TopBuild Home Services, Inc. has conducted BPI and/or RESNET/HERS testing on the following property. The information and results
are outlined below. (Note: This document does not certify compliance with the entirety of the 2009 IECC. It certifies the results of the
performance testing only).
Builder: David Weekley Homes Subdivision: Jacksons Grant On Creekside
Property Owner:Total Conditioned Floor Area:4,375 ft 2
Permit Date/No.:Conditioned Volume:44,068 ft 3
IECC Version:2009
Property Address:12336 Ams Ct, Carmel, IN 46032
Testing Performed
2009 IECC (Sec. 402.4.2.1 – Testing Air Leakage) Blower Door Test 06/01/2018
Measured Air Leakage:1709 CFM @50Pa Result: PASS
Air Infiltration:2.33 Confirmed ACH ACH 50 Target ≤ 7
2009 IECC (Sec. 403.2.2 – Testing Duct Leakage) Duct Blaster Test 06/01/2018
System 1 Duct Leakage:341 CFM @25Pa Result: N/A
Confirmed Leakage:7.79%DL % Target ≤ 4.00%
Phase N/A CFA: 4,375 ft 2
System 2 Duct Leakage:N/A Result: N/A
Confirmed Leakage:N/A DL % Target ≤ N/A
Phase N/A N/A
System 3 Duct Leakage:N/A Result: N/A
Confirmed Leakage:N/A DL % Target ≤ N/A
Phase N/A N/A
Rater Of Record:RESNET #: 1215999
06/01/2018 BPI Certification #: 5019702