HomeMy WebLinkAbout281 P-1.1 2 PLUMBING WATER PLAN 1/4" = 1'0" A//l= C PLUMBING SANITARY AND VENT PLAN P-1.1 1 1/4" = 1' 0" KEY NOTES 1. CONNECT NEW COLD WA TER LINE TO EXISTING COLD WA TER OR EQUAL OR GREA TER SIZE. VERIFY SIZE AND LOCA TION OF EXISTING COLD WA TER PRIOR TO CONSTRUCTION/BID. PROVIDE SUB -METER AND REMOTE READER IF REQUIRED BY LANDLORD. PROVIDE PRESSURE REGULA TING VALVE IF EXISTING PRESSURE EXCEEDS 80 PSI. 2. CONNECT NEW SA NI TAR Y TO EXISTING SANT TAR Y OF EQUAL OR GREA TER SIZE. VERIFY SIZE, DEPTH, AND LOCA TION OF EXISTING SANI TAR Y PRIOR TO CONS TRUC 770N. 3. PRO VIDE NEW WA 7FR HEA TER (WH -1) BRADFORD WHI IF MODEL: M-1-1OU65S 150OW. INSTALL PER MANUFACTURER AND CODE REQUIREMENTS. SET 7FMPERATURE AS REQUIRED BY ✓URISDIC770N. 4. CONNECT NEW VENT TO EXIS77NG VENT OF 2" OR GREA IFR. VERIFY LOCA TION AND SIZE OF EXIS77NG VENT PRIOR TO C0NSTRUC770N. PIPE NEW VENT UP THROUGH ROOF IF NEEDED. VERIFY NEW VTR LOCA 77ON WITH LANDLORD. LOCA 77ON SHALL NOT BE CLOSER THAN 10' FROM ANY FRESH AIR INTAKE. 5. SPACE RESERVED FOR ELECTRICAL EQUIPMENT. NO PIPING SHALL CROSS 7HIS SPACE IN BUILDING. 6. 1/2" TYPE 'K" FLEXIBLE COPPER FROM AUTOMA77C TRAP PRIMER (7P-1) TO FLOOR DRAIN. MOUNT TRAP PRIMER ONE FOOT (1'-0") MINIMUM ABOVE FLOOD RIM OF FLOOR DRAIN. NO RT77NGS OR SPLICES BELOW GRADE. PROVIDE LOCKABLE ACCESS PANEL IF NEEDED. 7. RECONNECT NEW AIR HANDLING UNIT AT REPLACED UNIT'S LOCATION. VERIFY EXIS77NG ROU77NG OF CONDENSA IF AND REROUTE TO APPROVED DRAIN IF NEW TENANT'S LA YOU AFFECTS CONDENSA TE DRAINAGE. GENERAL NOTES A. THE EXIS77NG CONDI 77ONS ARE BASED ON "AS -BUIL T" DRAWINGS AND/OR LIMITED FIELD VERIFICA77ONS THE CON7RACTOR SHALL ADJUST TO ACTUAL FIELD COND177ONS A T NO ADD177ONAL EXPENSE TO THE PROJECT. NO ADDITIONAL COMPENSA77ON WILL BE PROVIDED FOR ANY EX7RAS DUE TO 711E CONTRACTOR'S FAILURE TO WS/T THE PROJECT SITE AND/OR PREDE 7ERYINA 77ON OF EXIS77NG COND177ONS PRIOR TO SUBMIT77NG THE BID. ANY DISCREPANCIES SHALL BE IMMEDIA 7FL Y REPOR7FD TO THE ARCH17FCT/ENGINEER FOR RESOLUTION. B. THE CONTRACTOR SHALL FAMILIARIZE HIMSELF WITH 711E INCIDENTAL DEMOLITION WORK PRIOR TO BIDDING AND COMMENCEMENT OF WORK. THE CONTRACTOR IS RESPONSIBLE FOR DEMOL177ON OF ALL EXIS77NG EQUIPMENT AS REQUIRED FOR THE INSTALLA 770NICONSTRUC77ON OF NEW WORK. C. ALL WORK SHALL BE COMPLE7FD IN ACCORDANCE W177-1 ALL APPLICABLE GOVERNMENTAL AND LOCAL CODE REQUIREMENTS. D. COORDINA 7F ALL SLAB PENE IRA 77ONS WI71I GENERAL CONTRACTOR PRIOR TO CONSTRUCTION. MAINTAIN A MINIMUM OF 2" CLEARANCE FROM 711E EDGE OF THE SLAB OPENING TO ANY STRUCTURAL MEMBERS AND PIPES. E. PIPE SIZES IND/CA 7FD ON THE PLANS ARE MIN/MUM. THE CONTRACTOR SHALL PROVIDE PIPE SIZES EQUAL TO OR GREA7FR THAN THE SPECIFIED SIZES THE CONTRACTOR MA Y INCREASE PIPE SIZES AS REQUIRED A T NO ADDI 77ONAL EXPENSE TO THE PROJECT. F. REFER TO THE PLUMBING FIXTURE SCHEDULE OF PROJECT MANUAL FOR INDIVIDUAL PLUMBING FIXTURE CONNECTION SIZE REQUIREMENTS. G. THE CONTRACTOR SHALL OBTAIN A COPY OF THE LANDLORD'S 7EIVANT CR17ERIA MANUAL PRIOR TO BIDDING. THE 7FNANT CRITERIA MANUAL REQUIREMENTS SHALL BE INCLUDED IN 711E CONTRACTOR CONTRACT. 711E CONTRACTOR SHALL BE RESPONSIBLE FOR COMPL YING WI TH THE LANDLORD REQUIREMENTS A T NO ADD177ONAL EXPENSE TO 71/E PROJECT. H. PRO VIDE TEMPORARY COVERS, CAPS, OR PLUGS ON SANI TAR Y SEWER S YS7FM 7HROUGHOUT THE DURA 77ON OF CONSTRUCTION. RAG WADS, DUCT TAPE, OR 077-IER SIMILAR METHODS OF TEMPORARY COVERS SHALL NOT BE UTILIZED. UPON COMPLETION OF CONS TRUC 77ON, COMPLE7FL Y REMOVE ANY AND ALL OBSTRUCTIONS INSIDE 711E ENTIRE SYS7FM BY SNAKING, ROOING, OR ✓ET77NG 711E SYS7FM IMMEDIATELY PRIOR TO PROJECT TURNOVER TO 711E OWNER. I. ALL BELOW GRADE SANITARY LINES SHALL BE A MINIMUM OF 2" OR IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS. J. ALL PUBLIC USE LA VA TORY FAUCETS SHALL HA VE AN AUTOMA 77C SAFETY WA TER MIXING DEVICE IN ACCORDANCE WITH ANSI/ASSE 1016 OR 1017. K. THE EN77RE BUILDING SHALL BE PROVIDED WITH A COMPLE7F FIRE SPRINKLER SYS7FM /N ALL RESPECTS. COORDINA 7F THE FIRE SPRINKLER PIPING AND SPRINKLER HEAD LOCA 77ONS WITH ALL 7RADES PRIOR TO FABR/CA 77ON OR INSTALLA TION. IF CONFLICTS OCCUR BETWEEN THE FIRE SPRINKLER PIPING/HEADS AND LIGHTS, DIFFUSERS, DUCTWORK, ETC., THE FIRE SPRINKLER PIPING/HEADS SHALL BE RELOCA 7FD OR REROU7FD A T NO ADD177ONAL EXPENSE TO 111E PRO✓ECT. AN ADEQUA IF SUPPL Y OF EX77?A PIPING AND FI T77NGS SHALL BE MAINTAINED ON SITE TO ALLOW FOR FIELD MODIFICA TIONS. PERFORM HYDRAULIC CALCULA 77ONS AS REQUIRED BY NFPA, LOCAL, STA IF CODES, AND 711E OWNER'S INSURANCE AGENCY. APPROVED SHOP DRA WINGS DO NOT PRECL UDE REROUTING IF SO REQUIRED BY THE ARCHI7FCT/ENGINEER. L. THIS PROJECT U77LIZES A PLENUM RETURN AIR CEILING. ALL EQUIPMENT AND MATERIALS INSTALLED IN THE PLENUM RETURN CEILINGS MUST MEET 111E FLAME SPREAD AND SMOKE DEVELOPED RA77NGS OF 25/50 AND BE APPROVED FOR USE IN PLENUM RETURNS CEILINGS. NO PVC/ABS PIPING WILL BE PERMIT7FD IN CEILING SPACES M. PROVIDE FLOOR DRAINS WITH TRAP PRIMER PRO 7FC77ON ONL Y IF THE ✓URISDIC77ON REQUIRES THE INSTALLA TION. N. VERIFY EXIS77NG CONDENSA 7F ROUTING AND PIPE TO APPROVED DRAIN IF NEW LA YOU AFFECTS EXIS77NG DRAINAGE. LEGEND EXIS77NG NEW WORK ® NEW TO EXIS171VG CONNECTION Cr Ln ul 4;, / ......... : Ix E Lu Lu 7- O z ^ O O Z COX a Q LuX��tL O Z~OU)00 — W�CC J J _ Z F= IJJ? ZHy'aco F W a N 0., j Z Z Q3leaN O O rs t: CC()av- � D U t9 to a co ao project no. xxxxxx.00 drawn check by HDU BB S' E Z O Z ® O p c N O J J _ J J � a V u o W 3 U Z C14 M Wco 0 N M >_ O Ce co O U > r�_ H � o of P lm 0 zo0 v)v�F_w �1 z g v w 0 0 m W LjU J - W (D C-4 �UCOW UM wLu v(DF– OD project no. xxxxxx.00 drawn check by HDU BB S' ® M W U �14TW o W Ce) Z W >_ O P H Q 0 Z �1 �Ji - �UCOW UM Q U project no. xxxxxx.00 drawn check by HDU BB S' �i FULL SCALE (24X36): 1/8"= V-0" HALF-SIZE (12X18): 1/16"= V-0" (unless otherwise noted) sheet pml ■ PLUMBING PLAN