HomeMy WebLinkAboutComCheck 3-29-18COMcheck Software Version 4.0.8.1
Envelope Compliance Certificate
Project Title:
90.1 (2007) Standard
Project Type: Addition
Vertical Glazing / Wall Area: 19%
Location: Carmel, Indiana
Climate Zone: 5a
Construction Site:
14454 Communicty Drive
Carmel, IN 46033
Owner/Agent: Designer/Contractor:
Shawn Curran
Curran Architecture
5719 Lawton Loop E. Drive
Indianapolis, IN 46216
Project Information
Energy Code:
The Playschool at Legacy Addition
Building Area Floor Area
1-School/University : Nonresidential 2749
Envelope Assemblies
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Floor 1: Slab-On-Grade:Unheated, Vertical 2 ft., [Bldg. Use 1 -
School/University] (c)
169 --- 0.0 0.730 0.730
Exterior Wall 1: Wood-Framed, 16" o.c., [Bldg. Use 1 -
School/University]
1673 19.0 7.5 0.043 0.064
Window 1: Metal Frame, Perf. Specs.: Product ID NA, SHGC 0.45,
[Bldg. Use 1 - School/University] (b)
217 --- --- 0.300 0.550
Door 1: Glass (> 50% glazing):Metal Frame, Entrance Door, Perf.
Specs.: Product ID NA, SHGC 0.45, [Bldg. Use 1 -
School/University] (b)
107 --- --- 0.300 0.800
Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - School/University] 2243 38.0 0.0 0.027 0.027
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c) Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 90.1 (2007) Standard requirements in COMcheck Version 4.0.8.1 and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Envelope PASSES: Design 6% better than code
Project Title:
Data filename:
The Playschool at Legacy Addition
P:\170340 PlaySchool at Legacy Classroom Addition\DOCS\STATE SUBMITTAL\ComCheck.cck
Name - Title Signature Date
Project Title:
Data filename:
The Playschool at Legacy Addition
P:\170340 PlaySchool at Legacy Classroom Addition\DOCS\STATE SUBMITTAL\ComCheck.cck
Report date: 03/29/18
Page 2 of 9
Inspection Checklist
Requirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.8.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 90.1 (2007) Standard
Section
#
& Req.ID
Plan Review Complies? Comments/Assumptions
4.2.2
[PR1]1
Plans and/or specifications provide all
information with which compliance
can be determined for the building
envelope and document where
exceptions to the standard are
claimed.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Playschool at Legacy Addition
P:\170340 PlaySchool at Legacy Classroom Addition\DOCS\STATE SUBMITTAL\ComCheck.cck
Report date: 03/29/18
Page 3 of 9
Section
#
& Req.ID
Footing / Foundation
Inspection
Plans Verified
Value
Field Verified
Value Complies? Comments/Assumptions
5.5.3.3
[FO1]1
Below-grade wall insulation R-
value.
R-_____ R-_____ Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.5.3.5
[FO3]1
Slab edge insulation R-value. R-_____
Unheated
Heated
R-_____
Unheated
Heated
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.1.2
[FO4]1
Slab edge insulation installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.5.3.5
[FO5]1
Slab edge insulation
depth/length.
_____ ft _____ ft Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.1.7.3
[FO7]1
Insulation in contact with the
ground has <=0.3% water
absorption rate per ASTM C272.
Complies
Does Not
Not Observable
Section
#
& Req.ID
Framing / Rough-In Inspection Plans Verified
Value
Field Verified
Value Complies? Comments/Assumptions
5.4.3.2
[FR1]3
Factory-built fenestration and
doors are labeled as meeting air
leakage requirements.
Fenestration____
_ cfm/ft2
Doors_____
cfm/ft2
Fenestration____
_ cfm/ft2
Doors_____
cfm/ft2
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.5.4.3a
[FR8]1
Vertical fenestration U-Factor. U-_____ U-_____ Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.5.4.3b
[FR9]1
Skylight fenestration U-Factor. U-_____ U-_____ Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.5.4.4.1
[FR10]1
Vertical fenestration SHGC value. SHGC:_____ SHGC:_____ Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.5.4.4.2
[FR11]1
Skylight SHGC value. SHGC:_____ SHGC:_____ Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.2.1,
5.8.2.4
[FR12]2
Section
#
& Req.ID
Insulation Inspection Plans Verified
Value
Field Verified
Value Complies? Comments/Assumptions
5.4.3.1
[IN1]1
All sources of air leakage in the
building thermal envelope are
sealed, caulked, gasketed,
weather stripped or wrapped with
moisture vapor-permeable
wrapping material to minimize air
leakage.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.5.3.1
[IN2]1
Roof R-value. For some ceiling
systems, verification may need to
occur during Framing Inspection.
R-_____
Above deck
Metal
Attic
R-_____
Above deck
Metal
Attic
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.1.2,
5.8.1.3
[IN3]1
Roof insulation installed per
manufacturer’s instructions.
Blown or poured loose-fill
insulation is installed only where
the roof slope is <=3 in 12.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.5.3.1.1
[IN5]3
High-albedo roofs meet solar
reflectance of 0.70 and thermal
emittance of 0.75 or SRI of 82.
SR:_____
SRI:_____
Section
#
& Req.ID
Insulation Inspection Plans Verified
Value
Field Verified
Value Complies? Comments/Assumptions
5.8.1.7
[IN14]2
Exterior insulation is protected
from damage with a protective
material. Verification for exposed
foundation insulation may need
to occur during Foundation
Inspection.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.8.1.7.1
[IN15]2
Attics and mechanical rooms
have insulation protected where
adjacent to attic or equipment
access.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.8.1.7.2
[IN16]2
Foundation vents do not interfere
with insulation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.8.1.8
[IN17]3
Insulation intended to meet the
roof insulation requirements
cannot be installed on top of a
suspended ceiling. Mark this
requirement compliant if
insulation is installed accordingly.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Playschool at Legacy Addition
P:\170340 PlaySchool at Legacy Classroom Addition\DOCS\STATE SUBMITTAL\ComCheck.cck
Report date: 03/29/18
Section
#
& Req.ID
Final Inspection Complies? Comments/Assumptions
5.4.3.3
[FI1]1
Weatherseals installed on all loading
dock cargo doors in Climate Zones 4-
8.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Playschool at Legacy Addition
P:\170340 PlaySchool at Legacy Classroom Addition\DOCS\STATE SUBMITTAL\ComCheck.cck
Report date: 03/29/18
Page 8 of 9
Project Title:
Data filename:
The Playschool at Legacy Addition
P:\170340 PlaySchool at Legacy Classroom Addition\DOCS\STATE SUBMITTAL\ComCheck.cck
Report date: 03/29/18
Page 9 of 9
COMcheck Software Version 4.0.8.1
Interior Lighting Compliance Certificate
Project Title:
90.1 (2007) Standard
Project Type: Addition
Construction Site:
14454 Community Drive
Carmel, IN 46033
Owner/Agent: Designer/Contractor:
Samuel L. Hurt
The Engineering Collaborative
2410 Executive Drive
Sute 100
Indianapolis, IN 46241
317.636.3941
sam@tec-mep.com
Project Information
Energy Code:
The Play School at Legacy Expansion
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-101 - Corridor (Common Space Types:Corridor/Transition) 304 0.50 152
2-102 - 3's Room (Common Space Types:Classroom/Lecture/Training) 716 1.40 1002
3-103 - Toilet (Common Space Types:Restrooms) 39 0.90 35
4-104 - Toilet (Common Space Types:Restrooms) 39 0.90 35
5-105 - Storage (Common Space Types:Active Storage) 55 0.80 44
6-106 - Mechanical (Common Space Types:Electrical/Mechanical) 80 1.50 120
7-107 - 4's Room (Common Space Types:Classroom/Lecture/Training) 1101 1.40 1541
8-108 - Storage (Common Space Types:Active Storage) 55 0.80 44
9-109 - Toilet (Common Space Types:Restrooms) 39 0.90 35
10-110 - Toilet (Common Space Types:Restrooms) 39 0.90 35
Total Allowed Watts = 3044
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
1-101 - Corridor (Common Space Types:Corridor/Transition)
LED L2: 'L2': 2x2 LED Troffer: Other: 1 6 19 Exempt
Exemption:Health, Safety Required by Regulation
2-102 - 3's Room (Common Space Types:Classroom/Lecture/Training)
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Exemption:Health, Safety Required by Regulation
5-105 - Storage (Common Space Types:Active Storage)
LED L2: 'L2': 2x2 LED Troffer: Other: 1 2 19 Exempt
Exemption:Health, Safety Required by Regulation
6-106 - Mechanical (Common Space Types:Electrical/Mechanical)
LED L4: 'L4': 2x4 LED Troffer: Other: 1 1 34 34
7-107 - 4's Room (Common Space Types:Classroom/Lecture/Training)
LED L1: 'L1': 2x4 LED Troffer: Other: 1 21 60 Exempt
Exemption:Health, Safety Required by Regulation
8-108 - Storage (Common Space Types:Active Storage)
LED L2: 'L2': 2x2 LED Troffer: Other: 1 2 19 Exempt
Exemption:Health, Safety Required by Regulation
9-109 - Toilet (Common Space Types:Restrooms)
LED L3: 'L3': LED Wraparound: Other: 1 1 36 Exempt
Exemption:Health, Safety Required by Regulation
10-110 - Toilet (Common Space Types:Restrooms)
LED L3: 'L3': LED Wraparound: Other: 1 1 36 Exempt
Exemption:Health, Safety Required by Regulation
Total Proposed Watts = 34
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 90.1 (2007) Standard requirements in COMcheck Version 4.0.8.1 and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Samuel L. Hurt
Name - Title Signature Date
Interior Lighting PASSES: Design 99% better than code
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 2 of 13
03/29/2018
COMcheck Software Version 4.0.8.1
Exterior Lighting Compliance Certificate
Project Title:
90.1 (2007) Standard
Project Type: Addition
Construction Site:
14454 Community Drive
Carmel, IN 46033
Owner/Agent: Designer/Contractor:
Samuel L. Hurt
The Engineering Collaborative
2410 Executive Drive
Sute 100
Indianapolis, IN 46241
317.636.3941
sam@tec-mep.com
Project Information
Energy Code:
The Play School at Legacy Expansion
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
Cooridor exit (Main entry/exit) 3 ft of door 30 Yes 90
Classroom exits (Other entry/exit) 9 ft of door 20 Yes 180
Attached canopy 105 ft2 1.25 Yes 131
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
401
401
20
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A supplemental allowance equal to 20 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Cooridor exit ( Main entry/exit 3 ft of door width): Tradable Wattage
LED C1: 'C1': LED Downlight: Other: 1 1 14 14
Samuel L. Hurt
Name - Title Signature Date
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 4 of 13
03/29/2018
COMcheck Software Version 4.0.8.1
Mechanical Compliance Certificate
Project Title:
90.1 (2007) Standard
Project Type: Addition
Location: Carmel, Indiana
Climate Zone: 5a
Construction Site:
14454 Community Drive
Carmel, IN 46033
Owner/Agent: Designer/Contractor:
Samuel L. Hurt
The Engineering Collaborative
2410 Executive Drive
Sute 100
Indianapolis, IN 46241
317.636.3941
sam@tec-mep.com
Project Information
Energy Code:
The Play School at Legacy Expansion
Mechanical Systems List
Quantity System Type & Description
Heating: 1 each - Central Furnace, Gas, Capacity = 60 kBtu/h
Proposed Efficiency = 92.00% Et, Required Efficiency = 80.00% Et
Cooling: 1 each - Split System, Capacity = 30 kBtu/h, Air-Cooled Condenser
Proposed Efficiency = 13.00 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 980 CFM, 0.3 motor nameplate hp
1 F-102 / ACCU-102 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 80 kBtu/h
Proposed Efficiency = 92.00% Et, Required Efficiency = 80.00% Et
Cooling: 1 each - Split System, Capacity = 36 kBtu/h, Air-Cooled Condenser
Proposed Efficiency = 13.00 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 980 CFM, 0.3 motor nameplate hp
1 F-107 / ACCU-107 (Single Zone):
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 90.1 (2007) Standard requirements in COMcheck Version 4.0.8.1 and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Samuel L. Hurt
Name - Title Signature Date
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 5 of 13
03/29/2018
Inspection Checklist
Requirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.8.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 90.1 (2007) Standard
Section
#
& Req.ID
Plan Review Complies? Comments/Assumptions
4.2.2,
6.4.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
4.2.2,
7.4.1
[PR3]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the service water
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
4.2.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the lighting and
electrical systems and equipment and
document where exceptions to the
standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Section
#
& Req.ID
Footing / Foundation Inspection Complies? Comments/Assumptions
6.4.3.8
[FO9]3
Freeze protection and snow/ice
melting system sensors for future
connection to controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 7 of 13
Section
#
& Req.ID
Mechanical Rough-In
Inspection
Plans Verified
Value
Field Verified
Value Complies? Comments/Assumptions
6.4.1.4,
6.4.1.5
[ME1]2
HVAC equipment efficiency
verified. Non-NAECA HVAC
equipment labeled as meeting
90.1.
Efficiency:_____ Efficiency:_____ Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list
for values.
6.4.3.4.1
[ME3]3
Stair and elevator shaft vents
have motorized dampers that
automatically close.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement
does not apply.
6.4.3.4.2,
6.4.3.4.3,
6.4.3.4.4
[ME4]3
Outdoor air and exhaust systems
have motorized dampers that
automatically shut when not in
use and meet maximum leakage
rates. Check gravity dampers
where allowed.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.4.3.4.5
[ME5]3
Ventilation fans >0.75 hp have
automatic controls to shut off fan
when not required.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.4.3.9
[ME6]1
Section
#
& Req.ID
Mechanical Rough-In
Inspection
Plans Verified
Value
Field Verified
Value Complies? Comments/Assumptions
6.5.2.3
[ME19]3
Dehumidification controls
provided to prevent reheating,
recooling, mixing of hot and cold
airstreams or concurrent heating
and cooling of the same
airstream.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.5.4.1
[ME25]3
HVAC pumping systems >10 hp
designed for variable fluid flow.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.5.6.1
[ME30]1
Exhaust air energy recovery on
systems >=5,000 cfm and 70%
of design supply air.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement
does not apply.
6.5.7.1
[ME32]2
Kitchen hoods >5,000 cfm have
make up air >=50% of exhaust
air volume.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement
does not apply.
6.5.7.2
[ME33]1
Fume hoods exhaust systems
>=15,000 cfm have VAV hood
exhaust and supply systems,
direct make-up air or heat
recovery.
Section
#
& Req.ID
Rough-In Electrical Inspection Complies? Comments/Assumptions
9.4.1.1
[EL1]2
Automatic controls to shut off all
building lighting installed in buildings
>5,000 ft2.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.1.2
[EL2]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.1.3
[EL3]2
Automatic lighting controls for exterior
lighting installed.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.1.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.2
[EL5]3
Ballasted one and three lamp fixtures
with >30 W/lamp have two lamp
tandem wired ballasts when >=2
fixtures in same space on same
control.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Section
#
& Req.ID
Final Inspection Complies? Comments/Assumptions
6.4.3.1.1
[FI2]2
Heating and cooling to each zone is
controlled by a thermostat control.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.4.3.1.2,
6.4.3.2,
6.4.3.3,
6.4.3.3.1,
6.4.3.3.2
[FI3]2
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
Exception: Thermostats requiring manual changeover
between heating and cooling.
6.4.3.7
[FI6]3
When humidification and
dehumidification are provided to a
zone, simultaneous operation is
prohibited.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.7.2.1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.7.2.2
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.7.2.3
[FI9]1
Section
#
& Req.ID
Final Inspection Complies? Comments/Assumptions
6.4.3.3.1
[FI21]1
HVAC systems equipped with at least
one automatic shutdown control.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.4.3.3.2
[FI22]1
Setback controls allow automatic
restart and temporary operation as
required for maintenance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 12 of 13
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 13 of 13
An air and/or hydronic system
balancing report is provided for HVAC
systems serving zones >5,000 ft2 of
conditioned area.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
6.7.2.4
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
8.7.1
[FI16]3
Furnished as-built drawings for
electric power systems within 30 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
8.7.2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.2.2.3
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
9.4.5
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
6.4.3.2
[FI20]1
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 11 of 13
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.4
[EL7]1
Exterior grounds lighting over 100 W
provides >60 lm/W unless on motion
sensor or fixture is exempt from scope
of code or from external LPD.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.6.2
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
10.4.1
[EL9]2
Electric motors meet requirements
where applicable.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 10 of 13
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement
does not apply.
6.5.8.1
[ME34]3
Unenclosed spaces that are
heated use only radiant heat.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement
does not apply.
6.5.9
[ME35]1
Hot gas bypass limited to: <=240
kBtu/h – 50% >240 kBtu/h – 25%
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.5.9
[ME35]1
Hot gas bypass limited to: <=240
kBtu/h – 50% >240 kBtu/h – 25%
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 9 of 13
Demand control ventilation
provided for spaces >500 ft2 and
>40 people/1000 ft2 occupant
density and served by systems
with air side economizer, auto
modulating outside air damper
control, or design airflow >3,000
cfm.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.4.4.1.1
[ME7]3
Insulation exposed to weather
protected from damage.
Insulation outside of the
conditioned space and associated
with cooling systems is vapor
retardant.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.4.4.1.2
[ME8]2
HVAC ducts and plenums
insulated.
R-_____ R-_____ Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.4.4.1.3
[ME9]2
HVAC piping insulation thickness. _____ in. _____ in. Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.4.4.2.1
[ME10]2
Ducts and plenums sealed based
on static pressure and location.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.4.4.2.2
[ME11]3
Ductwork operating >3 in. water
column requires air leakage
testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement
does not apply.
6.4.4.2.2
[ME11]3
Ductwork operating >3 in. water
column requires air leakage
testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement
does not apply.
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 8 of 13
Does Not
Not Observable
Not Applicable
Requirement will be met.
6.7.2.4
[PR5]1
Detailed instructions for HVAC
systems commissioning included on
the plans or specifications for projects
>=50,000 ft2.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
8.4.1.1,
8.4.1.2
[PR6]2
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the electrical systems
and equipment and document where
exceptions are claimed. Feeder
connectors sized in accordance with
approved plans and branch circuits
sized for maximum drop of 3%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 6 of 13
Classroom exits ( Other entry/exit 9 ft of door width): Tradable Wattage
LED C1: 'C1': LED Downlight: Other: 1 3 14 42
Attached canopy (105 ft2): Tradable Wattage
LED C1: 'C1': LED Downlight: Other: 1 1 14 14
Total Tradable Proposed Watts = 70
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 90.1 (2007) Standard requirements in COMcheck Version 4.0.8.1 and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Exterior Lighting PASSES: Design 83% better than code
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 3 of 13
LED L1: 'L1': 2x4 LED Troffer: Other: 1 16 60 Exempt
Exemption:Health, Safety Required by Regulation
3-103 - Toilet (Common Space Types:Restrooms)
LED L3: 'L3': LED Wraparound: Other: 1 1 36 Exempt
Exemption:Health, Safety Required by Regulation
4-104 - Toilet (Common Space Types:Restrooms)
LED L3: 'L3': LED Wraparound: Other: 1 1 36 Exempt
Project Title:
Data filename:
The Play School at Legacy Expansion
Y:\2018\18012 - The Play School at Legacy Addition - Carmel, IN\5.0 Design Data\18012 - Play
School at Legacy - Addition_MEP COMCheck.cck
Report date: 03/29/18
Page 1 of 13
Page 7 of 9
SR:_____
SRI:_____
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.5.3.2
[IN6]1
Above-grade wall insulation R-
value.
R-_____
Mass
Metal
Steel
Wood
R-_____
Mass
Metal
Steel
Wood
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.1.2
[IN7]1
Above-grade wall insulation
installed per manufacturer’s
instructions.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.5.3.4
[IN8]1
Floor insulation R-value. R-_____
Mass
Steel
Wood
R-_____
Mass
Steel
Wood
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.1.1
[IN10]2
Building envelope insulation is
labeled with R-value or insulation
certificate providing R-value and
other relevant data.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.8.1.4
[IN11]2
Eaves are baffled to deflect air to
above the insulation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.8.1.5
[IN12]2
Insulation is installed in
substantial contact with the
inside surface separating
conditioned space from
unconditional space.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.8.1.6
[IN13]2
Recessed equipment installed in
building envelope assemblies
does not compress the adjacent
insulation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Playschool at Legacy Addition
P:\170340 PlaySchool at Legacy Classroom Addition\DOCS\STATE SUBMITTAL\ComCheck.cck
Report date: 03/29/18
Page 6 of 9
Fenestration products rated in
accordance with NFRC.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.8.2.2
[FR13]1
Fenestration products are
certified as to performance labels
or certificates provided.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
5.8.2.3,
5.5.3.6
[FR14]2
U-factor of opaque doors
associated with the building
thermal envelope meets
requirements.
U-_____
Swinging
Nonswinging
U-_____
Swinging
Nonswinging
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Playschool at Legacy Addition
P:\170340 PlaySchool at Legacy Classroom Addition\DOCS\STATE SUBMITTAL\ComCheck.cck
Report date: 03/29/18
Page 5 of 9
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
The Playschool at Legacy Addition
P:\170340 PlaySchool at Legacy Classroom Addition\DOCS\STATE SUBMITTAL\ComCheck.cck
Report date: 03/29/18
Page 4 of 9