HomeMy WebLinkAboutG0.3 Life SafetyLEVEL
COMMON PATH OF TRAVEL = 11'-6"
2 1
3
4
4
5
5
5
6
27'-1"
25'-11"
EGRESS WIDTH = 36"
DOOR CAPACITY = 48 PERSONS
OVERALL TRAVEL DISTANCE = 35'-11"
7
LIFE SAFETY PLAN
A. 36 INCHES REQUIRED AISLE WIDTH MINIMUM. IBC SEC 1017.3.
B. ONE EXIT OR ACCESS DOORWAY REQUIRED FOR B,M USES UNDER 50 OCCUPANTS. IBC TABLE
1015.1
C. NO DEAD END CORRIDORS OVER 20'-0" IN LENGTH. (50'-0" ALLOWED FOR B, M USE WITH FULLY
AUTOMATED SPRINKLER SYSTEM). IBC SEC 1018.4
D. MAXIMUM COMMON PATH TRAVEL DISTANCE TO AN EXIT IS 75'-0". MEASURED AT THE MOST
REMOTE POINT ALONG THE NATURAL AND UNOBSTRUCTED PATH OF HORIZONTAL AND VERTICAL
TRAVEL TO THE EXIT FOR A SPACE WITH MORE THAN 1 EGRESS. FOR B, S OCCUPANCIES, WHERE
THE SPACE IS PROVIDED WITH A FULLY AUTOMATED SPRINKLER SYSTEM, THE MAXIMUM DISTANCE
IS 100'-0". IBC TABLE 1014.3
E. MAXIMUM EXIT ACCESS TRAVEL DISTANCE IS 250'-0" WITH SPRINKLERS. (M USE), AND 300'-0"
WITH SPRINKLERS (B USE). IBC TABLE 1016.2
F. WALKING SURFACES THAT ARE PART OF AN ACCESSIBLE ROUTE SHALL COMPLY WITH 2010 ADA SEC
403.
G. TRANSITIONS AT DOORWAYS AND BETWEEN FLOORING MATERIALS SHALL NOT BE GREATER THAN
1/2". 2010 ADA SEC 404.2.5
H. DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED MEANS OF EGRESS WIDTH BY
MORE THAN 7 INCHES. DOORS IN ANY POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY
MORE THAN ONE HALF. IBC SEC 1005.7.1.
LIFE SAFETY GENERAL NOTES
CODED NOTES X
1. LEASE LINE.
2. PROPOSED FIRE EXTINGUISHER LOCATION.
3. EXISTING ELECTRIC PANEL AND TRANSFORMER
LOCATION. REFER TO ELECTRICAL DRAWINGS.
4. ADJACENT TENANT, N.I.C.
5. EXISTING 1-HR RATED DEMISING WALL.
6. EMERGENCY LIGHTING. REFER TO MEP
DRAWINGS.
7. EXISTING STRUCTURAL COLUMN TO REMAIN.
FIRE EXTINGUISHER NOTES
1. G.C. TO PROVIDE MIN. OF 1 FIRE EXTINGUISHERS. G.C. TO VERIFY AND COORDINATE LOCATIONS
AND QUANTITIES WITH LOCAL FIRE MARSHAL.
2. PER IFC, THE MINIMUM IS A 2A10BC EXTINGUISHER WITHIN 75' OF TRAVEL DISTANCE OF ALL
AREAS.
3. NFPA INSPECTION TAGS SHALL BE ATTACHED TO ALL FIRE EXTINGUISHERS.
CALCULATIONS
743 S.F.
743 S.F.
LEASE AREA
LEASE AREA CALCULATIONS
F30A (MERCANTILE) 1 : 30 SF 25
CODE COMPLIANCE
MEANS OF EGRESS - INDIANA BLDG CODE (IBC 2006)
1 MEANS OF EGRESS
1 MEANS OF EGRESS
MEANS OF EGRESS - REQUIRED
EACH SPACE PROVIDED
75'-0"
(FULLY SPRINKLERED)
35'-11"
MAX COMMON PATH OF TRAVEL
ALLOWED
PROVIDED
FIRE-RESISTANCE RATINGS -
(TYPE IIB, SPRINKLERED)
EXISTING DEMISING
WALLS -
1 HR RATED
LEGEND
36" CLEAR FLOOR SPACE
DIRECTION OF TRAVEL
14390 CLAY TERRACE BLVD re d
CARMEL, INDIANA 46032
WPG007
SPACE F30A - LANDLORD IMPROVEMENTS
PROJECT NUMBER:
SHEET:
FOR
WASHINGTON PRIME GROUP
180 EAST BROAD STREET, COLUMBUS, OH 43215
ISSUE DATE
PERMIT FEB. 01, 2018
COPYRIGHT 2018. ALL DRAWINGS
AND SPECIFICATIONS SHALL
REMAIN THE PROPERTY OF RED
ARCHITECTURE + PLANNING LLC
AND MAY NOT BE USED,
DUPLICATED OR ALTERED
WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT.
G0.3
2/10/2017 10:16 AM
G0.3
LIFE SAFETY PLAN
1/4" = 1'-0"
1
04/30/18
Nick Mishler