCULATIONS AND/OR OTHER JUSTIFICATION TO THE SATISFACTION OF THE
ENGINEER.
30. MEMBER FORCES: THE POST-TENSIONED FORCE PROVIDED IN THE FIELD FOR EACH STRUCTURAL MEMBER
SHALL NOT BE LESS THAN THE VALUES NOTED ON THE STRUCTURAL DRAWINGS. IN THIS CONTEXT,
STRUCTURAL MEMBERS ARE BEAMS OR SLABS, WHETHER WITH BANDED OR DISTRIBUTED TENDONS, EACH
SERVING THEIR RESPECTIVE TRIBUTARY.
31. TENDON ENDS: DO NOT BURN OFF TENDON ENDS UNTIL THE ENTIRE FLOOR SYSTEM HAS BEEN
SATISFACTORILY STRESSED AND THE ENGINEER'S APPROVAL IS OBTAINED. THE STRESSING END ANCHORS
AND WEDGES SHALL BE SPRAY PAINTED WITH RUST-OLEUM OR A SIMILAR COATING FOR CORROSION
PROTECTION. INSTALL GREASE CAPS WITHIN THE FOLLOWING 24-HOUR PERIOD.
32. GROUTING OF STRESSING POCKETS: STRESSING POCKETS SHALL BE FILLED WITH NON-SHRINK GROUT AFTER
STRESSING, PAINTING & GREASE-CAPPING TO STOP MOISTURE PENETRATION.
33. DE-SHORING: SLABS OR BEAMS MAY BE DE-SHORED WHEN ALL TENDONS HAVE BEEN SATISFACTORILY
STRESSED AND THE ENGINEER'S APPROVAL IS OBTAINED, UNLESS SHORING IS REQUIRED TO CARRY FLOORS
ON ABOVE LEVELS.
POST-TENSIONING
1. SPECIFIED IN PROJECT CONCRETE PLACEMENT AND QUALITY: SPECIFICATIONS.
2. DEBRIS: REMOVE ALL DEBRIS FROM FORMS BEFORE POURING.
3. CONCRETE SHALL NOT BE SEGREGATION OF AGGREGATES: DROPPED THROUGH REINFORCING STEEL
(AS IN WALLS, COLUMNS AND DROP CAPITALS) SO AS TO CAUSE SEGREGATION OF AGGREGATES. USE
HOPPERS, CHUTES OR TRUNKS OF VARYING LENGTH SO THAT THE FREE UNCONFINED FALL OF
CONCRETE SHALL NOT EXCEED FIVE FEET, AND A SUFFICIENT NUMBER SHALL BE USED TO ENSURE
THAT THE CONCRETE IS KEPT LEVEL AT ALL TIMES.
4. INSERTS: ALL ITEMS TO BE CAST IN CONCRETE SUCH AS REINFORCING, DOWELS, BOLTS, ANCHORS,
PIPES, SLEEVES, ETC., SHALL BE SECURELY POSITIONED IN THE FORMS BEFORE PLACING THE
CONCRETE.
5. DOWELING: ALL WALLS AND COLUMNS SHALL BE DOWELED INTO FOOTINGS, WALLS, BEAMS, OR SLABS
WITH BARS OF THE SAME SIZE AND SPACING AS THE BARS ABOVE. USE A THIRTY SIX (36) BAR
DIAMETER LAP WHERE NOT SPECIFICALLY INDICATED ON PLANS OR DETAILS.
6. SPLICES: VERTICAL WALL BARS SHALL BE SPLICED AT OR NEAR FLOOR LINES. SPLICE BARS IN
MEMBERS SUCH AS SPANDRELS, BEAMS, ETC., AS FOLLOWS: TOP BARS AT CENTERLINE OF SPAN,
BOTTOM BARS AT THE SUPPORT. ALL REINFORCING STEEL SHALL BE SECURELY WIRED AND PROPERLY
SUPPORTED ABOVE GROUND AND AWAY FROM THE FORMS.
7. CONSTRUCTION JOINTS: CONSTRUCTION JOINTS SHALL HAVE ENTIRE SURFACE REMOVED TO EXPOSE
CLEAN, SOLIDLY EMBEDDED AGGREGATE. THE CONTRACTOR SHALL OBTAIN THE ENGINEER'S
APPROVAL OF CONSTRUCTION JOINT LOCATION IN SLABS AND BEAMS.
8. SHALL HAVE A TEMPERATURE AND SHRINKAGE REINFORCEMENT: LAP OF THIRTY (30) BAR DIAMETERS,
BUT NOT LESS THAN 18 INCHES, AND THE SPLICES IN ADJACENT BARS SHALL BE NOT LESS THAN FIVE
(5) FEET APART.
9. REBAR GRADES: ALL REINFORCING STEEL SHALL BE NEW STOCK DEFORMED BARS CONFORMING TO
ASTM A615 AS FOLLOWS:
• #9 AND SMALLER...............................GRADE 60
• #10 AND LARGER................................GRADE 75
10. WELDED WIRE FABRIC: WELDED WIRE FABRIC SHALL CONFORM TO ASTM A82 AND A185.
11. WELDING: TACK WELDING OF REBAR IS NOT PERMITTED UNLESS CALLED FOR OR APPROVED BY THE
ENGINEER.
12. REBAR COVER: MINIMUM REBAR COVER FOR PRESTRESSED CONCRETE SHALL BE AS SHOWN IN THIS
TABLE:
1. FOR USE IN CONCRETE:
A. THE STRUCTURAL ENGINEER MUST APPROVE ALL LOCATIONS WHERE EPOXY IS TO BE USED.
B. EPOXY: MUST BE HILTI HIT HY 150 INJECTION ADHESIVE ANCHOR OR TO BE APPROVED BY THE
STRUCTURAL ENGINEER PRIOR TO ITS USE.
C. THE CONCRETE, WHERE THE REINFORCING IS TO BE ATTACHED, MUST BE AT ITS DESIGN
STRENGTH OR HAS BEEN ALLOWED TO CURE FOR A MINIMUM OF 14 DAYS PRIOR TO
INSTALLATION.
D. THE INSTALLATION OF EPOXY ANCHORS MUST FOLLOW THE PROCEDURES SET IN THE
MANUFACTURERS INSTRUCTIONS.
E. THE EPOXY ANCHORS CANNOT BE USED TO RESIST VIBRATORY OR SHOCK LOADING OR BE
USED TO SUPPORT FIRE-RESISTIVE CONSTRUCTION.
F. SPECIAL INSPECTION MUST BE PROVIDED TO VERIFY THE DEPTH AND CLEANLINESS OF THE
DRILLED HOLE PRIOR TO INSTALLATION.
G. UNLESS OTHERWISE NOTED IN WRITING BY THE STRUCTURAL ENGINEER, PROOF TEST THE
FIRST THREE (3) BARS (BOLTS,ANCHORS), THEN EVERY FIFTH (5) BAR THEREAFTER AS PER THE
FOLLOWING SCHEDULE:
CONCRETE AND REINFORCEMENT
EPOXY EMBEDMENT OF REBAR AND ANCHOR BOLTS
INSPECTION AND TESTING:
1. OWNER WILL EMPLOY, AT HIS EXPENSE, AN INDEPENDENT TESTING LABORATORY TO
PERFORM A QUALITY ASSURANCE PROGRAM WHICH WILL EXECUTE THE REQUIRED
SPECIAL INSPECTIONS AS SET FORTH IN CHAPTER 17 OF THE INTERNATIONAL BUILDING
CODE AND ARE REPRODUCED BELOW.
SPECIAL INSPECTIONS
13. TOLERANCE FOR TOLERANCES FOR REBAR PLACEMENT: LONGITUDINAL LOCATION OF BENDS AND
ENDS OF REINFORCEMENT SHALL BE PLUS OR MINUS TWO (2) INCHES, EXCEPT AT DISCONTINUOUS
ENDS OF MEMBERS WHERE TOLERANCES SHALL BE ±1/2 INCH.
14. CONCRETE QUALITY: SHALL BE AS SHOWN IN TABLE BELOW:
EXPOSURE CONDITION MINIMUM COVER TOLERANCE (-)
CAST AGAINST AND PERMANENTLY
EXPOSED TO EARTH:
EXPOSED TO EARTH OR WEATHER:
NO. 5 AND SMALLER BARS
NO. 6 AND LARGER BARS
NOTE EXPOSED TO WEATHER OR IN
CONTACT WITH THE GROUND:
STRUCTURAL SLABS & WALLS
BEAMS AND COLUMNS
(PRIMARY REINFORCEMENT, TIES,
STIRRUPS & SPIRALS)
SLABS ON GRADE
3"
1 1/2"
2"
1 1/2"
1 1/2"
1 1/2"
3/8"
1/4"
1/4"
1/8"
1/4"
1/4"
15. CONCRETE MIX DESIGN:
• CONCRETE SHALL BE DESIGNED IN ACCORDANCE WITH STANDARD RECOMMENDED
PRACTICES FOR SELECTING PROPORTIONS FOR CONCRETE, ACI 221. THE LABORATORY,
AGENCY, OR READY-MIX PLANT SHALL MEET APPLICABLE REQUIREMENTS OF ASTM E329, AND
SHALL BE APPROVED BY THE ENGINEER.
16. ALL CONCRETE SHALL BE OF REGULAR WEIGHT CONCRETE WEIGHT: OF 150 POUNDS PER CUBIC FOOT
UNLESS NOTED OTHERWISE.
17. SIZE OF AGGREGATE SHALL CONFORM TO ASTM AGGREGATE: C33-85.
• 3/4".......................................ASTM SIZE C67
• 1"...........................................ASTM SIZE C57
18. CEMENT:SHALL BE TYPE II.
19. NO MORE THAN 90 MINUTES SHALL ELAPSE CONCRETE AGE: BETWEEN CONCRETE BATCHING AND
CONCRETE PLACEMENT UNLESS APPROVED BY TESTING AGENCY.
20. REINFORCEMENT MAY NOT BE WET SET IN CONCRETE WET SET: POURS.
21. ROUGHENED SURFACES: WHERE INDICATED ON THE DRAWINGS, ROUGHENED SURFACES SHALL BE
PROVIDED BY MEANS OF HEAVY RAKING OR GROOVING. OTHER METHODS MAY BE ACCEPTABLE
PENDING WRITTEN APPROVAL FROM THE ENGINEER. ALL INTERFACING SURFACES MUST BE CLEAN
AND FREE OF LOOSE MATERIALS.
22. NO ADMIXTURES SHALL BE ADDED TO THE CONCRETE ADMIXTURES: MIX WITHOUT THE APPROVAL OF
THE ENGINEER, UNLESS NOTED OTHERWISE. ADMIXTURES OR CONCRETE CONTAINING CHLORIDES
SHALL NOT BE USED IN THE POST-TENSIONED SLABS.
CONSTRUCTION USE STRENGTH AT 28
DAYS U.N.O
SLUMP AIR AGGREGATE
SIZE
AGGREGATE
TYPE
SUSPENDED POST-TENSIONED SLABS
3750 @ 3
5000 @28
4" 3% 1" HARDROCK
GRADE 60
REINFORCING BAR
EMBEDMENT DEPTH/
CONCRETE STRENGTH LOAD TEST (lbs)
#4 8"
3000 psi
6 1/2" 5,000
3000 psi 3000 psi
6 1/2"
#5
#6
#7
#8
#9
8,000
10,000
11,000
13,000
18,000
12" 9" 9"
15" 11" 11"
17" 13" 13"
19" 15" 15"
21" 17" 17"
ALL VALUES NOTED ABOVE ARE SUBJECT TO CHANGE DEPENDING ON THE MATERIAL SPECIFICATIONS.
ALL VALUES MUST BE CONFIRMED WITH THE STRUCTURAL ENGINEER PRIOR TO USE.
IBC 2012 TABLE 1705.3
REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC REFERNCED STANDARD IBC REFERENCE
1. INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING
TENDONS, AND PLACEMENT.
2. INSPECTION OF REINFORCING STEEL WELDING IN ACCORDANCE
WITH TABLE 1705.2.2, ITEM 2B.
3. INSPECTION OF ANCHORS CAST IN CONCRETE WHERE
ALLOWABLE LOADS HAVE BEEN INCREASED OR WHERE
STRENGTH DESIGN IS USED.
4. INSPECTION OF ANCHORS POST-INSTALLED IN HARDENED
CONCRETE MEMBERS.
5. VERIFYING USE OF REQUIRED MIX DESIGN.
6. AT THE TIME FRESH CONCRETE IS SAMPLED TO FABRICATE
SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP AND AIR
CONTENT TESTS, AND DETERMINE THE TEMPERATURE OF THE
CONCRETE.
7. INSPECTION OF CONCRETE AND SHOTCRETE PLACEMENT FOR
PROPER APPLICATION TECHNIQUES.
8. INSPECTION FOR MAINTENANCE OF SPECIFIED CURING
TEMPERATURE AND TECHNIQUES.
9. INSPECTION OF PRESTRESSED CONCRETE:
A. APPLICATION OF PRESTRESSING FORCES
B. GROUTING OF BONDED PRESTRESSING TENDONS IN
THE SEISMIC FORCE-RESISTING SYSTEM
10. ERECTION OF PRECAST CONCRETE MEMBERS.
11. VERIFICATION OF IN-SITU CONCRETE STRENGTH, PRIOR TO
STRESSING OF TENDONS IN POST-TENSIONED CONCRETE AND
PRIOR TO REMOVAL OF SHORES AND FORMS FROM BEAMS AND
STRUCTURAL SLABS.
12. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF
THE CONCRETE MEMBER BEING FORMED.
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X
X
X
X
X
X
X
X
X
X
X
X
-
-
-
-
-
-
ACI 318: 3.5, 7.1-7.7
AWS D1.4, ACI 318: 3.5.2
ACI 318: 8.1.3, 21.1.8
ACI 318: 3.8.6, 8.1.3, 21.1.8
ACI 318: CH. 4, 5.2-5.4
ASTM C 172, ASTM C 31,
ACI 318: 5.6, 5.8
ACI 318: 5.9, 5.10
ACI 318: 5.11-5.13
ACI 318: 18.20
ACI 318: 18.18.4
ACI 318: 6.2
ACI 318: 6.2
ACI 318: 6.1.1
1910.4
1908.5, 1909.1
1909.1
1904.2, 1910.2, 1910.3
1910.10
1910.6, 1910.7, 1910.8
1910.9