HomeMy WebLinkAboutE14.0SECTION 16010 -GENERAL PROVISIONS A. WORK CONSISTS OF FURNISHING LABOR. MATERIALS. EQUIPMENT AND SERVICES REQUIRED FOR ME COMPLETE INSTALLATION OF ELECTRICAL WORK SHOWN IN WE CONTRACT DOCUMENTS AND SPECIFIED IN DIVISION 16. B. INCLUDE ALL PARTS AND UBOR, WHICH ARE INCIDENTAL AND NECESSARY FOR A COMPLETE AND OPERABLE INSTALLATION EVEN THOUGH NOT SPECIFICALLY MENTIONED IN THE CONTRACT DOCUMENTS. SUCH ITEMS INCLUDE NUTS. BOLTS, ANCHORS, BRACKETS, SLEEVES. OFFSETS IN CONDUIT, FITTINGS. RELAYS. ETC. C. ARRANGE WTH LANDLORD TO PROVIDE TEMPORARY AND PERMANENT UTILITY SERVICES AS REWIRED AND COORDINATE THEIR INSTALLATION WITH CONSTRUCTION PROGRESS OF THIS PROJECT. PAY ALL FEES AND COSTS CHARGED BY UTLITY COMPANIES FOR UTILITY SERVICES D. OBTAIN ALL TEMPORARY AND PERMANENT PERMITS AND LICENSES REWIRED IN CONNECTION WTH THIS DIVISION'S WORK. PAY ALL FEES AND EXPENSES REQUIRED FOR SUCH PERMITS AND LICENSES. E. REQUEST INSPECTIONS AS REQUIRED BY REGULATING AGENCIES AND/Wd REGULATIONS. PAY ALL CHARGES FOR INSPECTIONS BY REGULATING AGENCIES OF INSTALLATIONS OF PUNS AND SPECIFICATIONS. F. INCLUDE STATE AND LOCAL SALES TAXES IN ME BID. KEEP ACCURATE RECORDS OF THESE TAXES AND FURNISH SUCH RECORDS TO ME TENANT UPON REQUEST. G. MEET OR EXCEED ALL CURRENT APPLICABLE CODES, ORDINANCES AND REGI)i FOR ALL INSTALLATIONS. PROMPTLY NOTIFY ME ENGINEER, IN WRITING, IF ME CONTRACT DOCUMENTS APPEAR TO CONVICT WTH GOVERNING CODES AND REGULATIONS. CONTRACTOR ASSUMES ALL RESPONSIBILITY AND COSTS FOR CORRECTING NW -COMPLYING WORK INSTALLED WTHOUT NOTIFYING ME ENGINEER. H. HIGHER QUALITY OF WORKMANSHIP AND MATERIALS INDICATED IN ME CONTRACT DOCUMENTS TAKES PRECEDENCE OVER THAT ALLOWED IN REFERENCED CODES AND STANDARDS. I. ME TERMS DEFINED BELOW APPLY TO ALL WORK INCLUDED IN DIVISION 15. 1. ME TERM 'WORK' MEANS ME CONSMUCTON AND SERVICES REWIRED BY ME CONTRACT DOCUMENTS AND INCLUDES ALL OTHER LABOR. MATERIALS. EQUIPMENT AND SERVICES PROVIDED OR TO BE PROVIDED BY ME CONTRACTOR TO FULFILL ME CONTRACTOR'S OBLIGATIONS. 2. FURNISH - TO OBTAIN IN NEW CONDITION READY FOR INSTALLATION INTO ME WORK. 3. INSTALL - TO STORE, SET IN PLACE, CONNECT AND PLACE INTO OPERATION INTO ME WORK 4. PROVIDE - TO FURNISH AND INSTALL. S. CONNECT - TO BRING SERVICE TO ME EQUIPMENT AND MAKE FINAL ATTACHMENT INCLUDING NECESSARY SWTCHES, CUTLETS, BOXES, TERMINATIONS, ETC. 6. CONDUIT - INCLUDES IN ADDITION TO CONDUIT, ALL FITTINGS, PULL BO%ES, HANGERS AND OTHER SUPPORTS AND ACCESSORIES RELATED TO SUCH CONDUIT. 7. CONCEALED - HIDDEN FROM SIGHT IN CHASES, FURRED SPACES, SHAFTS, HUNG CEILINGS, EMBEDDED IN CONSTRUCTION, IN CRAWL SPACES OR BURIED. B. EXPOSED: NOT INSTALLED UNDERGROUND NOR CONCEALED AS DEFINED ABOVE. J. ME DRAWING AND SPECIFICATIONS CONSTITUTE ME CONTRACT DOCUMENTS. ANY ITEM NOTED IN ME SPECIFICATION OR SHOWN ON ME DRAWNGS IS INCLUDED IN ME CONTRACT DOCUMENTS. K. ALL ELECTRICAL DETAILS AND DRAWNGS ARE DIAGRAMMATIC, UNLESS SPECIFICALLY NOTED. FIELD VERIFY ALL DIMENSIONS AND NOTIFY ME ENGINEER OF ANY CONFLICTS OR DISCREPANCIES, IN MING. PRIOR TO INSTALLATICN. L. INITIATE, MAINTAIN AND SUPERVISE ALL SAFETY PRECAUTIONS REQUIRED WTH THIS WORK IN ACCORDANCE WITH ME REGULATIONS OF THE OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) AND OTHER GOVERNING AGENCIES. M. DO NOT REMOVE OR DISTURB ANY ASBESTOS CONTAINING MATERIALS FROM ME PROJECT. IMMEDIATELY STOP WORK AND NOTIFY ME TENANT IF ASBESTOS CONTAINING MATERIALS ARE SUSPECTED. N. BEFORE SUBMITTING A PROPOSAL ON ME WORK CONTEMPLATED, EXAMINE ME SITE OF THE PROPOSED WORK AND BECOME THOROUGHLY FAMILIAR WTH EXISTING CONDITIONS AND LIMITATIONS. NO EXTRA COMPENSATION WILL BE ALLOWED BECAUSE OF MISUNDERSTANDING AS TO THE AMOUNT OF WORK INVOLVED NOR BIDDERS LACK OF KNOWPDGE OF EXISTING CONDITIONS WHICH COULD HAYS BEEN DISCOVERED OR REASONABLY ANTICIPATED PRIOR TO BIDDING. 0. CONDUITS. PIPES. DUCTS, LIGHTS. DEVICES, SPEAKERS, ETC.. SHOWN ON ME DRAWNGS AS EXISTING HAVE BEEN BASED ON EXISTING PLANS AND MAY NOT BE INSTALLED AS ORIGINALLY SHOWN. IT IS ME CONTRACTORS RESPONSIBILITY TO VISIT ME SITE AND MAKE EXACT DETERMINATION OF ME EXISTENCE, LOCATION AND CONDITION OF SUCH FACILITIES PRIOR TO SUBMITTING A BIO. P. CONSULT ME DRAWNGS AND SPECIFICATIONS OF MECHANICAL AND OMER TRADES FOR CORRELATING INFORMATION AND LAY OUT WORK SO THAT IT WILL COORDINATE WITH OTHER TRADES. VERIFY DIMENSIONS AND CONDITIONS (I.E., FINISHED COLLINS HEIGHTS, FOOTING AND FOUNDATION ELEVATORS, BEAM DEPTHS, ETC.) WTH ME ARCHITECTURAL AND STRUCTURAL DRAWNGS. NOTIFY ME ARCHITECT/ENGINEER OF ANY CONFLICTS THAT CANNOT BE RESOLVED, IN ME FIELD, BY AFFECTED TRADES. REPLACEMENT OF WORK DUE TO LACK OF COORDINATION AND FAILURE TO VERIFY EXISTING CONDITIONS WILL BE COMPLETED AT NO COST TO ME TENANT. 0. INSTALL ALL CONDUIT, CABLE MAY. SUSOUCT, EQUIPMENT, ETC. ALLOWING PROPER CODE AND MAINTENANCE CLEARANCES AND TO AVOID BLOCKING PASSAGEWAYS AND ACCESS PANELS. R. WHERE WORK MUST BE REPLACED DUE TO ME FAILURE OF ME CONTRACTOR TO VERIFY ME CONDITIONS EXISTING ON ME JOB, SUCH REPLACEMENT MUST BE ACCOMPLISHED AT NO COST TO ME TENANT. THIS APPLIES TO SHOP FABRICATED WORK AS WELL AS TO WORK FABRICATED IN PLACE. S. THROUGHOUT ME COURSE OF ME WORK, MINOR CHANGES AND ADJUSTMENTS TO ME INSTALLATION MAY BE REQUESTED BY ME ENGINEER. ME CONTRACTOR SHALL MAKE ADJUSTMENTS WITHOUT ADDITIONAL OST TO ME TENANT, WHERE SUCH ADJUSTMENTS ARE NECESSARY TO WE PROPER INSTALLATION AND OPERATION WITHIN ME INTENT OF ME CONTRACT DOCUMENTS. THIS DOES NOT INCLUDE WORK ALREADY COMPLETED. T. OBTAIN EXACT LOCATION OF CONNECTION TO EQUIPMENT, FURNISHED BY OTHERS, :ROM ME PERSON FURNISHING ME EQUIPMENT. U. DRAWNGS AND SPECIFICATIONS ARE COMPLEMENTARY AND KHAT IS CALLED FOR IN EIMER ONE IS AS BINDING AS IF CALLED FOR IN BOW. V. INCLUDE ME BETTER QUALITY, GREATER QUANTITY OR HIGHER OST FOR AN ITEM OR ARRANGEMENT WHERE A DISAGREEMENT EXISTS IN ME DRAWNGS AND SPECIFICATIONS. W. WARANTEE AND MAINTAIN ME STABILITY OF WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND CONDITION FOR ME PERIOD OF ONE (1) YEAR AFTER ME FINAL COMPLETION OF ME WORK. X. DEFECTS OF ANY KIND DUE TO FAULTY WORK OR MATERIALS APPEARING DURING ME ABOVE MENTIONED PERIOD MUST BE IMMEDIATELY MADE GOOD BY ME CONTRACTOR AT HIS OWN EXPENSE TO ME ENTIRE SATISFACTION OF ME TENANT AND ARCHITECT AND ENGINEER. INCLUDE DAMAGE TO ME FINISH OR ME BUILDING RESULTING FROM ME ORIGINAL DEFECT OR REPAIRS. Y. REPLACE ALL RECEPTACLES, SWTCHES. COVERPUTES. ETC., DAMAGED BY ANY CONTRACTOR DURING ME COURSE OF CONSMUCTION. Z. MATERIALS FURNISHED FOR ME TEMPORARY LIGHT AND POWER SYSTEM REMAIN CONTRACTORS PROPERTY. REMOVE WHEN WERE IS NO LONGER ANY NEED FOR TEMPORARY LIGHT AND POWER. AA. COORDINATE/SCHEDULE ALL WORK WTH ME TENANT TO MINIMIZE ANY DISRUPTIONS. CONFINE ALL INTERRUPTONS TO ME SMALLEST POSSIBLE AREA. PROVIDE TEMPORARY CONNECTIONS IF REQUIRED TO PROVIDE CONTINUITY OF SERMCE. RELEASED FOR CONSTRUCTION Subject to compliance with all regulations of State and Uncal Codes at, City GF Camel IVT�tDN�ADA� DATE: \ 06/06/18 BB. INSPECT ALL AREAS AFFECTED BY ME INTERRUPTIONS AND RETURN ALL AUTOMATICALLY CONTROLLED EQUIPMENT, ELECTRICALLY OPERATED EQUIPMENT TO THE SAME OPERATING CONDITION PRIOR TO THE INTERRUPTION. CC. NO FIRE ALARM SYSTEMS ARE TO REMAIN INACTIVE AT ME END OF ME WORK DAY, ASSURE THAT ME FIRE ALARM SYSTEM IS OPERATIONAL AT THE END OF EACH WORK DAY. COORDINATE WITH ME LANDLORD. DD. DO NOT DISTURB NORMAL USE OF THE FACUTY, EXCEPT WTHIN THE IMMEDIATE CONSTRUCTION AREA. KEEP WALKS, DRIVEWAYS, ENTRANCES, ETC. FREE AND CLEAR OF EQUIPMENT, MATERIAL AND DEBRIS. EE. STORE ALL EQUIPMENT AND MATERIAL IN A PLACE AND MANNER THAT MINIMIZES CONGESTION AND IS APPROVED BY ME TENANT. FF. PROVIDE NEW MATERIAL AND EQUIPMENT. UNLESS NOTED OWERWISE. PROTECT EQUIPMENT AND MATERIAL FROM DAMAGE. DIRT AND ME WEATHER. 0. PROVIDE ME HIGHEST QUAL TY WORKMANSHIP AND PERFORM ALL WORK ONLY BY SKILLED MECHANICS. INSTALL MATERIAL AND EQUIPMENT IN ACCORDANCE MW MANUFACTURERS' RECOMMENDATIONS. INSTRUCTIONS AND CURRENT NECA STANDARDS. HH. ME TENANT RESERVES ME RIGHT TO REJECT MATERIAL OR WORKMANSHIP NOT IN ACCORDANCE WTH ME SPECIFICATONS, BEFORE OR AFTER INSTALLATION. IL PERFORM ALL CUTTING AND PATCHING NECESSARY TO WORK, UNLESS SPECIFICALLY DELEGATED TO ME GENERAL CONTRACTOR. OBTAIN SPECIAL PERMISSION FROM ME LANDLORD BEFORE CUTTING STRUCMRAL MEMBERS OR FINISHED MATERIAL PERFORM ALL PATCHING IN SUCH A MANNER AS TO LEAVE NO MSIBLE TRACE AND RETURN ME AREA AFFECTED TO ME CONDITION OF UNDISTURBED WORK. PERFORM ALL PATCHING BY WORKERS EXPERIENCED, SKILLED, AND LICENSED FOR ME PARTICULAR TYPE OF WORK INVOLVED. INFERIOR WORK WILL NOT BE ACCEPTED. JJ. PATCH ALL HOLES LEFT AS A RESULT OF DEMWTON OF ELECTRICAL EQUIPMENT AND DEVICES. KK. PREVENT ME SPREAD OF DUST, DEBRIS, AND OTHER MATERIAL INTO ADJACENT AREAS. LL. REPLACE ALL CEILING TILES DAMAGED DURING INSTALLATION OF WORK, WITH NEW TILE. MM. REFINISH ALL ELECTRICAL EQUIPMENT DAMAGED DURING SHIPPING AND/OR INSTALLATION TO ITS ORIGINAL CONDITION. REMOVE ALL RUST: PRIME. AND PAINT PER MANUFACTURER'S RECOMMENDATIONS FOR FINISH EQUAL TO ORIGINAL. NN. PAINT ALL NEW RACEWAY SYSTEMS IN EXPOSED FINISHED AREAS. 00. AFTER TESTS HAVE BEEN MADE AND ACCEPTED, CLEAN LIGHT FIXTURES, PANELS AND OTHER EQUIPMENT INSTALLED BY ME CONTRACTOR, LEAVING ME ENTRE WORK AREA IN A CLEAN AND COMPLETE WORKING ORDER. PP. OPERATE EQUIPMENT AND SYSTEMS IN ALL THEIR OPERATING MODES, TO VERIFY PROPER OPERATION, PRIOR TO FINAL INSPECTION AND OMER INSTRUCTIONS. NOTIFY ME ENGINEER, IN WRITING, THAT ALL SYSTEMS HAYS BEEN TESTED AND ARE FUNCTIONING AND OPERATING PROPERLY Go. INCLUDE DOCUMENTATION OF INSTRUCTIONS IN ME OPERATION AND MAINTENANCE MANUALS. RR. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO ELECTRICAL EQUIPMENT OR MATERIALS UNTIL FINAL ACCEPTANCE OF ME ENTRE PROJECT BY ME TENANT. KEEP ALL EQUIPMENT CLEAN MATERIALS UNTIL FINAL ACCEPTANCE OF ME ENTRE PROJECT BY ME TENANT. SS. ROOF PENETRATIONS: COORDINATE WITH LANDLORD. TT. MECHANICAL SUBSTTUTONS: INVOICE MECHANICAL CONTRACTOR, NOT TENANT, FOR COSTS INCLUDED DUE TO SUBSTITUTION OF MECHANICAL EQUIPMENT HAVING ELECTRICAL REQUIREMENTS DIFFERING FROM THOSE INDICATED ON PUNS. SECTION 16050 - BASIC MATERIALS AND METHODS A. ENCASE ML CONDUCTORS IN A CONTINUOUS RACEWAY SYSTEM. PROVIDE PULL AND JUNCTION BOXES AS REWIRED BY ME NEC. SIZE ALL RACEWAY PER ME NEC WW OVERSIZE CONDUITS AS INDICATED. PROVIDE MINIMUM 3/4" CONDUIT FOR BRANCH CIRCUIT HOMERUNS, PROVIDE MINIMUM 1/2" CONDUIT, UNLESS NOTED OTHERWISE. B. PROVIDE EMT FOR ALL CONDUCTORS UNLESS NOTED OTHERWISE. PROVIDE CONCRETE -TIGHT STEEL COMPRESSION OR STEEL SETSCREW TYPE FITTINGS, COUPLINGS AND BUSHINGS. (MC CABLE IS ACCEPTABLE FOR 4' WHIPS AND LESS FOR FINAL FIXTURE CONNECTION MAPS WHERE PERMITTED BY NEC AND APPROVED BY LOCAL AUTHORITY HAMNG JURISDICTION -ELECTRICAL CONTRACTOR SHALL VERIFY PRIOR TO PERFORMING WORK) C. PROVIDE IMC OR CONCRETE -ENCASED PVC CONDUIT FOR SERMCE ENTRANCE CONDUCTORS. D. PVC CONDUIT MAY BE USED UNDERGROUND OR BELOW CONCRETE SLABS. PROVIDE COATED RIGID STEEL ELBOWS FOR ALL ELECTRICAL SERVICE ELBOWS WHERE PVC IS USED. ALL UNDERGROUND PVC PIPING AND ELBOWS FOR BRANCH CIRCUITS ARE ACCEPTABLE WHERE APPROVED BY AUTHORITY HAVING JURISDICTION, ELECTRICAL CONTRACTOR TO VERIFY. E. PROVIDE FLEXIBLE METAL CONDUIT FOR CONNECTIONS TO TRANSFORMERS, MOTORS AND OTHER VIBRATING PIECES OF EQUIPMENT. PROVIDE LIQUID -TIGHT CONDUIT FOR ALL CONNECTIONS IN DAMP OR WET LOCATIONS. PROVIDE GROUND TYPE FITTINGS AND GROUNDING CONDUCTOR INSIDE ALL FLEXIBLE CONDUIT. ADJUST CONDUIT SIZE IF REQUIRED. F. PROVIDE RECESSED OUTLET BOXES AND JUNCTION BOXES IN ALL NEW CONSTRUCTION. CONCEAL ALL CONDUIT WORK IN NEW CONSTRUCTION, EXCEPT MECHANICAL ROOMS. CONDUIT AND BOXES IN MECHANICAL ROOMS MAY BE RUN EXPOSED. G. PROVIDE EXPANSION FITTINGS WHERE RACEWAY CROSSES BUILDING EXPANSION JOINTS. H. J. PROVIDE 4' BOXES THROUGHOUT. PROVIDE 3 1/2" DEEP BOXES WHERE INSTALLED IN MASONRY. 2 1/2" MINIMUM ELSEWHERE. PROVIDE SINGLE GANG MUD OR TLE RING FOR SINGLE DEVICES. K. MOUNT OUTLETS BOXES IN EXPOSED MASONRY WALLS WTH ME BOTTOM OF ME BOX ON ME TOP OF ME MORTAR JOINT AND ME VERTICAL LINE OF ME BOX EITHER ON ME MORTAR JOINT OR ON ME CENTER LINE OF ME MASONRY UNIT. PLUMB AND ACCURATELY ALIGN ALL WALL OUTLETS IN ROWS. MOUNT CEIUNG BOXES SYMMETRICAL WITH WALLS, BEAMS AND/OR TILES. MOUNTING HEIGHTS INDICATED W ME DRAWNGS ARE FROM ME CENTER OF ME OUTLET BOX TO ME FINISHED FLOOR DIRECTLY BELOW ME OUTLLT. EXTERIOR HEIGHTS ARE FROM INSIDE ADJACENT DOOR, OR IF NO DOOR, FROM ME FIRST ROOK ABOVE GRADE, UNLESS NOTED OTHERWISE. L. COORDINATE ME LOCATION OF ALL OUTLETS WITH ARCHITECTURAL AND MECHANICAL DRAWINGS BEFORE INSTALLATION. COORDINATE ALL DOOR SWINGS IN ME FIELD BEFORE LOCATING SWITCHES. M. PROVIDE NEW WRING DEVICES IN EACH OUTLET INDICATED ON ME DRAWINGS, PROVIDE ALL DEVICES FROM ONE MANUFACTURER. N. APPROVED TOGGLE SWITCH MANUFACTURERS/MOEL NUMBERS MANUFACTURER A - ALL - - - - - U L % W ILOT AM 1 -POLE CONTACT 7AROW HART 1991 HBL- 119911 HBL- '992'990HUBBELL HBL- HBL- HSI HSL_ HBL- GF5362 1221 1221PL 1222 1223 1224 1221L 1555 PASS & SEYMOUR 20AC1 20ACl-RPL 20AC2 20AC3 20AC4 20AC1-L 1251 0. APPROVED STANDARD RECEPTACLE MANUFACMRERS/MWEL NUMBERS: MANUFACTURER 201V STANDARD RECEPTACLE S 17L U L % AM RES START ARROW MAKI aa"HUBBELL H85361 H85306Z62 GF5362 IG536 IG5362S N A 53625 PASS & SEW 5361 5382 2091 IG6300 IN N/A S 2 (15 AMP) EATON 5361A 5382A - - - - - P. PROVIDE NEW COWRPLATES OVER ALL BOXES WTH ME FOLLOWING SPECIFICATIONS: ALL FINISHED AREAS AND UNFINISHED AREAS PROVIDE SMOOTH PLASTIC COVERS, COLOR TO BE BLACK IN COLOR FOR DEVICES & COVERPLATES REPLACE ALL EXISTING TO REMAIN DEVICES & COVERPLAMS WITH BLACK. PROVIDE APPROPRIATE COVERS OVER SPECIAL PURPOSE RECEPTACLES. PROVIDE NEW WEATHERPROOF COVERPLATES FOR OUTLETS AND SWTCHES AS INDICATED ON ME DRAWNGS AND FOR ALL EXTERIOR DEMCES. Q. PROVIDE WRE AND CABLE WW INSULATION VOLTAGE RATING EQUAL TO OR GREATER THAN ME APPLIED SYSTEM VOLTAGE. PROVIDE SOLID OR PHASE OR R. PRIOR TO TURNING ME BUILDING OVER TO ME OWNER TURN ON ALL EQUIPMENT IN ME BUILDING INCLUDING LIGHTING AND WTH A MULTMETER, READ ME CURRENT DRAWN ON EACH HOT LEG OF FEEDER SUPPLYING EACH DISTRIBUTION PANEL IF ME CURRENT IN ANY ONE LEG VARIES MORE THAN 5% (PLUS OR MINUS) FROM ME ARIMMETC AVERAGE OF ME CURRENT IN ALL ME HOT LEGS, RECONNECT ME BRANCH CIRCUITS TO OBTAIN A BALANCED LOADING. S. PROVIDE ARE BARRIERS AROUND CONDUIT, PIPE, TUBING, BUS DUCTS AND CABLES PASSING THROUGH SMOKE AND ARE RATED FLOORS AND WALLS. PROVIDE CP 25, 303 AND PSS7904 SERIES BY 3M, OR "FLAME -SAFE" SYSTEM BY THOMAS AND BETTS CORP FOR FIRE SEALS. T. MAKE CONNECTORS TO ALL MOTORS AND EQUIPMENT FURNISHED AND SET IN PLACE BY OTHERS. PROVIDE STARTERS, MANUAL CONTROLS AND AUXILIARY EQUIPMENT WHERE INDICATED IN SCHEDULES AND SPECIFIED HEREIN. PROVIDE ALL DISCONNECT SWITCHES AS INDICATED IN SCHEDULES, SPECIFIED HEREIN AND REQUIRED BY CODE. U. VOLTAGE DROP: FOR CONDUCTORS SIZED PER NEC ON DRAWNGS, INCREASE SIZE BY NUMBER OF STANDARD SIZES SHOWN IN TABLE BELOW TO COMPENSATE FOR VOLTAGE DROP. CONTACT ENGINEER FOR ASSISTANCE IF CIRCUIT LENGTH FROM SOURCE TO LOAD EXCEEDS MAXIMUMS SHOWN. INCREASE j CCT VOLTS/PH GCT LENGTH IT CONDUCTOR SIZES 120/1 75-150 1 120/1 150-200 2 208/3 OR 277/1 150-200 1 208/3 OR 277/1 200-250 2 V. IDENTIFICATION AND LABELING: PROVIDE IOENT KATION AND NAMEPLATES W PANELBOARDS, DISCONNECT SWITCHES AND CONTROLS CUMIN ME TENANT SPACE. NAMEPLATES SHALL BE ENGRAVED LAMINATED PLASTIC, WHITE LETTERS ON BLACK BACKGROUND. LETTERS FOR PANELBOARDS AND SWTCHBOARDS SHALL BE X4" HIGH. LETTER HEIGHTS FOR ALL OTHER NAMEPLATES SHALL BE 1 8" HIGH. PROVIDE SCREW MOUNTED ENGRAVED NAMEPLATES FOR EACH. A RETAIL METERING CENTER 1. METERING: COORDINATE WITH LANDLORD. B. DISCONNECT SWITCH: NEMA K51, GENERAL DUTY. 3 -POLE. S/N IN NEUTRAL IS PRESENT. NEMA W ENCLOSURE IF OUTDOORS. LOCK -OFF. NON -FUSIBLE UNLESS INDICATED WIM FUSES. C. PROVIDE FUSES OF ME FOLLOWING TYPES (SUSSMAN USED AS REFERENCE): 1. 600 AMPS AND ABOVE: TME -DELAY TYPE DESIGNED TO HOD 500% OF RATED CURRENT FOR A MINIMUM OF 4 SECONDS AND CLEAR 20 TIMES CURRENT IN 0.01 SECONDS OR LESS WITH INTERRUPTING RATINGS OF 200.000 AMPERES RMS SYMMETRICAL AND PEAK LET -THROUGH CURRENT AND ENERGY LET -THROUGH VALUES ESTABLISHED BY U.L STANDARD FOR CUSS L FUSES. PROVIDE KRP-C FUSES. 2. BELOW 600 AMPS DUAL -ELEMENT CONSTRUCTION WITH INTERRUPTING RATING OF 200,00 AMPERES RMS SYMMETRICAL AND PEAK LET-THRU CURRENT ESTABLISHED BY U.L. STANDARD FOR CUSS RK -1 FUSES. PROVIDE LPN-RK/LPS-RK. 3. MOTOR CIRCUITS: PROTECT ALL INDIVIDUAL MOTOR CIRCUITS WTH FULL LOAD AMPERE RATING (FLA) OF 4TH AMPERES OR LESS WTH DUAL -ELEMENT TME -DELAY FUSES. PROVIDE LPN-RK/LPS-RK. PROTECT URGER HORSEPOWER MOTORS WTH TME -DELAY FUSES. PROVIDE KRP-C FUSES. PROVIDE U.L. CLASS RK1, DUAL -ELEMENT TME -DELAY FOR ALL OTHER MOTORS 4. MOTOR CONTROLLERS: PROTECT NEMA AND IEC STYLE MOTOR CONTROLLERS WTH DUAL -ELEMENT, TME -DELAY FUSES TO PROVIDE TYPE 2 COORDINATION FOR ME CONTROLLER. PROVIDE LPS-RK FUSES. 5. PROTECT CIRCUIT BREAKER PANELS WTH U.L. CUSS RKY, CUSS L FUSES. PROVIDE LPN -RK, LPS-RK, OR KRP-C FUSES. 6. PROVIDE FUSE SIZES AS INDICATED ON ME DRAWNGS. 7. ACCEPTABLE MANUFACTURERS: BUSSMAN, MRRAZ-SHAWMUT. UTTELFUSE OR PRE -APPROVED EQUAL. D. REUSE EXISTING PANELSOARD.(PROVIDE NEW FOR THE FOLLOWING AS REWIRED) PROVIDE LIGHTING AND APPLIANCE PANELBOARD ASSEMSUES ADHERING TO THE FOLLOWING SPECIFICATIONS 1. ENCLOSURES CONSTRUCTED OF GALVANIZED SHEET STEEL OF THICKNESS AS REQUIRED BY CODE, WITH ENAMELED STEEL TRIM, DISTRIBUTED BUSING, HINGED STEEL DOORS LATCHES, LOCKS AND ADJUSTABLE TRIM CLAMPS. PROVIDE NEMA 3R ENCLOSURES FOR EXTERIOR LOCATIONS. PAINT PANEL. MATCH ADJACENT WALL COLOR. COORDINATE WM ARCHITECT. 2. PROVIDE WELDED METAL FRAME WTH TYPED CIRCUIT DIRECTORY FOR EACH PANEL 3. COMPLIANT TO THE FOLLOWING STANDARDS: UL 50, UL 67, VENA PB -1, NAPA 70 AND FED. SPEC W -P -115C , UL 489, NOMA AB -1, FED. SPEC. W-C-375B/CEN, IEC 157-1 AND BS 4752. 4. COMPLIANT TO ARTICLE 384 OF ME NEC: "UGHTNG AND APPLIANCE PANELBOARD". MAXIMUM OF 42 POLES PER PANELBOARD ASSEMBLY. S PROVIDE PANELBOARDS WITH INTERRUPTING RATINGS AS SHOWN ON ME PLANS. 6. PROVIDE 240 VOLT AC RATED PANELBOARDS FOR 208/120 AND 240 VOLT AC SYSTEMS. 7. PROVIDE TIN-PLATED COPPER BUS BARS OR TIN-PLATED ALUMINUM BUS BARS. 8. PROVIDE PROPER LUGS (75' C. MINIMUM TEMPERATURE RATING) AND GUTTER SPACE FOR CABLE SIZE INDICATED ON ME PUNS. 9. PROVIDE ALL PANELS BY ME SAME MANUFACTURER, 10. PROVIDE MOLDED CASE, NON-ADJUSTABLE, THERMAL-MAGNETC, QUICK -MAKE, QUICK -BREAK, BOLT -ON TYPE CIRCUIT BREAKERS. REFER TO ME SCHEDULES ON ME PUNS FOR SIZES AND QUANTITIES. 11. PROVIDE MULTI -POLE BREAKERS WHERE INDICATED ON ME SCHEDULES. HANDLE TIES ON SINGLE POLE BREAKERS ARE NOT ACCEPTABLE. 12. SERIES RATING OF CIRCUIT BREAKERS IS NOT ALLOWED. 13. ACCEPTABLE MANUFACTURERS: a. 240 VOLT: SQUARE D TYPE MOOD OF NF, SIEMENS TYPE St SERIES, CUTLER HAMMER POW -R -LINE 1A SERIES. GENERAL ELECTRIC M SERIES, OR PRE -APPROVED EQUAL E. PROVIDE PANEL IDENTIFICATION LABEL FOR EACH PANEL INCLUDING PANEL NAME, VOLTAGE AND FEEDER. FOR EXAMPLE: "L-1, 120/208 V. 30, 4 WRE, 2"C - 4 # 4/0 MOON". F. MOUNT PANELBOARDS AND CABINETS TO BUILDING SMUCTURE OR INTERIOR WALL CONSTRUCTION. MOUNT INDEPENDENT OF CONDUIT AND RACEWAYS ENTERING BOXES. G. MOUNT PANELBOARDS WTH CABINET TOP AT 78" ABOVE FINISHED FLOOR. H. PROVIDE 3/4 -EMPTY CONDUITS FROM EACH RUSH MOUNTED PANELBOARD. WHEN ME FLOOR IS ON GRADE, PROVIDE THREE (3) CONDUITS INTO ME CEIUNG CAVITY ABOVE. WHEN ME FLOOR HAS ACCESSIBLE SPACE BELOW, PROVIDE TWO (2) CONDUITS INTO ME CEILING SPACE ABOVE AND TWO (2) CONDUITS INTO ME ACCESSIBLE SPACE BELOW ME FLOOR. ENDS SHALL BE CAPPED AND SHALL BE TAGGED AT BOTH ENDS WITH PERMANENT TAGS. I. EQUIPMENT GROUND - SOLIDLY GROUND ALL CONDUIT SYSTEMS, SWITCH BOXES, CABINETS, MOTOR FRAMES, SWTCHGEAR, TRANSFORMERS, AND ALL OTHER PERMANENTLY INSTALLED EQUIPMENT IN ACCORDANCE WITH ME LATEST EDITION OF ME NATIONAL ELECTRICAL CODE TO FORM A CONTINUOUS, PERMANENT AND EFFECTW GROUNDING SYSTEM. BOND EXPANSION JOINTS AND METAL RACEWAY SECTIONS. PROVIDE GROUND CONDUCTOR AS INDICATED ON ME DRAWNGS OR SPECIFIED HEREIN. J. DRY -TYPE TRANSFORMERS: REUSE EXISTING OR PROVIDE NEW PER ME FOUOWNG. NEW NEMA ST20, 480V - 120/208Y CONNECTED, 115 DEGREE RISE, KVA RATING AS INDICATED. INSTALL USING MBRATION ISOLATORS. FOR JURISDICTIONS WITH REQUIREMENTS FOR ENERGY EFFICIENT TRANSFORMERS, PROVIDE NEMA TYPE Wt, 150 DEGREE RISE. SECTION 16430 - MOTOR CONTROL A. PROVIDE "W -OFF" TOGGLE TYPE MANUAL STARTER SWITCH WTH THERMAL OVERLOAD PROTECTION FOR SINGLE PHASE MOTORS, WHERE MANUAL CONTROL IS INDICATED. PROMOE EACH SWITCH WTH A RED PILOT LIGHT INDICATING WHEN MOTOR IS ON. B. PROVIDE FULL VOLTAGE TYPE STARTERS AND THERMAL OVERLOAD PROTECTION AND EXTERNAL MANUAL RESET FOR ALL THREE-PHASE MOTORS, UNLESS INDICATED OTHERWISE. EQUIP EACH STARTER WITH 120 VOLT COIL, CONTROL POWER TRANSFORMER, SECONDARY FUSE BLOCK AND FUSES, AU%IUARY CONTACTS AS INDICATED, RED "ON" PILOT LIGHT, AND "HAND -OFF -AUTO" CONTROL SWITCH. PROVIDE COMBINATION STARTER/DISCONNECT WHEN INDICATED ON ME PLANS. ACCEPTABLE MANUFACTURERS FOR MAGNETIC STARTERS: ALLEN -BRADLEY BULL. 509 &512. SQUARE D CLASS 8536. CUTLER HAMMER. GENERAL ELECTRIC. ITE/SIEMENS EQUIVALENT OR PRE -APPROVED EQUAL. C. PROVIDE MANUAL MOTOR STARTING SWITCH OR TYPE "SS" FUSED DISCONNECT ADJACENT TO EACH 120 VAC SINCE PHASE MOTOR LOCATED OUT OF SIGHT AND/OR IN EXCESS OF 501 FROM ME CONTROLLER, OR AS INDICATED ON ME DRAWNGS. SECTION 16500 - LIGHTING A. COMPLY WITH NEC AS APPLICABLE TO ME INSTALLATION AND CONSTRUCTION OF LIGHT FIXTURES. B. PROVIDE LIGHT FIXTURES THAT ARE LISTED AND LABELED BY U.L OR ANOTHER NATIONALLY RECOGNIZED TESTING LABORATORY FOR THE APPLICATOR. C. PROVIDE UMP BALLASTS THAT COMPLY WITH CERTIFIED BALLAST MANUFACTURERS ASSOCIATION STANDARDS AND CARRY ME CBM LABEL. D. COMPLY WITH ALL LOCAL, STATE AND FEDERAL ENERGY CODES. E. PROVIDE FIXTURES WITH LAMPS, FOR EACH OUTLET SHOWN ON ME DRAWNGS AND AS SPECIFIED HEREIN. SEE FIXTURES UST W ME PUN. F. PROVIDE FLUORESCENT LAMP BALLASTS WITH ME FOLLOWING MINIMUM SPECIFICATIONS 1. PROVIDE U.L. LISTED AND LABELED, C.B.M. APPROVED BALLASTS. 2. PROGRAMMED RAPID START TECHNOLOGY TO ENSURE LONGEST LAMP UAE 3. TO ONLY: PARALLEL-WRED OPERATION TO ENSURE LIGHT OUTPUT FROM ONE BALLAST EVEN WITH ONE OR TWO LAMPS EXTINGUISHED. 4. COMPACT FLUORESCENT ONLY: SERIES WRED LAMPS FOR MULTIPLE LAMP CONFIGURATIONS. AND PLUG-IN LEAD CONNECTORS FOR ALL UMP LEADS 5. CUSS "P" RATED MW THERMALLY ACTIVATED AUTOMATIC RESETTING PROTECTIVE DEVICES SEALED IN HOUSING. 6. CURRENT CREST FACTOR: 1.7 OR LESS ON 60 HZ MODULATED CURRENT. 7. COMPLY WTH FCC RULES PART 18 REQUIREMENTS GOVERNING ELECTROMAGNETIC AND RADIO FREQUENCY INTERFERENCE 8. COMPLIES WITH IEEE 587 FOR WTHSTANDING UNE TRANSIENTS, VOLTAGE REGULATION + 10 PERCENT, LIGHT REGULATION + 10 PERCENT. 9. BALLAST FACTOR: 0.88 OR HIGHER. 10. POWER FACTOR: GREATER MAN 95 PERCENT 11. SOUND RATING: "A" 12. MINIMUM 5 YEAR WARRANTY INCLUDING S10/13ALLAST LABOR 13, TOTAL HARMONIC DISTORTION: Q07, BUT GREATER MAN 10% 14. END -OF -UAE LAMP SENSING FOR ALL COMPACT FLUORESCENT BALLASTS. G. APPROVED MANUFACTURERS - T8 ELECTRONIC BALLASTS 1. ADVANCE CENTUM PROGRAM RAPID START SERIES 2. UNIVERSAL LIGHTING TECHNOLOOES TRIAD ACCUSTART SERIES H. APPROVED MANUFACTURERS - COMPACT FLUORESCENT 1. MOTOROLA GOD EDITION 2. ROBERTSON 3. OSRAM OUICKTRONIC SERIES 4. UNIVERSAL LIGHTING TECHNOLOGIES I. PROVIDE LAMPS AS NOTED IN UGHT FIXTURE SCHEDULE J. SCUD STATE TYPE TIME SWTCHES. 1. PROVIDE SOLD STATE, PROGRAMMABLE 24 HOUR OR 7 -DAY, El ECMIC TIME SWITCH WITH FOUR (6) SPST CONTACT RATED 20A AT 240 VOLTS. PROVIDE LONG LIFE LITHIUM BATTERY BACKUP TO MAINTAIN TIME AND MEMORY SETTING DURING A POWER OUTAGE. 2. ACCEPTABLE MANUFACTURERS a. PARAGON EC7000 SERIES b. TORK MODEL D100 SERIES c. PRE -APPROVED EQUAL K. NOT USED. L PROVIDE ALL HANGERS, RODS. MOUNTING BRACKETS, SUPPORTS, FRAMES, ETC. FOR PROPER AND SAFE FIXTURE INSTALLATION. INSTALL ALL FIXTURES IN ACCORDANCE WTH MANUFACTURERS' RECOMMENDATIONS AND INSTRUCTIONS. M. PROVIDE FIXTURES COMPLETE WITH ALL AUXILIARIES REQUIRED FOR PROPER, SAFE AND DISTORTION FREE INSTALLATION IN ME VARIOUS CEIUNG CONSTRUCTONS IN WHICH THEY APPEAR. COORDINATE CEIUNG TYPES WITH ME ARCHITECTURAL DRAWNGS AND PROVIDE COMPATIBLE FIXTURES. N. PROVIDE FELT OR FIBERGLASS GASKETS ON ALL INCANDESCENT LIGHTING FIXTURES WHERE NECESSARY TO PREVENT LIGHT LEAKAGE AT ME CEILING UNE. 0. SECURELY SUPPORT ALL LIGHT FIXTURES DIRECTLY FROM BUILDING STRUCTURAL MEMBERS OR 1 1/2" OR LARGER STEEL CEILING FRAMING CHANNELS. USE STEEL CHANNEL EQUIVALENT TO KINDORF #6029 WERE IT IS NECESSARY TO SPAN ME BUILDING STRUCTURAL MEMBERS FOR FIXTURE SUPPORT. WOOD SUPPORTING MEMBERS OR WRES WILL NOT BE ACCEPTABIE. PROVIDE MINIMUM M" DIAMETER LAG SCREWS WHEN ANCHORING INTO WOOD STRUCTURAL MEMBERS. PENETRATE MOOD STRUCTURAL MEMBERS A MINIMUM OF 2" WITH ALL SCREWS. PROVIDE STEM OR LEAD, EXPANDABLE TYPE, ANCHORS WITH MINIMUM PENETRATION OF 1 1/2" WHEN ANCHORING TO CONCRETE. WHEN INSTALLING LIGHT FIXTURES IN A SEISMIC ZONE, SECURE TO MEET ALL REQUIREMENTS. P. DO NOT SUSPEND ANY CONDUIT. LIGHT FIXTURES. OR BALLASTS FROM METAL RIDGE DECK OR FROM ME CEILING SUSPENSION CURES. SUPPORT ALL LAY -IN FIXTURES INDEPENDENT OF ME CEIUNG SUPPORT SYSTEM. PROVIDE FASTENING CUPS ON EACH CORNER OF EACH FIXTURE IN ACCORDANCE WM ME APPLICABLE BUILDING CODES. 0. SUPPORT ALL SURFACE MOUNTED FLUORESCENT FIXTURES WITH A MINIMUM OF ONE HANGER PER FIXTURE PLUS ONE PER ROW. SUPPORT INDIVIDUAL FIXTURES WITH A MINIMUM OF TWO HANGERS. ATTACH FIXTURE HANGERS TO ME CEIUNG GRID PER CODE. R. SUPPORT ALL SUSPENDED FLUORESCENT FIXTURES WITH A MINIMUM OF TWO FIXTURE HANGERS. ATTACH EACH HANGAR TO A DEDICATED ANCHOR. LOCATE HANGARS DIRECTLY ABOVE ME CORNERS OF ME LIGHT FIXTURES. S. WRE ALL RECESSED UY-IN FIXTURES MW 6 FEET OF FLEXIBLE METAL CONDUIT WTH TYPE "MHN/TUWN" WRE TO ME OUTLET BOX. PROVIDE GROUNDING TYPE CONNECTORS FOR ALL CONDUIT AND CABLE. T. PROVIDE OUTLET BOXES ADJACENT TO EACH RECESSED FIXTURE OUTLET IN SUSPENDED CEILINGS TO PERMIT EACH FIXTURE TO BE ADJUSTED TO FIT CEILING PATTERN AND TO PERMIT "FEED THROUGH" WRING. U. AT THE TIME OF SUBSTANTIAL COMPLETION, ALL FIXTURES MUST BE INSTALLED AND LAMPED WW NEW LAMPS. INSTALL ALL FIXTURES COMPLETE WTH LENSES, DIFFUSERS, REFLECTORS, LWYERS AND OTHER REQUIRED ACCESSORIES. V. REPLACE ANY DAMAGED REFLECTORS. DIFFUSERS, LOUVERS OR OTHER COMPONENTS AT NO EXPENSE TO THE OWNER. W. CLEAN ALL FIXTURES FREE OF DUST, FINGER PRINTS, PAINT, ETC.. X. PERFORM AIMING AND ADJUSTMENT OF ALL LIGHTING FIXTURES IN ACCORDANCE WTH INSTRUCTIONS ISSUED BY THE ENGINEER/TENANT. ADJUST ALL DIRECTIONAL TYPE FIXTURES (INTERIOR AND EXTERIOR) AFTER DARK UNDER ME DIRECTION OF THE ARCHITECT, ENGINEER, AND/OR TENANT. Y. REPLACE ALL DEFECTW BALLASTS WITHIN ME GUARANTEE PERIOD AT NO COST TO ME TENANT. Z. INSTALL TIME SWTCHES ADJACENT TO ME SOURCE LIGHTING PANEL, UNLESS SPECIFICALLY LOCATED ELSEWHERE ON ME PUNS. M. PROVIDE 'NAMEPLATES" AS SPECIFIED IN SECTION 16050 FOR ALL CONTACTORS AND TIME SWTCHES. LABEL CONTACTORS AND TIME SWTCHES TO INDICATE LOAD SERVED (E.G., CANOPY LIGHTS, STORE SIGN, ETC.). SECTION 16535- EMERGENCY LIGHTING A PROVIDE AUTOMATIC BATTERY POWERED LIGHTING UNITS AS INDICATED ON ME DRAWNGS. B. PROVIDE EMERGENCY UGHTNG AS SHOWN ON ME PLANS TO ILLUMINATE ME EGRESS CORRIDORS AND OTHER REQUIRED AREAS. REFER TO ME LIGHT FIXTURE SCHEDULE ON ME DRAWNGS FOR TYPES. C. PROVIDE AN INTENSITY OF NOT LESS MAN 1.0 FOOTCANDLE AT ME FLOOR LEVEL ALONG ME PAM OF EGRESS. D. PROVIDE AN EXIT LIGHT AT EACH EXIT AND ALONG ME EGRESS PATH AS REQUIRED. E. CONNECT EMERGENCY UGHM TO ME UNSWTCHED BRANCH CIRCUITS) IN ME AREA PROVIDE HANDLE -LOCK DEVICE FOR THAT CIRCUIT. SECTION 16700 - SYSTEM A. DATA SYSTEM ROUGH -IN: PROVIDE DEDICATED CONTINUOUS 3/4" MINIMUM EMT RACEWAY SYSTEM WITH CAT 5e CABLE FROM DATA SYSTEM EQUIPMENT LOCATION TO ALL DATA SYSTEM OUTLETS FOR NON -PLENUM ACCESSIBLE CEILING SPACES, AND WHERE APPROVED BY TENANT. LANDLORD AND LOCAL AUTHORITY. BUSHED RACEWAY STUBS FROM OUTLET BOXES TO CEILING SPACE ARE PERMITTED IN LIEU OF CONTINUOUS SYSTEM OR AS NOTED. FOR WALL OUTLETS, PROVIDE 4" SQUARE OUTLET BOX WW SINGLE GANG ADAPTER RING AND DATA PLATE. FOR ROOK OUTLET, PROVIDE FLOOR BOX AS ELSEWHERE SPECIFIED AND DATA PLATE. PROVIDE FINAL TERMINATIONS UPON SUCCESSFUL CABLE CONTINUITY TEST. B. TELEPHONE SYSTEM ROUGH -IN: PROVIDE DEDICATED CONTINUOUS 3/4" MINIMUM EMT RACEWAY SYSTEM WITH CAT 5e CABLE FROM LANDLORD STUB -IN TO BACKBOARD AND FROM BACKBOARD TO ALL TELEPHONE OUTLETS. FOR NON -PLENUM ACCESSIBLE CEIUNG SPACES. AND WERE APPROVED BY TENANT. LANDLORD AND LOCAL AUTHORITY, BUSHED RACEWAY STUBS FROM OUTLET BOXES TO CEILING ARE PERMITTED IN LIEU OF CONTINUOUS SYSTEM OR AS NOTED. FOR WALL OUTLETS, PROVIDE 4" SQUARE CUTLET BOX WITH SINGLE BANG ADAPTER RING AND TELEPHONE PLATE. FOR FLOOR OUTLET, PROVIDE FLOOR BOX AS ELSEWHERE SPECIFIED AND TELEPHONE PLATE. PROVIDE 3/4" FIRE -TREATED PLYWOOD BACKBOARD OF SIZE REQUIRED FOR TELEPHONE EQUIPMENT. PROMPTLY NOTIFY TENANT WHEN ROUGH -IN INSTALLATION IS COMPLETE. ME FOUOWNG REQUIREMENTS APPLY TO ME PHONE AND DATA INSTALLATION AND CONSTRUCTION PROCESS. PROVIDE FINAL TERMINATIONS UPON SUCCESSFUL CABLE CONTINUITY TEST. C. CWOUIT MUST BE INSTALLED AND FIRE RATED CAULKING/SEAUNT USED AT ME POINT WHERE ME UNE CROSSES ME DEMISING PARTITION AND ENTERS INTO ME SERVE CORRIDOR (WHICH ARE RATED FOR MPE SAFETY). THIS IS A REQUIREMENT OF ME FIRE MARSHALL. FOR CONSISTENCY, CONDUIT CULL BE USED ABOVE ME TENANT SPACE AND THROUGHOUT ME SPACE. CONDUIT IS LIMITED TO 2" DIAMETER FOR PHONE/DATA LINES. D. SECURITY SYSTEM ROUGH -IN: PROVIDE CONTINUOUS RACEWAY SYSTEM WTH PULL WRE AS INDICATED FOR INSTALLATION OF SECURITY SYSTEMS BY OTHERS. E. SOUND SYSTEWINSTALL SPEAKERS PROVIDED BY RED WNG TO BOTTOM OF ROOF DECK OR TRUSSES- COORDINATE LAYOUT IN FIELD. INSTALL SPEAKER WRE NEATLY FROM SPEAKERS AND EXTEND TO SHELF ABOVE WORK DESK AT 84" A.F.F. LEAVE APPROXIMATELY 10' COIL OF WRE AT END TO ALLOW FOR FINAL INSTALLATION INTO ME AMP AND PLAYER BY OTHERS. Alan J.Plutowski ARCHITECT 4125 Lakeland Ave. N., Suite 200 Minneapolis, Minnesota 55422 763-533-7171 fax 763-533-7979 Consultants 01D p !Mma RED WING SHOES s14 ION 7sr) so wHa w saW M1pXE (SO) SFYIN Certification Project Information RED WING SHOES BUILD -OUT FOR NEW DEALER STORE Red Wing Shoe Store 9893 N. Michigan Rd, ate 1204 Carmel, Indiana 46032 Revisions Date: 04/06/18 Drawn By: SMB Checked By: NMM Job Number: 18RW-007 Sheet Information ELECPRICAL SPECIFICATIONS COPYRIGHT 2018 ALAN J. PLUTOWSKI E4a0 6440.74