HomeMy WebLinkAboutS300-G-TYPICAL-FOUNDATION-DETAIL5-Rev.2CONTROL JOINTS SHALL BE SAWN NOT LATER THAN THE FOLLOWING TABLE, OR 16 HOURS AFTER FINAL TROWELING (WHICHEVER IS LESS), WHERE TEMP EQUALS THE AMBIENT TEMPERATURE IN DEGREES FAHRENHEIT AT THEN TIME OF FINAL TROWELING. SAWCUTTING SHALL BE SUSPENDED ONLY IF THE LARGE AGGREGATE IS DISLODGED OR LOOSENED. ALTERNATE: USE PRE-FORMED JOINT FORMER. TEMP, DEG. F TIME, HOURS 40 50 60 70 80 90 < 16 14 8 1/2 5 1/2 4 3 SLAB "t" PER PLAN 1/8" W. X 1/4 SLAB "t" IN UNEXPOSED AREAS WHERE JOINTS WILL NOT BE FILLED. 1/4" W. X 1/4 SLAB "t" WET SAWCUT - SEE TABLE BELOW F.F. PER PLAN TOOL OR CHASE w/ SAWCUT SIM. TO CONTROL JOINT SLAB "t" PER PLAN 8" 2 '- 0" FORMED KEYWAY W/ 3/4" DIA. x 18" LONG SMOOT DOWELS @ 18" O.C., GREASE ONE END FOR BOND BREAK PROVIDE CONSTRUCTION JOINT IN LIEU OF CONTROL JOINT AT TERMINATION OF POUR 2 '- 0" 3/4" CHAMFER, TYPICAL HOUSEKEEPING PAD - SIZE, LOCATION & HT. PER MEP DRAWINGS #4 @ 12" O.C. EACH WAY #4 w/ 6" HORIZ. LEGS @ 4'-0" O.C. (MIN. 1 PER CORNER) 1'-0" MIN. 1'-0" MIN. 1'-0" MIN. 1'-0" MIN. 1'-0" MIN. 8" 8" F.F. PER PLAN F.F. PER PLAN F.F. PER PLAN F.F. PER PLAN F.F. PER PLAN F.F. PER PLAN DEPTH OF RECESS/STEP OR DEPRESSION DEPTH OF RECESS/STEP OR DEPRESSION DEPTH OF RECESS/STEP OR DEPRESSION + SLAB THICKNESS FORMED KEYWAY CONCRETE SLAB ON GRADE PER PLAN FORMED KEYWAY CONCRETE SLAB ON GRADE PER PLAN CONCRETE SLAB ON GRADE PER PLAN 2" MAX. W.W.F. TO BE DEPRESSED OR LAPPED AT DEPRESSIONS REFER TO ARCH. PLANS & ROOM FINISH SCHEDULES FOR LOCATION, & DEPTH OF RECESSED SLABS. SECOND POUR FIRST POUR 36 BAR DIA. LAP INTERIOR FACE COLD-JOINT WATERSTOP FOR BASEMENT/RETAINING WALLS FORMED KEYWAY EXTERIOR FACE SECOND POUR FIRST POUR 36 BAR DIA. LAP INTERIOR FACE COLD-JOINT WATERSTOP FOR BASEMENT/RETAINING WALLS FORMED KEYWAY EXTERIOR FACE EXTERIOR FACE INTERIOR FACE 36 DIA. 36 DIA. #5 @ 12" O.C. NOTE: AT "TEES" PROVIDE TWO HOOKED BARS NOTE: PROVIDE SIMILAR CORNER BARS FOR CONC. WALLS WITH ONE LAYER OF REINFORCEMENT. LOCATE ON OUTSIDE FACE & PROVIDE (3) #4 VERT'S FOR SUPPORT 36 DIA. 36 DIA. 36 DIA. PIPE SLEEVE 3" LARGER THAN PIPE DIAMETER LOOSE INSULATION SEE STEPPED FOOTING DETAIL CONTIN. FOOTING REINF. PER NOTES: SECTIONS/SCHEDULE 1. REFER TO PLUMBING DRAWINGS FOR INVERT ELEVATOIN OF ALL UNDERGROUND PIPING. 2. STEP FOOTING FOR PIPE PENETRATION THROUGH FOUNDATION WALL UNLESS WRITTEN PERMISSION IS OBTAINED FROM THE MEP ENGINEER. 3. PROVIDE PRECAST OR BOND BEAM LINTEL FOR MULTIPLE PENETRATIONS OR OPENINGS GREATER THAN 24" IN WIDTH. COLUMN OR WALL FOOTING 1'-6" REFER TO M.E.P. DRAWINGS & SPECIFICATIONS FOR INFO. RELATING TO TRENCH EXCAVATION, BEDDING, AND BACKFILL FOR ANY EXCAVATION THAT MUST EXTEND BEYOND THIS LINE, SHORING MUST BE PROVIDED TO KEEP THE EXCAVATION FROM UNDERMINING THE FOUNDATIONS. 1V 1.5H NOTE: ANY SHORING SCHEME REQUIRED MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW, PRIOR TO EXCAVATION. PROTECTED ZONE SECOND POUR FIRST POUR 36 BAR DIA. LAP FORMED KEYWAY 1/3 1/3 1/3 FTG. DEPTH PER SECTIONS (2) #5 x 3'-0" LONG AT JOINT 1' - 6" 3" 12" HORIZ. LEG TYPICAL CONTINUOUS FTG. REINF. PER SECTIONS FTG. DEPTH PER SECTIONS MAINTAIN MIN. 6" OF CONCRETE COVER ALL AROUND BARS TO MATCH FTG. REINF. w/ (4) #4 TRANSVERSE BARS x FOOTING WIDTH - 6" PIPE SLEEVE 3" LARGER THAN PIPE DIAMETER LOOSE INSULATION NOTES: 1. REFER TO PLUMBING DRAWINGS FOR INVERT ELEVATION OF ALL UNDERGROUND PIPING. 2. PROVIDE THIS DETAIL WHERE A PENETRATION THROUGH A WALL FOOTING IS UNAVOIDABLE. 3. NO SLEEVES IN COLUMN FOOTINGS ARE PERMITTED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER. 1. REFER TO THE SPECIFICATIONS FOR APPLICATION OF UNIT COSTS FOR REMOVAL OF UNSUITABLE BEARING MATERIAL & REPLACEMENT WITH COMPACTED, ENGINEERED FILL 2. REFER TO THE GEOTECHNICAL ENGINEERING REPORT FOR ADDITIONAL INFORMATION RE: EXPECTED SOIL CONDITIONS, SUITABILITY OF EX. SOILS FOR USE AS ENGINEERED FILL, GROUNDWATER CONDITIONS, ETC. 1 1 2 SEE NOTE ABOVE 1 2 SEE NOTE ABOVE 1 SUITABLE BEARING MATERIAL AS DETERMINED BY TESTING AGENCY COMPACTED/ENGINEERED FILL REFERENCE EARTHWORK SPECS. & GEOTECHNICAL INVESTIGATION BOTTOM/FOOTING ELEVATION SLOPE OF EXCAVATION TO CONFORM WITH APPLICABLE REQUIREMENTS OF OSHA AND/OR STATE & LOCAL CODES STRUCTURAL COLUMN OR WALL FOOTING PROPOSED GRADE NOTE: 1. REFER TO THE SPECIFICATIONS FOR APPLICATION OF UNIT COSTS FOR REMOVAL OF UNSUITABLE BEARING MATERIAL & REPLACEMENT WITH LEAN CONCRETE FILL. 2. REFER TO THE GEOTECHNICAL ENGINEERING REPORT FOR ADDITIONAL INFORMATION RE: EXPECTED SOIL CONDITIONS, SUITABILITY OF EX. SOILS FOR USE AS ENGINEERED FILL, GROUNDWATER CONDITIONS, ETC. NOTE: MAX. DEPTH OF UNSHEETED/UNSHORED EXCAVATION TO CONFORM WITH THE APPLICABLE REQUIREMENTS OF OSHA AND/OR STATE & LOCAL CODES STRUCTURAL COLUMN OR WALL FOOTING PROPOSED GRADE LEAN CONCRETE FILL (MIN. 2000 PSI @ 28 DAYS) BOTTOM/FOOTING EXCAVATION WRAP BASE OF COLUMN w/ 1/2" ISOLATION JOINT MATERIAL & CAULK OUTLINE OF BASE PLATE BELOW IN AREAS SUBJECT TO HIGH MOISTURE CONDITIONS, SUCH AS BELOW GRADE APPLICATIONS, THICKEN SLAB TO 8" MIN. SUBSTITUTE A COLD-JOINT WATERSTOP FOR THE 1/2" ISOLATION MATERIAL. NOTE: THIS DETAIL SHOULD BE USED IN LIEU OF A DIAMOND OR ROUND ISOLATION JOINT TO PREVENT TELEGRAPHING THROUGH FINISH FLOOR MATERIALS SUCH AS THIN-SET TERRAZZO, CERAMIC TILE, VINYL TILE, ETC. SOME MINOR RANDOM SHRINKAGE CRACKS SHOULD BE ANTICIPATED. DETAIL IS SIMILAR AT WIDE-FLANGE COLUMNS. SLAB CONTROL JOINTS - SEE GENERAL NOTES, DTL. THIS SHEET, & FDN. PLAN FOR LOC'N. SLAB CONTROL JOINTS - SEE GENERAL NOTES, DTL. THIS SHEET, & FDN. PLAN FOR LOC'N. COLUMN BLOCKOUT SECONDARY POUR 2'-0" OR AS REQ'D. WRAP BASE OF COLUMN w/ 1/2" ISOLATION JOINT MATERIAL & CAULK ISOLATION JOINT - 1/2" PREFORMED JOINT MATERIAL OUTLINE OF BASE PLATE BELOW IN AREAS SUBJECT TO HIGH MOISTURE CONDITIONS, SUCH AS BELOW GRADE APPLICATIONS, THICKEN SLAB TO 8" MIN. SUBSTITUTE A COLD-JOINT WATERSTOP FOR THE 1/2" ISOLATION MATERIAL. 1. TUBE COLUMN SHOWN FOR ILLUSTRATIVE PURPOSES ONLY. WIDE FLANGES, PIPES, AND OTHER STEEL SHAPES ARE SIMILAR. 2. ADJUST 2'-0" DIMENSION AS REQUIRED TO ACCOMMODATE COLUMN BASE PLATES AND GROUTING PROCEDURES. 3. WHERE THIN-SET EPOXY TERRAZZO OR VINYL SHEET GOODS ARE THE SCHEDULED FLOOR FINISH, ELIMINATE THE DIAMOND-SHAPED ISOLATION JOINT AND EXTEND THE CONTROL JOINTS TO THE COLUMN. S300-G SCALE: NONE 1 SLAB CONTROL/CONTRACTION JOINT S300-G SCALE: NONE 2 SLAB CONSTRUCTION JOINT S300-G SCALE: NONE 3 MECHANICAL EQUIPMENT PAD DETAIL S300-G SCALE: NONE 6 RECESSED SLAB DETAIL S300-G SCALE: NONE 7 CIP WALL CONSTRUCTION JOINTS S300-G SCALE: NONE 10 CIP WALL CORNER REINF. DETAIL S300-G SCALE: NONE 8 CMU FOUNDATION WALL SLEEVE S300-G SCALE: NONE 4 EXCAVATION LIMITS DETAIL S300-G SCALE: NONE 5 WALL FOOTING CONSTRUCTION JOINT S300-G SCALE: NONE 9 WALL FOOTING SLEEVE DETAIL SHEET PROJECT INFO SEAL REVISIONS DRAWING TITLE PROJECT ARCHITECT MERCHANTS CORPORATE CENTER CARMEL, IN CLIENT # DESCRIPTION DATE NOVEMBER 10, 2017 17104 ISSUED FOR CONSTRUCTION 2017-11-10 S300-G TYPICAL FOUNDATION DETAILS S300-G SCALE: 3/4" = 1'-0" 13 OVEREXCAVATION DETAIL - ENGINEERED FILL S300-G SCALE: 3/4" = 1'-0" 14 OVEREXCAVATION DETAIL - LEAN CONC. FILL S300-G SCALE: 3/4" = 1'-0" 11 COLUMN ISOLATION JOINT DETAIL S300-G SCALE: 3/4" = 1'-0" 12 COLUMN ISOLATION JOINT DETAIL 05/01/18 Nick Mishler