Loading...
HomeMy WebLinkAbout3CODE ANALYSIS IBC - 2009 Description: 1010.7.2 Outdoor ramps shall be designed so that water will not accumulate on the walking surface. 1011.1 Exit signs shall be positioned in exit corridors so as to be visible within 100 feet. Main entrance doors that are clearly identified as exits do not need to have exit signs when approved by building official. 1012.2 Handrails shall be provided between 34" and 38" above stair nosings, 1 %4 to 2" in diameter. 1012.6 The extensions of handrails shall be in the same direction of the stair flights and ramp runs. 1012.9 Intermediate handrails shall be located so that all portions of the stairway width required for egress capacity are within 30" of a handrail. On monumental stairs, handrails shall be along the most direct path of egress travel. 1013.3 If exterior stairs or landings are encountered with a vertical change in elevation exceeding 30", provide balusters spaced to prohibit passage of a 4" diameter sphere and a 6" diameter sphere at the triangular openings between riser, tread and bottom rails. 1015.1 Two exits are required for spaces with more than 49 occupants spaced at not less than 1/2 of the max. diagonal distance of the area served. In fully sprinklered buildings the required distance is reduced to 1/3 of the diagonal distance. 1018.1 Corridors serving an occupant load of 30 or more shall be one hour fire resistance rated construction. Rated corridors are not required in fully sprinklered buildings. 1018.4 Exit access shall be arranged such that there are no dead ends exceeding 20 feet in length. 1018.6 Fire rated corridors shall not be interrupted by intervening rooms except foyers, lobbies and reception areas constructed same as corridors. 1021.1 Occupant loads over 500 require 3 exits. 1028.2 Buildings shall have a "Main Exit' with an exit width not less than 1/2 of the total required exit width. Exception: where multiple exits are distributed around the perimeter of the building. 1028.9.1 Minimum aisle width shall be 48" except for aisles serving 50 occupants or less which only require 36". 1028.10 Space between pews shall be 12" where seating rows have 14 or fewer seats. Rows with single access shall be increased by 0.6" for each additional seat beyond seven seats. 1028.12.1 Seating for areas exceeding 200 occupants shall be secured to the floor, or separated into portions or areas not exceeding 200 seats. Chapter 11 -Accessibility 1104.2 At least one accessible route shall connect accessible buildings and facilities on the site. 1105.1 At least 60% of public entrances shall be accessible. 1106.1 Provide accessible parking stalls in accordance with Table 106.1. 1106.5 One out of every six accessible stalls shall be van accessible. 1108.2.2.1 In assembly areas with fixed seating, provide wheelchair spaces in accordance with Table 1108.2.2.1. 1108.2.3 At least one companion seat shall be provided for each wheelchair space. 1108.2.5 At least 5% and not less than one of the seats shall be aisle seats without arm rests designated for those with mobility impairments. 1108.2.8 An accessible route shall be provided from performance areas. 1109.2 Toilet rooms and bathing facilities shall be accessible. 1109.2.1 Family or assisted use toilet rooms shall be provided where an aggregate of six or more male and female water closets is required. 1109.3 At least 5% of sinks provided shall be accessible. 1109.5 Provide at least two drinking fountains (one for wheelchair access, one for standing) or a single drinking fountain that complies with the requirements for both wheelchair and standing. 1109.7.1 A wheelchair lift may be used as part of the accessible route to a performing area and/or speaker platform. Chapter 12 - Interior Environment 1109.7.1 Enclosed attic spaces shall have cross ventilation with a minimum of 1" air space between the insulation and the roof sheathing. The net free ventilating area shall be not less than 1/300th of the ventilation area with 50% provided in the upper area (ridge vents) and the remainder at the eaves (ventilated soffit). Chapter 29 - Plumbing Systems 2902.1 Provide 1 water closet per 150 male and 1 water closet per 75 female occupants. Provide 1 lavatory per 200 occupants and 1 drinking fountain per 1000 occupants complying with 1109.5. In general, the building is intended to be used as a meetinghouse for the wk 1944 Church of Jesus Christ of Latter-day Saints. The design allows for the DRINKING FOUNTAINS construction of phased additions to the building to accommodate the 1:200 = 4 current and future needs of the congregation without major disruption of WOMEN 618/75=9 service. The initial phase may vary from approximately 2,400 square feet PROVIDED up to a possible full build -out of about 20,000 square feet with various sizes N_:' _ , in between. Each phase of construction has similar code requirements and 4 are therefore summarized herein as a complete building with notations for WOMEN 9 exceptions permissible in the smaller building phases. Chapter 3 - Use and Occupancy 303.1 Places of religious worship are categorized as an A-3 Occupancy Chapter 4 -Special Detailed Requirements 410.2 Larger building phases contain a platform or rostrum in the chapel area and Z may have a platform in conjunction with a multi-purpose room. 410.3.1 Platform may be constructed of same materials required for the type of N construction (V -B). Chapter 5 - General Building Heights & Areas Table 503 A-3 Occupancy (Type V -B construction) basic allowable square footage= 6,000 S.F. and a maximum of 1 story in height. 504.2 Allowable building height is allowed to be increased by one story (20 feet) if building is protected throughout by an approved automatic fire sprinkler LLQ system. 504.3 Spires and steeples are not limited in height if constructed of J non-combustible materials. 506.2 Building allowable size may be increased by 75% due to frontage on a public way and open space around the building exceeding 20 feet to 10,500 square feet. 506.3 Area of A-3 occupancy may be increased an additional 300% to 28,500 when protected throughout by an automatic fire sprinkler system. Table 508.2.5 Mechanical rooms do not contain a piece of equipment with an input of over 400,000 Btu/hr and are therefore not required to have a fire resistance rated N separation from the remainder of the building. Chapter 6 - Types of Construction Table 601 Type V -B construction does not require any fire resistance rated construction. Table 602 No fire resistance required for exterior walls (separation exceeds 30 feet). 603.1.25.3 Attic spaces of building requiring fire sprinklers may be protected by use of qualified fire resistive construction in lieu of fire sprinklers to include roof trusses, roof sheathing, blocking, bracing and, in general, all roof framing exposed within the concealed attic space. Fire retardant treated wood products complying with ASTM E 84 and bearing a UL stamp, qualify as non-combustible construction. Chapter 7 - Fire and Smoke Protection Features 717.4.3 Draft stopping of attic space shall be provided such that any horizontal area does not exceed 3,000 square feet. However, draft stopping is not required in buildings protected with an approved automatic sprinkler system. 719.2 Insulation shall have a flame spread index of not more than 25 and a smoke -developed index of not more than 450. Chapter 8 - Interior Finishes Table 803.9 The following finish requirements apply: Corridors - Type B finishes. Rooms and enclosed spaces - Type C finishes. (If the building, due to its size, is not required to be fire sprinklered, corridors would be required to have Type A finishes). Places of religious worship are permitted to have wood paneling or furnishings for ornamental purposes. 804.4.1 Floor finish materials in corridors shall be not less than Class II and comply with DOC FF -1 pill test. 806.1 Decorative materials suspended from walls or ceilings such as draperies shall meet the flame propagation performance criteria of NFPA 701. Acoustic or crash pads attached to walls that exceed 10 percent of the wall or ceiling shall not be considered "decorative". 806.5 Combustible interior trim shall not exceed 10 percent of the wall or ceiling area in which it is attached. Chapter 9 - Fire Protection Systems 903.2.1.3 Fire sprinklers are required in areas that have an occupant load of 300 or exceed 12,000 square feet in size. Local jurisdictions may require fire sprinklers in smaller buildings as well depending on fire flow requirements and other considerations. (If the construction consists of a smaller phase building and is not required to be protected with fire sprinklers, see Chapter 10 requirements for rated corridor construction). 903.3.1.1.1 Attic spaces constructed of non-combustible materials do not require fire sprinklers. Fire retardant treated lumber and roof sheathing complying with ASTM E 84 and bearing a UL stamp qualify as non-combustible construction. 903.4 Fire sprinkler systems exceeding 20 heads are required to be electrically supervised by a listed fire alarm control unit. 903.4.2 Activation of fire sprinkler system shall sound an alarm to be located on the outside of the building in an approved location as well as activate the building fire alarm system. 906 Provide a portable fire extinguisher (2-A) at a minimum of one per 6,000 sq. ft. (low Class A fire hazard) Maximum travel distance to extinguisher shall not exceed 75 feet. 907 A fire alarm and detection system is required in buildings with an occupant load exceeding 300. A manual pull station is not required in buildings protected throughout with an automatic sprinkler system, but the alarm should activate by sprinkler water flow. Chapter 10 - Means of Egress 1003.3.3 Structural elements or fixtures shall not protrude more than 4" over any walking surface between heights of 27" to 80" A.F.F. 1003.3.4 Protruding objects shall not reduce required clearance widths. Table 1004.1.1 Occupant Loads Assembly areas with fixed seats = actual number of seats. Assembly areas without fixed seats = 7 square feet/person. Offices = 100 square feet/person Stages & platforms = 15 square feet / person. 1004.3 Spaces designated as A -occupancies shall have the occupant load of the space posted near the exit door to the space. 1004.7 Fixed seating without dividing arms the occupant load shall not be less than the # of seats based on one person for each 18" of seating length. 1004.8 Outdoor courtyard requires two means of access. Occupant load of courtyard should be added to building load when calculating egress requirements. 1005.1 The total required egress width (all exits combined) shall be equal to the occupant load multiplied by 0.2 inches per occupant. 1005.2 Doors, when fully opened and handrails shall not reduce the required egress width by more than 7". Doors in any position shall not reduce the required width by more than half. 1006.1 Means of egress including exit discharge shall be illuminated when the building is occupied. 1006.3 Emergency lightings with battery backup for 90 minute duration shall illuminate corridors, any exit stairways and exit discharge in the event of a power failure. 1008.1.2 Doors shall swing in the direction of exit travel when serving an occupant load of 50 or more. 1008.1.5 Exterior Landings may slope up to 2%. 1008.1.6 Landings at doors shall have a length measured in the direction of travel of not less than 44". 1008.1.7 Thresholds shall not exceed %" in height. 1008.1.10 Exit doors serving an occupant load of 50 or more shall not be provided with a latch or lock unless it is panic hardware. 1009.4 Stair risers shall not exceed 7" in height nor be less than 4". 1010.2 Ramps shall have a maximum slope of 1:12 1010.5.1 The clear width of a ramp between handrails shall be 36" min. 1010.6.3 Ramp landing length shall be 60" min. 1010.7.2 Outdoor ramps shall be designed so that water will not accumulate on the walking surface. 1011.1 Exit signs shall be positioned in exit corridors so as to be visible within 100 feet. Main entrance doors that are clearly identified as exits do not need to have exit signs when approved by building official. 1012.2 Handrails shall be provided between 34" and 38" above stair nosings, 1 %4 to 2" in diameter. 1012.6 The extensions of handrails shall be in the same direction of the stair flights and ramp runs. 1012.9 Intermediate handrails shall be located so that all portions of the stairway width required for egress capacity are within 30" of a handrail. On monumental stairs, handrails shall be along the most direct path of egress travel. 1013.3 If exterior stairs or landings are encountered with a vertical change in elevation exceeding 30", provide balusters spaced to prohibit passage of a 4" diameter sphere and a 6" diameter sphere at the triangular openings between riser, tread and bottom rails. 1015.1 Two exits are required for spaces with more than 49 occupants spaced at not less than 1/2 of the max. diagonal distance of the area served. In fully sprinklered buildings the required distance is reduced to 1/3 of the diagonal distance. 1018.1 Corridors serving an occupant load of 30 or more shall be one hour fire resistance rated construction. Rated corridors are not required in fully sprinklered buildings. 1018.4 Exit access shall be arranged such that there are no dead ends exceeding 20 feet in length. 1018.6 Fire rated corridors shall not be interrupted by intervening rooms except foyers, lobbies and reception areas constructed same as corridors. 1021.1 Occupant loads over 500 require 3 exits. 1028.2 Buildings shall have a "Main Exit' with an exit width not less than 1/2 of the total required exit width. Exception: where multiple exits are distributed around the perimeter of the building. 1028.9.1 Minimum aisle width shall be 48" except for aisles serving 50 occupants or less which only require 36". 1028.10 Space between pews shall be 12" where seating rows have 14 or fewer seats. Rows with single access shall be increased by 0.6" for each additional seat beyond seven seats. 1028.12.1 Seating for areas exceeding 200 occupants shall be secured to the floor, or separated into portions or areas not exceeding 200 seats. Chapter 11 -Accessibility 1104.2 At least one accessible route shall connect accessible buildings and facilities on the site. 1105.1 At least 60% of public entrances shall be accessible. 1106.1 Provide accessible parking stalls in accordance with Table 106.1. 1106.5 One out of every six accessible stalls shall be van accessible. 1108.2.2.1 In assembly areas with fixed seating, provide wheelchair spaces in accordance with Table 1108.2.2.1. 1108.2.3 At least one companion seat shall be provided for each wheelchair space. 1108.2.5 At least 5% and not less than one of the seats shall be aisle seats without arm rests designated for those with mobility impairments. 1108.2.8 An accessible route shall be provided from performance areas. 1109.2 Toilet rooms and bathing facilities shall be accessible. 1109.2.1 Family or assisted use toilet rooms shall be provided where an aggregate of six or more male and female water closets is required. 1109.3 At least 5% of sinks provided shall be accessible. 1109.5 Provide at least two drinking fountains (one for wheelchair access, one for standing) or a single drinking fountain that complies with the requirements for both wheelchair and standing. 1109.7.1 A wheelchair lift may be used as part of the accessible route to a performing area and/or speaker platform. Chapter 12 - Interior Environment 1109.7.1 Enclosed attic spaces shall have cross ventilation with a minimum of 1" air space between the insulation and the roof sheathing. The net free ventilating area shall be not less than 1/300th of the ventilation area with 50% provided in the upper area (ridge vents) and the remainder at the eaves (ventilated soffit). Chapter 29 - Plumbing Systems 2902.1 Provide 1 water closet per 150 male and 1 water closet per 75 female occupants. Provide 1 lavatory per 200 occupants and 1 drinking fountain per 1000 occupants complying with 1109.5. 20,819 SQ. FT. OCCIJPANCY PLA 1 lx TOTAL OCCUPANT LOAD FOR ALL OCCUPANCIES= 1,235 EXITING PLAN COMPLIES WITH IBC PLUMBING FIXTURE COUNT 1,241 OCCUPANTS wk 1944 LAVS DRINKING FOUNTAINS MEN 618/150=5 20,819 SQ. FT. OCCIJPANCY PLA 1 lx TOTAL OCCUPANT LOAD FOR ALL OCCUPANCIES= 1,235 EXITING PLAN COMPLIES WITH IBC PLUMBING FIXTURE COUNT 1,241 OCCUPANTS WATER CLOSETS LAVS DRINKING FOUNTAINS MEN 618/150=5 1:200 = 4 2 REQUIRED WOMEN 618/75=9 1:200 = 4 PROVIDED o z N_:' _ , MEN 5 4 4 TOTAL WOMEN 9 4 a0 LEGEND SYMBOL DESCRIPTION 152 SF ROOM SQUARE FOOTAGES: 2�8s4 OCCUPANT LOAD SERVED BY EXIT NOT COUNTED IN TOTAL OCCUPANT LOAD 22 ROOM OCCUPANT LOAD AT 7 SQ. FT. PER PERSON 20 ROOM OCCUPANT LOAD AT 15 SQ. FT. PER PERSON 2O ROOM OCCUPANT LOAD AT 100 SQ. FT. PER PERSON L a W W H Z a" 0000000 U W 0 Z V)V W F. a= V V) 06 a Ce 9501 E. 86th St. Indlanapoils IN (317) 849-6992 fax (317) 849-6993 103 Wind Haven Nleholsvllle KY (859) 523-1500 fax (859) 523-1514 Q : ...........�! qQ::��C,� Z C5 I— N Qir t. N 21 o z N_:' _ , 0 a0 Q LLJ Z o Q 0 a0 Z rn � a L U rj Z �Z H N Z Z JPq 0 W ag Q Z LLQ J J HCC G W FZ N O � y F14 V) 0 01 x�d VAN 2__ V W0 Project Number: 50049487510 Plan Series: IPF -SC -10-04 Property Number: 500-4948 Sheet Title: CODE INFORMATION IBC Sheet: G102 e o U OLU o � a L U rj N N y^ J J N O � Y fo Project Number: 50049487510 Plan Series: IPF -SC -10-04 Property Number: 500-4948 Sheet Title: CODE INFORMATION IBC Sheet: G102 e