Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
04080104 Building Plans
ARCHITECTURAL: T1 TITLE SHEET D1 DEMOLITION PLAN Al EAST ARCHITECTURAL PLAN RC1 DESIGN/BUILD EAST REFLECTED CEILING PLAN ELECTRICAL: EO ELECTRICAL SPECIFICATIONS E1 ELECTRICAL PLAN MECHANICAL: MO MECHANICAL SPECIFICATIONS M1 MECHANICAL PLANS � Re9'tas' ka bpd cE sesta �1't`l SOWS OF 1001GPRMNp1P ' 01w -.1 al�jf�mmj c Sitte:40 SO f50 AVAILABLE REPUBLIC BAR AVAILABLE 3 1 5 ?`.: 1,513RSF 133( ?SF BUILDING 3105 z BUILDING PLAN SCALE:1,16 1-0 APPROVAL CONSTRUCTION WORK SHALL NOT PROCEED UNTIL OWNER & TENANT HAVE GIVEN THEIR APPROVAL TO THESE WORKING DRAWINGS. APPROVAL BY THESE PARTIES SHALL BE INTERPRETED AS APPROVAL OF THE DRAWINGS FOR CONTENT, SCOPE OF WORK AND ALL DIMENSIONS REGARDED BY EITHER PARTY AS BEING NECESSARY TO THEIR OPERATIONS, USE OF SPACE FURNITURE/EOUIPMENT INSTALLATION, AND ANY AGREEMANTS BETWEEN THE OWNER AND TENANT. CONSTRUCTION AND/OR INTENTION OF CONSTRUCTION AUTHORIZED BY THE OWNER FROM THESE WORKING DRAWINGS SHALL BE INTERPRETED BY THE DESIGNER AS APPROVAL IN FULL OF THESE WORKING DRAWINGS BY BOTH OWNER AND TENANT. TENANT: DATE: OWNER: : DATE: CONTACTS: BUILDING OWNER: CHASNEY SUSKOUICH AMERIVEST PROPERTIES INC. 3095 E. 98TH STREET INDIANAPOLIS, INDIANA 46280 PHONE: (317)574-1400 FAX: (317)574-1414 GENERAL CONTRACTOR: TO BE DETERMINED ARCHITECT/DESIGNER: RENEE'STROUD DESIGN/APPLICATIONS, INC. 118 W. LORETfA DRIVE INDIANAPOLIS, INDIANA 46217 PHONE: (317)782-8957 FAX: (317)782-0976 MECHANICAL/ELECTRICAL: MARK FROST FROST ENGINEERS 920 NORTH SHADELAND AVE., SUITE G -11A INDIANAPOLIS, INDIANA 46219 PHONE: (317)359-0901 FAX: (317)359-0902 CODE INFORMATION BUILDING CODE SUMMARY BASE BUILDING: BUILDING ADDRESS: CODE JURISDICTIONS BUILDING: FIRE: CODE SUMMARY 3105 BUILDING 3105 E. 98TH STREET INDIANAPOLIS, INDIANA 46280 CARMEL CARMEL ARCHITECTURAL 2.003 IBC MECHANICAL 2003 UMC PLUMBING 2003 UPC ELECTRICAL 2002 NEC FIRE PROTECTION 2003 UFC BUILDING INFORMATION NUMBER OF STORIES 1 CONSTRUCTION TYPE IIB FIRE PROTECTION NON COMBUSTABLE/ EXTINGUISHERS TENANT SEPERATION NON RATED EXIST ACCESS CORRIDORS NON RATED USE/ OCCUPANCY CLASSIFICATION GROUP B OCCUPANT LOAD OFFICE 55 design/applications, inc. 118 West Loretta Drive Indianapolis, Indiana 46217 phone: (317) 782-8957 for. (317) 782-0976 PROJECT NAME WHITE BOXES 9 3105 BLDG. PROJECT NUMBER 2004-22 SUBMITTAL DATE JULY 30, 2004 y U O U ' C U U O O o r• ow O COD est 0 - O M �- F � GAS LU co _r O F— �-a y O O N o =NJ CO0 rI LU CL. a WS H Cc N co ON11t J (n o0 W Cm ca c� a. _0_� z LA; O Z oma¢ r W OHO T3 0 X y != Q d y U O U ' C U U O O o r• ow O O est O M �- Tm LU co O O F— y O O N =NJ u, a cc LU CL. a WS H Cc v— ON11t =,U.CA o0 W Cm ca c� a. LU z LA; O Z oma¢ r W y f. y O �- co O y O N > °� Zz " J y R � •y � y v y w.r n R m tOr � G vdi c!y' G ^T Rf - 7z y p y -o N� W m r "R11-1 rr �/ 1-1 � N LL z y d O y d Revisions: ++ moi. � 1'r � i • • n � a."• 1,1t iti � i � w >t1:, �w'C�, � aft �, ✓�; i�i a Vs• Ro Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: T1 EA Suite 100 INTEGRITY TITLE ;Suite 190 AVAIL" R S F Suite 110 1MRSON & FRANKENBURGER/PENDING �, DEMOLITION PLAN 3105 BUILDING PLAN Z SCALE:1/a'-- T-0° DEMOLITION NOTES: O CONT'R TO REMOVE PORTION OF WALL EXTENDING BEYOND DEMISING WALLS. RELOCATE ELECTRICAL CONDUIT AS REQUIRED FOR TENANT IN SUITE 170. WALL LEGEND EXISTING WALL TO REMAIN EXISITING WALL TO BE REMOVED DOOR LEGEND EXISTING DOOR AND FRAME TO REMAIN �\ EXISTING DOOR AND FRAME TO BE REMOVED SALVAGE FOR REUSE r m n c* Vm L{ �v C4 LULU Q Cc LY C4 Nam L16 W Lb. J � � ® a ®. Lit Ln ®wC2 Mb� Revisions: 1 LU LU X LU Cl Issue. STATE SUBMITTAL Date: JULY 30, 2004 Sheet: O C.� N I-- to CD ao rn GASv � o0 � 0l N co O n � oo v 'v � 0 r m n c* Vm L{ �v C4 LULU Q Cc LY C4 Nam L16 W Lb. J � � ® a ®. Lit Ln ®wC2 Mb� Revisions: 1 LU LU X LU Cl Issue. STATE SUBMITTAL Date: JULY 30, 2004 Sheet: Suite 100Suite 190 INTEGRITY TITLE o o - - - ! o G AVAILABLE 41203 RSF � � 11161 RSF Suite 170 mm _qnm R FRdUFMIllIIR m/PFIUnINp 4,203 RSF GENERAL NOTES 1, VERIFY ALL BUILDING STANDARDS WITH OWNER PRIOR TO PURCHASE OF ANY PRODUCT. 2, ALL DEMISING THERLSIDE BETWEEN FLOORT SUITES TO BE 3 TO UNDERSIDE OF DECK' METAA OVEL STUDS W/ 5/8' GYP. E 3 1/2' INSULATION TO BE INSTALLED BETWEEN STUDS, 4. ALL PERIMETER WALLS TO RECEIVE 5/8' GYP. TO EXISTING STUDS W/ INSULATION. 5. FINISHED CEILING HEIGHT TO BE 9`0' W/ BLDG STD TILE & GRID. SEE REFLECTED CEILING PLAN FOR LITE FIXTURE AND DIFFUSER LOCATIONS. 6. ALL DOOR. ROUGH OPENINGS SHALL BE FRAMED 6' FROM ADJACENT WALL CORNER UNLESS OTHERWISE NOTED, 9, GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD CHECKING ALL DIMENSIONS AND MEASUREMENTS. IF JOB CONDITIONS PREVENT OBTAINING DIMENSIONS OR RESULTS AS SHOWN OR SPECIFIED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR INFORMING DESIGN/APPLICATIONS, INC. BEFORE ANY CONSTRUCTION IS STARTED, 10. EACH CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AS INDICATED ON THE DRAWINGS AND REPORT ANY DISCREPANCY THAT MAY OCCUR TO THE GENERAL CONTRACTOR. ANY IRREGULARITIES SHALL BE REPORTED TO DESIGN/APPLICATIONS, INC., FROM THE GENERAL CONTRACTOR. 11, SHOP DRAWINGS OR CATALOG CUTS MUST BE SUBMITTED TO DESIGN/APPLICATIONS, INC. FOR APPROVAL, ON ALL MATERIALS OR ITEMS IF THE CONTRACTOR CHOOSES TO DEVIATE FROM THAT H�AWN ON THE DRAWINGSNUFACTURER OR MODE p IF NU BER.E DRAWING DOES NOT INDICE A SPECIFIC 12. GENERAL CONTRACTOR SHALL EXPEDIATE PREPARATION AND SUBMITTAL OF ALL SHOP DRAWINGS RDER NG AND DELIVERY OFSUFFICIENT MATERIALSFOR &FOR CHECKING, FABRICATION, AND/OR O EQUIPMENT. �13. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OVERSEEING THAT ALL MATERIALS AND LABOR SHALL BE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF THE RESPECTED TRADE. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OVERSEEING THAT ALL WORK SHALL BE IN ACCORDANCE WITH THE STATE UNIFORM BUILDING CODES AND STANDARDS FOR ALL GENERAL CONSTRUCTION, MECHANICAL, AND ELECTRICAL WORK AND LOCAL AND FEDERAL CODES AND STANDARDS. 14. ALL DETAILS, MATERIALS, AND INSTALLATIONS OF SAME ARE SUBJECT TO APPROVAL BY DESIGN/APPLICATIONS, INC. AND FINAL APPROVAL BY THE OWNER. Suite 130 Suite 14U AVAILABLE REPUBLIC BANK 3115 RSF 11513 RSF ARCHITECTURAL PLAN Z 3105 BUILDING PLAN SCALE: 1/8'r 1'-0' ARC H ITETU RAL NOTES: OCONT'R TO WRAP COLUMNS TIGHT W/ 3 5/8" STUDS & 5/8" GYP BD. TIE INTO EXISTING WALLS WHERE APPLICABLE. OCONT'R TO INSTALL 1X6 CHERRY WOOD STAINED SILL & DRYWALL WRAPPED WINDOW TO MATCH EXISTING IN OTHER OCCUPIED SUITES. OCONT'R TO EXTEND ADDITIONAL METAL STUDS & GYP BD TO EXISTING WALL & SEAL AT DECK. OCONT'R TO COMPLETE WOOD TRIM WORK ON EXISTING DOOR & WINDOW FRAME. OCONT'R TO INSTALL WOOD TRIM WORK ON EXISTING DOOR & INSTALL NEW SIDE SIDE LIGHT TO MATCH BLDG. STD. SEE 1/A1 FOR DETAILS. OCONT'R TO TAPE & PRIME ALL WALLS SO READY FOR FINISH PAINT. !'ALL LEGEND EXISTING WALL TO REMAIN EXISITING WALL TO BE REMOVED NEW WALL CONSTRUCTION. SEE WALL TYPES FOR DETAILS. W DOOR LEGEND �s Ii EXISTING DOOR AND FRAME TO REMAIN F==� EXISTING DOOR AND FRAME TO BE REMOVE . _ SALVAGE FOR REUSE NEW DOOR, AND FRAME. REFER ## TO DOOR SCHEDULE ON THIS SHEET. ca W-1 W-2 JUll-t I DU AVAILABLE 1,337 RSF EXIST METAL STUD FRAMING NEW 5/8° GYPSUM WALLBOARD INTERIOR SUITE SIDE EXIST WALL OUTSIDE TENANT SUITE EXIST SOUND—ATTENUATING BATTS INSIDE WALL NEW GYP WALL BD TO EXTEND TO DECK & SEAL EXIST METAL STUD FRAMING NEW 5/8" GYPSUM WALLBOARD INTERIOR SUITE SIDE EXIST WALL OUTSIDE TENANT SUITE NEW SOUND -ATTENUATING BATTS INSIDE WALL NEW GYP WALL BD & SOUND—ATTENUATING BATTS TO EXTEND TO DECK & SEAL WALL TYPES 1 ENTRY ELEVATIUN Al SCALE: 1/2" =1'-0" 1'-0" cm cn 4M' co m Tm n co LU �s Ii 0 i= ccs h ca C.. .j N Uj 0 Vd A n w 0� o QQ��� cNz LLi � � OI N ®y � � `O J c cn p00 C 0 - •- a. O v . cm cn 4M' co m Tm n co LU CO) LU UJI UJI cz ad ImIll LU LU vd LU Revisions: .• d � r Zia .0. a tsi �'ti- � � y - 05" op Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: �s Ii ca .j LU Uj Vd A n w 0� LAW r� QQ��� U1 LLi � � ®y � LU CO) LU UJI UJI cz ad ImIll LU LU vd LU Revisions: .• d � r Zia .0. a tsi �'ti- � � y - 05" op Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: Suite 100 Suite 190 INTEGRITY TITLE O o — — — o O AVAILABLE 41203 RSF ( 19161 RSF Suite 170 ■tri nnu a pn a uvwunsinnwn inwunsun 4,203 RSF Suite 130 Suite 140 Suite 150 AVAILABLE REPUBLIC BANK AVAILABLE 3,115 RSF 1,513 RSF 1,337 RSF REFLECTED CEILING PLAN GZ 3105 BUILDING PLAN SCALE: 1/8'=V_0• MEI' GENERAL NOTES: 1. FIRE PROTECTION CONTRACTOR TO BE RESPONSIBLE FOR LOCATING SPRINKLER HEADS AS REQUIRED BY NFPA AND FILING THE APPROPRIATE DRAWINGS WITH THE CITY AND STATE OFFICIALS. FIRE PROTECTION CONTRACTOR RESPONSIBLE FOR SMOKE DETECTION DEVICES. 2. MECHANICAL CONTRACTOR TO BE RESPONSIBLE FOR MEETING MO AND M1 SPECIFICATIONS PER FROST ENGINEERS PLANS. 3. MECHANICAL CONTRACTOR TO BE RESPONSIBLE FOR LOCATING THERMOSTATS ON MO AND M1 SHEETS PER FROST ENGINEERS. 4. ELECTRICAL CONTRACTOR TO BE RESPONSIBLE FOR PROVIDING LIFE SAFETY DEVICES WHERE REQUIRED BY CODE. SUCH AS EXIT SIGNS, HORNS, STROBES AND SPEAKERS ON EO AND E1 SHEETS PER FROST ENGINEERS. 5. ELECTRICAL DESIGN/BUILD CONTRACTOR TO MEET ALL CIRCUITING OF OUTLETS AND LIGHT FIXTURES PER FROST ENGINEERS PLANS. 6. ELECTRICAL CONTRACTOR TO MEET ALL EMERGENCY LIGHTING IN SPACE PER EO AND E1 PLANS PROVIDED BY FROST ENGINEERS. 7. WHERE MULTIPLE SWITCHES ARE REQUIRED, PROVIDE ONE COVER PLATE. I REFLECTED CEILING LEGEND I ® NEW 2'X4' FLOURESCENT FIXTURES ® NEW 2'X4' NITE LITES c* a) T= ca 0 n c bd 04 o �—fie o .2 UJ c 00 o � 2. 0. LU LLJ o = X ai�� co -D :-3: C �.7 U00 C 0 c* a) T= ca !m Y n LU bd 04 p.. L&j UJ iCC C013 Simmons 9% w.. LL Eii sma c00 u � 2. 0. LU LLJ o = X ai�� v— LU M bg .� w tu 1 CD ;a an LU m Ckd LU LU m W cz 2c awn LU cj C LUQ LU Uj Revisions: x ,? �v � ��C cin iaG 6�: is► 1 Lu iF L!4-3 w Ar w Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: HCPI L SECTION 16010 -BASIC ELECTRICAL REQUIREMENTS A. DEFINITIONS AND TERMS 1. THE WORD "OWNER" SHALL MEAN ANY REPRESENTATIVE OF HIS PARTY DULY AUTHORIZED TO ACT IN HIS BEHALF IN THE EXECUTION OF ANY WORK. 2. THE WORD "CONTRACTOR" SHALL MEAN THE PERSON, FIRM OR CORPORATION ENTERING INTO A CONTRACT OR AGREEMENT WITH THE OWNER TO CONSTRUCT AND COMPLETE THE WORK AS SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN. 3. THE WORD "ARCHITECT OR ENGINEER" SHALL MEAN THEIR REPRESENTATIVES THEIR REPRESENTATIVES ACTING AS THE OWNER'S APPOINTED AGENT. 4. THE WORD "FURNISH" SHALL MEAN TO SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION AND SIMILAR SUBSEQUENT REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND CALLED ON THE DRAWINGS AND SPECIFIED HEREIN. 5. THE 'WORD "INSTALL" SHALL MEAN OPERATIONS AT THE PROJECT SITE, INCLUDING, BUT NOT LIMITED TO, UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, AND SIMILAR REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND ON THE DRAWINGS AND SPECIFIED HEREIN. 6. THE TERM "PROVIDED" SHALL BE INTERPRETED AS MEANING "FURNISHED AND INSTALLED" BY THIS CONTRACTOR WITH THE EXCEPTION WHERE ITEMS ARE PROVIDED BY THE OWNER' WHICH MEANS "FURNISHED ONLY" AND INSTALLED BY THIS CONTRACTOR, UNLESS NOTED OTHERWISE. REFER TO THE RESPONSIBILITY SCHEDULES FOR ADDITIONAL INFORMATION. B. SUMMARY OF WORK 1. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, PERMITS, SERVICES, TOOLS, PERSONNEL, TRANSPORTATION AND FACILITIES PIECESSARY FOR AND REASONABLY IMPLIED, AND INCIDENTAL TO, THE FURNISHING, INSTALLATION, COMPLETION AND TESTING OF ALL THE WORK FOR ALL INSTALLED SYSTEMS AS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN AND AS REQUIRED BY JOB CONDITIONS. THESE CONDITIONS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING: A. A COMPLETE ELECTRICAL DISTRIBUTION SYSTEM INCLUDING THE INSTALLATION OF PANELBOARDS, SAFETY AND DISCONNECT SWITCHES, MOTOR STARTERS, LIGHTING CONTACTORS AND TRANSFORMER. IT IS THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INCLUDE IN HIS BID THE NECESSARY SERVICE EQUIPMENT OR TO OBTAIN SERVICE FROM THE LOCAL UTILITY COMPANY. THIS CONTRACTOR SHALL ALSO INCLUDE IN THE BID ALL NECESSARY MATERIALS REQUIRED TO COMPLETE THE SYSTEM INCLUDING, BUT NOT LIMITED TO, FEEDERS, BRANCH CIRCUITS, JUNCTION BOXES, OUTLET BOXES, WIRING DEVICES, CO'✓ERPLATES, CONDUITS, ETC. B. METERING AND CURRENT TRANSFORMERS AS REQUIRED BY THE DRAWINGS OR SPECIFIED HEREIN, THE UTILITY COMPANY REGULATIONS. F A IP THE WIRING 0 M HANK U EQUIPMENT TIN ON WIN C. EMECHANICAL EQ E AS ED 0 E DRAWINGS OR SPECIFIED HEREIN. WORK SHALL INCLUDE ALL STARTERS, DISCONNECTS, AND POWER WIRING OF MECHANICAL EQUIPMENT EXCEPT UNLESS NOTED OTHERWISE. ALL LOW VOLTAGE 24 VOLT) TEMPERATURE CONTROL WIRING SHALL BE BY THE MECHANICAL CONTRACTOR UNLESS NOTED OTHERWISE. D_ THE INSTALLATION OF LIGHT FIXTURES AND ;.AMPS AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN, INCLUDING ALL DEVICES, EQUIPMENT, ETC., REQUIRED FOR MOUNTING. E. A CONDUIT SYSTEM FOR TELEPHONE,/DATA INCLUDING THE TERMINAL BOARD, BRANCH CONDUITS, OUTLET BOXES, PULL WIRES, GROUND CONDUCTORS, ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN, F. A COMPLETE EMERGENCY AND EXIT LIGHTING SYSTEM AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. G. TEMPORARY SERVICE AS SPECIFIED HEREIN AND ITS REMOVAL. H. ALL FINAL CONNECTIONS TO SIGNS, LIGHTING, OWNER PROVIDED EQUIPMENT; ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. I. THE INSTALLATION AND WIRING OF SPEAKERS. CONDUIT, ETC., FOR A SOUND SYSTEM AS SHOwrJ ArJD CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. J_ ALL SMOKE/FIRE ALARM WIRING, DEVICES, CONDUITS, ETC., AS REQUIRED TO MEET ALL FEDERAL, STATE AND LOCAL APPLICABLE CODES AND INSURANCE AND FIRE DEPARTMENT REQUIREMENTS AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. K. THE INSTALLATION OF CONDUITS STUBBED ABOVE THE CEILING FOR HVAC AND/OR LIGHTING CONTROL PANELS AND ANY ADDITIONAL CONDUIT FOR HVAC EQUIPMENT CONTROL WIRING WHERE PLENUM RATED CABLES ARE NOT PERMITTED. 2. WORK NOT INCLUDED OR TO BE PROVIDED BY 'HIS CONTRACTOR SHALL BE AS FOLLOWS: A. LOW VOLTAGE (24 VOLT) TEMPERATURE CONTROL WIRING FOR HVAC EQUIPMENT. B. TELEPHONE DEVICES AND WIRING UNLESS NOTED OTHERWISE ON THE DRAWINGS. C. DATA LINE WIRING. C. GENERAL REQUREMEtJTS 1. THIS CONTRACTOR SHALL VERIFY THE EXTENT OF ALL EXISTING CONDITIONS, UTILITY CONNECTION POINTS, EQUIPMENT PROVIDED BY OTHERS, ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO THIS CONTRACTOR FOR FAILURE OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET THE ItNTENT OF THE DRAWINGS AND SPECIFICATIONS. FAILURE OF KNOWLEDGE OF EXISTING CONDITIONS BY VIS.TING THE SITE PRIOR TO BIDDING DOES NOT RELIEVE THIS CONTRACTOR OF RESPONSIBILITY IN WORK OR WORKMANSHIP. 2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK, AND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE PROVIDED AS PART OF THIS CONTRACT. 3. ALL WORK BY THIS CONTRACTOR SHALL BE INSTAL,ED SO AS TO BE READILY ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING, REPAIRING, ETC. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS FOR MAINTENANCE OF THE EQUIPMENT AND MAINTAINING ALL MANUFACTURES REQUIRED CLEARANCES. 4. ALL ROOF CUTTING, PATCHING AND FLASHING SHALL BE BY THE OWNER'S ROOFING CONTRACTOR OR OWNER'S APPROVED ROOFING CONTRACTOR AT THIS CONTRACTOR'S EXPENSE, COORDINATE ALL ROOF PENETRATIONS. 5. THIS CONTRACTOR SHALL PROVIDE ANY ADDITIONAL STRUCTURAL STEEL OR SUPPORTS TO SUPPORT ANY INSTALLED E:'QUIPMENT AS SHOWN AND CALLED FOR ON THE DRAWINGS OR IN THE SPECIFICATIONS. THIS CONTRACTOR SHALL COORDINATE ALL ADDITIONAL STEEL OR SUPPORT LOCATIONS WITH THE OWNER PRIOR TO BIDDING AND INSTALLATION. 6. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF OF THE FLOOR FOR ALL INSTALLED CONDUIT, SLEEVES, ETC., AS SHOWN AND CALLED FOR ON THE DRAWINGS OR SPECIFIED HEREIN. COORDINATE ALL FLOOR CUTS WITH THE OWNER. CUTTING AND PATCHING SHALL BE HELD TO A MINIMUM. 7. ALL SWITCH GEAR, CIRCUIT BREAKERS AND DISCONNECTS IN SWITCH GEAR, PANELBOARDS, TRANSFORMERS, TIME CLOCKS, THERMAL OVERLOAD FAN SWITCHES, EQUIPMENT CONTROL SWITCHES, SAFETY SNITCHES, MOTOR STARTERS, AND SIMILAR ITEMS SHALL BE IDENTIFIED BY NAME, FUNCTION, AND/OR CONTROL. N NAMEPLATES SHALL BE AT LEAST 1" X 3" WITH CHARACTERS NOT LESS THAN 1/4". THEY SHAL_ BE MADE UP OF PLASTIC- LAMIrIATED TAGS AND CHARACTERS ENGRAVED TO ENGRAVER'S STANDARD THICKNESS AND LETTER STYLE WITH WHITE CORE AND BLACK BACKGROUND. NAMEPLATES SHALL BE FASTENED WITH POP RIVETS OR SCREWS. 8. PROVIDE TYPED DIRECTORIES IN PANELBOARDS TO DEPICT ACTUAL EQUIPMENT CONNECTED TO INDIVIDUAL BREAKERS/SWITCHES. D. CODES, FEES AND MISCELLANEOUS COSTS 1. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE CODES, SPECIFICATIONS, LOCAL ORDINANCES, INDUSTRY STANDARDS, REQUIREME14TS AND UTILITY COMPANY REGULATIONS. 2. IN CASES CF DIFFERENCE BETWEEN BUILDING CODES, SPECIFICATIONS, STATE LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS. OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND THE CONTRACT DOCUMENTS, THE MOST STRINGENT SHALL GOVERN. THIS CONTRACTOR SHALL PROMPTLY NOTIFY THE ENGINEER IN WRITING OF ANY SUCH DIFFERENCE. 3. NON-COMPLIANCE: SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF APPLICABLE BUILDING CODES, STATE LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS, UTILITY COMPANY REGULATIONS OR THE CONTRACT DOCUMENTS, THIS CONTRACTOR SHALL BEAR ALL COSTS ARISING FOR THE CORRECTION OF NON -COMPLYING ITEMS. 4. APPLICABLE CODES AND STANDARDS SHALL INCLJDE ALL FEDERAL AND STATE LAWS, LOCAL ORDINANCES, OWNER REQUIREMENTS, UT!bTY COMPANY REGULATIONS AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES AND STANDARDS. THOSE REQUIREMENTS ARE TO BE CONSIDERED A MINIMUM AND ARE TO BE EXCEEDED WHEN SO INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN. THIS CONTRACTOR SHALL INQUIRE INTO AND COMPLY WITH ALL APPLICABLE CODES AND STANDARDS AND ANY CHANGES OR MODIFICATIONS TO THE DRAWINGS OR SPECIFICATIONS AS REQUIRED BY THE CODES SHALL BE INCLUDED IN THE BID. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO THE CONTRACTOR FOR FAILURE OF CODE INQUIRY OR COMPLIANCE. 5. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PAYMENT OF ALL FEES, NECESSARY DRAWINGS AND ARRANGING AND PAYING FOR ALL INSPECTIONS, TESTS, ETC., WHICH MAY BE REQUIRED BY ANY AUTHORITY OR UTILITY COMPANY IN CONNECTION WITH THE FURNISHING OR INSTALLATION OF ANY OF HIS RESPECTIVE WORK E. WORK AND WORKMANSHIP 1, ALL MATERIALS AND EQUIPMENT SHALL BE OF THE HIGHEST QUALITY IN EVERY RESPECT. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE, OF THE LATEST DESIGN AND FREE OF DEFECTS. 2. WORKMANSHIP SHALL BE BY SKILLED WORKMEN OF HIGHEST STANDARD IN STRICT ACCORDANCE WITH ALL APPLICABLE MANUFACTURERS PRINTED SPECIFICATIONS, PERFORMED UNDER SUPERVISION OF COMPETENT FOREMAN AT ALL TIMES. 3. THE OWNER AND THE ARCHITECT HAVE FULL POWER TO CONDEMN OR REJECT ANY WORK, MATERIALS OR EQUIPMENT NOT IN ACCORDANCE WITH THESE SPECIFICATIONS AND DRAWINGS OR ARE NQ' IN CONFORMANCE WITH THE MANUFACTURES SPECIFICATIONS OR DRAWINGS WHICH WERE APPROVED BY THE OWNER OR ARCHITECT. 4. WORK OR EQUIPMENT THAT IS REJECTED SHALL BE REMOVED AND REPLACED TO THE SATISFACTION OF THE OWNER OR ARCHITECT AT THIS CONTRACTORS EXPENSE. WORK OR EQUIPMENT THAT IS REJECTED SHALL BE SO STATED IN WRITING BY THE OWNER OR THE ARCHITECT. 5. SUCH DECISIONS AS THE OWNER OR THE ARCHITECT MAY MAKE WITH RESPECT TO QUESTIONS CONCERNING THE QUALITY, FITNESS OF MATERIALS, EQUIPMENT AND WORKMANSHIP SHALL BE BINDING UPON THE PARTIES THERETO. F. DEVIATIONS FROM DRAWINGS 1. THE DRAWINGS SHOW THE INTENDED ARRANGEMENT OF ALL CONDUITS, LIGHT FIXTURES, PANELBOARDS, EQUIPMENT AND APPURTENANCES. THEY SHALL BE FOLLOWED AS CLOSELY AS. ACTUAL BUILDING CONSTRUCTION AND WORK OF OTHER TRADES WILL PERMIT. 2. THIS CONTRACTOR SHALL INVESTIGATE STRUCTURAL AND FINISH CONDITIONS AFFECTING HIS WORK AND SHALL PROVIDE ANY FITTINGS, OFFSETS AND ACCESSORIES REQUIRED TO ACCOMMODATE SAID CONDITIONS IN THE BID PROPOSAL 3. WHERE TRADE NAMES AND MANUFACTURES ARE USED ON THE DRAWINGS OR SPECIFIED HEREIN, THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR THE BASE BID. MANUFACTURES CONSIDERED AS AN EQUAL OR BETTER IN ALL ASPECTS TO THAT SPECIFIED WILL BE SUBJECT TO APPROVAL IN WRITING BY THE OWNER OR THE ENGINEER PRIOR THROUGH SHOP DRAWING OR SUBMITTAL PROCESS, TO ACCEPTANCE. THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT THIS CONTRACTORS EXPENSE. 4. THE DRAWINGS INDICATE AN INSTALLED SYSTEM BASED UPON SELECTED MANUFACTURERS OF EQUIPMENT. ELECTRICAL SERVICES, SIZE, CONFIGURATIONS, ETC., ARE CONSISTENT WITH THE MANUFACTURER'S RECOMMENDATIONS. OTHER MANUFACTURERS ARE ENCOURAGED TO FURNISH EQUIPMENT FOR THIS PROJECT; HOWEVER, IT SHALL BE THIS CONTRACTORS RESPONSIBILITY TO ASSURE THAT THE EQUIPMENT IS CONSISTENT WITH THE DESIGN BASE. NO ADDITIONAL COMPENSATION SHALL BE AWARDED FOR REVISIONS, MODIFICATIONS, ETC., TO ELECTRICAL SERVICES, WIRING, BREAKERS, SPACE, CLEARANCE, CONDUIT, PANELBOARDS, ETC., REQUIRED BY OTHER MANUFACTURES. 5. THE LOCATION OF OUTLETS, PANELBOARDS, ELECTRICAL EQUIPMENT, ETT., AS SHOWN AND CALLED FOR ON THE DRAWINGS IS APPROXIMATE AND THE OWNER OR HE LANDLORD SHALL HAVE THE RIGHT TO RELOCATE ANY SAID EQUIPMENT, RECEPTACLES, LIGHT FIXTURES, ETC., UPON THEIR REQUEST AT NO ADDITIONAL COMPENSATION TO THIS CONTRACTOR. G. HANGERS AND SUPPORTS 1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, WIRE, UNISTRUT, C CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC., NECESSARY FOR THE INSTALLATION OF WORK. 2. HANGERS AND SUPPORTS SHALL BE FASTENED TO THE BUILDING STEEL, CONCRETE OR MASONRY, BUT NOT TO OR FROM OTHER CONDUIT, PIPING, EQUIPMENT, DUCTWORK, SOFFIT, NEUTRAL PIERS, PIPING DUCTWORK, METAL ROOF DECK, LATERAL BRACING, BRIDGING, OR CONDUIT. HANGERS SHALL BE ATTACHED TO THE UPPER CHORD OF THE BAR JOIST. HANGING FROM THE MEAL DECK IS NOT PERMITTED. WHERE INTERFERENCES OCCUR, AND IN ORDER TO SUPPORT CONDUIT, THIS CONTRACTOR SHALL INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS DOORS TO FIRE DAMPERS, VALVES, JUNCTION BOXES, ACCESS DOORS, EQUIPMENT, ETC. HANGER TYPES AND INSTALLATION METHODS SHALL BE SUBJECT TO ALL APPLICABLE CODES. H. OCCUPATIONAL SAFETY AND HEALTH ACT 1. ALL WORK SHALL BE COMPLY WITH THE CURRENT REQUIREMENTS OF THE U.S. DEPARTMENT OF LABOR OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, ENTITLED OCCUPATIONAL SAFETY AND HEALTH STANDARDS; NATICNAL CONSENSUS STANDARDS AERAL STANDARDS. I. COORDINATION BETWEEN CONTRACTORS 1. BEFORE THE COMMENCEMENT OF ANY WORK, THIS CONTRACTOR SHALL EXAMINE ALL THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS AND SPECIFICATIONS TO SEQUENCE, COORDINATE AND INTEGRATE THE VARIOUS COMPONENTS OF THE INSTALLED SYSTEMS, MATERIALS, CONDUIT, EQUIPMENT, ETC., WITH OTHER TRADE CONTRACTORS TO AVOID OTHER TRADE INTERFERENCES AIJD CONFLICTS. 2. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO LEAVE THE REQUIRED, NECESSARY ROOM AOR OTHER TRADES. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO THIS CONTRACTOR FOR FAILURE TO COORDINATE WITH OTHER TRADE CONTRACTORS TO AVOID OTHER TRADE INTERFERENCES, CONFLICTS, RELOCATION OF PANELBOARDS, CONDUIT, EQUIPMENT, ETC., FOUND ENCROACHING ON SPACE REQUIRED BY OTHERS. 3. THIS CONTRACTOR SHALL PROVIDE COMPLETE INFORMATION AND COOPERATION TO THE OTHER CONTRACTORS AND TRADES PERTAINING TO HIS WORK TO ACCOMPLISH COORDINATION OF THE COMPLETED PROJECT. J. EQUIPMENT DRAWINGS 1. THIS CONTRACTOR SHALL PROVIDE EQUIPMENT DRAWIIJGS OF PROVIDED EQUIPMENT AS SPECIFIED HEREIN. 2. THE FOLLOWING ITEMS ARE A MINIMUM REQUIREMENT FOR EACH EQUIPMENT DRAWING SUBMITTAL A. SHEET SIZE 8-1/2" X 11". B. MANUFACTURE'S STANDARD SCHEMATIC DRAWINGS: 1, MODIFY DRAWINGS TO DELETE INFORMATION THAT IS NOT APPLICABLE TO APPLICABLE TO THIS PROJECT. 2. SUPPLEMENT STANDARD INFORMATION TO PROVIDE ADDITIONAL INFORMATION C. MANUFACTURER'S CATALOG SHEETS, BROCHURES, DIAGRAMS, SCHEDULES, PERFORMANCE CHARTS, ILLUSTRATIONS AND OTHER STANDARD DESCRIPTIVE DATA. 1. CLEARLY MARK EACH COPY TO IDENTIFY PERTINENT MATERIALS, PRODUCTS, REQUIRED. 2. SHOW EQUIPMENT DIMENSIONS AND MAINTENANCE OR CONSTRUCTION CLEARANCES 3. SHOW PERFORMANCE CHARACTERISTICS AND CAPABILITIES. 4. SHOW WIRING DIAGRAMS AND CONTROLS. 5. MATERIAL AND SAFETY DATA SHEETS. 6. THE FULL MANUFACTURE'S MODEL NUMBER OF EACH ITEM. 7. IDENTIFICATION OF COLOR OR FINISHES. 8. THIS CONTRACTOR'S STAMP, SIGNATURE AND DATA SHALL BE AFFIXED TO EACH 3. COPIES OF THE EQUIPMENT DRAWINGS AND ALL OTHER RELATED INFORMATION MUST APPEAR IN THE OPERATIONS MANUAL LEFT ON SITE AFTER PROJECT COMPLETION. K_ RECORD DRAWINGS 1. DURING CONSTRUCTION THIS CONTRACTOR SHALL MAINTAIN A COMPLETE AND LEGIBLE SET OF DRAWINGS SHOWING CHANGES AND DEVIATIONS BETWEEN ACTUAL CONSTRUCTION AND THE ENGINEER'S DRAWINGS. 2. AT THE COMPLETION OF THE PROJECT AND BEFORE FINAL ACCEPTANCE, THIS CONTRACTOR SHALL MAKE ANY FINAL CORRECTIONS TO THE DRAWINGS AND CERTIFY THE ACCURACY OF EACH PRINT WITH THIS CONTRACTOR'S STAMP AND SIGNATURE THEREON. THIS 70PY OF THE RECORD DRAWINGS SHALL BE PLACED IN A DRAWING TUBE AND MARKED "RECORD DRAWIIJGS - DO NOT REMOVE FROM PREMISES" AND SHALL BE KEPT WITH THE OPERATIONS MANUAL. L. OPERATIONS MANUAL 1. ONE COPY OF AN OPERATIONS AND MAINTENANCE MANUA_ FOR THE PROJECT SFOR ALL EQUIPMENT FU RNISHED HALL BE COLLECTED AND INSERTED IN LABELED INCH (3') THREE (3) RING BINDER. 2. OPERATIONS AND MAINTENANCE MANUALS SHALL BE ASSEMBLED AS FOLLOWS: A. SECTION 1 TI F P. 1. TLE PROJECT 0 2. LOCATION OF PROJECT 3. 14AME AND ADDRESS OF OWNER 4. NAME AND ADDRESS OF ENGINEER 5. NAME AND ADDRESS OF THIS CONTRACTOR. B. SECTION 2 1. SHOP DRAWINGS OF ALL APPROVED EQUIPMENT. C. SECTION 3 1. A LISTING OF ALL EQUIPMENT WARRANTIES INDICA-ING THE EQUIPMENT MODEL NUMBER, SERIAL NUMBER, START AND ENDING DATE OF THE WARRANTY, ETC. 3. EACH SECTION SHALL BE SEPARATED BY A PASTEBOARD TABBED DIVIDER. 4, ALL INFORMATION SHALL BE ARRANGED IN AS MANY BINDERS AS NECESSARY. 5. OPERATION AND MAINTENANCE MANUAL AND DRAWING TUBE SHAL- BE LEFT WITH THE STORE M.ANACER. M_ TESTS, ADJUSTMENTS, INSTRUCTIONS AND CLEANING 1. ALL CONNECTIONS AT PANELS AND SWITCHES ARE TO BE MADE, ALL SPICES COMPLETE, ALL FUSES IN PLACE, AND ALL CIRCUITS CONTINUOUS FROM POINT OF SERVICE CONNECTION TO ITS FINAL DESTINATION, AND ALL COVERS AND PLATES INSTALLED PRIOR TO THE TIME OF FINAL INSPECTION BY THE OWNER'S CONSTRUCTION MANAGER. 2. TEST FOR GROUNDS, SHORT CIRCUITS AND PROPER FUNCTION OF ALL EQUIPMENT AFTER INSTALLATION IS COMPLETE. FAULTS IN THE INSTALLATION SHALL BE CORRECTED AT THIS CONTRACTORS EXPENSE. 3. UPON COMPLETION OF THE WORK, ALL PARTS OF THE ELECTRICAL INSTALLATION SHALL BE TESTED AND PROVED FREE OF UNWANTED GROUtJDS AND OTHER DEFECTS. 4. ALL OVERLOAD DEVICES, INCLUDING EQUIPMENT, FURNISHED UNDER OTHER CONTRACTS, SHALL BE SET AND ADJUSTED TO SUIT THE LOAD CONDITIONS. 5. TEST AND MAKE CORRECTIONS/ADJUSTMENTS FOR PHASE BALANCING. 6. AFTER ALL TESTS AND ADJUSTMENTS HAVE BEEN MADE, THIS CONTRACTOR SHALL FULLY INSTRUCT THE REPRESENTATIVES OF THE OWNER IN ALL DETAILS OF OPERATION AND MAINTENANCE OF THE EQUIPMENT INSTALLED UNDER THIS CONTRACT. INSTRUCTION SHALL BE FURNISHED UNTIL THE OWNER IS SATISFIED. FURNISH THE OWNER WITH TWO INSTRUCTIO14 MANUALS ON EACH SYSTEM_ INSTRUCTION MANUALS SHALL CONTAIN ALL SHOP DRAWINGS, MANUFACTURERS INSTALLATION AND OPERATION INSTRUCTION. GUARANTEES, MAINTENANCE SCHEDULE, ETC. 7. AT THE END OF THE PROJECT, THIS CONTRACTOR SHALL CLEAN ALL EQUIPMENT, INCLUDING LIGHT FIXTURES, TO THE SATISFACTION OF THE OWNER. ALL DUST, DIRT, DEBRIS, AND FOREIGN MATTER SHALL BE REMOVED FROM ALL EQUIPMENT. N. INSPECTIONS, FINAL REPORTS AND GUARANTEE 1. AT THE COMPLETION OF THE WORK, THIS CONTRACTOR SHALL INFORM THE LOCAL AND STATE AUTHORITIES AND THE OWNER TO ARRANGE FOR FINAL INSPECTIONS OF THIS WORK. 2. THIS CONTRACTOR SHALL FURNISH TO THE OWNER ALL CERTIFICATES OF INSPECTION AND FINAL INSPECTION APPROVAL AT THE COMPLETION OF THIS PROJECT. 3. THIS CONTRACTOR SHALL SUBMIT TO THE OWNER UPON COMPLETION OF THIS WORK A LETTER CERTIFYING THAT THIS WORK IS IN ACCORDANCE WITH ALL APPLICABLE STATE AND LOCAL LAWS, LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND APPLICABLE REQUIREMENTS OF NATTONALLY ACCEPTED CODES AND STANDARDS. 4. THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT, WORK, ETC., UNDER THIS CONTRACT FOR ONE (1) YEAR AFTER THE ACCEPTANCE OF ALL SYSTEMS INSTALLED BY THIS CONTRACTOR UNDER THIS CONTRACT. THIS CONTRACTOR SHALL MAKE GOOD, REPAIR OR REPLACE AT THIS CONTRACTORS OWN EXP_NSE, ANY DEFECTIVE WORK, MATERIAL, OR EQUIPMENT WHICH MAY BE DISCOVERED FORM THE DATE OF ACCEPTA14CE IN WRITING. EXTENDED WARRANTIES ARE AS SPECIFIED WITH THE INDIVIDUAL EQUIPMENt. 5. UNDER THE ONE (1) YEAR GUARANTEE PERIOD TH'S CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO THE PREMISES CAUSED BY DEFECTS 1N ANY WORKMANSHIP OR ANY EOUIPME14T FURNISHES AND/OR INSTALLED BY THIS CONTRACTOR. U. SLEEVES 1. THIS CONTRACTOR SHALL PROVIDE SLEEVES TO PROTFCT EQUIPMENT OR FACILITIES IN THE INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH IT'S RESPECTIVE FLOOR, WALL OR PARTITION AND SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT PE14ETRATE THE FLOOR, WHICH SHALL EXTEND Two INCHES (2") ABOVE THE FLOOR. 2_ SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS, OR FOR CONCEALED VERTICAL PIPING, SLEEVES SHALL BE 140. 22 U.S.G. GALVANIZED STEEL MINIMUM. P. FIRE STOPPING 1. ALL OPENINGS THROUGH FIRE RATED WALLS AND,/OR FLOORS FOR CONDUITS SHALL BE FIRE SEALED IN ACCORDANCE WITH NEPA 101 WITH CALCIUM SILICATE, SILICONE "RTV' FOAM, 3M FIRE RATED SEALANTS OR EQUAL, SO AS TO RETAIN THEIR FIRE RATING. PROVIDE SLEEVES AS REQUIRED BY ALL APPLICABLE CODES OR LANDLORD REQUIREMENTS. END OF SECTION 16010 SECTION 16111 - CONDUIT A. THIS CONTRACTOR SHALL PROVIDE ALL CONDUITS SERVING ALL EQUIPMENT INCLUDING BUT NOT LIMITED TO, LIGHTING, RECEPTACLES, HEATING, AIR CONDITIONING, PLUMBING EQUIPMENT, TELEPHONE, SPEAKERS, AND ELECTRICAL EQUIPMENT. B. ALL CONDUITS SHALL BE GAL'✓ANIZED IMC OR MC UNLESS OTHERWISE SPECIFIED IN SPECIFICATIONS OR ON DRAWINGS. ALL CONDUIT IS TO BE UL LABELED. MC CONNECTORS SHALL BE STEEL COMPRESSION OR SET SCREW TYPE. CONDUIT UNDER SLAB ON GRADE SHALL BE RIGID STEEL. C. MINIMUM SIZES OF CONDUIT SHALL BE 1/2" FOR INDIVIDUAL LIGHTING FIXTURES CONNECTIONS OR TO INDIVIDUAL LIGHT SWITCHES (IF ACCEPTABLE BY THE LANDLORC AND LOCAL CODE OFFICIALS) AND 3/4" FOR ALL OTHER LOCATIONS. HVAC CONTROL WIRING, SPEAKER WIRING AND FIRE ALARM WIRING SHALL BE RUN IN CONDUIT AND SHALL BE A MINIMUM OF 3/4" SIZE, UNLESS NOTED OTHERWISE ON DRAWINGS. ALL IN AND/OR UNDER FLOOR SLAB CONDUIT SHALL BE OF MId!MUM 1" SIZE. D. SUPPORT ALL CONDUIT, INCLUDING SEISMIC AND SWAY BRACING, IN ACCORDANCE WITH THE N.E.C. AND LOCAL CODES. E. GENERALLY, ALL CONDUIT SHALL BE CONCEALED EXCEPT FOR UNFINISHED AREAS, SUCH AS EQUIPMENT ROOMS. EXPOSED CONDUIT SHALL BE ALLOWED ONLY AS NOTED ON PLAN. PAINTING OF CONDUITS IN FINISHED AREAS, NOTED ON DRAWINGS OR SPECIFICATIONS WILL BY GENERAL CONTRACTOR. F. FLEXIBLE METAL CONDUIT OR MC TYPE CABLE. 1. FLEXIBLE CONDUIT OR MC TYPE CABLE SHALL BE ACCEPTABLE FOR THE FOLLOWING APPLICATIONS ONLY: A. FINAL CONNECTIONS TO MOTORS. B. FINAL CONNECTIONSJ ECTI NS INTO AND D OUT 0F THE TRANSFORMER. C. FINAL CONNECTIONS TO VIBRATING EQUIPMENT. D. INTERCONNECTIONS BETWEEN ALL LIGHT FIXTURES. (NOT TO INCLUDE HOME RUN TO PANEL BOARD WHICH MUST BE RIGID.) E. FINAL CONNECTIONS WHERE RIGID CONDUIT IS NOT PRACTICAL. F_ IN WALLS (FOR LIGHT SWITCHES AND 120 VOLT POWER RECEPTACLES AND HVAC CONTROL EQUIPMENT. 2. FLEXIBLE METAL CONDUIT OR MC TYPE CABLE MUST BE THE SAME SIZE AS THE IMC OR MC CONDUIT TO WHICH IT IS CONNECTED. BOTH THE FLEXIBLE METAL CONDUIT AND ITS FITTINGS ARE TO BE LISTED FOR GROUNDING. A GREEN GROUNDING CONDUCTOR SHALL BE INSTALLED. ALL CONNECTORS ARE TC BE OF A NEMA APPROVED TYPE. 3. THE USE 0�7 ROMEX, BX, ETC. IS NOT PERMITTED. 4_ CONNECTION TO OUTDOOR EQUIPMENT MUST BE WEATHERPROOF, I.E. LIQUIDT'.GHT CR SEALTIGHT. 5. MAXIMUM LENGTH OF FLEXIBLE METAL CONDUIT SHALL BE 3'-O". G. PROVED AS A MINIMUM #10 AWG PULL -WIRE IN ALL EMPTY CONDUITS EXCEPT AS NOTED OTHERWISE ON DRAWINGS. H. HOME RUNS AND MAIN CONDUIT RUNS ARE TO BE HELD TIGHT TO STRUCTURE ABOVE CR AS REQUIRED TO ALLOW PROPER SERVICE ACCESS AND OTHER TRADES WORK. CONDUIT MUST BE TRAPEZED TO ALLOW 3 FEET MINIMUM CLEARANCE ABOVE CEILING. I. ALL CONDUIT SHALL BE RUN PARALLEL OR PERPENDICULAR TO COLUMN LINES. J. ALL CONDUITS MUST 3E SIZED PER N.E.C., LOCAL CODES AND LANDLORD REQUIREMENTS. K. PVC CONDUIT SHALL NOT BE PERMITTED. L. CONDUIT SHALL NOT 3E INSTALLED IN OR THROUGH ANY DUCTWORK. M. ANCHOR ALL CONDUITS INSTALLED HORIZONTALLY IN STEEL STUDS TO PREVENT VIBRATION. .ND OF SECTIOtd 16111 SECTION 16120 - WIRING A. CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS SHALL BE COPPER AND THE AWG SIZE AND TYPE AS SHOWN ON DRAWINGS. MINIMUM WIRE SIZE #12. THE CONDUCTORS SHALL BE 600 VOLT INSULATION, TYPE THW, THWN OR THHN. (CONDUIT SIZE BASED ON THHN AND THWN). B. MINIMUM WIRE SIZE - 20 AMP BRANCH CIRCUIT SHALL BE AWG LISTED SIZE PER DISTANCE SHOWN BELOW. DISTANCE SHALL BE MEASURED FROM THE PANELBOARD CIRCUIT BREAKER TO THE FURTHEST OUTLET. i. #12 LESS THAra "00 FEET 2. #10 BETWEEN 100-150 FEET 3. #8 BETWEEN 150-250 FEET 4. #6 OVER 250 FEET NOTE: THE ELECTRICAL CONTRACTOR MAY SUBMIT VOLTAGE DROP CALCULATIONS OR ACTUAL FIELD READINGS FOR EACH RECEPTACLE CIRCUIT TO THE OWNER FOR APPROVAL OF SMALLER WIRE SIZE THAN THOSE LISTED ABOVE. MAXIMUM vOLTAGE DROP SHALL BE 3% PER N.E.C. C. ON ALL 20 AMP BRANCH CIRCUITS, CONDUCTORS LARGER THAN #10 AWG SHALL 3E REDUCED TO # 1 Q AWG WITHIN 10 FEET OF PANEL BOARD AND DEVICE IN JUtNCTI0IJ BOXES ON RATED TERMINAL STRIPS. D. CONDUCTORS MAY BE STRANDED FOR SIZES #10 AWG AND LARGER. CONDUCTORS SIZE #12 SHALL BE SOLD (NOT STRANDED). E. ALUMINUM CONDUCTORS ARE NOT PERMITTED, EXCEPT AT SERVICE ENTRANCE, WHERE REQUIRED BY LANDLORD. CONDUCTOR CONNECTION MUST BE PER MANUFACTURER'S REQUIREMENTS. F. HVAC CONTROL WIRING SHALL BE 8-#16 MULTI -COLORED CABLE WITH 600 V. INSULATION. G. ALL WIRING AND CABLE SHALL BE NEW AND SHALL BE BROUGHT TO THE SITE IN UPJBROKEN PACKAGES. H. ALL WIRING SHAL- BE CONDUIT, UNLESS SPECIFICALLY NOTED OTHERWISE (I.E. LOW VOLTAGE, PLE`JUM RATED WIRE)_ 1. THE USE OF SHARED NEUTRALS IS NOT ALLOWED FOR LIGHTING CIRCUITS. SHARED NEUTRALS FOR POWER CIRCUITS SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL CODES. ALL OTHER EQUIPMENT REQUIRING A NEUTRAL CONDUCTOR SHALL HAVE A DEDICATED FULL SIZE NEUTRAL. J. THE USE OF ROMEX, BX, ETC. IS NOT PERMITTED. K. WIRE CONNECTORS SHAL_ 3E EQUAL TO "SCOTCH LOCK" FOR #8 AWG WIRE AND SMALLER AND EQUAL TO T & 3 "LOCKTIGHT" FOR #6 AWG AND LARGER. L. ALL WIRING TO 3E COLOR -CODED AS FOLLOWS: 120/208 `VOLT SYSTEM 277/480 VOLT SYSTEM NEUTRAL - WHITE NEUTRAL - GRAY PHASE A OR L1 -- BLACK PHASE 1 OR L1 - BROWN PHASE B OR L2 - RED PHASE B OR L2 - ORANGE PHASE C OR L3 - BLUE PHASE C OR L3 - YELLOW GROUhaD - GREEN GROUND - GREEN M. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED POWER AND CONTROL INTERLOCK FOR At_!_FRE SUPPRESSION SYSTEMS. N. LOW VOLTAGE WIRING FOR SIGNALLING OR CONTROL SYSTEMS OR DEVICES WHICH ARE ENCLOSED IN PARTITIONS, WALLS, OR ANY WAY MADE INACCESSIBLE BY BUILDING CONSTRUCTION SHALL BE ENCASED IN A RACEWAY_ THE ABOVE RACEWAY NEED NOT TERMINATE IN A BOX OR FITTING SO LONG AS NORMAL PRECAUTIONS ARE TAKEN TO PROTECT THE CONDUCTORS AGAINST INJURY OR DAMAGE (N.E.C. 725-38B AND 760-28C). THIS ALSO SHALL INCLUDE COAXIAL CABLE ASSEMBLIES (N.E.C. 820-50). 0. HEATING, VENTILATING & AIR CONDITIONING, PLUMBING, AND FIRE PROTECTION WIRING 1. ELECTRICAL CONTRACTOR SHALL REFER TO MECHANICAL DRAWINGS FOR FOR ADDITIONAL ELECTRICAL WORK TO BE INCLUDED IN THIS BID_ 2. ELECTRICAL CONTRACTOR SHALL DO ALL POWER WIRING, LINE VOLTAGE WIRING, AND LIiJE VOLTAGE CONTROL WIRING INDICATED UNDER THE HEATING, VENTILATION AND AIR CONDITIONING, PLUMBING AND FIRE PROTECTION SPECIFICATIONS AND DRAWINGS. THIS CONTRACTOR SHALL ALSO DO ALL INTERCONNECTING LINE VOLTAGE WIRING BETWEEN RELAYS AND SWITCHES AS REQUIRED. 3. ELECTRICAL CONTRACTOR SHALL PROVIDE AS A MINIMUM, ONE (1) CONDUIT STUBBED FROM HVAC AND/OR LIGHTING CONTROL PANEL TO 12" ABOVE CEILING WITH PLASTIC CONDUIT BUSHING TO PREVENT WIRE CHAFFING. 4. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING CONDUIT FOR HVAC CONTROL WIRING WHERE REQUIRED BY CODE TO BE IN CONDUIT, 5. REFER TO MECHANICAL DRAWINGS FOR AVAILABLE SCHEMATIC WIRING DIAGRAMS OF EQUIPMENT. 6. ROUTE ELECTRIC POWER AND CONTROL FOR ROOF MOUNTED HVAC EQUIPMENT THROUGH A SEPARATE ROOF PENETRATION FOR THE ELECTRIC POWER AND CONTROL CONDUITS. DO NOT ROUTE CONDUIT THROUGH HVAC ROOF MOUNTED EQUIPMENT CURB. DO NOT DRILL HOLES IN CONDENSATE PAN OR COMPRESSOR OR CONDENSER SECTAN FLOOR. 7. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL SMOKE DETECTORS AS REQUIRED BY ALL APPLICABLE CODES. VERIFY CONNECTION REQUIREMENTS TO THE FIRE ALARM SYSTEM PRIOR TO BIDDING. PROVIDE A RESET/TEST AND ALARM LIGHT FOR ALL INSTALLED SMOKE DETECTORS. VERIFY RESET/TEST AND ALARM LIGHT LOCATION WITH THE OWNER PRIOR TO INSTALLATION. P. GENERAL WIRING REQUIREMENTS 1. ALL EQUIPMENT FURNISHED AND INSTALLED UNDER CONTRACTS OTHER THAN THE ELECTRIC CONTRACT SHALL BE FURNISHED WITH FULL COMPLEMENT OF CONTROL EQUIPMENT AND CONTROL WIRING DIAGRAMS NECESSARY FOR SATISFACTORY OPERATION. 2. THE ELECTRICAL CONTRACTOR SHALL COMPLETE ALL ELECTRICAL CONNECTIONS THROUGH THE DISCONNECT, STARTER AND MOTOR TERMINALS. 3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER ROTATION OF ALL THREE PHASE EQUIPMENT. 4. EQUIPMENT FURNISHED BY OTHERS SHALL BE ROUGHED IN WITH CONDUIT AND BOXES BY MANUFACTURER. INTERNAL WIRING SHAL: BE COMPLETED ACCORDING TO THE MANUFACTURER'S SHOP DRAWINGS OF THE EQUIPMENT BY ELECTRICAL CONTRACTOR. THIS CONTRACTOR IS TO WIRE TO ALL LINES VOLTAGE CONTROLS AND CONTROLLERS. END OF SECTION 16120 SECTION 16131 -JUNCTION AND PULL 90XES A. THE PLANS INDICATE ONLY SCHEMATIC ROUTINGS FOR CONDUIT RUNS. THIS CONTRACTOR SHALL PROVIDE ADDITIONAL BOXES WHERE REQUIRED BY FIELD CONDITIONS OR BY CODE. B. BOXES AND COVERS SHALL BE GALVANIZED STEEL OF CODE GAUGE SIZE. C. INSTALL BOXES RIGIDLY SUPPORTED FROM THE BUILDING STRUCTURE AND INDEPENDENT SUPPORTED OF THE CONDUIT SYSTEM D. ARRANGE CIRCUITS TO AVOID THE USE OF JUNCTION BOXES IN INACCESSIBLE LOCATIONS. THE USE OF JUNCTION BOXES ABOVE DRYWALL CEILING SHALL BE LIMITED TO LOCATIONS NEAR ACCESS FRAMES USED FOR DIFFUSERS AND RETURN AIR GRILLES OF ACCESS PANELS AS LOCATED ON PLANS. E JUNCTION AND PULL BOXES MUST BE LABELED WITH CIRCUIT NUMBER IDENTIFICATION AIJD SYSTEM TYPE ON COVER. END OF SECTION 16131 71 r 1 - SEC 0 J 16 4 T 3 OU LET BOXES O E5 A. ALL OUTLET BOXES SHALL BE GALVANIZED PRESSED STEEL OF THE STANDARD KNOCKOUT TYPE. NO ROUND OUTLET BOXES SHALL BE PERMITTED, EXCEPT AS SPECIFICALLY NOTES ON DRAWINGS. CONCEALED BOXES SHALL NOT BE LESS THAN 4 INCHES SQUARE AND 1 1/2" DEEP, WITH PLASTIC RINGS. B. ALL KNOCKOUT BOXES, UPON WHICH LIGHTING FIXTURES ARE TO BE INSTALLED, SHALL BE EQUIPPED WITH 3/4" FIXTURE STUDS. C. EXTERIOR BOXES SHALL BE CAST RUST -RESISTING METAL WITH GASKETED COVERS. D. INSTALL BOXES RIGIDLY FROM BUILDING STRUCTURE AND SUPPORT INDEPENDENTLY OF THE CONDUIT SYSTEM. ALSO PROVIDE SUITABLE BOX EXTENSIONS TO EXTEND BOXES TO FINISHED FACES OF FLOORS, CEILINGS, WALLS, ETC. ALL OUTLET BOXES TO HAVE SUITABLE BLOCKING BEHIND THEM TO MINIMIZE THE DEFLECTION THAT OCCURS WHEN PLUGGING/.UNPLUGGING INTO THESE DEVICES. E. UNLESS OTHERWISE NOTED ON DRAWINGS OR OTHERWISE REQUIRED BY NATIONAL ELECTRICAL CODE, HANDICAP CODES OR LOCAL CODES, OUTLET HEIGHTS SHALL BE AS FOLLOWS: 1. SWITCH HEIGHT 48" FROM FINISHEDFLOOR TO CENTERLINE OF OUTLIE . 2. CONVENIENCE OUTLETS A. SALES - HORIZONTALLY IN BASEBOARD BENEATH CABINETS, AS SHOWN ON DRAWINGS, OR AS REQUIRED BY LOCAL CODES. B. NON -SALES - 18" FROM FINISHED FLOOR TO CENTERLINE OF OUTLET. 3. TELEPHONE OUTLETS SHALL BE LOCATED AS NOTED ON DRAWINGS. END CF SECTION 16134 SECTION 16140 - WIRING DEVICES A. THIS CONTRACTOR SHALL FURNISH AND INSTALL SWITCHES AND RECEPTACLES AS SHOWN ON THE DRAWINGS AND AS NECESSARY FOR A COMPLETE INSTALLATION. COLOR OF DEVICES AND PLATES SHALL BE SELECTED BY THE ARCHITECT. THE DEVICES SHALL BE OF THE TYPES AND RATINGS LISTED, OR EQUALS BY ARROW - HART, GENERAL ELECTRIC OR PASS & SEYMOUR. WEATHERPROOF G.F.I. RECEPTACLES SHALL BE INSTALLED WHERE SHOWN ON DRAWINGS OR AS REQUIRED BY CODE. 1. SINGLE POLE SWITCHES: 20 A - 125 v HUBBELL - 1221 2. THREE WAY SWITCHES: 20 A - 125 V HUBBELL - 1223 3. FOUR WAY SWITCHES: 20 A - 125 V HUBBELL - 1224 4. DUPLEX RECEPTACLES: 20 A - 125 V HUBBELL - 5362 5. ISOLATED GROUND RECEPTACLES: 20 A - 125 V HUBBELL - IG5362 6. FLOOR OUTLET BOX: STEEL CITY #841 7. FLOOR OUTLET BRASS COVER: STEEL CITY #P-64-1 OR P -64-p7, ADD "AL" FOR ALUMINUM 8. GROUND FAULT CIRCUIT INTERRUPTING RECEPTACLES: 20 A-125 V HUBBELL-GF5352 9. DIMMERS: LUTRON 10. MOTOR STARTERS: SQUARE D 11. EXHAUST FAN TIMER: MARK TIME 12. LIGHTING TIMERS: PARAGON 7007-0 (24 HOUR - 7 DAY TYPE) B. ALL DEVICE CO ERPLATES SHALL BE PASS AND SEYMOUR SERIES "RP" OR EQUAL. END OF SECTION 16140 SECTION 16155 - MOTOR STARTERS A. MANUAL MOTOR STARTERS WITH OVERLOAD PROTECTION MAY BE USED FOR FRACTIONAL HORSEPOWER MOTORS THAT DO NOT REQUIRE AUXILIARY CONTROL. THREE PHASE STARTERS SHALL BE PROVIDED WITH OVERLOAD DEVICE IN EACH PHASE h4ATCHED TO MOTOR NAMEPLATE RATING. MAGNCTIC MOTOR STARTERS SHALL BE ELECTRICALLY HELD (MINIMUM SIZE #1) AND BE USED FOR ALL SIraGLE PHASE AND THREE PHASE MOTORS RATED ABOVE 1/2 HP OR THAT REQUIRED AUXILIARY CONTROL. PROVIDE CONTROL DEVICES (AUXILIARY CONTACTS, TRANSFORMERS, ETC.) IN STARTERS AS REQUIRED FOR INTERLOCKS. COORDINATE WITH MECHANICAL CONTRACTORS. COMBINATION STARTERS SHALL CONTAIN FUSIBLE SWITCHES AND ONLY USED WHERE INDICATED ON DRAWINGS. B. MANUFACTURER SHALL BE SQUARE "D" OR EQUAL. END OF SECTION 16155 SECTION 16160 PANELBOARDS A. ALL PANELBOARDS SHALL BE FACTORY ASSEMBLED OF THE BOLTED CIRCUIT BREAKER TYPE WITH SOLID -COPPER BUSSING, FULL SIZED COPPER NEUTRAL, 100% GROUND BUSSING, AND OVERALL HINGED/LOCKABLE DOOR. ALL CIRCUIT BREAKERS SHALL BE OF THE QUICK -MAKE AND QUICK -BREAK DESIGN, THERMAL - MAGNETIC TYPE, TRIP FREE AND TRIP -INDICATING. ALL PANELS SHALL BE DEAD FROPlT AND FLUSH OR SURFACE MOUNTED AS SHOWN AND SHALL BE FURNISHED WITH A TYPEWRITTEN DIRECTOR CARD OF THE CIRCUITS AND AN ENGRAVED NAMEPLATE. B. CIRCUIT BREAKER PANELBOARDS SHALL HAVE FULL LENGTH NON-TAPERED BUS BARS ARRANGED AND DRILLED FOR SEQUENCE PHASING. C. ALL PANELS SHALL HAVE DOORS FLUSH WITH THE TRIM, EQUIPPED WITH LOCKS, AND KEYED ALIKE. ALL MULTI -POLE BREAKERS SHALL BE COMMON TRIP. D. ALL PANELBOARDS PHASE AMPERAGE SHALL BE BALANCED TO WITHIN 7 PERCENT MAX. TO MIN. REARRANGE NON -LIGHTING BRANCH CIRCUITS AS REQUIRED AND N H OTE AN N C GES 0 RECORD DRAWINGS. LIGHTING PANEL CIRCUIT BREAKERS MUST BE INSTALLED AND WIRED EXACTLY AS SHOWN ON DRAWINGS. E. PANELS SHALL BE AS INDICATED ON THE DRAWINGS. ALL BRANCH CIRCUIT BREAKERS (C/B) SHALL BE RATED 20 AMPERES SINGLE POLE MINIMUM, EXCEPT AS NOTED OR REQUIRED BY LOCAL CODES. F. PROVIDE LOCKOUT CLIPS ON NIGHT LIGHT, TIME CLOCK CONTROLLED, LIFE SAFETY, AND ALL OTHER CIRCUIT BREAKERS WHERE INDICATED ON PANEL SCHEDULE. PROVIDE 5 ADDITIONAL CLIPS TO BE INSTALLED AS DIRECTED BY THE OWNER. G. PRO`/IDE ONE SPARE 1" CONDUIT FOR EACH SIX SPACES OR SPARE CIRCUIT BREAKERS IN EACH RECESSED MOUNTED PANEL. MINIMUM 1 SPARE CONDUIT PER PANEL. RUN CONDUIT TO A LOCATED JUST ABOVE CEIJNG. H. ALL CIRCUIT BREAKERS FEEDING LIGHTING LOADS SHALL BE LISTED AND SHALL BE MARKED "SWD" (SWITCHING DUTY). REFER TO ELECTRICAL RISER DIAGRAM AND DRAWINGS FOR ADDIT'ONAL INFORMATION I. CIRCUIT BREAKERS SERVING HEATING, VENTILATION, AND/OR AIR CONDITIONING (HVAC) EQUIPMENT SHALL BE RATED AND MARKED "HACR", IF FUSING IS NOT PROVIDED AT PIECE OF HVAC EQUIPMENT. FIELD VERIFY EXACT "HACR" BREAKER REQUIREMENTS WITH HVAC EQUIPMENT NAMEPLATE AND MANUFACTURER'S REQUIREMENTS PRIOR TO INSTALLATION. J. IN SERVICE ENTRANCE APPLICATIONS, PANELS, SHALL BEAR THE MANUFACTURER'S !ABEL INDICATING THE EQUIPMENT IS RATED FOR SUCH APPLICATION IN ACCORDANCE WITH THE N.E.C. AND AS INDICATED ON DRAWINGS. K. PANELBOARDS MUST BE MOUNTED ON MINIMUM 3/4" A/D PLYWOOD AND PAINED TO A COLOR TO MATCH THE SURROUNDING WALLS OR A COLOR AS REQUIRED BY LOCAL CODE. PLYWOOD SHALL EXTEND 1 FOOT MINIMUM BEYOND EDGE 017 EQUIPMENT., L. PANELBOARDS SHALL HAVE A MINIMUM SHORT CIRCUIT CURRENT RATING AND LUG CONPJECTIOrJS AS FOLLOWS: 1. 120/208 VOLT PANELBOARDS: 10,000 A.I.C. 2. 277/480 VOLT PANELBOARDS: 14,000 A.I.C. 3. FUSIBLE DISTRIBUTION PANELBOARDS: 100,000 A.I.C. M. VERIFY ACTUAL A.I.C. SHORT CIRCUIT CURRENT REQUIREMENTS WITH UTILITY COMPANY PRIOR TO ORDERING EQUIPMENT. N. ALL LUG CONNECTIONS TO BE 75"C 0. PANELS SHALL BE MANUFACTURED BY SQUARE "D" OR EQUAL. END OF SECTION 16160 SECTION 16170 -SAFETY AND DISCONNECT SWITCHES A. SAFETY AND DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE, QUICK -MAKE, QUICK -BREAK FUSED OR NON -FUSIBLE WITH RATINGS AND SIZES AS NOTED ON PLANS AND REQUIRED BY CODES. B. SWITCHES SHALL BE WEATHERPROOF IN OUTDOOR LOCATIONS OR AS REQUIRED BY LOCAL CODES. C. DISCONNECT SWITCHES THAT ARE INSTALLED AT HEATING, VENTILATING AND AIR CONDITIONING (HVAC) EQUIPMENT SHALL BE FUSED IF NOT PROTECTED WITH A "HACR" BREAKER IN ACCORDANCE WITH THE EQUIPMENT'S NAMEPLATE AND MANUFACTURER'S REQUIREMENTS PER THE NATIONAL ELECTRICAL CODE, STATE AND LOCAL CODES. D. AT SERVICE ENTRANCE, DISCONNECT SHALL BEAR MANUFACTURER'S LABEL INDICATING THE EQUIPMENT IS UL RATED FOR APPLICATION IN ACCORDANCE WITH ALL CODES. E. MANUFACTURER SHALL BE SQUARE "D" OR EQUAL. END OF SECTION 16170 SECTION 16450 -GROUNDING A. PROVIDE COMPLETE WIRED GROUNDING CONDUCTOR SYSTEM, #12 AWG MINIMUM, SIZED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, STATE AND LOCAL CODES, THE LANDLORD'S TENANT CRITERIA AIJD AS NOTED IN THE SPECIFICATIONS AND AS INDICATED ON THE DRAWINGS. B. ALL CONDUIT, INCLUDING FLEXIBLE CONDUIT, SHALL BE GROUNDED WITH A GREEN GROUNDING CONDUCTOR. C. GROUNDING CONNECTIONS MADE TO THE WATER PIPING SYSTEM SHALL BE COORDINATED WITH THE PLUMBING CONTRACTOR AND BONDING JUMPERS SHALL BE INSTALLED PER CODES AND AS INDICATED ON DRAWINGS. D. ALL DEVICES SHALL BE BONDED TO THE CONDUIT SYSTEM. USE A BONDING JUMPER BETWEEN THE OUTLET BOX AND THE DEVICE GROUNDING TERMINAL. METAL -TO -METAL CONTRACT BETWEEN THE DEVICE YOKE AND THE OUTLET BOX IS NOT ACCEPTABLE AS A BOND FOR EITHER SURFACE MOUNTED BOXES OR FLUSH TYPE BOXES. ALL JUNCTION BOXES, OUTLET BOXES, AND PULL BOXES SHALL BE BONDED TO THE CONDUIT SYSTEM. E. RUN A SEPARATE ISOLATED GROUNDING CONDUCTOR, 012 AWG MINIMUM, IN EACH CONDUIT FEEDING THE HVAC CONTROL PANEL, AND OTHER COMPUTERIZED EQUIPMENT AS SHOWN ON DRAWINGS. FOR PANEL FEEDERS, BOND THE GROUNDING CONDUCTOR TO THE CONDUIT, WHERE ENTERING AND LEAVE THE CONDUIT. THE GROUNDING CONDUCTOR SHALL BE SIZED PER CODE, GREEN COLORED, COPPER WIRE. F. ALL ENCLOSURES AND NON-CURRENT CARRYING METAL PARTS ARE TO BE GROUNDED. CONDUIT SYSTEM IS TO BE ELECTRICALLY CONTINUOUS. ALL LOCK NUTS MUST CUT THROUGH ENAMELED OR PAINTED SURFACES ON ENCLOSURES. NIHERE ENCLOSURES AND NON-CURRENT CARRYING METAL PARTS ARE ISOLATED FROM TI -E CONDUIT SYSTEM, USE BONDING JUMPERS WITH APPROVED CLAMPS. ALL GROUND CLAMPS_ SHALL BE "PENN -UNION" OR EQUAL, SIMILAR TO "GPL" TYPE. END OF SECTION 16450 SECTION 16477 - FUSES A. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY FUSES FOR A COMPLETE INSTALLATION. B. FUSES FOR FEEDER CIRCUITS AND PANELBOARDS SHALL BE U.L. CLASS RKI FAST - ACTING TYPE. C. FUSES FOR MOTOR OVERCURRENT AND TRANSFORMER PROTECTION SHALL BE DUAL ELEMENT, U.L CLASS RKI TIME DELAY TYPE. D. FUSES MANUFACTURES: 1. BUSSMANN DIVISION 2. GENERAL ELECTRIC COMPANY 3. GOULD, INC. 4. LITTELFUSE, INC. END OF SECTION 16477 SECTION 16500 - LIGHTING FIXTURES AND LAMPS A. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL LIGHTING FIXTURES AND LAMPS AS SHOWN ON THE DRAWINGS.ALL FIRE RATED ENCLOSURES FOR ELECTRICAL LIGHTING FIXTURES, SPEAKERS, EQUIPMENT, ETC., SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. B. ALL RECESSED INCANDESCENT FIXTURES SHALL BE PROVIDED WITH APPLICABLE THERMAL PROTECTION. C. WHERE FLUORESCENT FIXTURES ARE SPECIFIED, THEY SHALL BE PROVIDED WITH HIGH POWER FACTOR RAPID START BALLASTS, U.L. LISTED, C.B.M. CERTIFIED AND E.T.L. APPROVED. D. THIS CONTRACTOR SHALL FURNISH ADDITIONAL AUXILIARY SUPPORT STEEL HANGER WIRED ADEQUATELY SIZED TO SUPPORT THE WEIGHT OF THE FIXTURE FASTENED TO THE BUILDING STRUCTURE (MINIMUM TWO PER FIXTURE) FOR ALL FIXTURES IN LAY -IN CEILINGS AND OTHER FIXTURES AS REQUIRED BY THE LOCAL CODE OFFICIALS. E. THIS CONTRACTOR SHALL VERIFY THE MODEL NUMBERS AND QUANTITY OF ALL LIGHT AND FIXTURES PROVIDED BY THE OWNER. CONTACT THE OWNER'S CONSTRUCTION MANAGER IMMEDIATELY IF THE MODELS DIFFER FROM THOSE LISTED ON THE LIGHTING FIXTURE SCHEDULE OR IF THEY DO NOT HAVE PROPER THERMAL PROTECTION. F. PROVIDE APPLICABLE FIRE RATED DRYWALL BOXES OVER RECESSED FIXTURES IN FIRE RATED CEILINGS AS REQUIRED BY CODES. FIELD COORDINATE AS REQUIRED TO AVOID CONFLICTS. END OF SECTION 16500 SECTION 16740 -TELEPHONE DATA AND COMPUTER WIRING A. PROVIDE A SYSTEM OF CONDUIT RACEWAYS, OUTLET BOXES, PULL WIRES, AND TERMINAL BOARDS AS SHOWN ON THE DRAWINGS UNLESS OTHERWISE NOTED ON PLANS. TELEPHONE SWITCHING APPARATUS, CONDUCTORS, INSTRUMENTS, MISCELLANEOUS EQUIPMENT AND APPURTENANCES ARE NOT PART CF THIS CONTRACT AND WILL BE PROVIDED AND INSTALLED BY THE OWNER. B. OUTLET BOXES TO BE 4" SQUARE MINIMUM WITH SINGLE FOR DEVICE COVER AND TELEPHONE PLATE WITH CONDUIT DROP AND PULL WIRE TO ABOVE CEILING. C. ALL PULL WIRES ARE TO BE LABELED FOR PURPOSE DESIGNATED. D. NO OTHER CIRCUITS ARE TO BE RUN IN SAME CONDUIT FEEDING ISOLATED GROUND RECEPTACLES. E. PROVIDE A 3/4" THK X 36" X 72" ACX PLYWOOD BOARD MOUNTED VERTICALLY AT 12" A.F.F. FOR MOUNTING TELEPHONE EQUIPMENT, PLYWOOD SHOULD BE PAINTED WITH HIGH QUALITY GRAY OIL BASE PAINT ON BOTH SIDES, FRONT, AND BACK. END OF SECTION 16740 com Q°�- 0 0`3cv E ^�O o61 } •V O U <= p...._4 W ) a -n - cl= 4V)_.c fl- > tca4) C.� 70� _ w t` QCL C Ud y > qd' rncn crD 0 c 00 F- =" "p 4-0 q> �p 04 = ^ C=) fV _ � J �_ " V_�,/.� .O � ftmAD ,p.-..♦ � to `. a r- M � C.1)C.1)= U C a C "=J --X c Q 'v � F/�/ Q°�- 0 0`3cv E ^�O o61 } •V O U W ) a -n - 0 4V)_.c > tca4) (V 70� _ w QCL C Ud ZLUoa _ O D N Z O a I - 01 j = 0) Tm 015 0 Lo r W IIIIIIIIIIIII 0 "I- IIIIIIIIIIIIIIIIIII 0 = Q ® ��� LU 0. d v = CC iii in ICE 103 LL'V� =�IIIIIIIIIIIIIIIIIIIII %n °O LTi 0 a)2cCL LU m 0 cc WIZ Iv Loy Q = O 9m p V- Lia Z M=. Revisions: ``0%,%%II111111ll., ' %�,K S' FRS s i `% •�©1 ST fj pF,o .� 1 i No. ' =*. =x:60910220 0: STATE OF * 4 AA '�, F ' SND I AN* ' 1z, 1-1 I �NA%%%% � 111111 Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: / t TITi i 9225 USF � 4 Suite 100 I— — I VITEf q'TTL_ — I 3,0:2 USF TO ABOVE CEILING FOR FUTURE USE. (TYPICAL ALL RECEPTICALS AND DATA OUTLETS) 5 I i ELECTRICAL PLAN N SCALE: 1/8" =1'-0" PROVIDE JUNCTION BOX AND TZAA TO ABOVE -CEILING FOR FUIU (TYPICAL. ALL RECEPTICALS AND i & FRANRENFl,.;AGER, PENDING 4,606 uSFI I i TO ABOVE CEILING FOR FUTURE USE (TYPICAL ALL RECEPTICALS AND DATA OUTLETS) LIGHT FIXTURE SCHEDULE SYMBOL MANUFACTURER CATALOG # DESCRIPTION MOUNTING VOLTS NOTES LAMPS -7 DAY-BRF1E 2P4GAM2R-365L- 12D-1/3EB 3 TUBE, . 2' X 4' 18 CELL FLUORESCENT PARALOUVER LAY -IN 12p FIXTURES MARKED NL FOR NIGHTLIGHT USE REUSE AS MANY EXISTING LIGHTS AS AVAILABLE (3) 38 W T8 GROUND FAULT INTERUPT OUTLET +15 ABOVE FINISHED FLOOR U.N.O. . QGn WP=WEATHER PROOF COVER FOUR PLEX OUTLET +15 ABOVE FINISHED FLOOR, TYPICAL USE LIGHTS WITH BATTERIES FOR NIGHT LIGHT'S UNLESS NOTED OTHERWISE. NO MORE THAN 3 PER CIRCUIT. OJUNCTION J LITHONIA LHQM SW 3R 120 COMBINATION EXff/EMERG. WITH BATTERY PACK SURFACE 120 cc LED ELECTRICAL SYMBOLS SYMBOL DESCRIPTION v J ELECTRICAL PANE, FIELD VERIFY -LOCATION. SEE EIECTRICAI RIS ® FOR MORE INFORMATION AND WORK RESPONSIBILITY W SWITCH D=DIMMER M=MOTION SENSOR -7 N"pMM�� DUPLEX OUTLET +15 ABOVE FINISHED FLOOR, TYPICAL UNLESS NOTED OTHERWISE OUTLETS SHALL NOT BE IN MIRRORS, ADJUST LOCATIONS ACCORDINGLY VERIFY CHANGES WITH TMW OR ARCHITECT. GROUND FAULT INTERUPT OUTLET +15 ABOVE FINISHED FLOOR U.N.O. . QGn WP=WEATHER PROOF COVER FOUR PLEX OUTLET +15 ABOVE FINISHED FLOOR, TYPICAL .c �E 1_ UNLESS NOTED OTHERWISE. NO MORE THAN 3 PER CIRCUIT. OJUNCTION J BOX O N TELEPHONE/DATA BOX MOUNTED AT 15' AFF WITH CONDUIT TO ABOVE COUNG. ? PROVIDE PULL STRING. O r 06 O Lt's r O co r W W i O 1� Q � Z =a LU LLI 0 y LL. g LL. y m OWO W ��a = Opp rWZ Revisions: Z mi CL J Q C9 v LUmmiW ,�,K S. Sick— No. ' - * 0220'rc 0 STATE OF r 0 NAL Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: v J i 10 O O U � cc M M0 � W 9^^ C -7 N"pMM�� CX� 0 L N Q N 0 o W .c �E 1_ C.� N Z N t\ O N r =� ? co rn cc : °O r__ ` 0 G� DDlo CV 0 Cos. 00 �. caN co c a 4- O r 06 O Lt's r O co r W W i O 1� Q � Z =a LU LLI 0 y LL. g LL. y m OWO W ��a = Opp rWZ Revisions: Z mi CL J Q C9 v LUmmiW ,�,K S. Sick— No. ' - * 0220'rc 0 STATE OF r 0 NAL Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: v J i 10 O O U � cc M M0 � W 9^^ C -7 N"pMM�� CX� 0 L N Q N V o W .c �E 1_ N Z O N 01 O r 06 O Lt's r O co r W W i O 1� Q � Z =a LU LLI 0 y LL. g LL. y m OWO W ��a = Opp rWZ Revisions: Z mi CL J Q C9 v LUmmiW ,�,K S. Sick— No. ' - * 0220'rc 0 STATE OF r 0 NAL Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: SECTION 15010 - BASIC MECHANICAL REQUIREMENTS A. DEFINITIONS AND TERMS . 1. HE WORD "OWNER" SHALL MEAN 'CELADON TRUCKING SERVICES, INC.", OR ANY REPRESENTATIVE OF HIS PARTY.DULY AUTHORIZED TO ACT IN HIS BEHALF IN HE EXECUTION OF THE WORK. 2. HE WORD "CONTRACTOR" SHALL MEAN HE PERSON, FIRM OR CORPORATION ENTERING INTO A CONTRACT OR AGREEMENT WITH THE OWNER TO CONSTRUCT ND COMPLETE HE WORK AS SHOWN ON HE DRAWINGS ND SPECIFIED HEREIN. 3. HE WORD "ARCHITECT ND ENGINEER" SHALL MEAN "PETERSON ARCHITECTURE" AND FROST ENGINEERS, INC' ND HEIR REPRESENTATIVES ACTING AS THE OWNER'S APPOINTED AGENT. 4. HE WORD "FURNISH" SHALL MEAN TO SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION AND SIMILAR SUBSEQUENT REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND CALLED ON THE DRAWINGS AND SPECIFIED HEREIN. 5. THE WORD "INSTALL" SHALL MEN OPERATIONS AT THE PROJECT SiTE, INCLUDING, BUT NOT LIMITED TO, UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION. FINISHING, CURING, PROTECTING, CLEANING, AND SIMILAR REQUIREMENTS FOR A COMPLETE SYSTEM AS SHOWN AND ON THE DRAWINGS AND SPECIFIED HEREIN. 6. HE TERM "PROVIDED" SHALL BE INTERPRETED AS MEANING "FURNISHED AND INSTALLED" BY HIS CONTRACTOR WITH THE EXCEPTION WHERE ITEMS ARE PROVIDED BY THE OWNER' WHICH MEANS "FURNISHED ONLY' AND INSTALLED BY THIS CONTRACTOR, UNLESS NOTED OTHERWISE. B. SUMMARY OF WORK 1. HIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, PERMITS, SERVICES, TOOLS, PERSONNEL, TRNSPORTATION AND FACILITIES NECESSARY FOR AND REASONABLY IMPLIED, ANO INCIDENTAL TO, THE FURNISHING, INSTALLATION, COMPLETION TESTING AND BALNCING OF ALL THE WORK FOR ALL INSTALLED SYSTEM§ AS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN ND AS REQUIRED BY JOB CONDITIONS. THESE CONDITIONS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING: A A COMPLETE HVAC SYSTEM INCLUDING SUPPLY, RETURN AND EXHAUST AIR DUCTWORK, SUPPLY AIR DIFFUSERS RETURN AIR GRILLES EXHAUST AIR GRILLES, DUCTWORK INSULATION, FIYTiNGS, HVAC EQUIPMENT, DAMPERS ROOF CURBS ND CAPS, EXHAUST FANS, CONTROL WIRING, ETC., AND ALL RELATED COMPONENTS NECESSARY FOR A COMPLETE INSTALLATION AS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN. B. A COMPLETE PLUMBING SYSTEM INCLUDING SANITARY WASTE, VENTS, DRAINS, DOMESTIC COLD AND HOT WATER PIPING SYSTEM PIPE HANGERS, PiPE INSULATION, VALVES, PLUMBING FIXTURES AND EQUTAMENT, NATURAL GAS PIPING, ETC., AND ALL RELATED COMPONENTS NECESSARY FOR A COMPLETE INSTALLATION AS SHOWN AND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN. C. GENERAL REQUIREMENTS 1. H S CONTRACTOR SHALL VERIFY HE EXTENT OF ALL EXISTING CONDITIONS, UTILITY CONNECTION POINTS, EQUIPMENT PROVIDED BY OTHERS, ETC., AS SHOWN ND CALLED FOR ON THE DRAWINGS AND REPORT ANY _DISCREPANCIES INS AND SPECIFICATIONS. NO RE UIRED TO MEET H E INTENT OF THE DRAW G Q ADDITIONAL COMPENSATION SHALL BE AWARDED TO THIS CONTRACTOR FOR FAILURE OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. FAILURE OF KNOWLEDGE OF EXISTING CONDITIONS BY VISITING THE SITE PRIOR TO BIDDING DOES NOT RELIEVE THIS CONTRACTOR OF RESPONSIBILITY IN WORK OR WORKMANSHIP. 2. HE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK, AND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE PROVIDED AS PART OF THIS CONTRACT. 3. RE-OCATION OF ANY EXISTING WATER, GAS, WASTE, VENT, DRAINAGE LINES, DUCTWORK, EQUIPMENT, ETC., TO FACILITATE STORE DESIGN CRITERIA MUST BE INCLUDED IN BID PROPOSAL. THIS CONTRACTOR SHALL NOT REMOVE OR RELOCATE ANY LANDLORD EQUIPMENT, PIPING, ETC., WITHOUT PRIOR WRITTEN APPROVAL FROM THE LANDLORD - 4. ALL WORK BY HIS CONTRACTOR SHALL BE INSTALLED SO AS TO BE READILY 5. ALL ROOF CUTTING, PATCHING ND FLASHING SHALL BE BY THE OWNER'S ROOFING CONTRACTOR OR OWNER'S APPROVED ROOFING CONTRACTOR AT THIS CONTRACTOR'S EXPENSE. COORDINATE ALL ROOF PENETRATIONS WIH HE OWNER. MAINTAIN ALL CODE REQUIRED CLEARANCES FROM ALL OUTSIDE AIR OR FRESH AIR INTAKES LOCATED ON THE ROOF. 6. THIS CONTRACTOR SHALL PROVIDE ANY ADDITIONAL STRUCTURAL STEEL OR SUPPORTS TO SUPPORT ANY INSTALLED EQUIPMENT AS SHOWN AND CALLED FOR ON HE DRAWINGS OR IN THE SPECIFICATIONS. THIS CONTRACTOR SHALL COORDINATE ALL ADDITIONAL STEEL OR SUPPORT LOCATIONS WITH THE OWNER PRIOR TO BIDDING AND INSTALLATION. 7. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF OF HE FLOOR FOR ALL INSTALLED PIPING, DRAINS, SLEEVES, ETC., AS SHOWN ND CALLED FOR ON HE DRAWINGS OR SPECIFIED HEREIN. COORDINATE ALL FLOOR CUTS WITH HE OWNER AND ANY AFFECTED TENANTS. CUTTING AND PATCHING SHALL BE HELD TO A MINIMUM. 8. HIS CONTRACTOR SHALL COORDINATE ALL ROOF MOUNTED EQUIPMENT LOCATIONS WiTH THE OWNER PRIOR TO INSTALLATION. 9. ALL ROOF TOP MECHANICAL EQUIPMENT SHALL BE IDENTIFIED WITH A MINIMUM TWO INCH (2") HIGH LETTERING INDICATING THE UNIT DESIGNATOR. REFER TO THE AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) FOR LETTERING SIZE, LENGTH OF COLOR FIELD, COLORS AND VIEWING ANGLES OFF ID NTIFiCATION DEVICES. D. CODES FEES AND MISCELLANEOUS COSTS 1. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE CODES, SPECIFICATIONS, LOCAL ORDINANCES, INDUSTRY STANDARDS, OWNER REQUIREMENTS AND UTILITY COMPANY REGULATIONS. 2_ IN CASES OF DIFFERENCE BETWEEN BUILDING CODES, SPECIFICATIONS, STATE ZLAWS, LOCAL ORDINANCES INDUSTRY STANDARDS, OWNER REQUIREMENTS, TY COMPANY REGULATIONS AND THE CONTRACT DOCUMENTS, HE MOST STRINGENT SHALL GOVERN. THIS CONTRACTOR SHALL PROMPTLY NOTIFY THE ARCHITECT IN WRITING OF ANY SUCH DIFFERENCE. W R THAT DOES NOT 3. NON-COMPLIANCE: SHOULD THE CONTRACTOR PERFORM ANY 0 K COMPLY WITH THE REQUIREMENTS OF APPLICABLE BUILDING CODES STATE LAWS LOCAL ORDINANCES, INDUSTRY STANDARDS, LANDLORD REQUIREMENYS, UTILITY CbMPNY REGULATIONS OR THE CONTRACT DOCUMENTS, THIS CONTRACTOR SHALL BEAR ALL COSTS ARISING FOR HE CORRECTION OF NON -COMPLYING ITEMS. 4. APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL FEDERAL ND STATE LAWS, LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES ND STANDARDS. HOSE RECUIREMENTS ARE TO BE CONSIDERED A MINIMUM AND ARE TO BE EXCEED WHEN SO INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN. THIS CONTRACTOR SHALL INQUIRE INTO AND COMPLY WITH ALL APPLICABLE CODES AND STANDARDS AND ANY CHANGES OR MODIFICATIONS TO THE DRAWINGS OR SPECIFICATIONS AS REQUIRED BY HE CODES SHALL BE INCLUDED IN THE BID. NO ADD ITIONAL COMPENSATION SHALL BE AWARDED TO THE CONTRACTOR FOR FAILURE OF CODE INQUIRY OR COMPLIANCE. PERMIT PAYMENT OF 5. Ht5 CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL S, ALL FEES, NECESSARY DRAWINGS AND ARRANGING AND PAYING FOR ALL INSPECTIONS, TESTS, ETC., WHICH MAY BE REQUIRED BY ANY AUTHORITY OR UTILITY COMPANY IN CONNECTION WITH THE FURNISHING OR INSTALLATION OF ANY OF HIS RESPECTIVE WORK_ MA SHIP E. WORK AND WORK N 1. ALL MATERIALS AND EQUIPMENT SHALL BE OF THE HIGHEST QUALITY IN EVERY RESPECT. AL1 MATERIALS AND EQUIPMENT SHALL BE NEW, UNLESS NOTED OTHERWISE. OF HE LATEST DESIGN AND FREE OF DEFECTS. 2. WORKMANSHIP SHALL BE BY SKILLED WORKMEN OF HIGHEST STANDARD IN STRICT ACCORDANCE WITH ALL APPLICABLE MANUFACTURERS PRINTED SPECIFICATIONS, PERFORMED UNDER SUPERVISION OF COMPETENT FOREMAN AT ALL TIMES. 3. THE OWNER AND THE ARCHITECT HAVE FULL POWER TO CONDEMN OR REJECT ANY WORK, MATERIALS OR EQUIPMENT NOT IN ACCORDANCE WITH THESE SPECIFICATIONS AND DRAWINGS OR ARE NOT IN CONFORMANCE WITH THE MANUFACTURES SPECIFICATIONS OR DRAWINGS WHICH WERE APPROVED BY THE OWNER OR ENGINEER. 4. WORK OR EQUIPMENT THAT IS REJECTED SHALL BE REMOVED AND REPLACED TO THE SATISFACTION OF THE OWNER OR ARCHITECT AT THIS CONTRACTORS EXPENSE. WORK OR EQUIPMENT THAT IS REJECTED SHALL BE SO STATED IN WRITING BY THE OWNER OR THE ENGINEER. 5. SUCH DECISIONS AS THE OWNER OR THE ENGINEER MAY MAKE WITH RESPECT TO QUESTIONS CONCERNING THE QUALITY, FITNESS OF MATERIALS, EQUIPMENT AND WORKMANSHIP SHALL BE BINDING UPON THE PARTIES HERETO. F. DEVIATIONS FROM DRAWINGS i. THE DRAWINGS SHOW THE INTENDED ARRANGEMENT AND ROUTING OF ALL PIPING, DUCTWORK, EQUIPMENT AND APPURTENANCES. THEY SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND WORK OF OTHER TRADES WILL PERMIT. 2. THIS CONTRACTOR SHALL INVESTIGATE STRUCTURAL AND FINISH CONDITIONS AFFECTING HIS WORK AND SHALL PROVIDE ANY FITTINGS, OFFSETS AND ACCESSORIES REQUIRED TO ACCOMMODATE SAID CONDITIONS IN THE BID PROPOSAL 3. WHERE TRADE NAMES ND MNUFACTURES ARE USED ON HE DRAWINGS OR SPECIFIED HEREIN, THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR HE BAS= BID. MANUFACTURES CONSIDERED AS AN EQUAL OR BETTER IN ALL ASPECTS TO HAT SPECIFIED WILL BE SUBJECT TO APPROVAL IN WRITING BY THE OWNER OR THE ARCHITECT PRIOR THROUGH SHOP DRAWING OR SUBMITTAL PROCESS, TO ACCEPTANCE. THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT THIS CONTRACTORS EXPENSE. 4. HE DRAWINGS INDICATE AN INSTALLED SYSTEM BASED UPON SELECTED MNUFACTURERS OF EQUIPMENT. ELECTRICAL SERVICES, SIZE, CONFIGURATIONS, ETC., ARE CONSISTENT WITH HE MANUFACTURER'S RECOMMENDATIONS. OHER MANUFACTURERS ARE ENCOURAGED TO =URNISH EQUIPMENT FOR THIS PROJECT; HOWEVER, IT SHALL BE THIS CONTRACTORS RESPONSIBILITY TO ASSURE THAT THE EQUIPMENT IS CONSISTENT WITH THE DESIGN BASE. NO ADDITIONAL COMPENSATION SHALL BE AWARDED FOR REVISIONS, MODIFICATIONS, ETC., TO ELECTRICAL SERVICES, WIRING, BREAKERS, SPACE, CLEARANCE, DUCTWORK, PIPING, ETC., REQUIRED BY OHER MANUFACTURES. G. OCCUPATIONAL SAFETY AND HEALTH ACT 1. ALL WORK SHALL BE COMPLY WITH THE CURRENT REQUIREMENTS QF HE U.S. DEPARTMENT OF LABOR OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, ENTITLED OCCUPATIONAL SAFETY AND HEALTH STANDARDS; NATIONAL CONSENSUS STANDARDS ND ESTABLISHED FEDERAL STANDARDS. H. COORDINATION BETWEEN CONTRACTORS 1. BEFORE THE COMMENCEMENT OF ANY WORK, THIS CONTRACTOR SHALL EXAMINE ALL HE ARCHITECTURAL.. MECHANICAL AND ELECTRICAL DRAWINGS AND SPECIFICATIONS TO SEQUENCE, COORDINATE AND INTEGRATE THE VARIOUS COMPONENTS OF THE INSTALLED SYSTEMS, MATERIALS, PIPING, EQUIPMENT, ETC., WITH OHER TRADE CONTRACTORS TO AVOID OHER TRADE INTERFERENCES AND CONFLICTS. 2. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TG LEAVE THE REQUIRED. NECESSARY ROOM FOR OHER TRADES. NO ADDITIONAL COMPENSATION SHALL BE AWARDED TO THIS CONTRACTOR FOR FAILURE TO COORDINATE WiTH OTHER TRADE CONTRACTORS TO AVOID OTHER TRADE INTERFERENCES, CONFLICTS, RELOCATION OF DUCTWORK, PIPING, EQUIPMENT, ETC., FOUND ENCROACHING ON SPACE REQUIRED BY OTHERS. 3. HIS CONTRACTOR SHALL PROVIDE COMPLETE INFORMATION AND COOPERATION TO THE OHER CONTRACTORS AND TRADES PERTAINING TO HIS WORK TO ACCOMPLISH COORDINATION OF THE COMPLETED PROJECT. I. EQUIPMENT DRAWINGS 1. THIS CONTRACTOR SHALL PROVIDE EQUIPMENT_ DRAWINGS OF PROVIDED EQUIPMENT AS SPECIFIED HEREIN. 2. THE FOLLOWING ITEMS ARE A MINIMUM REQUIREMENT FOR EACH EQUIPMENT DRAWING SUBMITTAL - A. SHEET SIZE 8-i/2" X 11"_ B. MANUFACTURE'S STANDARD SCHEMATIC DRAWINGS: 1. MODIFY DRAWINGS TO DELETE INFORMATION THAT IS NOT APPLICABLE TO THIS PROJECT. 2. SUPPLEMENT STNDARD INFORMATION TO PROVIDE ADDITIONAL INFORMATION APPLICABLE TO THIS PROJECT. C. MANUFACTURER'S CATALOG SHEETS, BROCHURES, DIAGRAMS, SCHEDULES, PERFORMANCE CHARTS, ILLUSTRATIONS AND OTHER STANDARD DESCRIPTIVE DATA. 1. CLEARLY MARK EACH COPY TO IDENTIFY PERTINENT MATERIALS, PRODUCTS, MODELS, ETC. 2. SHOW EQUIPMENT DIMENSIONS AND MAINTENANCE OR CONSTRUCTION CLEARANCES REQUIRED. 3. SHOW PERFORMANCE CHARACTERISTICS AND CAPABILITIES. 4. SHOW WIRING DIAGRAMS AND CONTROLS. 5. MATERIAL AND SAFETY DATA SHEETS. 6. THE FULL MANUFACTURE'S MODEL NUMBER OF EACH ITEM. 7. IDENTIFICATION OF COLOR OR FINISHES. 8. THIS CONTRACTOR'S STAMP, SIGNATURE AND DATA SHALL BE AFFIXED TO EACH COPY OF THE SHOP DRAWINGS WITH INDICATION OF HIS REVIEW. 3. COPIES OF THE EQUIPMENT DRAWINGS AND ALL OHER RELATED INFORMATION MUST APPEAR IN HE OPERATIONS MANUAL LEFT ON SITE AFTER PROJECT COMPLETION. J. RECORD DRAWINGS 1. DURING CONSTRUCTION THIS CONTRACTOR SHALL MAINTAIN A COMPLETE AND LEGIBLE SET OF DRAWINGS SHOWING CHANGES AND DEVIATIONS BETWEEN ACTUAL CONSTRUCTION AND THE ENGINEER'S DRAWINGS. 2. AT THE COMPLETION OF THE PROJECT AND BEFORE FINAL ACCEPTANCE, THIS CONTRACTOR SHALL MAKE ANY FINAL CORRECTIONS TO THE DRAWINGS AND CERTIFY HE ACCURACY OF T R' TAMP AND IGNATURE EACH PRIM WiTH THIS CONTRAC 0 S 5 S HEREON. HIS COPY OF HE RECORD DRAWINGS SHALL BE PLACED IN A DRAWING TUBE AND MARKED 'RECORD DRAWINGS - DO NOT REMOVE FROM PREMISES' AND SHALL BE KEPT WITH THE OPERATIONS MANUAL K. OPERATIONS MANUAL 1. THREE COPIES OF THE OPERATIONS ND MAINTENANCE MANUAL FOR ALL EQUIPMENT 3�NTHREE (3) RHING BINDERS. SHALL BE COLLECTED ND INSERTED IN LABELED THREE INCH 2. OPERATIONS ND MAINTENANCE MANUALS SHALL BE ASSEMBLED AS FOLLOWS: A SECTION 1 1. TITLE OF PROJECT 2. LOCATION OF PROJECT 3. NAME AND ADDRESS OF OWNER 4. NAME ND ADDRESS OF ENGINEER 5. NAME ND ADDRESS OF THIS CONTRACTOR. B. SECTION 2 i. SHOP DRAWINGS OF ALL APPROVED EQUIPMENT. C. SECTION 3 1. A LISTING OF ALL EQUIPMENT WARRANTIES INDICATING THE EQUIPMENT MODEL NUMBER, SERIAL NUMBER, START ND ENDING DATE ON' THE WARRANTY, ETC. D. SECTION 4 1. COPIES OF ALL AIR AND WATER BALANCE REPORTS. 3. EACH SECTION SHALL BE SEPARATED BY A PASTEBOARD TABBED DIVIDER. 4. ALL INFORMATION SHALL BE ARRANGED IN AS MANY BINDERS AS NECESSARY. 5. OPERATION AND MAINTENANCE MANUAL AND DRAWING TUBE SHALL BE SENT TO THE ENGINEER. L INSPECTIONS. FINAL REPORTS AND GUARANTEE 1. AT THE COMPLETION OF THE WORK, THIS CONTRACTOR SHALL INFORM THE LOCAL ND STATE AUTHORITIES AND THE OWNER TO ARRANGE FOR FINAL INSPECTIONS OF THIS WORK. 2. THIS CONTRACTOR SHALL FURNISH TO THE OWNER ALL CERTIFICATES OF INSPECTION AND FINAL INSPECTION APPROVAL AT THE COMPLETION OF THIS PROJECT. 3. THIS CONTRACTOR SHALL SUBMIT TO THE OWNER UPON COMPLETION OF THIS WORK T 1 W RK IS IN ACCORDANCE W R C RTIF'`YING THA H S 0 A LETTE E ffH ALL APP CAB U LE STATE NO LOCAL LAWS, LOCAL ORDINANCES, OWNER REQUIREMENTS, UTILITY COMPANY REGULATIONS AND APPLICABLE REQUIREMENTS OF NATIONALLY ACCEPTED CODES ND STANDARDS. 4. THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT, WORK, ETC., UNDER THIS CONTRACT FOR ONE (J YEAR AFTER THE ACCEPTANCE OF ALL SYSTEMS INSTALLED BY THIS CONTRACTOR UNDtE�R THIS CONTRACT. THIS CONTRACTOR SHALL MAKE GOOD, REPAIR OR REPLACE AT THIS CONTRACTORS OWN EXPENSE, ANY DEFECTIVE WORK MATERIAL, OR EQUIPMENT WHICH MAY BE DISCOVERED FORM THE DATE OF ACCEPTANCE, IN WRITING. EXTENDED WARRANTIES ARE AS SPECIFIED WiTH THE INDIVIDUAL EQUIPMENT. 5. UNDER THE ONE (1) YEAR GUARANTEE PERIOD THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO HE PREMISES CAUSED BY DEFECTS IN ANY WORKMANSHIP OR 1 Y N7 IPM T RANI HES AND OR NSTALLED B THIS CO ANY EQU EN FU S / R,ACTOR. M. SLEEVES 1. THIS CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN THE INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH IT'S RESPECTIVE FLOOR, WALL OR PARTITION AND SHALL BE CUT FLUSH WiTH EACH SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL EXTEND TWO INCHES (2') ABOVE HE FLOOR. 2. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOH EDGES. FOR OTHER THAN MASONRY PARTITIONS THROUGH SUSPENDED CEILINGS, OR FOR CONCEALED VERTICAL PIPING, SLEEVES SHALL BE NO. 22 U.S.G. GALVANIZED STEEL MINIMUM. N. FIRE STOPPING i. ALL OPENINGS THROUGH FIRE RATED WALLS ND/OR FLOORS FOR CONDUITS SHALL BE FIRE SEALED IN ACCORDNCE WITH NFPA 101 WITTH CALCIUM SILICATE, SILICONE 'RTV" FOAM. 3M FIRE RATED SEALANTS OR EQUAL. SO AS TO RETAIN THEIR FIRE RATING. PROVIDE SLEEVES AS REQUIRED BY ALL APPLICABLE CODES OR OWNER REQUIREMENTS. (INCLUDING FACTORY MUTUAL)) FIELD VERIFY ALL EXISTING PENETRATIONS THROUGH FIRE WALLS AND/OR FLOORS AND SEAL A5 REQUIRED IN ACCORDNCE WiTH NFPA 101 AS LISTED ABOVE. 0, P865ING REQUIREMENTS 1. THIS CONTRACTOR- SHALL INCLUDE__ IN HIS. BID ALL_ NECESSARY SERVICES_ REQUIRED TO KEEP SECTION 15145 - HANGERS AND SUPPORTS A. RELATED WORK 1. MECHANICAL INSULATION: SECTION 15250 B. MANUFACTURES 1. BI -LINE 2. FEE AND MASON 3. GRINNELL 4. MICHIGAN HANGER COMPANY C. INSTALLATION 1. HNGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, BANDS, C -CLAMPS WITH RETAINING CLIPS, CHANNELS, HNGER RODS, ETC., NECESSARY FOR THE COMPLETE INSTALLATION OF WORK. 2. HNGERS SHALL BE FASTENED TO THE BUILDING STEEL, CONCRETE, OR MASONRY, BUT NOT TO EQUIPMENT OR PIPING. HNGING FROM METAL DECK SHALL NOT BE PERMITTED. HANGERS SHALL BE ATTACHED TO THE UPPER CHORD OF THE BAR JOIST. WHERE INTERFERENCES OCCUR, AND IN ORDER TO SUPPORT DUCTWORK OR PIPING, THIS CONTRACTOR SHALL INSTALL TRAPEZE TYPE HNGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS DOORS TO FIRE DAMPERS, VALVES, EQUIPMENT ETC. HANGER TYPES AND INSTALLATION METHODS SHALL BE SUBJECT TO ALL AOPUCABLE CODES AND HE LANDLORD REQUIREMENTS. VERIFY ANY LANDLORD REQUIREMENTS PRIOR TO BIDDING. 3. HANGERS OR SUPPORTS FOR EQUIPMENT, PIPING DUCTWORK, ETC., SHALL NOT BE SUPPORTED FROM HE LANDLORD'S CEILING, SOFFITS, NEUTRAL PIERS, PIPING, DUCTWORK, METAL ROOF DECK, LATERAL BRACING, BRIDGING, ELECTRICAL CONDUITS, ETC. 4. HNGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR HE OUTER DIAMETER OF INSULATION. INSTALL SIX INCH (6 LONG SPLIT CIRCLE GALVANIZED HN AND THE PIPE IN ULATION. R SADDLE BETWEEN THE GER EFER TO THE DRAWINGS FOR PIPE HNGER DETAILS. 5. HNGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI -ELECTRICALLY SEPARATED. 6_ PROVIDE SWAY AND SEISMIC BRACING WHERE REQUIRED BY THE OWNER OR CODE. END OF SECTION 15145 SECTION 15241 - VIBRATION ISOLATION A. RELATED WORK 1. HNGERS AND SUPPORTS: SECTION 15145 2. HEATING, VENTILATION ND AIR CONDITIONING: SECTION 15800 B. MANUFACTURES 1. AMBER/BOOTH COMPANY 2. KORFUND DYNAMICS CORPORATION 3. MASON INDUSTRIES, INCORPORATED 4. PEABODY NOISE CONTROL, INCORPORATED 5. KINETICS NOISE CONTROL, INCORPORATED C. INSTALLATION 1. VIBRATION ISOLATION DEVICES SHALL BE PROVIDED IN ALL SUPPORTS BETWEEN VIBRATING EQUIPMENT. FANS, ROOF TOP AIR CONDITIONING EQUIPMENT, EXHAUST FNS, ETC., AND THE BUILDING STRUCTURE. 2. VIBRATING EQUIPMENT HUNG FROM THE STRUCTURE SHALL BE ISOLATED WITH RUBBER AND SPRING DEVICES. VIBRATING EQUIPMENT SUPPORT FROM THE FLOOR OR DECK SHALL BE ISOLATED WITH HOUSED SPRING MOUNT DEVICES. 3. EXAMINE DEAD LOAD AND OPERATING LOAD CONDITIONS WHEN SELECTING DEVICES. ADJUST FOR PROPER ALIGNMENT AND LOADING. AVOID GROUNDING" THE ISOLATOR. 4. CHECK HANGER ROD SIZE FOR ALLOWABLE LOADS AT THE ISOLATING DEVICE AND AT HE UPPER NO LOWER ATTACHMENTS TO THE STRUCTURES, EQUIPMENT,ETC. 5. CONSULT MANUFACTURER FOR FURHER APPLICATION AND INSTALLATION DATA END OF SECTION 15241 SECTION 15250 - MECHNICAL INSULATION A. jtELATED WORK 1. HNGERS AND SUPPORTS: SECTION 15145 2_ PLUMBING: SECTION 15400 3. HYDRONIC/REFRIGERANT PIPING: SECTION 15500 4. HEATING, VENTILATION ND AIR CONDITIONING: SECTION 15800 B. PRODUCTS 1. BLNKET INSULATION WITH ALUMINUM FOIL FACING A CERTAIN TEED CORPORATION. B. KNAUF FIBERGLASS C. MANVILLE D. OWENS-CORING FIBERGLASS CORPORATION 2. FLEXIBLE ELASTOMERIC A. ARMSTRONG WORLD INDUSTRIES B. PITTSBURGH CORNING PRODUCTS C. RUBATEX CORPORATION C. INSULATION SCHEDULES TYPE OF DUCTWORK FORM HICKNESS JACKET INTERIOR SUPPLY, RETURN, RELIEF AND OUTSIDE AIR DUCTWORK BLANKET i-1/2" - INTERIOR EXPOSED SUPPLY, RETURN, BOARD 1" - RELIEF ND OUTSIDE AIR DUCTWORK 1/2" - 1-1/4" 3/4" - ALL DUCTWORK RISERS 1" - I INTERIOR HYDRONIC (100' - 250') TO ROOF MOUNTED EQUIPMENT BLANKET 1-1/2" - (SEE NOTE 3 BELOW) 3/4" - 1-1/2' - 4" TYPE OF PIPING PIPE SIZE THICKNESS JACKET INTERIOR DOMESTIC HOT WATER 1/2' - 4' 1/2" - SANITARY DRAINS AND TRAPS EXPOSED AT FIXTURES FOR THE DISABLED (SEE NOTE 1 BELOW) - 1/2" - ' INTERIOR HYDRONIC (35' - 99') 1/2" - 1-1/4" 3/4" - 1-1/2' - 4" 1" - I INTERIOR HYDRONIC (100' - 250') 1/2' - 2- 3/4" - INTERIOR REFRIGERANT (LIQUID AND SUCTION ONLY) 1/2" - 1-1/4" 3/4" - 1-1/2' - 4" 1" - EXTERIOR EXPOSED REFRIGERANT (UQUID AND SUCTION ONLY) 1/2" - 1-1/4" 3/4" ALUM. 1-1/2" - 4" 1" ALUM. SNITARY DRAINS LOCATED IN THE CEILING SPACE OF OHER TENNTS ALL SIZES 1/2" - INTERIOR DOMESTIC COLD WATER - 1/2' 4' 1/2" - EXTERIOR EXPOSED NATURAL GAS (SEE NOTE 2 BELOW) 1/2" - 1-1/4 3/4" ALUM. 1-1/2' - 4" 1" ALUM. INTERIOR CONDENSATE DRAIN ALL SIZES - - EXTERIOR CONDENSATE DRAIN 3/4" - 4" i -i/2" ALUM. 1 II P P NG INSULATI N IS BAS P 0 ED U ON FLEXIBLE ELASTOMERIC TYPE. 2. ALL INSULATION SHALL MEET LOCAL CODE REQUIREMENTS AND UL FLAME SPREAD AND SMOKE DEVELOPED RATINGS. NOTES: 1. TRUEBRO MODEL 102W "HAND] LAV GUARD' INSULATION KIT SHALL BE USED UNDER ADA LAVATORIES. 2. CORROSION -RESISTANT POLYETHYLENE COATING MAY BE SUBSTITUTED. END OF SECTION 15250 SECTION 15300 - FIRE PROTECTION A. RELATED WORK 1. BASIC MECHANICAL REQUIREMENTS. SECTION 15010 B. SUMMARY OF WORK 1. THE FIRE PROTECTION CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, PERMITS, SERVICES, TOOLS, PERSONNEL, TRANSPORTATION AND FACILITIES NECESSARY FOR AND REASONABLY IMPLIED, AND INCIDENTAL T0, THE FURNISHING, INSTALLATION, COMPLETION AND TESTING OF ALL THE WORK FOR A COMPLETE FIRE PROTECTION SYSTEM AS SPECIFIED HEREIN ND AS REQUIRED BY JOB CONDITIONS. THESE CONDITIONS INCLUDE, BUT ARE NOT UMITED TO THE FOLLOWING: A A COMPLETE FIRE PROTECTION SYSTEM AS REQUIRED BY NFPA, LOCAL CODES, OWNER'S CRITERIA AND THE OWNER'S INSURANCE CARRIER INCLUDING SPRINKLER PIPING, TAPS, RISERS, LATERALS BRANCHES, VALVES ALARMS, SPRINKLE] HEADS, ETC., FIRE PUMPS AND ALL RELATEd COMPONENTS NECESSARY FOR A COMPLETE INSTALLATION AS SPECIFIED HEREIN. B. DESIGN DRAWINGS, HYDRAULIC CALCULATIONS, SUBMITTALS ND APPROVALS. C. TESTS AND TEST CERTIFICATES. D. FIRE EXTINGUISHER(S). C. GENERAL REQUIREMENTS 1_ THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALL D FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED I OTH. NY M N B A ATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS. BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK, ND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE PROVIDE AS PAST OF THIS CONTRACT. 2. ALL WORK BY THE FIRE PROTECTION CONTRACTOR SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING REPAIRING, ETC. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACG�ESS FOR MAINTENANCE OF HE EQUIPMENT AND MAINTAINING ALL MANUFACTURES REQUIRED CLEARANCES. 3_ RELOCATION OF ANY EXISTING FIRE PROTECTION PIPING, EQUIPMENT, VALVES, SPRINKLER HEADS, ETC., TO FACILITATE STORE DESIGN CRITERIA MUST BE INCLUDED IN THE BID PROPOSAL THE FIRE PROTECTION CONTRACTOR SHALL NOT REMOVE OR RELOCATE NY LNDLORD EQUIPMENT, PIPING, ETC., WITHOUT PRIOR WRITTEN APPROVAL FROM THE LANDLORD. SECTION 15400 - PLUMBING A. RELATED WORK 1. VALVES: SECTION 15100 2. HANGERS AND SUPPORTS: SECTION 15145 3. MECHANICAL INSULATION: SECTION 15250 4. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800 B. EQUIPMENT AND MATERIALS 1. REFER TO THE DRAWINGS FOR PLUMBING FIXTURE SPECIFICATIONS. 2. SANITARY WASTE ND VENT PIPING SHALL BE AS FOLLOWS: A SERVICE WEIGHT CAST IRON PIPE. VENT PIPING ABOVE HE FLOOR TWO INCHES (2') OR SMALLER MAY BE GALVANIZED STEEL PVC PIPING SHALL BE ALLOWED AS A SUBSTITUTE WHEN PERMITTED BY THE LOCAL CODES, AND BUILDING DEPARTMENT OFFICIALS AND IT DOES NOT AFFECT OHER TRADES. PROVIDE DIELECTRIC SEPARATION BETWEEN DISSIMILAR METALS. 3. CONDENSATE DRAIN PIPING SHALL BE AS FOLLOWS: A TYPE "L" DRAWN COPPER TUBE WITH 95-5 TIN -ANTIMONY SOLDERED JOINTS AND WROUGHT COPPER FITTINGS WITH DIELECTRIC SEPARATION BETWEEN DISSIMILAR METALS. B. ALL CONDENSATE DRAIN PENETRATIONS SHALL BE MADE WITHIN THE ROOF CURB OF THE ROOF TOP AIR CONDITIONING UNIT. TERMINATE CONDENSATE DRAINS AT CODE APPROVED TERMINATION POINTS. CONDENSATE DRAINS SHALL NOT TERMINATE ABOVE THE ROOF LEVEL. 4. DOMESTIC HOT AND COLD WATER PIPING SHALL BE AS FOLLOWS: A, TYPE "K' ANNEALED TEMPERED COPPER TUBE FOR PIPE SIZES TWO INCH (2.) AND SMALLER BELOW GRADE. BRAZE ALL JOINTS. DIELECTRIC SEPARATION BETWEEN DIS5SI LAR METALS. B. TYPE "L" DRAWN COPPER TUBE WITH 95-5 TIN -ANTIMONY SOLDERED JOINTS AND WROUGHT FITTINGS FOR ALL OTHER PIPING. DIELECTRIC SEPARATION BETWEEN DISSIMILAR METALS. 5. NATURAL GAS PIPING SHALL BE AS FOLLOWS: A BLACK STEEL. SCHEDULE 40, ASTM A-120, WITH MALLEABLE THREADED FITTINGS FOR TWO INCH (2') AND SMALLER AND WELDED JOINTS FOR TWO AND ONE-HALF INCH (2-1/2') AND ER. 6. INSTALL WATER HAMMER ARRESTORS ON EACH HOT AND COLD WATER SUPPLY TO EACH FIXTURE. WATER HAMMER ARRESTORS SHALL BE SIMILAR JAY R. SMIH HYDROTROL" SERIES 5000 OR EQUAL. REFER TO THE PLUMBING DRAWINGS FOR SHOCK ABSORBER SCHEDULE. 7. BACKFLOW PREVENTERS SHALL BE AS FOLLOWS: A. BRONZE BODY WiTH THREADED ENDS, 150 PSIG MINIMUM WORKING PRESSURE UNLESS NOTED OTHERWISE, CORROSION RESISTANT INTERIOR COMPONENTS ND STRAINER ON INLET. 8. ESCUTCHEONS SHALL BE CHROME PLATED, SIZE AS REQUIRED AND PLACED AT ALL PIPE PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, ETC., IN ALL FINISHED AREAS. 9. INSTALL FIXTURE CARRIERS OR SUPPORT FOR ALL WALL MOUNTED PLUMBING FIXTURES. FIXTURE CARRIERS OR SUPPORTS SHALL BE AS FOLLOWS: A. JAY R. SMITH MANUFACTURING COMPANY B. JOSAM COMPANY C. WADE DIVISION; TYLER PIPE D. ZURN INDUSTRIES, INCORPORATED; HYDROMECHANICS DIVISION C. INSTALLATION 1. VALVE LOCATIONS SHALL BE AS FOLLOWS: A. PROVIDE A SHUT OFF VALVE IN THE SUPPLY PIPING TO EACH FIXTURE PROVIDE A MINIMUM 24" X 24" ACCESS DOOR WHERE REQUIRED FOR VALVE ACCESS. B. PR VIDE A GAS COCK IN THE UPP Y PIP T 0 S L LNG 0 EACH PI CE F E 0 UIPMENT RE UIRING GAS SERVICE. EQ Q 2. PROVIDE A DIRT LEG AND UNION CONNECTION TO EACH PIECE OF EQUIPMENT REQUIRING GAS SERVICE. 3. PITCH GAS PIPING AT A UNIFORM GRADE Or 1/4" IN FIFTEEN FEET (15'-0") UPWARD IN THE DIRECTION OF FLOW. 4. GAS PIPING INSTALLED IN RETURN AIR PLENUMS SHALL BE SLEEVED AND VENTED OR WELDED IN ACCORDANCE WiTH UTILITY COMPANY REGULATIONS, LOCAL CODES AND ALL APPLICABLE NFPA CODES. 5. PRCVIDE FLOOR DRAINS AND CLEN-OUTS PER CODE REQUIREMENTS. D. TEST OF SYSTEMS 1. PR ST Ti N F H T P NOR TO HE IN ALLA 0 0 E SNI ARY (PING SYSTEM SNAKE HE SANITARY SYSTEM A MINIMUM OF FIFTY FEET (50'-0') AND REPORT ANY BLOCKAGE. 2. TEST WATER PRESSURE TO INSURE MINIMUM PSI MATCHES MOST DEMANDING EQUIPMENT SUPPLIED. 3. STERILIZE WATER SYSTEM PIPING IN ACCORDNCE WITH ALL CODE REGULATIONS. 4. TEST THE WATER PIPING SYSTEM AT 100 PSIG FOR FOUR (4) HOURS OR AS REQUIRED BY THE LANDLORD, UTILITY COMPANY REGULATIONS OR BY CODE REQUIREMENTS. 5. TEST HE SANITARY WASTE, VENT ND DRAIN PIPING BY A TEN FOOT (10') WATER COLUMN FOR ONE HOUR OR AS REQUIRED BY THE UTILITY COMPANY REGULATIONS OR BY CODE REQUIREMENTS. 6. TEST AND PURGE THE GAS PIPING SYSTEM AS PER THE REQUIREMENTS OF THE UTILITY COMPANY REGULATIONS, LOCAL CODES AND APPLICABLE NEPA CODES. END OF SECTION 15400 SECTION 15530 - REFRIGERANT PIPING A. RELATED WORK 1. HNGERS AND SUPPORTS: SECTION 15145 2. MECHANICAL INSULATION: SECTION 15250 3. HEATING, VENTILATION AND AIR CONDITIONING: SECTION 15800 B. REFRIGERANT EQUIPMENT AND MATERIALS 1. REFRIGERANT PIPING SHALL BE AS FOLLOWS: A. TYPE "L" HARD DRAWN COPPER TUBING (ASTM 888). TUBING SHALL BE CLEAN, CAPPED AND NITROGEN CHARGED. 1. ALL UNITS SHALL HAVE CERTIFIED SOUND DATA RATINGS AT OR BELOW AN NC LEVEL OF 35. 3. DUCTWORK SHALL BE AS FOLLOWS: A. ONE INCH (1-) HICK FOIL FACED FIBERGLASS DUCT BOARD SHALL BE USED IN LIEU OF GALVANIZED S EET METAL DUCTWORK WHEN PERMITTED BY ALL APPLICABLE CODES. B. VERIFY ALL EXISTING CONDITIONS PRIOR TO HE FABRICATION OF SHEET METAL DUCTWORK. C. ALL DUCTWORK DIMENSIONS ARE INSIDE CLEAR DIMENSIONS. D. FABRICATE ALL RECTNGULAR DUCTWORK WITH GALVANIZED SHEET METAL STEEL IN ACCORDANCE WITH SMANCA, HVAC DUCT CONSTRUCTION STANDARDS' AND ALL REQUIRED APPLICABLE CODES. E FABRICATE ALL ROUND DUCTWORK WITH GALVANIZED SHEET METAL STEFL IN F. ROUND SPIRAL DUCTWORK MAY BE USED IN PLACE OF RECTANGULAR DUCTWORK WHEN CEILING HEIGHTS PERMIT AND EQUIVALENT FREE AREA IS MAINTAINED. ALL SUPPLY AND RETURNrAIR DUCTWORK , WITHIN TEN FEET (10 -O -)..OF THE AIR CONDITIONING UNIT SHALL G. DUCTWORK CLASSIFICATION SHALL BE AS FOLLOWS: A. LOW PRESSURE 1. SUPPLY AND RELIEF AIR DUCTWORK: 2" W.G. POSITIVE 2. RETURN, EXHAUST AND OUTSIDE AIR DUCTWORK: 2" W.G. NEGATIVE .8. MEDIUM PRESSURE 1. SUPPLY AIR DUCTWORK: 3' W.G. POSITIVE H. INSTALL TURNING VANES IN ALL SUPPLY AIR RIGHT ANGLE ELBOWS. I. INSTALL ALL DUCTWORK SUPPORTS IN ACCORDNCE WITH SMACNA STANDARDS, AND ALL APPLICABLE CODES. PROVIDE SWAY ND SEISMIC BRACING AS REQUIRED BY APPLICABLE CODES. J. DUCTWORK TRANSITIONS SHALL NOT EXCEED THIRTY DEGREE (30') SLOPE UNLESS NOTED OHERWISE. K. PROVIDE ACCESS TO ALL MNUAL VOLUME DAMPERS, MOTORIZED DAMPERS FIRE DAMPERS, CONTROLS, ETC., THAT REQUIRE SERVICE OR INSPECTION. MINIMUM ACCES§ PANEL SIZE SHALL BE 24' X 24'. SUPPLY AIR DIFFUSERS AND RETURN ND EXHAUST AIR GRILLES OR REGISTERS WITH PLASTER FRAMES MAY BE USED AS ACCESS LOCATIONS. L PROVIDE CONICAL OR 'BELL -MOUTH' TAKE -OFFS FROM MAIN DUCTWORK TO BRANCH DUCTWORK. 4. FLEXIBLE CONNECTIONS SHALL BE AS FOLLOWS: A. FLEXIBLE CONNECTIONS SPALL BE PROVIDED AT ALL CONNECTIONS BETWEEN VIBRATING EQUIPMENT AND DUCTWORK OR CASINGS. PROVIDE FLEXIBLE CONNECTIONS WHERE DUCTWORK CROSSES BUILDING EXPANSION JOINTS. B. FLEXIBLE CONNECTIONS SHALL BE CONSTRUCTED OF NEOPRENE COATED FLAMEPROOF FABRIC. PROVIDE ADEQUATE JOINT FLEXIBILITY TO ALLOW FOR MOVEMENT AND PREVENT THE TRANSMISSION OF VIBRATION. 5. FLEXIBLE DUCTWORK SHALL BE AS FOLLOWS: A. FLEXIBLE UCTW RK B H 1 1 D 0 SHALL E ONE INC NSUTATED CLASS i N D RA OP TING R F TED FOR HE ERA PRESSU E 0 HE SYSTEM. DISC�ORK CONSTRUCTION MATERIAL SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES. VERIFY ALL REQUIREMENTS PRIOR TO BIDDING. B. FLEXIBLE DUCTWORK MANUFACTURERS 1. GENFLEX /SLR -25C 2. NORFLEX 3. OWENS CORNING INL-25 4. THERMAFLEX #G- M 5. WIREMOLD C. FLEXIp4E DUCTWORK SHALL NOT EXTEND OVER THREE FEET (3'-0'l IN LENGH AT ANY ONE (1) LOCATION, AND SHALL NOT BE USED AS A REPLACE ENT OR ELBOWS. 6. MNUAL VOLUME DAMPERS SHALL BE AS FOLLOWS: A LOCKING QUADRANT VOLUME CONTROL DAMPERS WITH HANDLE OPERATORS IN EACH BRANCH DUCTWORK TO THE SUPPLY AIR DIFFUSER. B. MANUAL VOLUME DAMPERS MANUFACTURERS 1. AMERICN WARMING ND VENTILATING, INCORPORATED 2. LOUVERS AND DAMPERS, INCORPORATED 3. NAILOR HART 4. NATIONAL CONTROLLED AIR 5. RUSKIN C. OPERATING HNDLES ON ALL DAMPERS SHALL BE A MINIMUM EIGHTEEN INCHES (18') LONG. 7. FIRE DAMPERS SHALL BE AS FOLLOWS: A. PROVIDE FIRE DAMPERS AS SHOWN AND CALLED FOR ON THE DRAWINGS, SPECIFIED HEREIN, REQUIRE BY APPLICABLE CODE. 6. 1 IR AMERIPCAN WARMING ANND VENTILATING INCORPORATED 2. LOUVERS AND DAMPERS, INCORPORATED 3. NAILOR HART 4. NATIONAL CONTROLLED AIR 5. RUSKIN C. ALL FIRE DAMPERS SHALL BE UL LABELED. D. HIS CONTRACTOR SHALL PROVIDE ALL NECESSARY LINTELS, FRAMING, SLEEVES, ETC., AS REQUIRED FOR FIRE DAMPER INSTALLATION. E. REFER TO THE FIRE DAMPER DETAIL ON THE DRAWINGS_ 8. DIFFUSERS, REGISTER AND GRILLES SHALL BE AS FOLLOWS: A. REFER TO THE DRAWINGS FOR THE DIFFUSER• REGISTER AND GRILLE SCHEDULE. 4. THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY CALCULATED, FULLY SUPERVISED 2. REFRIGERANT PIPING FITTINGS SHALL BE AS FOLLOWS: r.�� B. DIFFUSERS, REGISTER AND GRILLE MNUFACTURERS W AND INSTALLED ACCORDING TO NFPA 13. SUPERVISION WILL INCLUDE VALVE TAMPER SWITCHES AND WATER FLOW INDICATORS WHICH SHALL TRANSMIT CONDITIONS TO com A WROUGHT COPPER OR CAST BRONZE (ANSI B16.22). ALL COPPER TO COPPER JOINTS Z 1. ANEMOSTAT 2. PRICE Vm THE MASTER FIRE ALARM PNET. V SHA�L BE BRAZED WiT SILOS -5 ALLOY. Z 3. TITUS 5. THIS CONTRACTOR SHALL ASSUME FINANCIAL RESPONSIBILITY FOR COMPLIANCE OF ALL CODES ND REGULATIONS OF GOVERNING STNDARDS AND AGENCIES. 3. REFRIGERANT PIPING SPECIALTIES SHALL BE FURNISHED AS PART OF THE CONDENSING UNIT BY THE CONDENSING UNIT MANUFACTURER. REFER TO AIR COOLED CONDENSING g, ROOF/EQUIPMENT CURB ND PIPE SUPPORT CURB SHALL BE AS FOLLOWS: 6. ALL SPRINKLER PIPING SHALL BE INSTALLED CONCEALED, AVOIDING INTERFERENCE WITH v 00 UNIT A COIL PIPING DETAIL FOR REFRIGERANT PIPING SPECIALTIES FURNISHED BY HIS CONTRACTOR. �� A. THIS CONTRACTOR SHALL PROVIDE ALL THE NECESSARY CURBING ND FRAMING AS 'D 000 h LIGHTS, DUCTWORK, PIPING, ETC. HE FIRE PROTECTION CONTRACTOR SHALL _1 L- J C y V- "0 REQUIRED TO INSTALL ALL ROOF MOUNTED EQUIPMENT AND PIPING ABOVE THE ROOF AS O PREPARE COORDINATED SHOP DRAWINGS INDICATING THE LOCATIONS OF ALL SPRINKLER C. INSTALLATION r- DESCRIBED, IMPLIED OR SHOWN AND CALLED FOR ON THE DRAWINGS(OgR HEREIN. W EARS, SPRINKL MO ]PING, LI HTS AND DIFFUSERS, GRILLES, REGISTERS, ETC., PRIOR TO M Q) , )SPECIFIED A MINI CALL "016 ABO EL ROOFING = U6 y � 1. SUCTION LINES SHALL HAVE ADEQUATE UFT TRAPS ND/OR DOUBLE SUCTION RISERS TO v v"" MEMBRANE CURBS MUST BEET ME M D SO THAT HE TOPH SS 7. PROPERLY COMPLETED AND SIGNED TEST CERTIFICATES SHALL BE FURNISHED TO THE MEET THE REQUIREMENTS OF FIELD CONDITIONS AND UNIT MANUFACTURES RECOMMENDATIONS. oCc5 � 2c ROOF CURBS SHALL FULL PERIMETER. �� � bd � OWNER, AUTHORITIES HAVING JURISDICTION, THE OWNER'S INSURANCE CARRIER, ETC. UNIT MANUFACTURER SHALL VERIFY ALL REFRIGERANT PIPING SIZES BEFORE INSTALLATION AND THE INSTALLATION HAS BEEN MADE TO THE UNIT MANUFACTURES SPECIFICATIONS AND END OF SECTION 15800 8. CONCEALED SPRINKLER HEADS SHALL BE INSTALLED IN CEILINGS BELOW 8'-0" RECOMMENDATIONS. D. QUALITY ASSURANCE 2. BRAZE ALL REFRIGERANT PIPING JOINTS WITH SILOS -5 STARTING AT THE INDOOR UNIT AND WORKING TOWARD THE OUTDOOR UNIT. THE SEALS ON THE OUTDOOR UNIT SHALL BE SECTION 15900 -TEMPERATURE CONTROL 1. ALL MATERIALS AND DEVICES USED ARE TO BE NEW AND ARE TO BE LISTED FOR USE BY HE "UNDERWRITERS LABORATORIES• INCORPORATED" AND SHALL BEAR THEIR LABEL WHENEVER BROKEN LAST. A NITROGEN BLEED SHALL BE USED DURING ALL BRAZING AND ANY TIME THE SYSTEM IS OPEN. ALL OPEN LINES SHALL BE CAPPED AND SEALED WHENEVER THIS A. RELATED WORK - (ABEL SERVICE' IS A REQUIREMENT OR IS AVAILABLE. CONTRACTOR IS NOT N THE PR MI . 0 E SES 2. THE FIRE PROTECTION SYSTEM SHALL COMPLY WITH ALL REGULATING AGENCIES, ORGANIZATIONS, D. TEST OF SYSTEM 1. HEATING, VENTILATION ND AIR CONDITIONING: SECTION 15800 PUBLICATIONS, ETC. B. EQUIPMENT AND MATERIALS SHOP DRAWINGS 1. PRESSURE TEST FOR LEAKAGE OF SYSTEM WITH N INERT GAS UP TO 245 PSI. SEAL _. NY LEAKING JOINTS AND RETEST UNTIL THE SYSTEM IS LEAK FREE. CHARGE THE SYSTEM WITH 25 PSI OF THE SYSTEM REFRIGERANT ANS INERT GAS MIXTURE UP TO 245 PSI 1. THIS CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE TEMPERATURE CONTROL SYSTEM 1. THE FIRE PROTECTION CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS ND MAXIMUM AND RETEST SYSTEM WITH A HALIDE LEAK DETECTOR. SEAL ANY LEAKING JOINTS AUTOMATICALLY CONTROL HEATING, VENTilATiON, ND AIR CONDITIONING EQUIPMENT ND CALCULATIONS OF HE NEC S Y W IR _ E SAR ORK REQU ED SUBMIT ALL REQUIRED COPIES TO HE STATE FIRE MARSHALL FOR APPROVAL PRIOR TO THE SUBMISSION TO THE OWNER. ANO RETEST UNTiL HE SYSTEM IS LEAK FREE. CRANK CASE HEATERS SHALL BE ENERGIZED TWENTY FOUR 24 HOURS PRIOR TO COMPRESSOR ACTIVATION TO ENSURE ALL REFRIGERANT OT OTHER COMPONENTS AS SHOWN N F WN D CALLED OR ON THE DRAWINGS ND SPECIFIED HEREIN. FAILURE TO MENTION ANY SPECIFIC DEVICE DOES NOT RELIEVE HE MECHANICAL CONTRACTOR 2. DRAWINGS SUBMITTED TO THE OWNER SHALL BEAR THE APPROVAL" OR 'RELEASE" STAMP IS OUT OF TH� COMPRESSOR. OF TH R F E ESPONSIBIUIY OR THE FURNISHING OR IN TI STALLA ON OR PROVIDING THE DEVICES OR ITEMS NECESSARY IN ORDER TO ACHIEVE THE INTENT OF THE DRAWING OR SPECIFICATIONS. 3. OF HE STATE FIRE MARSHALL ND LETTERS OF APPROVAL OR COMMENTS FROM THE STATE FIRE MARSHALL SHALL ALSO BE SUBMITTED AT THIS TIME. 2. UPON COMPLETION OF TESTING. THE REFRIGERANT PIPING SYSTEM SHALL BE INSPECTED BY THE AUTHORITY HAVING JURISDICTION AS REQUIRED. AFTER SYSTEM APPROVAL BY THE 2. ALL CONTROL WIRING SHALL BE TWENTY FOUR VOLT (24 V.) AND SHALL BE FURNISHED AND INSTALLED APPROVAL FROM HE OWNER'S INSURANCE CARRIER AND GOVERNING AGENCIES SHALL BE GOVERNING AUTHORITY THIS CONTRACTOR SHALL INSTALL ALL REFRIGERANT PIPING INSULATION. BY THIS CONTRACTOR. ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH OBTAINED PRIOR TO FABRICATION, INSTALLATION, MODIFICATION, ETC.. OF THE FIRE PROTECTION ALL APPLICABLE CODES. ALL CONTROL WIRING SHALL BE IN CONDUIT. SYTM Y I T S E B THS CON RACTOR. - cND OF SECTION 75530 3. ZERO TO ONE HUNDRED PERCENT (0 - 100')_ OUTSIDE AIR ECONOMIZER CONTROL SHALL 4. THE FIRE PROTECTION CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR ALL WORK CONSIST OF LOW LEAKAGE OUTSIDE, RETURN AND EXHAUST AIR DAMPERS, MOTOR AND PERFORMED ON THE FIRE PROTECTION SYSTEM PRIOR TO RECEIVING SAID APPROVALS. NO SECTION 15800 - HEATING, VENTILATION ND AIR CONDITIONING ADJUSTABLE ENTHALPY CONTROLLER MOUNTED IN THE OUTSIDE AIR STREAM OF EACH UNIT. N ADDITIONAL COMPENSATION SHALL BE AWARDED TO THE FIRE PROTECTION CONTRACTOR FOR ENTHALPY CONTROLLER SHALL BE PROVIDED TO SENSE THE DRY BULB TEMPERATURE AND RELAT WORK DONE PRIOR TO THE RECEIPT OF SAID APPROVALS IF WORK PERFORMED IS NOT IN A. RELATED WORK HUMIDITY OF THE OUTSIDE AIR FOR USE IN THE COOLING CYCLE THE ENTHALPY CONTROLLER COMPLANCE WITH SAID APPROVALS. SHALL PREVENT THE COMPRESSOR OPERATION WHEN THE OUTSIDE AIR AND HUMIDITY CAN 1. HANGERS AND SUPPORTS: SECTION 15145 SATISFY HE COOLING LOAD. THE OUTSIDE AND RELIEF AIR DAMPER MOTORS SHALL BE OF F. EQUIPMEN- AND MATERIALS 2. VIBRATION ISOLATION: SECTION 15241 THE MODULATING SPRING TYPE TO CLOSE WHENEVER THE UNIT IS IN UNOCCUPIED MODE. 3. MECHANICAL INSULATION: SECTION 15250 1. FIRE PROTECTION PiPING MATERIALS SHALL BE AS FOLLOWS: 4. HYDRONIC PIPING: SECTION 15510 A SCHEDULE 40, BLACK STEEL PIPE, ASTM A-53 FOR FERROUS PIPING, WELDED AND 5. REFRIGERANT PIPING: SECTION 15530 SEAMLESS, ANSI B-36-10-70 FOR WROUGHT IRON STEEL PIPE. 6. TEMPERATURE CONTROL: SECTION 15900 SECTION 15990 - TESTING, ADJUSTING AND BALANCING B. CAST IRON OR MALLEABLE IRON SCREWED FITTINGS FOR PIPES TWO INCHES (2' 7. TESTING, ADJUSTING AND BALANCING: SECTION 15990 AND SMALLER. SCREWED OR CAST IRON FLANGED JOINTS FOR PIPES LARGER TRE B, TWO INCHES (2'). EQUIPMENT AND MATERIALS A. RELATED WORK C. GALVANIZED OR BLACK MALLEABLE IRON WIH BRASS SEAT SCREWED UNIONS FOR 1. ROOFTOP AIR CONDITIONING UNITS SHALL BE AS FOLLOWS: 1. HYDRONIC PIPING: SECTION 15510 PIPES TWO INCHES (2') AND SMALLER. A. REFER TO THE DRAWINGS FOR ROOFTOP AIR CONDITIONING UNIT SCHEDULE. ALL UNITS 2. HEATING, VENTILATION ND AIR CONDITIONING: SECTION 15800 D. VICTAULIC TYPE COUPLINGS ARE ACCEPTABLE WHERE APPROVED BY CODE AND THE SHALL BE FURNISHED WITH N EXTENDED FIVE (5) YEAR COMPRESSOR WARRANTY. B. GENERAL REQUIREMENTS OWNER: E. FIRE PROTECTION PIPING MANUFACTURES B. ROOF TOP AIR CONDITIONING UNIT MANUFACTURERS 1. CARRIER AIR CONDITIONING: DMSION OF CARRIER CORPORATION i. TESTING, ADJUSTING ND BALANCING OF ALL WORK SHALL BE MADE BY A SEPARATE ND 1. ALLIED TUBE AND CONDUIT CORPORATION 2. BERGER INDUSTRIES 2. MC QUAY INTERNATIONAL 3. TRNE (THE)) COMPANY; DIVISION OF AMERICAN STANDARD, INCORPORATED INDEPE)NDENT CONTRACTOR WHO IS CURRENTLY A LICENSED (ASSOCIATED AIR BALANCING COUNCIL (A OTHEOR A NAT] ANC] N CONTRAC OR. REPORONMEN L BALANCING U REVItNEDB) 3. JONES AND LAUGHLIN 4. BRYNT AIRGONDITIONING ABA E 4. U.S. STEEL SHALL BE DONE IN ACCORDNCE WITH THE MOST RECENT STANDARDS OF THEIR SOCIETY. 5. REPUBLIC C. All UNITS SHALL BE FURNISHED WiTH A MINIMUM SIXTEEN INCH (16") HIGH ROOF PAYMENT OF ALL COSTS FOR THE TESTING AND BALANCING SHALL BE INCLUDED IN THE F. FIRE PROTECTION FITTING MANUFACTURES CURB BY THE UNIT MANUFACTURER. UNIT MNUFACTJRER SHALL ALSO PROVIDE ALL MECHANICAL CONTRACTORS- BID. 1. CRANE NECESSARY VIBRATION ISOLATION EQUIPMENT TO ISOLATE ALL MOVING EQUIPMENT FROM 2. ALL TESTING, ADJUSTING AND BALANCING AND REPORTS MUST BE COMPLETED AND SUBMITTED 2_ GUSTIN-BACON THE BUILDING STRUCTURE. TO THE ENGINEER PRIOR TO THE FINAL ACCEPTANCE OF HE SYSTEMS. 3. ITT GRINNELL GRUVLOK 4. ST D. ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT WITH ALL DEVICES, APPURTENANCES, 3. THE MECHNICAL CONTRACTOR SHALL BE PRESENT FOR THE AIR BALNCE TO VERIFY 5. VICTAULIC TAULIC ACCESSORIES, ETC., PROVIDED TO MEET THE DESIGN INTENT AND OPERATION OF THE SYSTEMS ACCESSIBILITY TO ALL DEVICES, VERIFY ALL OPERATING SEQUENCES AND INSTALL NEW FILTERS 2. SPRINKLER HEADS SHALL BE AS FOLLOWS: SHOWN ND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN. IN ALL UNITS JUST PRIOR TO HE AIR BALANCE. THE COMPLETE AIR BALANCE SHALL TAKE A. ALL SPRINKLER HEADS SHALL BE NEW AND RATED FOR 165' F. OR AS REQUIRED BY E. THE ROOFTOP AIR CONDITIONING EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDNCE PLACE WITH THE OUTSIDE AIR DAMPERS IN THE MINIMUM POSITION, UNLESS NOTED OHERWISE. THE LANDLORD, THE OWNERS INSURANCE CARRIER OR THE AUTHORITY HAVING JURISDICTION. WITH THE UNIT MANUFACTURERS REQUIREMENTS. MAINTAIN ALL UNIT MANUFACTURER REQUIRED CLEARANCES. 4. AIR AND WATER QUANTITIES SHALL BE BALANCED TO WITHIN (+ -) TEN PERCENT (10%) OF THE B. SPRINKLER LOCATED IN A FINISHED CEILING AREA SHALL BE PENDANT MOUNTED ON CONCEALED PIPING. F. OUTSIDE, RELIEF AND RETURN AIR DAMPERS SHALL BE OPPOSED BLADE TYPE AND LAW INDICATED QUANTITY AS SHOWN ND CALLED FOR ON HE DRAWINGS. ANY REQUIRED CHANGES IN SHEAVES BELTS, PULLEYS OR THE ADDITION OF DAMPERS REQUIRED TO ACHIEVE SPECIFIED FLOW RA{E5 SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR C. SPRINKLER HEADS SHALL BE AS FOLLOWS: LEAKAGE. AT NO ADDITIONAL COMPENSATION TO THE OWNER. 1. OFFICE: RECESSED PENDANT TYPE, BRIGHT CHROME WITH BRIGHT CHROME ESCUTCHEON. 2. WAREHOUSE do SERVICE GARAGE (NO CEILING): UPRIGHT PENDANT TYPE. ROUGH BRASS. 2. VARIABLE AIR VOLUME (VAV)/FAN POWERED VARIABLE AIR VOLUME (FPVAV) BOXES SHALL BE 5. THE BALANCE REPORT SHALL BE ON HE AABC NATIONAL STANDARD REPORT FORMS OR 3. SPRINKLER HEADS SHALL HAVE A MINIMUM ORIFICE SIZE OF 1/2' OR 17/32" AND BE AS FOLLOWS: THE NEBB CERTIFIED REPORT FORMS AS PUBLISHED IN THEIR MOST CURRENT EDITIONS SHALL BE UL LISTED. A. REFER TO THE DRAWINGS FOR VARIABLE AIR VOLUME/FAN POWERED VARIABLE AIR VOLUME AND SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION: (WHERE APPLICABLE) D. HE FIRE PROTECTION CONTRACTOR SHALL VERIFY THE SPRINKLER HEAD REQUIREMENTS PRIOR TO BIDDING. BOX SCHEDULE. A. AABC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF SEPARATE AND INDEPENDENT E. PROVIDE SPARE HEADS AS REQUIRED BY NEPA. B. VARIABLE AIR VOLUME/FAN POWERED VARIABLE AIR VOLUME BOX MANUFACTURERS: BALANCING CONTRACTOR. F. SPRINKLER HEAD MANUFACTURES 1. CARRIER AIR CONDITIONING; DMSION OF UNITED TECHNOLOGIES B. A COPY OF A CERTIFICATE OF CONFORMANCE WiTH NATIONAL STANDARDS FOR THIS 1. CENTRAL SPRINKLER CORPORATION 2. GRINNELL FIRE PROTECTION SYSTEMS COMPANY, INCORPORATED 2. TITUS PRODUCTS DIVISION 3. TRNE (THE)_ COMPANY; DIVISION OF AMERICAN STANDARD, INCORPORATED PROJECT. 3. RELIABLE AUTOMATIC SPRINKLER COMPANY, INCORPORATED 4. ENVIRONMENTAL TE HN OGIES C OL C. INSTRUMENTATION UST WiTH ]AST CALIBRATION DATES. 4. VIKING CORPORATION C. ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT WITH ALL DEVICES, APPURTENANCES, D. MAKE AND MODEL NUMBER OF ALL HVAC EQUIPMENT TESTED. G. HANGERS AND SUPPORTS ACCESSORIES, ETC. PROVIDED TO MEET THE DESIGN INTENT AND OPERATION OF THE SYSTEMS SHOWN ND CALLED FOR ON THE DRAWINGS AND SPECIFIED HEREIN. E. CFM AND STATIC PRESSURE READINGS (DISCHARGE AND SUCTION) AS MEASURED BY t. ALL HANGER AND SUPPORT COMPONENTS SHALL BE PER NEPA. PITOT TUBE DUCT TRAVERSE AT EACH UNIT. 2. HNGER AND SUPPORT SPACING SHALL BE PER NFPA. D. THE VARIABLE AIR VOLUME/FN POWERED VARIABLE AiR VOLUME BOX SHALL BE INSTALLED IN STRICT ACCORDANCE WITTH THE UNIT MANUFACTURES REQUIREMENTS. F. MOTOR NAMEPLATE DATA Wffh ACTUAL FiELD VOLTAGE AND AMPERAGE READINGS FOR 3. WHEN MECHANICAL GROOVES OR PUSH ON FITTINGS ARE USED HANGERS AND SUPPORTS MAINTAIN ALL UNIT MANUFACTURERS REQUIRED CLEARANCES. EACH LEG. SHALL NOT EXCEED THE MAXIMUM SPACING RECOMMENDED BY YHE MANUFACTURE. E. CONTROLS SHALL BE PROVIDED BY THIS CONTRACTOR. G. MOTOR AND FAN RPMS, SHEAVE SIZES, AND BELT SIZES. H. TEST OF SYSTEM H. OUTSIDE, RETURN, MIXED AND SUPPLY AIR TEMPERATURES ND VOLUMES SHALL BE i. THE FIRE PROTECTION CONTRACTOR SHALL FLUSH ND TEST TH(E FI@RE PROTECTION SYSTEM F. PROVIDE CONTROLS ACCURATE TO 1.5' F. AND ADJUSTABLE FROM 65' F. TO 85' F. MEASURED AT FULL COOLING WiTH MINIMUM OUTSIDE AIR. RETURN AND RELIEF SHALL BE BALANCED AND MEASUREMENTS RECORDED BY PITOT DUCT TRAVERSE AT FULL N PASTANDLARDS. TESTHAND RPRESSOURE H NFNP.)• OR PER ECONOMIZER AND POWER EXHAUST. RESURLTSQSHALLLI COMPLYOOI G. PROVIDE DUCT PRESSURE POWERED CONTROLS, DESIGNED TO OPERATE WITH DUCT 2. ALL TESTS SHALL BE MADE IN THE PRESENCE OF HE OWNER'S REPRESENTATIVE PRESSURES FROM 1.0" W.G. TO 5.0" W.G. 1. WATER BALANCE DATA INCLUDING GPM WITH INLET AND OUTLET TEMPERATURE AND OF THE INSURANCE INTEREST. A COMPLETE WRITTEN REPORT OF THE ST PRESSURE READINGS. RESULTS SHALL BE SENT TO THE OWNER OR ARCHITECT WITHIN TEN (10 DAYS OF THE H. FAN POWERED VARIABLE AIR VOLUME BOX FILTERS SHALL BE ONE INCH (1') 307. EFFICIENT COMPLETION OF THE TESTS STATING HE RESULTS OF HE TEST AND 7TH NAME OF HE THROWAWAY TYPE WIM MOUNTING CLIPS ND FRAMES FOR HOLDING DISPOSAL MEDIA J. MAKE ND MODEL NUMBERS OF ALL AIR DISTRIBUTION EQUIPMENT. REPRESENTATIVES PRESENT DURING THE TEST PRIOR TO FINAL ACCEPTANCE. K. FINAL BALANCED AIF; VOLUMES AT ALL OUTLETS (INCLUDING RETURNS WHEN DUCTED). 3. ANY ALTERATIONS OR REPAIRS SHALL BE MADE IMMEDIATELY AND THE TESTS SHALL BE RERUN TO PROVE FINAL SECURITY OF HE SYSTEM. 6. ALL CONTROL SEQUENCES SHALL BE TESTED (INTERLOCKED EQUIPMENT, SMOKE DETECTORS, SMOKE EVACUATION, ECONOMIZER, ETC.) AND OPERATING STATUS RECORDED IN THE END OF SECTION 15300 REPORT. 7. THREE S3) COPIES OF THE BALANCE REPORT SHALL BE SUBMITTED TO THE ENGINEER FOR APPPROVAL. THE OWNER OR ARCHITECT SHALL RETURN ONE APPROVED BALANCE �1) REPORT TO THE MECHNICAL CONTRACTOR. HIS BALANCE REPOR SHALL APPEAR IN THE OPERATIONS MNUAL 8. HHE NEXT S IEAASONO(HHEATi GROR COOLING) CYC] RN INSPECTION OF HE SYSTEM DURING END OF SECTION 15990 O Q0%"-N E a) i 10 0 0 0 C7 `� 0. 0, r.�� � G r< ch 0) W � 0^N c •0) com N 'C} f; CM Z j C c 0 ) Vm � 0 � LL O V Q � Z O W .-0 .: D C-) �� N Z N f` cai o v 00 n �� -4 Q> 'D 000 h O GV _1 L- J C y V- "0 000 O � - CL r- ^� �� W C M Q) , p C -v s = U6 y � . - � d v v"" O Q0%"-N E a) i 10 0 0 0 C7 `� 0. 0, �.1..� � G r< ch 0) W � 0^N c •0) O N 'C} f; CM Z j C c 0 ) Vm � 0 � LL O V Q � Z O W .-0 .: D W �� N Z cai a O a) r 08 O m Vm O M r W c bw yi a O b Q gm = Z W a � .d I� W � = /Uq ~ = yUm X = U6 y O P O= O0 W O ��� W �_ Uj O m oCc5 � 2c go �� � bd � Revisions: ```t%%1u 1111111 j4f/ �KS.Fq Q...... 0 ST• s i J �;:�pt FR f.• j� '� ;* No. ° *S � .60910220: 0 :. STATE OF 4�1 /#fill Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: / VAV TERMINAL SCHEDULE TAG MANUFACTURER INLET MAX MIN C.. MATERIAL AND SIZE CFM CFM NOTES NOTES MODEL NUMBER - try p` v o0 VAV-1 C VADAA 1 a 1000 750 250 o VAV-2A VADANE 10"0 BOO 270 24"X24" VAV-3A TRANE VADA- 10 10"0 750 250 - VAV-313 VADANE 1000 600 200 10'0 VAV-5A VADA � 0 1000 3DO 100 p G VAV-6CVADAN 10TRAE 1000 300 100 VAV-61) TRANE 'F VADA 10 10"o 500 170 MECHANICAL PLAN SCALE: 1/8" =1'-0" PLAN NOTES: �1 CONNECT NEW DUCT TO EXISTING DUCTWORK AT THIS POINT. �2 CAP EXISTING DUCT OPENING AND SEAL TIGHT. �3 VAV TERMINAL TO BE WIRED BACK TO CENTRAL CONTROL PANEL INSTRUCTION. - �4 CAP ANY EXISTING DUCT OPENINGS IN THIS AREA OF MAIN DDUCT. FOLLOW MANUFACTURER'S DIFFUSER, REGISTER AND GRILLE SCHEDULE TAG N0. PATTERN NECK SIZE FACE SIZE MODULE SIZE C.. MATERIAL N CFM RANGE ACCESSORIES . MODEL NO. NOTES RG -1 - try p` v o0 F- ALUMINUM WHITE 0 - 1,500 . .2 ^ o 50 F _ SD -1 4 -WAY N 00 24"X24" 24"X24' J 2 WHITE 100 - 250 - TITUS TMSA - SD -2 cion 10'0 N 24"X24" (TYPE P EI3 ALUMINUM WHITE p G - TTTUS TMSA - DIFFUSER, REGISTER AND GRILLE SCHEDULE TAG N0. PATTERN NECK SIZE FACE SIZE MODULE SIZE FRAME STYLE MATERIAL FINISH CFM RANGE ACCESSORIES MANUFACTURER MODEL NO. NOTES RG -1 - 24'X24" 24'X24" - (DEIN) ALUMINUM WHITE 0 - 1,500 - TITUS 50 F - SD -1 4 -WAY 800 24"X24" 24"X24' TYPE Y EI3 ALUMINUM WHITE 100 - 250 - TITUS TMSA - SD -2 4 -WAY 10'0 24"X24" 24"X24" (TYPE P EI3 ALUMINUM WHITE 250 - 400 - TTTUS TMSA - --v, F�♦t/^� QPOO E W ,-�1� X00 U .2 � � i m Q �g Lcol 0 W D�� ' C NO ch eM m Z 0— ai I - <Z . oar o V Q C� 00 Z z =a E N Z O N O. 0 CD IT= 06 O r n C co V= W 1 Revisions: a J CAM sma cc C3 Z CD W ,."%J11111111111� RK S. FAQ'% STfR�0 No. STATE OF ?� NA i Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: C4 0 o°� z =a LU W CC W I COO) W ., COO �5� m a) . IC6 UJ W CDZ � = Oay-a r 1i1 Z M �C Revisions: a J CAM sma cc C3 Z CD W ,."%J11111111111� RK S. FAQ'% STfR�0 No. STATE OF ?� NA i Issue: STATE SUBMITTAL Date: JULY 30, 2004 Sheet: