HomeMy WebLinkAbout45I
A
O
N
N
COLD WATER
FEED TO OTHER
FIXTURES
TRAP PRIMER VALVE UNIT,
PPP-PR500 OR SIMILAR
TRAP PRIMER
DISTRIBUTION UNIT,
PPP DU -U OR SIMILAR
UJ
a
a
00
2i :z
Z:) =)
Z J
FLOOR DRAIN
a
N O
N
0 Q a d
• a
P -TRAP
Automatic Trap Primer Detail
1 1/2" BYPASS
PEAK GPM = 40
AVG. GPM = 20
TYP. BALL VALVE
TEST COCK
TYP., 1/4 TURN
BALL VALVE
TYP. STRAINER
11s
2" CW TO BUILDING
SERVICE
TYP. FLANGED
CONNECTION —
2" INCOMING DOMESTIC WATER METER BY
SERVICE LOCAL UTILITY, PAID FOR
UNDER THIS CONTRACT
1"
03 03
SUB -METER FOR IRRIGATION
ROUTE
UNDERGROUNDRPZ FOR IRRIGATION
TO S OUTSIDE
BUILDING FOR Z REDUCED PRESSURE BACKFLOW
IRRIGATION TO FLOOR DRAIN N PREVENTER ASSEMBLIES TO BE
LOCATED BOTTOM MIN. 12" A.F.F.,
SIZE PER AIR GAP TOP MAX 60" A.F.F.
Water Meter Backflow Preventer Detail
CLAMP
FLANGE
GAS
SIZE
SIZE
SIZE
3"
1/2"
2" - 2 1/2"
2"
1/4"
1 1/2"
1 1/2"
1/4"
1"- 1 1/4"
1"
1/4"
1/2" - 3/4"
— FLOW
SPLIT PIPE CLAMP
GRININEL 3138 OR EQUAL
BLACK IRON GAS PIPE
INSTALL PIPE LEVEL
— PIPE NIPPLE
COORDINATE HEIGHTS
12x12 20 GAUGE GALV. PLATE ON
ROOFING. NO GRAVEL UNDER PLATE
Natural Gas PiDe Suppoft
Not to Scale
CIAIIQUEM CI nnn
ADJUSTING COLLAR
RISER
1/8 BEND FULL SIZE, 4" MAX.
--------------
- PLUG IF END OF LINE
Floor Cleanout Detail
1. FURNISH WITH COND EN SATE/B LOW DOWN COOLER OPTION.
2. FURNISH WITH SHORT ABSORPTION MANIFOLD (SAM) FOR DISPERSION AT DUCTWORK
(SIZED PER EACH DUCT, SEE SHEET M2.1).
THERMOMETER
—110° F—�
ELECTRIC
WATER
HEATER
MOUNT APPROX. 6'-
0" A. F. F, SUPPORT AS
REQUIRED FOR FULL
OPERATING WEIGHT
PRESSURE & TEMPERATURE
ASME RELIEF VALVE
KUNKLE MODEL 912
LINE SIZE
T & P RELIEF VALVE
DRAIN VALVE
110° F
�—T CW
— CHECK VALVE
AQUASTAT
IHWR
-7
�
— � - BALL VALVE
STRAINER
HOT WATER
RECIRC. PUMP
ON @ 100
OFF @ 110
FLOOR DRAIN
Electric Water Heater w/ Recirc. Detail
STATE APPROVED REDUCED
PRESSURE BACKFLOW
PREVENTER ASSEMBLY
AIR GAP FUNNEL
PROVIDED BY RPBP CD
MFG. AS REQUIRED
TO FLOOR DRAIN
SIZE PER AIR GAP
115V ELECT""
ALARM BE
CHECK VAL'
FIRE DEPARTI
CONNECTION
BALL DRIP
115V TAMPER
�- PIPE
PATE STEPPED POLYVINYL PATE STAINLESS
CHLORIDE BOOT ADJUSTABLE CLAMPS
PATE SPUN INSULATION
ALUMINUM BASE ROOF DECK
ROOF MEMBRANE
Pate Pi-ve Seal Detail
Not to Scale
15V WATER FLOW
NDICATOR
-EE CONNECTION
VATER GAUGE
EE CONNECTION
1AIN DRAIN VALVE
1AIN DRAIN
=LOW TEST LINE)
OUBLE CHECK VALVE
SSEMBLY(APPROVED
OR WILKINS BRAND
NLY)
ISER FROM MAIN WATER
UPPLY (6"0 LEAD-IN)
Wet Pi -De Vertical Sprinkler Riser
Not to Scale
Plumbing Fixture Schedule:
CO -1 CLEANOUT - FLOOR
ZURN Z -1400 -NL "LEVEL-TROL" ADJUSTABLE FLOOR CLEANOUT. DURA -COATED CAST
S_1 SINK - SINGLE COMPARTMENT
A. ELKAY #LRAD2219, BOWL: 18"04N6" DEEP, 18 GA. STAINLESS STEEL SELF -RIMMING
IRON. SIZE PER LOCAL PLUMBING CODE. (JOSAM 58360 IS APPROVED EQUAL.)
HUMIDIFIER SCHEDULE
CO -2 CLEANOUT WALL
B. ELKAY #LKLFD2439 DUAL HANDLE LOW -FLOW KITCHEN FAUCET, 3-4" CENTERS, WRISTBLADE
ZURN Z-1441 WALL CLEANOUT WITH ROUND STAINLESS STEEL ACCESS COVER. SIZE
HANDLES, 1.5 GPM AERATOR.
C. #LK -35 BASKET STRAINER WITH NEOPRENE STOPPER AND TAILPIECE.
PER LOCAL PLUMBING CODE. (JOSAM 58910 W/ 58600 IS APPROVED EQUAL.)
D. P -TRAP, CHROME -PLATED CAST BODY WITH CLEANOUT, ESCHUCHEON.
CO -3 CLEANOUT OVERHEAD
E. SOLID BRASS ANGLES STOPS, CHROME PLATED, LOOSE KEY, CHROME -PLATED RISERS AND
STEAM CAP ADJ.RANGE
EXTENSION TUBES.
F. FURNISH TEMPLATE TO COUNTER TOP SUPPLIER.
BREAKER
---
MARK
MANUFACTURER
MODEUSIZE
SERVED
(LBS HR)
MIN
ELECTRICAL
SIZE
NOTES
HUM -1
Nortec
NHTC-010TU-1
tR
10
20%
208/1/60
25
1,2
HUM -2
Nortec
NHTC-010TU-2
C. FIAT #832AA HOSE AND HOSE BRACKET.
D. FIAT #833AA SILICON SEALANT.
10
20%
208/1/60
25
1,2
HUM -3
Nortec
NHTC-010TU-3
---
10
20%
208/1/60
25
_1 2
HUM -4
Nortec
NHTC-020
RTU -4
20
20%
208/3!60
30
1,2
HUM -5
Nortec
NHTC-010
RTU -5
10
20%
208/1/60
25
1,2
HUM 6
Nortec
NHTC-010
RTU -6
10
20%
208!1/60
25
1,2
HUM -7
Nortec
NHTC-010
RTU -7
10
20%
208/1/60
25
1,2
HUM -8
Nortec
NHTC-020
RTU -8
20
20%
208/3/60
30
1,2
1. FURNISH WITH COND EN SATE/B LOW DOWN COOLER OPTION.
2. FURNISH WITH SHORT ABSORPTION MANIFOLD (SAM) FOR DISPERSION AT DUCTWORK
(SIZED PER EACH DUCT, SEE SHEET M2.1).
THERMOMETER
—110° F—�
ELECTRIC
WATER
HEATER
MOUNT APPROX. 6'-
0" A. F. F, SUPPORT AS
REQUIRED FOR FULL
OPERATING WEIGHT
PRESSURE & TEMPERATURE
ASME RELIEF VALVE
KUNKLE MODEL 912
LINE SIZE
T & P RELIEF VALVE
DRAIN VALVE
110° F
�—T CW
— CHECK VALVE
AQUASTAT
IHWR
-7
�
— � - BALL VALVE
STRAINER
HOT WATER
RECIRC. PUMP
ON @ 100
OFF @ 110
FLOOR DRAIN
Electric Water Heater w/ Recirc. Detail
STATE APPROVED REDUCED
PRESSURE BACKFLOW
PREVENTER ASSEMBLY
AIR GAP FUNNEL
PROVIDED BY RPBP CD
MFG. AS REQUIRED
TO FLOOR DRAIN
SIZE PER AIR GAP
115V ELECT""
ALARM BE
CHECK VAL'
FIRE DEPARTI
CONNECTION
BALL DRIP
115V TAMPER
�- PIPE
PATE STEPPED POLYVINYL PATE STAINLESS
CHLORIDE BOOT ADJUSTABLE CLAMPS
PATE SPUN INSULATION
ALUMINUM BASE ROOF DECK
ROOF MEMBRANE
Pate Pi-ve Seal Detail
Not to Scale
15V WATER FLOW
NDICATOR
-EE CONNECTION
VATER GAUGE
EE CONNECTION
1AIN DRAIN VALVE
1AIN DRAIN
=LOW TEST LINE)
OUBLE CHECK VALVE
SSEMBLY(APPROVED
OR WILKINS BRAND
NLY)
ISER FROM MAIN WATER
UPPLY (6"0 LEAD-IN)
Wet Pi -De Vertical Sprinkler Riser
Not to Scale
Plumbing Fixture Schedule:
CO -1 CLEANOUT - FLOOR
ZURN Z -1400 -NL "LEVEL-TROL" ADJUSTABLE FLOOR CLEANOUT. DURA -COATED CAST
S_1 SINK - SINGLE COMPARTMENT
A. ELKAY #LRAD2219, BOWL: 18"04N6" DEEP, 18 GA. STAINLESS STEEL SELF -RIMMING
IRON. SIZE PER LOCAL PLUMBING CODE. (JOSAM 58360 IS APPROVED EQUAL.)
SINGLE COMPARTMENT SINK WITH 3 FAUCET HOLES @ 4" CENTERS.
CO -2 CLEANOUT WALL
B. ELKAY #LKLFD2439 DUAL HANDLE LOW -FLOW KITCHEN FAUCET, 3-4" CENTERS, WRISTBLADE
ZURN Z-1441 WALL CLEANOUT WITH ROUND STAINLESS STEEL ACCESS COVER. SIZE
HANDLES, 1.5 GPM AERATOR.
C. #LK -35 BASKET STRAINER WITH NEOPRENE STOPPER AND TAILPIECE.
PER LOCAL PLUMBING CODE. (JOSAM 58910 W/ 58600 IS APPROVED EQUAL.)
D. P -TRAP, CHROME -PLATED CAST BODY WITH CLEANOUT, ESCHUCHEON.
CO -3 CLEANOUT OVERHEAD
E. SOLID BRASS ANGLES STOPS, CHROME PLATED, LOOSE KEY, CHROME -PLATED RISERS AND
JOSAM 58900 SERIES COATED CAST IRON CLEANOUT FERRULE, NO -HUB CONNECTION, BRONZE
EXTENSION TUBES.
F. FURNISH TEMPLATE TO COUNTER TOP SUPPLIER.
COUNTERSUNK PLUG. SIZE PER LOCAL PLUMBING CODE.
---
FD -1 FLOOR DRAIN - ROUND WITH CLEANOUT - 6", 2" CONNECTION
JOSAM #30500-A SERIES CAST IRON COMBINATION FLOOR DRAIN AND INTEGRAL DEEP DRUM
S_2 SINK - SINGLE COMPARTMENT
A. ELKAY #LRAD1918, BOWLS: 16"x11 -1/2"x6" DEEP, 18 GA. STAINLESS STEEL SELF -RIMMING
"P" TRAP WITH DOUBLE DRAINAGE FLANGE, WEEP HOLES, SIDE OUTLET SPIGOT CONNECTION,
SINGLE COMPARTMENT SINK WITH 3 FAUCET HOLES @ 4" CENTERS.
B. ELKAY #LKD2438BH DUAL HANDLE LOW -FLOW KITCHEN FAUCET, 34" CENTERS, WRISTBLADE
NIKALOY INTEGRAL FLUSH -WITH -FLOOR CLEANOUT AND ADJUSTABLE SATIN NIKALOY 6" ROUND
HANDLES, 1.0 GPM AERATOR.
STRAINER.
C. #LK -35 BASKET STRAINER WITH NEOPRENE STOPPER AND TAILPIECE.
FD -2 FLOOR DRAIN - ROUND WITH CLEANOUT - 8", 3" CONNECTION
D. P -TRAP, CHROME -PLATED CAST BODY WITH CLEANOUT, ESCHUCHEON.
E. SOLID BRASS ANGLES STOPS, CHROME PLATED, LOOSE KEY, CHROME -PLATED RISERS AND
JOSAM #30500-A SERIES CAST IRON COMBINATION FLOOR DRAIN AND INTEGRAL DEEP DRUM
"P"
EXTENSION TUBES.
TRAP WITH DOUBLE DRAINAGE FLANGE, WEEP HOLES, SIDE OUTLET SPIGOT CONNECTION,
F. FURNISH TEMPLATE TO COUNTER TOP SUPPLIER.
NIKALOY INTEGRAL FLUSH -WITH -FLOOR CLEANOUT AND ADJUSTABLE SATIN NIKALOY 8" ROUND
STRAINER.
MB -1 MOP BASIN - SHEET MOLDING COMPOUND
ALL FLOOR DRAINS SHALL HAVE DEEP SEAL TRAPS.
A. FIAT #MSB -2424 24"x24", 10" HIGH WALLS.
B. FIAT #830AA FAUCET SET.
WHERE ANY TYPE FLOOR DRAIN IS NOT SPECIFIED FOR A GIVEN LOCATION, IT SHALL BE THE SAME
C. FIAT #832AA HOSE AND HOSE BRACKET.
D. FIAT #833AA SILICON SEALANT.
AS USED ELSEWHERE IN SIMILAR LOCATIONS AND/OR SIMILAR USAGE.
E. INCLUDE 2" P -TRAP.
RD -1 ROOF DRAIN
F. FIAT#889-CC MOP BRACKET 24"x3" WIDE STAINLESS STEEL WITH THREE RUBBER GRIPS.
ZURN #ZC100 15" DIAMETER DURA -COATED CAST IRON BODY, COMBINATION MEMBRANE
RCP -1 RECIRCULATION PUMP -DOMESTIC HOT WATER
FLASHING CLAMP/GRAVEL GUARD AND LOW SIHOUETTE CAST IRON DOME. (JOSAM #21500 -AE
SERIES IS AN APPROVED EQUAL.)
A. GRUNDFOS MAGNA 25-60N, 1/12 HP; 115/1/60
---
B. 1 GPM, 20 FT. HEAD
ORD -1 OVERFLOW ROOF DRAIN
C. CAST BRONZE PUMP BODYD. STAINLESS STEEL FACE PLATE
ZURN #ZC100-W2 15" DIAMETER DURA -COATED CAST IRON BODY, COMBINATION MEMBRANE
E. 30% GLASS FILLED NORYL IMPELLOR
FLASHING CLAMP/GRAVEL GUARD, LOW SIHOUETTE CAST IRON DOME, 2" INTERNAL WATER
F. SOLID HIGH-STRENGTH ALLOY STEEL SHAFT
DAM. (JOSAM #21500 -AE -16 SERIES IS AN APPROVED EQUAL.)
G CARBON/SILICON CARBIDE SEAL SYSTEM
L -1H LAVATORY -WALL MOUNTED, ADA
H. PERMANENTLY LUBRICTED SEALED BEARINGS
I. AQUASTAT
A. AMERICAN STANDARD #0495.300 "OVALYN" VITREOUS CHINA, UNDERCOUNTER LAVATORY
WITH 4" FAUCET CENTERS, 17"x14"x5-1/2" DEEP, ROUND, WHITE.
B. ZURN Z6915 -GEN "AQUASENSE" LAVATORY FAUCET WITH HYDROELECTRIC GENERATOR.
BFP-1 REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER
C. 1 1/4" POLISHED CHROME, CAST BRASS, ADJUSTABLE "P" TRAP, CLEANOUT PLUG, TAPPED
A. WILKINS MODEL #975XL; 2"
B. CAST BRONZE (ASTM B854) MAIN VALVE BODY AND ACCESS COVER
OUTLET FOR I.P.
D. 3/8" I.P.S. ANGLE SUPPLIES WITH LOOSE KEY STOPS AND ANNEALED VERTICAL TUBES.
C. STAINLESS STEEL (300 SERIES) SPRINGS AND FASTENERS
D. SILICONE SEAT DISC; NSF LISTED NORYL SEAT RING AND INTERNAL POLYMERS
E. LAVATORY TO BE MOUNTED AT 34" TO RIM (COUNTERTOP).
F. OFFSET DRAIN ASSEMBLY FOR WHEELCHAIRS.
E. THE FIRST AND SECOND CHECKS SHALL BE ACCESSIBLE FOR MAINENTANCE WITHOUT
G. TRUEBRO MODEL #103 HANDI LAV -GUARD INSULATION KIT.
REMOVING THE RELIEF VALVE OR THE ENTIRE DEVICE FROM THE LINE
F. INCLUDE AIR GAP
WC -1 WATER CLOSET - WALL HUNG, FLUSH VALVE
A. AMERICAN STANDARD "AFWALL" FLOWISE EL ADA1.1/1.6 GPF HIGH EFFICIENCY TOILET SYSTEM,
ET -1 EXPANSION TANK - POTABLE HOT WATER
"THERM-X-TROL"
ELONGATED BOWL, WALL MOUNTED AT 15" TO RIM, 1 1/2" TOP SPUD, 2-1/8" FULLY GLAZED
AMTROL ASME MODEL # ST -5-C, 2.1 GAL TOTAL VOLUME, 0.9 GAL MAX
MAXIMUM ACCEPTANCE, 3/4" NPT CONNECTION
TRAPWAY WITH SIPHON JET ACTION.
SHOCK ABSORBER
B. ZURN MODEL #P6000 -M ADA DF HIGH EFFICIENCY DUAL -FLUSH FLUSHOMETER VALVE.
EWH-1 WATER HEATER
C. JOSAM SERIES #12674 -HS, 12684 -HS, 12694 -HS CAST IRON CLOSET CARRIER - ADJUSTABLE
CLOSET CONNECTION, ADJUSTABLE FEET, CHROME PLATED TRIM AND COATED ACCESSORIES
A. A.O.SMITH MODEL ECL -30 PROMAX LOWBOY
FOR USE WITH TOILET SPECIFIED WITH TEST CAP. (J.R. SMITH IS APPROVED EQUAL)
B. HEATER STORAGE: 30 GAL
C. INPUT: 4500 W AT 240 V, ENERGY FACTOR 0.93
D. ELONGATED OPEN FRONT SEAT WITH STAINLESS STEEL CHECK HINGE. (OLSONITE AND
CHURCH ARE APPROVED.)
D. HEATER RECOVERY: 21 GPH @ 90 DEGREE RISE
WC -1H WATER CLOSET - WALL HUNG, FLUSH VALVE, ADA
DSP -1 KITCHEN SINK DISPOSAL
A. INSINKERATOR "BADGER 5" SINK DISPOSAL
A. AMERICAN STANDARD "AFWALL" FLOWISE EL ADA1.1/1.6 GPF HIGH EFFICIENCY TOILET SYSTEM,
B. 1/2 HP, 120V/1/60, 1725 RPM, 6.9 AVERAGE AMP.
ELONGATED BOWL, WALL MOUNTED AT 17" TO RIM, 1 1/2" TOP SPUD, 2-1/8" FULLY GLAZED
U-
TRAPWAY WITH SIPHON JET ACTION.
B. ZURN MODEL #P6000 -M -ADA -DF HIGH EFFICIENCY DUAL -FLUSH FLUSHOMETER VALVE.
JOSAM SERIES #12674 -HS, 12684 12694
General PlumbimyNotes:C.
-HS, -HS CAST IRON CLOSET CARRIER - ADJUSTABLE
VTR
VENT THROUGH ROOFS
CLOSET CONNECTION, ADJUSTABLE FEET, CHROME PLATED TRIM AND COATED ACCESSORIES
END
FOR USE WITH TOILET SPECIFIED WITH TEST CAP. (J.R. SMITH IS APPROVED EQUAL)
1. ALL WORK SHALL CONFORM TO STATE AND LOCAL PLUMBING AND BACKFLOW PREVENTION
D. ELONGATED OPEN FRONT SEAT WITH STAINLESS STEEL CHECK HINGE. (OLSONITE AND
CODES, AND THE REQUIREMENTS OF THE LOCAL WATER UTILITY.
CHURCH ARE APPROVED.)
--*—
2. VACUUM BREAKERS MUST BE INSTALLED ON ALL PROPOSED HOSE THREAD FITTINGS,
U -1H URINALS - AUTO FLUSH, ADA COMPLIANT
INCLUDING BUT NOT LIMITED TO HOSE BIBBS, WALL/YARD HYDRANTS, MOP/SERVICE SINKS.
A. ZURN MODEL #Z5738.205.00 "THE SMALL PINT" 1/8 GPF ECO -VANTAGE ULTRA LOW CONSUMPTION
BATTERY POWERED URINAL SYSTEM. 3/4" TOP SPUD WITH MANUAL OVERRIDE BUTTON.
3. A CROSS -CONNECTION CONTROL DEVICES INSPECTOR SHALL TEST ALL BACKFLOW DEVICES
B. JOSAM URINAL CARRIER #17560 -UR, COMPLETE WITH BLOCK FEET AND POSITIONING FRAME.
AT THE TIME OF INSTALLATION AND SUBMIT REPORTS TO THE LOCAL WATER UTILITY AS
(OR ZURN #Z-1222, AND J.R. SMITH ARE APPROVED EQUALS.) RETROFIT BRACKET AS REQUIRED.
REQUIRED.
C. MOUNT AT 17" TO RIM.
WASTE/STORM PIPING (UNDERGROUND)
4. COORDINATE EXACT LOCATION OF ROOF DRAINS WITH ARCHITECTURAL AND STRUCTURAL
SC -1 SILCOCK - FREEZING AREAS
PLANS.
A. B&K INDUSTRIES MODEL #104-559HC FROST -FREE SILCOCK
—SAN—
B. 3/4" HOSE OUTLET
5. ALL MATERIALS INSTALLED WITH PLENUM SHALL HAVE FLAME SPREAD RATING OF NOT MORE
C. CHROME -PLATED LEAD-FREE SILVER SOLDER CONSTRUCTION
THAN 25 AND A SMOKE DEVELOPED RATING NOT EXCEEDING 50 IN ACCORDANCE WITH STATE
CODES.
EWC-1 H ELECTRIC WATER COOLER - SPLIT-LEVEL
A. HALSEY TAYLOR #HTHB-HAC8BL "HAC", 3.7 AMPS, 325 W, 115/60/1, WALL MOUNTED, 8 GPH
6. THIS CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, MATERIALS AND LABOR FOR CORE
@ 50-F. INCLUDES "HYDROBOOST" BOTTLE FILLING STATION MOUNTED ON TOP.
DRILLING AS REQUIRED FOR INSTALLATION OF PIPING PENETRATING BUILDING CONSTRUCTION.
B. STAINLESS STEEL FINISH.
C. MOUNT AT 34.5" TO LOWER BUBBLER OUTLET.
7. ALL EQUIPMENT USING NATURAL GAS SHALL HAVE A GAS COCK AND DIRT LEG FOR EACH
D. ZURN Z-1225 PLATE TYPE SYSTEM WATER COOLER SUPPORT WITH DURA -COATED STEEL
PIECE OF EQUIPMENT.
UPRIGHTS, ADJUSTABLE SUPPORT PLATES AND MOUNTING. (JOSAM 17560-WCBL EQUAL)
8. REFERENCE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS, TYPICAL.
Fire ProtectionSDecification
9• ALL NATURAL GAS PIPING SERVING RTU'S ARE LOCATED ON ROOF. SEE SHEET M2.2.
THIS CONTRACTOR SHALL INSTALL SPRINKLER SYSTEM THROUGHOUT THE ENTIRE NEW BUILDING
10. CONNECT PLUMBING FIXTURES TO PIPING INDICATED PER THE PLUMBING FIXTURE/EQUIPMENT
PER NFPA 13. FIRE PROTECTION CONTRACTOR SHALL DEVELOP DRAWINGS WITH LISTED
CONNECTION SCHEDULE AND/OR AS NOTED. REFER TO PIPING ISOMETRICS FOR ADDITIONAL
EQUIPMENT AS REQUIRED, AND SUBMIT DRAWINGS TO THE STATE FOR APPROVAL. THIS
PIPING REQUIREMENTS.
CONTRACTOR MUST BE REGULARLY ENGAGED IN FIRE PROTECTION INSTALLATION.
11. COORDINATE MECHANICAL PENETRATIONS OF/WITH OTHER WORK TO AVOID INTERFERENCES,
SPRINKLER HEADS SHALL BE UPRIGHT, OR PENDANT WITH RECESSED ESCUTCHEON AS
SEAL PENETRATIONS AS NOTED AND/OR SPECIFIED.
MANUFACTURED BY GRINNEL, VIKING, FIKE, OR AUTOMATIC. RECESSED HEADS SHALL BE OF THE
BEST QUALITY CHROME PLATED, AND SHALL BE CENTERED IN CEILING TILE.
12. PIPING INVERTS AND/OR ELEVATIONS INDICATED ARE PRELIMINARY IN NATURE AND ARE FOR
COORDINATION ONLY. THE CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING AND
IN DRYWALL CEILINGS USE CONCEALED HEADS, HORIZON MIRAGE BY VIKING OR APPROVED EQUAL.
ESTABLISHING FINAL INVERTS AND/OR ELEVATIONS. INDICATE FINAL INSERTS AND/OR
ELEVATIONS ON RECORD DOCUMENTS.
IN ALL OTHER AREAS USE SEMI -RECESSED HEAD, MODEL M BY VIKING OR APPROVED EQUAL.
13. REFER TO ARCHITECTURAL PLANS FOR WALL TYPES IN WHICH PLUMBING IS TO BE INSTALLED.
SYSTEM SHALL COMPLY WITH ALL LOCAL, STATE AND NFPA CODES AND OWNER INSURANCE
COORDINATE PLUMBING INSTALLATION WITH OTHER WORK.
AGENCY.
ALL AREAS SHALL BE DESIGNED FOR LIGHT HAZARD.
Pl
b'
� iuiiivu491-A19111CC1111V, 13YI110015
**-*H
PLUMBING ROUGH -INS
--------- VENT PIPING
FIXTURE WASTE
VENT
HOT
COLD
WC-*
4"
2"
---
ill
U-*
2"
1 1/2"
---
3/4"
L-*
1 1/2"
1 1/2"
1/2"
1/2"
S-*
1 1/2"
2
MOP SINK
1/2"
EWC-*
1 1/2"
1 1/2"
MB-*
3"/2"
TEE
1 /2"
HB-*
---
---
---
3/4"
FD-*
3"
- -
---
---
SH-*
2"3/4"
RISER UP (TEE)
H = (1" FOR EACH V OF MAXIMUM
� iuiiivu491-A19111CC1111V, 13YI110015
**-*H
FOLLOW ADA GUIDELINES
--------- VENT PIPING
CO-
CLEAN OUT
—G— GAS PIPING
DF-
DRINKING FOUNTAIN
COLD WATER
EWC-
ELECTRIC WATER COOLER
-- HOT WATER
EWH
ELECTRIC WATER HEATER
----- RECIRCULATING HOT WATER
FD-
FLOOR DRAIN
—SOFT— SOFTENED WATER
GWH-
GAS WATER HEATER
— DE— DEIONIZED WATER
a e raU etal
MSKTD
& Associates, Inc.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
1715 MAGNAVOX WAY 930 NORTH MERIDIAN
FORT WAYNE, IN 46804 INDIANAPOLIS, IN 46204
voice 260.432.9337 voice 317.917.1190
fax 260.436.2402 fax 317.822.6236
http://www. m sktd.com
CERTIFICATION
PSL D.
* 890360
-)3 STATE OF : ,Qj
0 0. 5k\, %. %VD I AN .0 ��
The concepts, ideas, designs, plans, and details as
shown on this document are the sole property of
MSKTD & Associates, Inc., and were created,
developed and presented for use on this specific
project. None of the concepts, ideas, designs, plans,
and details shall be used by any person, firm, or
corporation for any purpose whatsoever, without the
expressed written consent of MSKTD & Associates,
Inc. The Owner shall be permitted to retain copies
for information and reference in connection with this
project.
Revisions: Date: By:
FSHEETE
bing Schedules
and Details
COMMISSION NUMBER DATE
MSKTD 5629 2-11-11
BUILD 65076
SHEET NUMBER
I P
5,0
HB-
HOSE BIB
—0—
OXYGEN
0---+
HOSE BIB
UNDERGROUND UTILITY SERVICE
L-
LAVATORY
MB-
MOP BASIN
METER
MS-
MOP SINK
4
THERMOMETER
MV-
MIXING VALVE
TEE
DRAIN PAN
=
P-
PUMP
a ---RISER
UP (ELBOW)
J
PRV-
PRESSURE REDUCING VALVE
RISER UP (TEE)
H = (1" FOR EACH V OF MAXIMUM
PV-
AUTOMATIC PLUMBING VENT
O—
RISER DOWN (ELBOW)
NEGATIVE STATIC PRESSURE) + 1"
�
DRAIN
J - H/2
SD- S_
SINK
—�
RISER DOWN (TEE)
SA
SHOCK ABSORBER
Is
BALL VALVE
L = H + J + PIPE DIAMETER + INSULATION
SH-
SHOWER
—40—
BUTTERFLY VALVE
T-
THERMOMETER
—
GAS COCK
NOTES:
U-
URINAL
T
GATE VALVE
1. AHU COMPONENT PRESSURE DROPS ARE BASED UPON THE SCHEDULED
VTR
VENT THROUGH ROOFS
DOUBLE BACK FLOW PREVENTER
EQUIPMENT. CONTRACTOR TO INCREASE TRAP DEPTH (AND HOUSEKEEPING PAD
WC-
WATER CLOSET
F—
CHECK VALVE
HEIGHT) AS NECESSARY PER INSTALLED EQUIPMENT.
--*—
UNION
2. FILTER PRESSURE DROP BASED UPON DIRTY FILTERS
— ST—
STORM WATER
3. APPLIES TO DRAW -THROUGH AIR HANDLING UNITS ONLY
ON
INDICATES DIRECTION OF FLOW
PRESSURE GAUGE
WASTE/STORM PIPING (UNDERGROUND)
e
CONNECT NEW TO EXISTING
Condens
t T D • 1
—SAN—
WASTE PIPING
NOTE:
SOME SYMBOLS MAY NOT BE USED
a e raU etal
MSKTD
& Associates, Inc.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
1715 MAGNAVOX WAY 930 NORTH MERIDIAN
FORT WAYNE, IN 46804 INDIANAPOLIS, IN 46204
voice 260.432.9337 voice 317.917.1190
fax 260.436.2402 fax 317.822.6236
http://www. m sktd.com
CERTIFICATION
PSL D.
* 890360
-)3 STATE OF : ,Qj
0 0. 5k\, %. %VD I AN .0 ��
The concepts, ideas, designs, plans, and details as
shown on this document are the sole property of
MSKTD & Associates, Inc., and were created,
developed and presented for use on this specific
project. None of the concepts, ideas, designs, plans,
and details shall be used by any person, firm, or
corporation for any purpose whatsoever, without the
expressed written consent of MSKTD & Associates,
Inc. The Owner shall be permitted to retain copies
for information and reference in connection with this
project.
Revisions: Date: By:
FSHEETE
bing Schedules
and Details
COMMISSION NUMBER DATE
MSKTD 5629 2-11-11
BUILD 65076
SHEET NUMBER
I P
5,0