HomeMy WebLinkAbout79PIPE GUIDES; 2 REQ'D EACH SIDE OF LOOP I nnlr RAnl IIC VVFI n EXPANSION LOOP SCHEDULE PIPE SIZE LENGTH (L) WIDTH (W) U LL r 3/4" - 1-1/2" 2'-0" 4'-0" 2" 4'-0" 4'-0" 3" 4'-0" 4'-0" 4" 4'-0" 5'-0" 6" 4'-0" 6'-0" 8" 4'-0" 6'-0" PIPE EXPANSION DETAIL NO SCALE "L" 6-0"MAX. ADD FRAMING CHANNEL OR ANGLE WHEN "L" IS GREATER THAN MAX. LENGTH. SAME AS OPPOSITE SIDE CLEVIS PIPE HANGER 3/8" ROD ATTACHED TO TOP OF STRUCTURAL ROOF FRAMING MEMBER WITH BEAM CLAMP. -PIPE HANGER ROD CLIP CONNECTION ADD PIPE SLEEVE THAT HAS AN INSIDE DIAMETER, Y"± LARGER THAN OUTSIDE DIA. SINGLE PIPE HANGER DETAIL NO SCALE 1" IPS TEMPERED WATER OUTLET TO HOSE BIB 3/4" IPS COLD SUPPLY INLET 1" IPS HOT SUPPLY INLET ISOLATION VALVES 3/4" IPS_j DIELECTRIC UNION SUPPLIED 1-5/8 X 13/16 X 14" L UNISTRUT TEMPERATURE GAUGE HOT SHUT OFF VALVE MAX TEMP SETSCREW TEMPERATURE ADJUSTMENT KNOB CHECKSTOP CHECKSTOP MIXING VALVE CAR WASH MIXING VALVE DETAIL NO SCALE M.J. X FL. ADAPTER 3/4" ALL THR. ROD BOLT OR TIE BOLT HEX NUT & WASHER ' 6" U.G. PIPING THRUST BLOCK ' (PER NFPA 24) K FIRE LINE DETAIL NO SCALE NOTE: 1. AIR DROP LOCATIONS SHALL BE COORDINATED WITH OWNER PRIOR TO ROUGH -IN. 2. COORDINATE ALL QUICK CONNECT FITTINGS WITH OWNER. 3. COORDINATE HEIGHT OF ALL AIR MAINS WITH OWNER. GENERALLY MOUNT PIPING AS HIGH AS ALLOWABLE. 3/4" TOP TAKE OFF WITH VALVE AT MAIN ON ALL DROPS. INSTALL FULL PORT SHUT-OFF BALL VALVE ON ALL COMPRESSED AIR COMPRESSED AIR CONNECTIONS. MAIN SEE PLANS FOR SIZE. ALL DROPS SHALL INCLUDE DIRT / LEG AND QUICK CONNECT FITTING. VERIFY FITTING TYPE WITH OWNER PRIOR TO I ROUGH -IN. COMPRESSED AIR CONNECTION DETAIL TYPICAL ALL AIR DROPS. METAL PROTECTION SHIELDS RIGID MOLDED FIBERGLASS INSULATION SUPPORT CHAIR BOLTED TO CHANNEL HANGING RODS INSULATED PLUMBING PIPES. %" MIN. NUTS & LOCK WASHERS STEEL CHANNEL ADEQUATE TO CARRY LOAD GENERAL NOTES: 1) PROTECTION SADDLES SHALL BE COPPER CLAD IF COPPER TUBE IS USED. 2) PROVIDE INTERMEDIATE HANGING ROD SUPPORT WHERE NUMBER OF PIPES EXCEED FIVE(5). TRAPEZE HANGER DETAIL NO SCALE PVC C.A. UP THROUGH ROOF DHW TO FIXTURES GALVANIZED TRAY 8 4 PVC FLUE UP THROUGH ROOF CONDENSATE LINE HOT WATER HEATER DETAIL NO SCALE COLD WATER HECK VALVE BALL VALVE EXPANSION TANK STEEL PIPE FLOOR SLEEVE FIRE CAULKING BOLT RISER CLAMP SLAB OAKUM PACKING (OMIT IF RUBBER SEAL IS USED.) • ,0:4..:.p:`t .. ,0:4...0 DETAIL -PIPE SLEEVE FLOOR PENETRATION NO SCALE PIPE 1-1/2 WATER SERVICE THROUGH 2" RPZB AND CONNECT TO 2-1/2" WATER DISTRIBUTION SYSTEM WITH TYPE L COPPER PIPING. CONTINUE 2-1/2" INSULATED WATER LINE AS SHOWN ON PLANS. 1-1/2" WATER METER WITH REMOTE READ INSTALLED IN STRICT ACCORDANCE WITH CARMEL WATER DEPARTMENT. ASME TEMF AND PRESS RELIEF VAL PROVIDE LEGEND VALVE T1001 OR EQUAL FULL PORT BALL VALVES. BRACE ENTIRE SERVICE TO WALL OR FLOOR AS NEEDED. I— r— 2-1/2" 2" 2" TO DISTRIBUTION RPZB REDUCED PRESSURE BACKFLOW PREVENTOR DETAIL NO SCALE FI IIF WATER HEATER DETAIL J SCALE: NOT TC SCALE EXPANSION TANK S LTER HEATER >TAINLESS STEEL DRAIN PAN SHELF BY WATER HEATER 4ANUFACTURER. (WALL HUNG >HOWN OR SUSPENDED TYPE iUPPORTED FROM STRUCTURAL /IEMBERS ONLY). 2" 1-1/2" 1-1/4" 1-1/4" Zones 1,2 & 3 Manifold Return line 1-1/4" Zone 4 Manifold Return line —�— u Brace piping to ZP-1 wall (Typ.) Union. (Typ.) Isolation valve (Typ.) 1" To Zone Manifold Check valve (Typ.) Union. (Typ.) Isolation valve (Typ.) 1" To Zone Manifold ZP-2 Check valve (Typ.) Union. (Typ.) Isolation valve (Typ.) 3/4" To Zone Manifold ZP-3 Check valve (Typ.) Union. (Typ.) Isolation valve (Typ.) 1-1/4" To Zone Manifold ZP-4 Check valve (Typ.) IN FLOOR ZONE PUMP DETAIL NO SCALE 3/4" Glycol Make up line To Glycol Feeder Connect to Butterfly valve side of mair 1 AS -1 Size per plan Air separator forto schedule for size) To drain; Pressure gauge Air vent TACO #400 T1 Pre -charging - air connection Vertical(full bladder type) expansion tank (refer to schedule for size) ET -1 High capacity float type air vent TACO #409 Size per plan 12" min. drop Shut-off valve 1" Line fHose Bibb Drain 4" Concrete pad EXPANSION TANK DETAIL NO SCALE W g 8 ZW NJefa 0 9�_;< 142 ����` E yCLP r,9 le i G g 8N,���� VRIESlffiragfil"15 Q Z _Q TO RISER BY DESIGN AND BUILD r— FIRE SUPPRESION CONTRACTOR U LL r SLAB LEVEL J Q w Q Uj o J D w Q � w F— W = Z w COa I— tn Q W D 0 ' 6" U.G. PIPING THRUST BLOCK ' (PER NFPA 24) K FIRE LINE DETAIL NO SCALE NOTE: 1. AIR DROP LOCATIONS SHALL BE COORDINATED WITH OWNER PRIOR TO ROUGH -IN. 2. COORDINATE ALL QUICK CONNECT FITTINGS WITH OWNER. 3. COORDINATE HEIGHT OF ALL AIR MAINS WITH OWNER. GENERALLY MOUNT PIPING AS HIGH AS ALLOWABLE. 3/4" TOP TAKE OFF WITH VALVE AT MAIN ON ALL DROPS. INSTALL FULL PORT SHUT-OFF BALL VALVE ON ALL COMPRESSED AIR COMPRESSED AIR CONNECTIONS. MAIN SEE PLANS FOR SIZE. ALL DROPS SHALL INCLUDE DIRT / LEG AND QUICK CONNECT FITTING. VERIFY FITTING TYPE WITH OWNER PRIOR TO I ROUGH -IN. COMPRESSED AIR CONNECTION DETAIL TYPICAL ALL AIR DROPS. METAL PROTECTION SHIELDS RIGID MOLDED FIBERGLASS INSULATION SUPPORT CHAIR BOLTED TO CHANNEL HANGING RODS INSULATED PLUMBING PIPES. %" MIN. NUTS & LOCK WASHERS STEEL CHANNEL ADEQUATE TO CARRY LOAD GENERAL NOTES: 1) PROTECTION SADDLES SHALL BE COPPER CLAD IF COPPER TUBE IS USED. 2) PROVIDE INTERMEDIATE HANGING ROD SUPPORT WHERE NUMBER OF PIPES EXCEED FIVE(5). TRAPEZE HANGER DETAIL NO SCALE PVC C.A. UP THROUGH ROOF DHW TO FIXTURES GALVANIZED TRAY 8 4 PVC FLUE UP THROUGH ROOF CONDENSATE LINE HOT WATER HEATER DETAIL NO SCALE COLD WATER HECK VALVE BALL VALVE EXPANSION TANK STEEL PIPE FLOOR SLEEVE FIRE CAULKING BOLT RISER CLAMP SLAB OAKUM PACKING (OMIT IF RUBBER SEAL IS USED.) • ,0:4..:.p:`t .. ,0:4...0 DETAIL -PIPE SLEEVE FLOOR PENETRATION NO SCALE PIPE 1-1/2 WATER SERVICE THROUGH 2" RPZB AND CONNECT TO 2-1/2" WATER DISTRIBUTION SYSTEM WITH TYPE L COPPER PIPING. CONTINUE 2-1/2" INSULATED WATER LINE AS SHOWN ON PLANS. 1-1/2" WATER METER WITH REMOTE READ INSTALLED IN STRICT ACCORDANCE WITH CARMEL WATER DEPARTMENT. ASME TEMF AND PRESS RELIEF VAL PROVIDE LEGEND VALVE T1001 OR EQUAL FULL PORT BALL VALVES. BRACE ENTIRE SERVICE TO WALL OR FLOOR AS NEEDED. I— r— 2-1/2" 2" 2" TO DISTRIBUTION RPZB REDUCED PRESSURE BACKFLOW PREVENTOR DETAIL NO SCALE FI IIF WATER HEATER DETAIL J SCALE: NOT TC SCALE EXPANSION TANK S LTER HEATER >TAINLESS STEEL DRAIN PAN SHELF BY WATER HEATER 4ANUFACTURER. (WALL HUNG >HOWN OR SUSPENDED TYPE iUPPORTED FROM STRUCTURAL /IEMBERS ONLY). 2" 1-1/2" 1-1/4" 1-1/4" Zones 1,2 & 3 Manifold Return line 1-1/4" Zone 4 Manifold Return line —�— u Brace piping to ZP-1 wall (Typ.) Union. (Typ.) Isolation valve (Typ.) 1" To Zone Manifold Check valve (Typ.) Union. (Typ.) Isolation valve (Typ.) 1" To Zone Manifold ZP-2 Check valve (Typ.) Union. (Typ.) Isolation valve (Typ.) 3/4" To Zone Manifold ZP-3 Check valve (Typ.) Union. (Typ.) Isolation valve (Typ.) 1-1/4" To Zone Manifold ZP-4 Check valve (Typ.) IN FLOOR ZONE PUMP DETAIL NO SCALE 3/4" Glycol Make up line To Glycol Feeder Connect to Butterfly valve side of mair 1 AS -1 Size per plan Air separator forto schedule for size) To drain; Pressure gauge Air vent TACO #400 T1 Pre -charging - air connection Vertical(full bladder type) expansion tank (refer to schedule for size) ET -1 High capacity float type air vent TACO #409 Size per plan 12" min. drop Shut-off valve 1" Line fHose Bibb Drain 4" Concrete pad EXPANSION TANK DETAIL NO SCALE W g 8 ZW NJefa 0 9�_;< 142 ����` E yCLP r,9 le i G g 8N,���� VRIESlffiragfil"15 Q Z _Q O Z LL J W _j� U U LL 01:� J Q w Q Uj o J D w Q � w F— W = Z Q 0) � I— tn Q W D G El 13h ''' qQ N o =