SITE LUMINAIRE SCHEDULE
Ballast
Detail
Basis of Design
Gardco Form 10
Alternate 1
Invue Vision VXM Series
Alternate 2
Lithonia Aeris AS2 Series
Alternate 3
McGraw -Edison GSM Series
Fixture Detail
Start Type
Super CWA
Lamp Detail
Max
THD %
0
Min.
Start
Temp. °F
-20
Input
Wattage
460 VA
Super CWA
1
0
-20
+ 460 VA
Gardco Form 10
Invue Vision VXM Series
Lithonia Aeris AS2 Series
McGraw -Edison GSM Series
1
Super CWA
1
10
Min.
129 VA
Gardco BRM824
McGraw -Edison BRL Series
Type
Mount
Description
Eff. %
Description
Qty
Wattage
Qty
Bronzelite GM5012 LED
S01
Pole
19" square extruded aluminum area, arm
0
PSMH; Clear; Horizontal;
1
400
1
mounted luminaire; clear tempered flat glass
15,OOOHR; 36,800 Lumens
lens. Direct pole mount. Type IV distribution;
Initial; 4300°K; 62CRI.
segmented optics; horizontal lamp. Square
Steel pole, 30' H, 4", 11ga.
SO2
Pole
19" square extruded aluminum area, arm
0
PSMH; Clear; Horizontal;
1
400
1
mounted luminaire; clear tempered flat glass
15,000HR; 36,800 Lumens
- -----_
lens. Direct pole mount. Type III distribution;
Initial; 4300°K; 62CRI.
—_ __
segmented optics; horizontal lamp. Square
Steel pole, 30' H, 4", 11ga.
S03
Base
aluminum, bevel top louver bollard
2
30
1-MHC100/U/3K
1
100
1
- '>-- --
high 4"
42" high
-- -
SO4
_
Ground
Ingrade, direct burial LED fixture with narrow
80
Included
1
8
0
beam optics
SITE LUMINAIRE SCHEDULE
Ballast
Detail
Basis of Design
Gardco Form 10
Alternate 1
Invue Vision VXM Series
Alternate 2
Lithonia Aeris AS2 Series
Alternate 3
McGraw -Edison GSM Series
Count
7
Start Type
Super CWA
BF
1
Max
THD %
0
Min.
Start
Temp. °F
-20
Input
Wattage
460 VA
Super CWA
1
0
-20
+ 460 VA
Gardco Form 10
Invue Vision VXM Series
Lithonia Aeris AS2 Series
McGraw -Edison GSM Series
1
Super CWA
1
10
-20
129 VA
Gardco BRM824
McGraw -Edison BRL Series
12
NIA
1
10
-20
8 VA
Lumascape LS79 LLED
Ilumipod TRI -3 Optic 25
Bronzelite GM5012 LED
5
S0
FROM SERVER ROOM TO 10' OUT FROM BUILDING.
iR>I >
6W
SO
�3/4" C., 2 #6 A
U --)E
t3 111 E �� NG 3/4" C., 2 - #12 AWG +GRD - I WG + GRD.
I i
{�
13 REFER TO LIGHTING CONTROL S03
SCHEDULE ON SHEET E5.2
1
3/4" C., 2 - #8 AWG + GRD. L-16,18
3/4" C., 2 - #12 AWG + GRD. L-13 REFER TO LIGHTING CONTROL
SO4 S03 SO SCHEDULE ON SHEET E5.2 -__ S01
EM -18 C. - : - - ` _ - N/L
W VIA INVERTER "
3/4" C., 2 - #10 AWG + GRD. - -i
3/4" C., 2 - #12 AWG + GRD.
3/4" C., 2 - #10 AWG + GRD.
I ; I
SL PAlll
Electrical Site Plan.
," - 20,_0,.
ELECTRICAL SITE PLAN NOTES:
1. Electrical contractor shall pay required fees and other costs not borne by the local power
company to provide complete new electrical service.
2. Electrical contractor shall pay all fees and other costs not borne by the local telephone
company to provide complete new telephone service.
3. Electrical contractor shall be responsible for relocating or removing any or all existing services,
poles, etc. (electric, telephone, cable tv) as may be required to accommodate any new
construction, unless otherwise noted, and shall include all fees for such work in their bid.
4. Electrical contractor shall backfill the excavation for all conduit runs under sidewalks and paved
areas with bank run gravel or sand.
5. All work shown on this sheet is new and by the electrical contractor, unless otherwise noted.
6. Pole bases are to be located 3-0" behind curbs, as measured to the center of the pole base,
from parking areas unless otherwise noted.
7. Locate all underground utilities prior to digging. Hand dig as required.
GENERAL SITE PLAN NOTES:
1. All dimensions are to the face of the curb, edge of the pavement, radius point, or pavement
markings, as shown.
2. Saw cut all existing pavement to be removed for new construction, including but not limited to
islands, curbs, walks, drives, and utilities.
3. Where new curbs, walks, and paving meet existing, they shall be aligned both vertically and
horizontally.
4. Contractor to verify all existing conditions before beginning construction and report any variation
to the design engineer before proceeding with construction.
5. Contact design engineer if additional dimensions or coordinates are needed for site layout.
POLE BASE
ANCHOR BOLTS
#6 REINFORCING ROD
1" BELOW TOPS
Section 'A -A'
NO SCALE
- POLE
GROUT BETWEEN TOP OF
POLE BASE AND POLE
BOTTOM PLATE AFTER #10 GROUNDING
POLE IS SET AND PLUMBED WIRE TO POLE
- 5/8" CANT., ALL AROUND
HAND RUBBED FINISH FINISHED GRADE
ABOVE GRADE b
ANCHOR BOLTS
18" DIAMETER BASE N
o #10AWG SOLID BARE TINNED
#6 REINFORCING ROD ( i. COPPER GND. CONNECT TO (1)
5/8" X 8' GROUND ROD WITH
1" RIGID GALVANIZED CADWELD CONNECTION
CONDUIT
Pole Base Detail 'A'
NO SCALE
MSKTD
& Associates, Inc.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
1715 MAGNAVOX WAY 930 NORTH MERIDIAN
FORT WAYNE, IN 46804 INDIANAPOLIS, IN 46204
voice 260.432.9337 voice 317.917.1190
fax 260.436.2402 fax 317.822.6236
http://www.msktd.corn
CERTIFICATION
D- .Rd
,G\STERFo�F
* 19600471
i -)3 : STATE OF :t c
ii INDIANP 0 '• c0000000000
Inllaa\\\\
The concepts, ideas, designs, plans, ]withthis
tails as
shown on this document are the sole y of
MSKTD & Associates, Inc., and were d,
developed and presented for use on tcific
project. None of the concepts, ideas, s, plans,
and details shall be used by any perso, or
corporation for any purpose whatsoevhout the
expressed written consent of MSKTD ociates,
Inc. The Owner shall be permitted to copies
for information and reference in conneith this
project.
Revisions: Date: By:
SHEET TITLE
Electrical Site Plan
COMMISSION NUMBER DATE
MSKTD 5629 2-11-11
BUILD 65076
SHEET NUMBER