DEEM PROJECT NUMBER:
DATE:
DRAWING TITLE:
DRAWING NUMBER:
REVISIONS:
DRAWN BY:
CLIENT PROJECT NUMBER:
201 N. Delaware Street, Suite B
Indianapolis, IN 46204
317.951.9192 T | 317.951.9194 F
www.arcdesign.us
This drawing and its contents are the property
of arcDESIGN P.C., and shall not be
reproduced in whole or in part by any means,
mechanical or electronic, without express
written permission of arcDESIGN.
CERTIFICATION:
4/3/2018 12:29:38 PM C:\Projects\CAD Files\17040 - St. Vincent - Firestone Bldg\40-Revit (ConDocs)\17040 - StVincent_Firestone_ELEC_17.rvt
ASCENSION | ST. VINCENT
E604
PANEL
SCHEDULES
17040
09.22.2017
PERMIT SET
INDIANAPOIS - ST. VINCENT HEALTH
ADMINISTRATION OFFICE
250 W. 96TH STREET - PARKWOOD BUILDING
INDIANAPOLIS, IN 46260
B.C.D.
1 2017.10.24 OWNER REVIEW
2 2017.11.15 CONSTRUCTION ISSUE
3 2017.11.28 REVISED CONSTRUCTION
ISSUE
14 2018.03.27 REVISED FLOOR PLAN
Notes:
Total Est. Demand: 61 A
Furniture Partitions 1500 VA 100.00% 1500 VA Total Conn.: 61 A
Power 7500 VA 100.00% 7500 VA Total Est. Demand: 21.8 kVA
Receptacle 9800 VA 100.00% 9800 VA Total Conn. Load: 21.8 kVA
Other 3000 VA 100.00% 3000 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Breaker Accessories (ACC):
BL = Breaker Lock / FA = Fire Alarm Circuit Breaker / GF = 30 mA GFCI Circuit Breaker
Legend:
Total Amps: 57 A 64 A 62 A
Total Load: 6.9 7.6 7.4
41 0.5 / 0.4 1 20 A Receptacles - Stat / Flight 42
39 0.5 / 0.2 40
37
Floor Boxes - Transfer
Center
20 A 3
0.5 / 0.2 38
35 0.3 / 0.2
3 20 A AVASYS Workstations
36
33 0.3 / 0.2 34
31
AVASYS Workstations 20 A 3
0.3 / 0.2 32
29 0.3 / 0.2
3 20 A AVASYS Workstations
30
27 0.3 / 0.4 1 20 A Monitors on Bulkhead 28
25
AVASYS Workstations 20 A 3
0.3 / 0.4 1 20 A Monitors on Bulkhead 26
23 0.3 / 0.5 1 20 A Furniture - Open Office 24
21 0.3 / 1.0 22
19
AVASYS Workstations 20 A 3
0.3 / 1.8 20
17 0.7 / 0.9
3 100 A
Panels 'DP-1', 'DP2', 'DP-4',
'DP-5'
18
15 0.7 / 1.3 1 20 A Receps - 2nd Fl. Meeting 16
13
Furniture Partitions - Call
Center
20 A 3
0.7 / 0.7 1 20 A Receptacles - Offices 14
11 0.7 / 1.7 1 20 A Receptacles - Offices 12
9 0.7 / 1.3 1 20 A Receptacles - Training 125 10
7
Furniture Partitions - Call
Center
20 A 3
0.7 / 0.4 1 20 A Monitor Receps - Telemetry 8
5 0.3 / 0.4 1 20 A Monitor Receps - Telemetry 6
3 0.3 / 0.2 1 20 A Receptacle - Data Room 4
1
Furniture Partitions - Call
Center
20 A 3
0.3 / 0.2 1 20 A Receptacle 2
CKT Circuit Description ACC Trip Poles
AΦ
(kVA)
BΦ
(kVA)
CΦ
(kVA)
Poles Trip ACC Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Recessed Wires: 4 Bus Rating: 225 A
Supply From: UPS-1 Phases: 3 Mains Type: MCB
Location: DATA ROOM 104 Volts: 120/208 Wye A.I.C. Rating: 22 k
Panelboard: PDU-1
Notes:
Total Est. Demand: 10 A
Total Conn.: 10 A
Total Est. Demand: 3.7 kVA
Total Conn. Load: 3.7 kVA
Receptacle 3680 VA 100.00% 3680 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Breaker Accessories (ACC):
BL = Breaker Lock / FA = Fire Alarm Circuit Breaker / GF = 30 mA GFCI Circuit Breaker
Legend:
Total Amps: 8 A 15 A 8 A
Total Load: 0.9 1.8 1.0
17 18
15 16
13 14
11 12
9 10
7 0.3 / 0.3 8
5 L6-20 Receptacle in Data
Room
20 A 2
0.3 / 0.8 6
3 0.3 / 1.5
3 100 A Panel 'DP-2'
4
1 L6-20 Receptacle in Data
Room
20 A 2
0.3 / 0.2 1 20 A Receptacle @ Demarc 2
CKT Circuit Description ACC Trip Poles
AΦ
(kVA)
BΦ
(kVA)
CΦ
(kVA)
Poles Trip ACC Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wires: 4 Bus Rating: 100 A
Supply From: PDU-1 Phases: 3 Mains Type: MLO
Location: DATA EXP. 132 Volts: 120/208 Wye A.I.C. Rating: 10 kA
Panelboard: DP-1
Notes:
Total Est. Demand: 7 A
Total Conn.: 7 A
Total Est. Demand: 2.5 kVA
Total Conn. Load: 2.5 kVA
Receptacle 2500 VA 100.00% 2500 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Breaker Accessories (ACC):
BL = Breaker Lock / FA = Fire Alarm Circuit Breaker / GF = 30 mA GFCI Circuit Breaker
Legend:
Total Amps: 13 A 7 A 2 A
Total Load: 1.5 0.8 0.3
17 18
15 16
13 14
11 12
9 10
7 8
5 0.0 / 0.3 6
3 0.3 / 0.5 4
1 L6-20 Receptacle in Data
Room
20 A 2
0.3 / 1.3
3 100 A Panel 'DP-4'
2
CKT Circuit Description ACC Trip Poles
AΦ
(kVA)
BΦ
(kVA)
CΦ
(kVA)
Poles Trip ACC Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Recessed Wires: 4 Bus Rating: 100 A
Supply From: DP-1 Phases: 3 Mains Type: MLO
Location: SUPPORT 231 Volts: 120/208 Wye A.I.C. Rating: 10 kA
Panelboard: DP-2
Notes:
Total Est. Demand: 6 A
Total Conn.: 6 A
Total Est. Demand: 2.0 kVA
Total Conn. Load: 2.0 kVA
Receptacle 2000 VA 100.00% 2000 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Breaker Accessories (ACC):
BL = Breaker Lock / FA = Fire Alarm Circuit Breaker / GF = 30 mA GFCI Circuit Breaker
Legend:
Total Amps: 11 A 4 A 2 A
Total Load: 1.3 0.5 0.3
17 18
15 16
13 14
11 12
9 10
7 0.0 / 0.0 8
5 0.3 / 0.0 6
3
Panel 'DP-5' 100 A 3
0.3 / 0.3 4
1 A-V Rack Receptacles 20 A 1 1.0 / 0.3
2 20 A
L6-20 Receptacle in Data
Room
2
CKT Circuit Description ACC Trip Poles
AΦ
(kVA)
BΦ
(kVA)
CΦ
(kVA)
Poles Trip ACC Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wires: 4 Bus Rating: 100 A
Supply From: DP-2 Phases: 3 Mains Type: MLO
Location: DATA 421 Volts: 120/208 Wye A.I.C. Rating: 10 kA
Panelboard: DP-4
Notes:
Total Est. Demand: 1 A
Total Conn.: 1 A
Total Est. Demand: 0.5 kVA
Total Conn. Load: 0.5 kVA
Receptacle 500 VA 100.00% 500 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Breaker Accessories (ACC):
BL = Breaker Lock / FA = Fire Alarm Circuit Breaker / GF = 30 mA GFCI Circuit Breaker
Legend:
Total Amps: 2 A 2 A 0 A
Total Load: 0.3 0.3 0.0
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 0.3 / 0.0 4
1 L6-20 Receptacle in Data
Room
20 A 2
0.3 / 0.0 2
CKT Circuit Description ACC Trip Poles
AΦ
(kVA)
BΦ
(kVA)
CΦ
(kVA)
Poles Trip ACC Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wires: 4 Bus Rating: 100 A
Supply From: DP-4 Phases: 3 Mains Type: MLO
Location: DATA 540 Volts: 120/208 Wye A.I.C. Rating: 10 kA
Panelboard: DP-5
3
3
3
14
14
Notes:
Total Est. Demand: 13 A
Total Conn.: 12 A
Furniture Partitions 1000 VA 100.00% 1000 VA Total Est. Demand: 4.8 kVA
Lighting 1440 VA 125.00% 1800 VA Total Conn. Load: 4.4 kVA
Power 2000 VA 100.00% 2000 VA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
Breaker Accessories (ACC):
BL = Breaker Lock / FA = Fire Alarm Circuit Breaker / GF = 30 mA GFCI Circuit Breaker
Legend:
Total Amps: 20 A 8 A 8 A
Total Load: 2.4 1.0 1.0
41 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 42
39 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 40
37 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 38
35 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 36
33 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 34
31 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 32
29 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 30
27 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 28
25 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 26
23 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 24
21 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 22
19 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 20
17 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 18
15 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 16
13 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 14
11 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 12
9 SPARE 20 A 1 0.0 / 0.0 1 20 A SPARE 10
7 SPARE 20 A 1 0.0 / 0.7 8
5 0.3 / 0.7 6
3 0.3 / 0.7
3 20 A Furniture Partitions
4
1
Furniture Partitions 20 A 3
0.3 / 1.4 1 20 A Lighting 2
CKT Circuit Description ACC Trip Poles
AΦ
(kVA)
BΦ
(kVA)
CΦ
(kVA)
Poles Trip ACC Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Recessed Wires: 4 Bus Rating: 200 A
Supply From: Phases: 3 Mains Type: MCB
Location: DATA ROOM 104 Volts: 120/208 Wye A.I.C. Rating:
Panelboard: PDU-2 14
05/01/18
Nick Mishler