HomeMy WebLinkAboutE14.0SECTION 16010 -GENERAL PROVISIONS
A. WORK CONSISTS OF FURNISHING LABOR. MATERIALS. EQUIPMENT AND
SERVICES REQUIRED FOR ME COMPLETE INSTALLATION OF ELECTRICAL
WORK SHOWN IN WE CONTRACT DOCUMENTS AND SPECIFIED IN
DIVISION 16.
B. INCLUDE ALL PARTS AND UBOR, WHICH ARE INCIDENTAL AND
NECESSARY FOR A COMPLETE AND OPERABLE INSTALLATION EVEN
THOUGH NOT SPECIFICALLY MENTIONED IN THE CONTRACT DOCUMENTS.
SUCH ITEMS INCLUDE NUTS. BOLTS, ANCHORS, BRACKETS, SLEEVES.
OFFSETS IN CONDUIT, FITTINGS. RELAYS. ETC.
C. ARRANGE WTH LANDLORD TO PROVIDE TEMPORARY AND PERMANENT
UTILITY SERVICES AS REWIRED AND COORDINATE THEIR INSTALLATION
WITH CONSTRUCTION PROGRESS OF THIS PROJECT. PAY ALL FEES AND
COSTS CHARGED BY UTLITY COMPANIES FOR UTILITY SERVICES
D. OBTAIN ALL TEMPORARY AND PERMANENT PERMITS AND LICENSES
REWIRED IN CONNECTION WTH THIS DIVISION'S WORK. PAY ALL FEES
AND EXPENSES REQUIRED FOR SUCH PERMITS AND LICENSES.
E. REQUEST INSPECTIONS AS REQUIRED BY REGULATING AGENCIES AND/Wd
REGULATIONS. PAY ALL CHARGES FOR INSPECTIONS BY REGULATING
AGENCIES OF INSTALLATIONS OF PUNS AND SPECIFICATIONS.
F. INCLUDE STATE AND LOCAL SALES TAXES IN ME BID. KEEP ACCURATE
RECORDS OF THESE TAXES AND FURNISH SUCH RECORDS TO ME
TENANT UPON REQUEST.
G. MEET OR EXCEED ALL CURRENT APPLICABLE CODES, ORDINANCES AND
REGI)i FOR ALL INSTALLATIONS. PROMPTLY NOTIFY ME
ENGINEER, IN WRITING, IF ME CONTRACT DOCUMENTS APPEAR TO
CONVICT WTH GOVERNING CODES AND REGULATIONS. CONTRACTOR
ASSUMES ALL RESPONSIBILITY AND COSTS FOR CORRECTING
NW -COMPLYING WORK INSTALLED WTHOUT NOTIFYING ME ENGINEER.
H. HIGHER QUALITY OF WORKMANSHIP AND MATERIALS INDICATED IN ME
CONTRACT DOCUMENTS TAKES PRECEDENCE OVER THAT ALLOWED IN
REFERENCED CODES AND STANDARDS.
I. ME TERMS DEFINED BELOW APPLY TO ALL WORK INCLUDED IN
DIVISION 15.
1. ME TERM 'WORK' MEANS ME CONSMUCTON AND SERVICES
REWIRED BY ME CONTRACT DOCUMENTS AND INCLUDES ALL
OTHER LABOR. MATERIALS. EQUIPMENT AND SERVICES PROVIDED
OR TO BE PROVIDED BY ME CONTRACTOR TO FULFILL ME
CONTRACTOR'S OBLIGATIONS.
2. FURNISH - TO OBTAIN IN NEW CONDITION READY FOR
INSTALLATION INTO ME WORK.
3. INSTALL - TO STORE, SET IN PLACE, CONNECT AND PLACE INTO
OPERATION INTO ME WORK
4. PROVIDE - TO FURNISH AND INSTALL.
S. CONNECT - TO BRING SERVICE TO ME EQUIPMENT AND MAKE
FINAL ATTACHMENT INCLUDING NECESSARY SWTCHES, CUTLETS,
BOXES, TERMINATIONS, ETC.
6. CONDUIT - INCLUDES IN ADDITION TO CONDUIT, ALL FITTINGS,
PULL BO%ES, HANGERS AND OTHER SUPPORTS AND ACCESSORIES
RELATED TO SUCH CONDUIT.
7. CONCEALED - HIDDEN FROM SIGHT IN CHASES, FURRED SPACES,
SHAFTS, HUNG CEILINGS, EMBEDDED IN CONSTRUCTION, IN CRAWL
SPACES OR BURIED.
B. EXPOSED: NOT INSTALLED UNDERGROUND NOR CONCEALED AS
DEFINED ABOVE.
J. ME DRAWING AND SPECIFICATIONS CONSTITUTE ME CONTRACT
DOCUMENTS. ANY ITEM NOTED IN ME SPECIFICATION OR SHOWN ON
ME DRAWNGS IS INCLUDED IN ME CONTRACT DOCUMENTS.
K. ALL ELECTRICAL DETAILS AND DRAWNGS ARE DIAGRAMMATIC, UNLESS
SPECIFICALLY NOTED. FIELD VERIFY ALL DIMENSIONS AND NOTIFY ME
ENGINEER OF ANY CONFLICTS OR DISCREPANCIES, IN MING. PRIOR TO
INSTALLATICN.
L. INITIATE, MAINTAIN AND SUPERVISE ALL SAFETY PRECAUTIONS
REQUIRED WTH THIS WORK IN ACCORDANCE WITH ME REGULATIONS OF
THE OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) AND
OTHER GOVERNING AGENCIES.
M. DO NOT REMOVE OR DISTURB ANY ASBESTOS CONTAINING MATERIALS
FROM ME PROJECT. IMMEDIATELY STOP WORK AND NOTIFY ME TENANT
IF ASBESTOS CONTAINING MATERIALS ARE SUSPECTED.
N. BEFORE SUBMITTING A PROPOSAL ON ME WORK CONTEMPLATED,
EXAMINE ME SITE OF THE PROPOSED WORK AND BECOME THOROUGHLY
FAMILIAR WTH EXISTING CONDITIONS AND LIMITATIONS. NO EXTRA
COMPENSATION WILL BE ALLOWED BECAUSE OF MISUNDERSTANDING AS
TO THE AMOUNT OF WORK INVOLVED NOR BIDDERS LACK OF
KNOWPDGE OF EXISTING CONDITIONS WHICH COULD HAYS BEEN
DISCOVERED OR REASONABLY ANTICIPATED PRIOR TO BIDDING.
0. CONDUITS. PIPES. DUCTS, LIGHTS. DEVICES, SPEAKERS, ETC.. SHOWN ON
ME DRAWNGS AS EXISTING HAVE BEEN BASED ON EXISTING PLANS
AND MAY NOT BE INSTALLED AS ORIGINALLY SHOWN. IT IS ME
CONTRACTORS RESPONSIBILITY TO VISIT ME SITE AND MAKE EXACT
DETERMINATION OF ME EXISTENCE, LOCATION AND CONDITION OF SUCH
FACILITIES PRIOR TO SUBMITTING A BIO.
P. CONSULT ME DRAWNGS AND SPECIFICATIONS OF MECHANICAL AND
OMER TRADES FOR CORRELATING INFORMATION AND LAY OUT WORK
SO THAT IT WILL COORDINATE WITH OTHER TRADES. VERIFY DIMENSIONS
AND CONDITIONS (I.E., FINISHED COLLINS HEIGHTS, FOOTING AND
FOUNDATION ELEVATORS, BEAM DEPTHS, ETC.) WTH ME
ARCHITECTURAL AND STRUCTURAL DRAWNGS. NOTIFY ME
ARCHITECT/ENGINEER OF ANY CONFLICTS THAT CANNOT BE RESOLVED,
IN ME FIELD, BY AFFECTED TRADES. REPLACEMENT OF WORK DUE TO
LACK OF COORDINATION AND FAILURE TO VERIFY EXISTING CONDITIONS
WILL BE COMPLETED AT NO COST TO ME TENANT.
0. INSTALL ALL CONDUIT, CABLE MAY. SUSOUCT, EQUIPMENT, ETC.
ALLOWING PROPER CODE AND MAINTENANCE CLEARANCES AND TO
AVOID BLOCKING PASSAGEWAYS AND ACCESS PANELS.
R. WHERE WORK MUST BE REPLACED DUE TO ME FAILURE OF ME
CONTRACTOR TO VERIFY ME CONDITIONS EXISTING ON ME JOB, SUCH
REPLACEMENT MUST BE ACCOMPLISHED AT NO COST TO ME TENANT.
THIS APPLIES TO SHOP FABRICATED WORK AS WELL AS TO WORK
FABRICATED IN PLACE.
S. THROUGHOUT ME COURSE OF ME WORK, MINOR CHANGES AND
ADJUSTMENTS TO ME INSTALLATION MAY BE REQUESTED BY ME
ENGINEER. ME CONTRACTOR SHALL MAKE ADJUSTMENTS WITHOUT
ADDITIONAL OST TO ME TENANT, WHERE SUCH ADJUSTMENTS ARE
NECESSARY TO WE PROPER INSTALLATION AND OPERATION WITHIN ME
INTENT OF ME CONTRACT DOCUMENTS. THIS DOES NOT INCLUDE WORK
ALREADY COMPLETED.
T. OBTAIN EXACT LOCATION OF CONNECTION TO EQUIPMENT, FURNISHED
BY OTHERS, :ROM ME PERSON FURNISHING ME EQUIPMENT.
U. DRAWNGS AND SPECIFICATIONS ARE COMPLEMENTARY AND KHAT IS
CALLED FOR IN EIMER ONE IS AS BINDING AS IF CALLED FOR IN BOW.
V. INCLUDE ME BETTER QUALITY, GREATER QUANTITY OR HIGHER OST
FOR AN ITEM OR ARRANGEMENT WHERE A DISAGREEMENT EXISTS IN
ME DRAWNGS AND SPECIFICATIONS.
W. WARANTEE AND MAINTAIN ME STABILITY OF WORK AND MATERIALS
AND KEEP SAME IN PERFECT REPAIR AND CONDITION FOR ME PERIOD
OF ONE (1) YEAR AFTER ME FINAL COMPLETION OF ME WORK.
X. DEFECTS OF ANY KIND DUE TO FAULTY WORK OR MATERIALS
APPEARING DURING ME ABOVE MENTIONED PERIOD MUST BE
IMMEDIATELY MADE GOOD BY ME CONTRACTOR AT HIS OWN EXPENSE
TO ME ENTIRE SATISFACTION OF ME TENANT AND ARCHITECT AND
ENGINEER. INCLUDE DAMAGE TO ME FINISH OR ME BUILDING
RESULTING FROM ME ORIGINAL DEFECT OR REPAIRS.
Y. REPLACE ALL RECEPTACLES, SWTCHES. COVERPUTES. ETC., DAMAGED
BY ANY CONTRACTOR DURING ME COURSE OF CONSMUCTION.
Z. MATERIALS FURNISHED FOR ME TEMPORARY LIGHT AND POWER SYSTEM
REMAIN CONTRACTORS PROPERTY. REMOVE WHEN WERE IS NO LONGER
ANY NEED FOR TEMPORARY LIGHT AND POWER.
AA. COORDINATE/SCHEDULE ALL WORK WTH ME TENANT TO MINIMIZE ANY
DISRUPTIONS. CONFINE ALL INTERRUPTONS TO ME SMALLEST POSSIBLE
AREA. PROVIDE TEMPORARY CONNECTIONS IF REQUIRED TO PROVIDE
CONTINUITY OF SERMCE.
RELEASED FOR CONSTRUCTION
Subject to compliance with all regulations
of State and Uncal Codes
at,
City
GF Camel
IVT�tDN�ADA�
DATE: \ 06/06/18
BB. INSPECT ALL AREAS AFFECTED BY ME INTERRUPTIONS AND RETURN
ALL AUTOMATICALLY CONTROLLED EQUIPMENT, ELECTRICALLY OPERATED
EQUIPMENT TO THE SAME OPERATING CONDITION PRIOR TO THE
INTERRUPTION.
CC. NO FIRE ALARM SYSTEMS ARE TO REMAIN INACTIVE AT ME END OF
ME WORK DAY, ASSURE THAT ME FIRE ALARM SYSTEM IS
OPERATIONAL AT THE END OF EACH WORK DAY. COORDINATE WITH
ME LANDLORD.
DD. DO NOT DISTURB NORMAL USE OF THE FACUTY, EXCEPT WTHIN THE
IMMEDIATE CONSTRUCTION AREA. KEEP WALKS, DRIVEWAYS, ENTRANCES,
ETC. FREE AND CLEAR OF EQUIPMENT, MATERIAL AND DEBRIS.
EE. STORE ALL EQUIPMENT AND MATERIAL IN A PLACE AND MANNER THAT
MINIMIZES CONGESTION AND IS APPROVED BY ME TENANT.
FF. PROVIDE NEW MATERIAL AND EQUIPMENT. UNLESS NOTED OWERWISE.
PROTECT EQUIPMENT AND MATERIAL FROM DAMAGE. DIRT AND ME
WEATHER.
0. PROVIDE ME HIGHEST QUAL TY WORKMANSHIP AND PERFORM ALL WORK
ONLY BY SKILLED MECHANICS. INSTALL MATERIAL AND EQUIPMENT IN
ACCORDANCE MW MANUFACTURERS' RECOMMENDATIONS. INSTRUCTIONS
AND CURRENT NECA STANDARDS.
HH. ME TENANT RESERVES ME RIGHT TO REJECT MATERIAL OR
WORKMANSHIP NOT IN ACCORDANCE WTH ME SPECIFICATONS, BEFORE
OR AFTER INSTALLATION.
IL PERFORM ALL CUTTING AND PATCHING NECESSARY TO WORK, UNLESS
SPECIFICALLY DELEGATED TO ME GENERAL CONTRACTOR. OBTAIN
SPECIAL PERMISSION FROM ME LANDLORD BEFORE CUTTING
STRUCMRAL MEMBERS OR FINISHED MATERIAL PERFORM ALL
PATCHING IN SUCH A MANNER AS TO LEAVE NO MSIBLE TRACE AND
RETURN ME AREA AFFECTED TO ME CONDITION OF UNDISTURBED
WORK. PERFORM ALL PATCHING BY WORKERS EXPERIENCED, SKILLED,
AND LICENSED FOR ME PARTICULAR TYPE OF WORK INVOLVED.
INFERIOR WORK WILL NOT BE ACCEPTED.
JJ. PATCH ALL HOLES LEFT AS A RESULT OF DEMWTON OF ELECTRICAL
EQUIPMENT AND DEVICES.
KK. PREVENT ME SPREAD OF DUST, DEBRIS, AND OTHER MATERIAL INTO
ADJACENT AREAS.
LL. REPLACE ALL CEILING TILES DAMAGED DURING INSTALLATION OF WORK,
WITH NEW TILE.
MM. REFINISH ALL ELECTRICAL EQUIPMENT DAMAGED DURING SHIPPING
AND/OR INSTALLATION TO ITS ORIGINAL CONDITION. REMOVE ALL RUST:
PRIME. AND PAINT PER MANUFACTURER'S RECOMMENDATIONS FOR
FINISH EQUAL TO ORIGINAL.
NN. PAINT ALL NEW RACEWAY SYSTEMS IN EXPOSED FINISHED AREAS.
00. AFTER TESTS HAVE BEEN MADE AND ACCEPTED, CLEAN LIGHT
FIXTURES, PANELS AND OTHER EQUIPMENT INSTALLED BY ME
CONTRACTOR, LEAVING ME ENTRE WORK AREA IN A CLEAN AND
COMPLETE WORKING ORDER.
PP. OPERATE EQUIPMENT AND SYSTEMS IN ALL THEIR OPERATING MODES,
TO VERIFY PROPER OPERATION, PRIOR TO FINAL INSPECTION AND
OMER INSTRUCTIONS. NOTIFY ME ENGINEER, IN WRITING, THAT ALL
SYSTEMS HAYS BEEN TESTED AND ARE FUNCTIONING AND OPERATING
PROPERLY
Go. INCLUDE DOCUMENTATION OF INSTRUCTIONS IN ME OPERATION AND
MAINTENANCE MANUALS.
RR. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO ELECTRICAL
EQUIPMENT OR MATERIALS UNTIL FINAL ACCEPTANCE OF ME ENTRE
PROJECT BY ME TENANT. KEEP ALL EQUIPMENT CLEAN MATERIALS
UNTIL FINAL ACCEPTANCE OF ME ENTRE PROJECT BY ME TENANT.
SS. ROOF PENETRATIONS: COORDINATE WITH LANDLORD.
TT. MECHANICAL SUBSTTUTONS: INVOICE MECHANICAL CONTRACTOR, NOT
TENANT, FOR COSTS INCLUDED DUE TO SUBSTITUTION OF MECHANICAL
EQUIPMENT HAVING ELECTRICAL REQUIREMENTS DIFFERING FROM THOSE
INDICATED ON PUNS.
SECTION 16050 - BASIC MATERIALS AND METHODS
A. ENCASE ML CONDUCTORS IN A CONTINUOUS RACEWAY SYSTEM.
PROVIDE PULL AND JUNCTION BOXES AS REWIRED BY ME NEC. SIZE
ALL RACEWAY PER ME NEC WW OVERSIZE CONDUITS AS INDICATED.
PROVIDE MINIMUM 3/4" CONDUIT FOR BRANCH CIRCUIT HOMERUNS,
PROVIDE MINIMUM 1/2" CONDUIT, UNLESS NOTED OTHERWISE.
B. PROVIDE EMT FOR ALL CONDUCTORS UNLESS NOTED OTHERWISE.
PROVIDE CONCRETE -TIGHT STEEL COMPRESSION OR STEEL SETSCREW
TYPE FITTINGS, COUPLINGS AND BUSHINGS. (MC CABLE IS ACCEPTABLE
FOR 4' WHIPS AND LESS FOR FINAL FIXTURE CONNECTION MAPS WHERE
PERMITTED BY NEC AND APPROVED BY LOCAL AUTHORITY HAMNG
JURISDICTION -ELECTRICAL CONTRACTOR SHALL VERIFY PRIOR TO
PERFORMING WORK)
C. PROVIDE IMC OR CONCRETE -ENCASED PVC CONDUIT FOR SERMCE
ENTRANCE CONDUCTORS.
D. PVC CONDUIT MAY BE USED UNDERGROUND OR BELOW CONCRETE
SLABS. PROVIDE COATED RIGID STEEL ELBOWS FOR ALL ELECTRICAL
SERVICE ELBOWS WHERE PVC IS USED. ALL UNDERGROUND PVC PIPING
AND ELBOWS FOR BRANCH CIRCUITS ARE ACCEPTABLE WHERE
APPROVED BY AUTHORITY HAVING JURISDICTION, ELECTRICAL
CONTRACTOR TO VERIFY.
E. PROVIDE FLEXIBLE METAL CONDUIT FOR CONNECTIONS TO
TRANSFORMERS, MOTORS AND OTHER VIBRATING PIECES OF EQUIPMENT.
PROVIDE LIQUID -TIGHT CONDUIT FOR ALL CONNECTIONS IN DAMP OR
WET LOCATIONS. PROVIDE GROUND TYPE FITTINGS AND GROUNDING
CONDUCTOR INSIDE ALL FLEXIBLE CONDUIT. ADJUST CONDUIT SIZE IF
REQUIRED.
F. PROVIDE RECESSED OUTLET BOXES AND JUNCTION BOXES IN ALL NEW
CONSTRUCTION. CONCEAL ALL CONDUIT WORK IN NEW CONSTRUCTION,
EXCEPT MECHANICAL ROOMS. CONDUIT AND BOXES IN MECHANICAL
ROOMS MAY BE RUN EXPOSED.
G. PROVIDE EXPANSION FITTINGS WHERE RACEWAY CROSSES BUILDING
EXPANSION JOINTS.
H.
J. PROVIDE 4' BOXES THROUGHOUT. PROVIDE 3 1/2" DEEP BOXES WHERE
INSTALLED IN MASONRY. 2 1/2" MINIMUM ELSEWHERE. PROVIDE SINGLE
GANG MUD OR TLE RING FOR SINGLE DEVICES.
K. MOUNT OUTLETS BOXES IN EXPOSED MASONRY WALLS WTH ME
BOTTOM OF ME BOX ON ME TOP OF ME MORTAR JOINT AND ME
VERTICAL LINE OF ME BOX EITHER ON ME MORTAR JOINT OR ON ME
CENTER LINE OF ME MASONRY UNIT. PLUMB AND ACCURATELY ALIGN
ALL WALL OUTLETS IN ROWS. MOUNT CEIUNG BOXES SYMMETRICAL WITH
WALLS, BEAMS AND/OR TILES. MOUNTING HEIGHTS INDICATED W ME
DRAWNGS ARE FROM ME CENTER OF ME OUTLET BOX TO ME
FINISHED FLOOR DIRECTLY BELOW ME OUTLLT. EXTERIOR HEIGHTS ARE
FROM INSIDE ADJACENT DOOR, OR IF NO DOOR, FROM ME FIRST ROOK
ABOVE GRADE, UNLESS NOTED OTHERWISE.
L. COORDINATE ME LOCATION OF ALL OUTLETS WITH ARCHITECTURAL AND
MECHANICAL DRAWINGS BEFORE INSTALLATION. COORDINATE ALL DOOR
SWINGS IN ME FIELD BEFORE LOCATING SWITCHES.
M. PROVIDE NEW WRING DEVICES IN EACH OUTLET INDICATED ON ME
DRAWINGS, PROVIDE ALL DEVICES FROM ONE MANUFACTURER.
N. APPROVED TOGGLE SWITCH MANUFACTURERS/MOEL NUMBERS
MANUFACTURER
A
- ALL
-
-
- -
-
U L %
W ILOT
AM
1 -POLE
CONTACT
7AROW HART
1991
HBL-
119911
HBL-
'992'990HUBBELL
HBL- HBL-
HSI
HSL_
HBL-
GF5362
1221
1221PL
1222 1223
1224
1221L
1555
PASS & SEYMOUR
20AC1
20ACl-RPL
20AC2 20AC3
20AC4
20AC1-L
1251
0. APPROVED STANDARD RECEPTACLE MANUFACMRERS/MWEL NUMBERS:
MANUFACTURER
201V
STANDARD
RECEPTACLE
S
17L
U L %
AM
RES START
ARROW MAKI
aa"HUBBELL H85361
H85306Z62
GF5362
IG536
IG5362S
N A
53625
PASS & SEW
5361
5382
2091
IG6300
IN
N/A
S 2 (15 AMP)
EATON
5361A
5382A
-
-
-
-
-
P. PROVIDE NEW COWRPLATES OVER ALL BOXES WTH ME FOLLOWING
SPECIFICATIONS: ALL FINISHED AREAS AND UNFINISHED AREAS PROVIDE
SMOOTH PLASTIC COVERS, COLOR TO BE BLACK IN COLOR FOR DEVICES
& COVERPLATES REPLACE ALL EXISTING TO REMAIN DEVICES &
COVERPLAMS WITH BLACK. PROVIDE APPROPRIATE COVERS OVER
SPECIAL PURPOSE RECEPTACLES. PROVIDE NEW WEATHERPROOF
COVERPLATES FOR OUTLETS AND SWTCHES AS INDICATED ON ME
DRAWNGS AND FOR ALL EXTERIOR DEMCES.
Q. PROVIDE WRE AND CABLE WW INSULATION VOLTAGE RATING EQUAL TO
OR GREATER THAN ME APPLIED SYSTEM VOLTAGE. PROVIDE SOLID OR
PHASE
OR
R. PRIOR TO TURNING ME BUILDING OVER TO ME OWNER TURN ON ALL
EQUIPMENT IN ME BUILDING INCLUDING LIGHTING AND WTH A
MULTMETER, READ ME CURRENT DRAWN ON EACH HOT LEG OF
FEEDER SUPPLYING EACH DISTRIBUTION PANEL IF ME CURRENT IN
ANY ONE LEG VARIES MORE THAN 5% (PLUS OR MINUS) FROM ME
ARIMMETC AVERAGE OF ME CURRENT IN ALL ME HOT LEGS,
RECONNECT ME BRANCH CIRCUITS TO OBTAIN A BALANCED LOADING.
S. PROVIDE ARE BARRIERS AROUND CONDUIT, PIPE, TUBING, BUS DUCTS
AND CABLES PASSING THROUGH SMOKE AND ARE RATED FLOORS AND
WALLS. PROVIDE CP 25, 303 AND PSS7904 SERIES BY 3M, OR
"FLAME -SAFE" SYSTEM BY THOMAS AND BETTS CORP FOR FIRE SEALS.
T. MAKE CONNECTORS TO ALL MOTORS AND EQUIPMENT FURNISHED AND
SET IN PLACE BY OTHERS. PROVIDE STARTERS, MANUAL CONTROLS
AND AUXILIARY EQUIPMENT WHERE INDICATED IN SCHEDULES AND
SPECIFIED HEREIN. PROVIDE ALL DISCONNECT SWITCHES AS INDICATED
IN SCHEDULES, SPECIFIED HEREIN AND REQUIRED BY CODE.
U. VOLTAGE DROP: FOR CONDUCTORS SIZED PER NEC ON DRAWNGS,
INCREASE SIZE BY NUMBER OF STANDARD SIZES SHOWN IN TABLE
BELOW TO COMPENSATE FOR VOLTAGE DROP. CONTACT ENGINEER FOR
ASSISTANCE IF CIRCUIT LENGTH FROM SOURCE TO LOAD EXCEEDS
MAXIMUMS SHOWN.
INCREASE j
CCT VOLTS/PH GCT LENGTH IT CONDUCTOR SIZES
120/1 75-150 1
120/1 150-200 2
208/3 OR 277/1 150-200 1
208/3 OR 277/1 200-250 2
V. IDENTIFICATION AND LABELING: PROVIDE IOENT KATION AND
NAMEPLATES W PANELBOARDS, DISCONNECT SWITCHES AND CONTROLS
CUMIN ME TENANT SPACE. NAMEPLATES SHALL BE ENGRAVED
LAMINATED PLASTIC, WHITE LETTERS ON BLACK BACKGROUND. LETTERS
FOR PANELBOARDS AND SWTCHBOARDS SHALL BE X4" HIGH. LETTER
HEIGHTS FOR ALL OTHER NAMEPLATES SHALL BE 1 8" HIGH. PROVIDE
SCREW MOUNTED ENGRAVED NAMEPLATES FOR EACH.
A RETAIL METERING CENTER
1. METERING: COORDINATE WITH LANDLORD.
B. DISCONNECT SWITCH: NEMA K51, GENERAL DUTY. 3 -POLE. S/N IN
NEUTRAL IS PRESENT. NEMA W ENCLOSURE IF OUTDOORS. LOCK -OFF.
NON -FUSIBLE UNLESS INDICATED WIM FUSES.
C. PROVIDE FUSES OF ME FOLLOWING TYPES (SUSSMAN USED AS
REFERENCE):
1. 600 AMPS AND ABOVE: TME -DELAY TYPE DESIGNED TO HOD
500% OF RATED CURRENT FOR A MINIMUM OF 4 SECONDS AND
CLEAR 20 TIMES CURRENT IN 0.01 SECONDS OR LESS WITH
INTERRUPTING RATINGS OF 200.000 AMPERES RMS SYMMETRICAL
AND PEAK LET -THROUGH CURRENT AND ENERGY LET -THROUGH
VALUES ESTABLISHED BY U.L STANDARD FOR CUSS L FUSES.
PROVIDE KRP-C FUSES.
2. BELOW 600 AMPS DUAL -ELEMENT CONSTRUCTION WITH
INTERRUPTING RATING OF 200,00 AMPERES RMS SYMMETRICAL
AND PEAK LET-THRU CURRENT ESTABLISHED BY U.L. STANDARD
FOR CUSS RK -1 FUSES. PROVIDE LPN-RK/LPS-RK.
3. MOTOR CIRCUITS: PROTECT ALL INDIVIDUAL MOTOR CIRCUITS
WTH FULL LOAD AMPERE RATING (FLA) OF 4TH AMPERES OR
LESS WTH DUAL -ELEMENT TME -DELAY FUSES. PROVIDE
LPN-RK/LPS-RK. PROTECT URGER HORSEPOWER MOTORS WTH
TME -DELAY FUSES. PROVIDE KRP-C FUSES. PROVIDE U.L. CLASS
RK1, DUAL -ELEMENT TME -DELAY FOR ALL OTHER MOTORS
4. MOTOR CONTROLLERS: PROTECT NEMA AND IEC STYLE MOTOR
CONTROLLERS WTH DUAL -ELEMENT, TME -DELAY FUSES TO
PROVIDE TYPE 2 COORDINATION FOR ME CONTROLLER. PROVIDE
LPS-RK FUSES.
5. PROTECT CIRCUIT BREAKER PANELS WTH U.L. CUSS RKY, CUSS
L FUSES. PROVIDE LPN -RK, LPS-RK, OR KRP-C FUSES.
6. PROVIDE FUSE SIZES AS INDICATED ON ME DRAWNGS.
7. ACCEPTABLE MANUFACTURERS: BUSSMAN, MRRAZ-SHAWMUT.
UTTELFUSE OR PRE -APPROVED EQUAL.
D. REUSE EXISTING PANELSOARD.(PROVIDE NEW FOR THE FOLLOWING AS
REWIRED) PROVIDE LIGHTING AND APPLIANCE PANELBOARD
ASSEMSUES ADHERING TO THE FOLLOWING SPECIFICATIONS
1. ENCLOSURES CONSTRUCTED OF GALVANIZED SHEET STEEL OF
THICKNESS AS REQUIRED BY CODE, WITH ENAMELED STEEL TRIM,
DISTRIBUTED BUSING, HINGED STEEL DOORS LATCHES, LOCKS AND
ADJUSTABLE TRIM CLAMPS. PROVIDE NEMA 3R ENCLOSURES FOR
EXTERIOR LOCATIONS. PAINT PANEL. MATCH
ADJACENT WALL COLOR. COORDINATE WM ARCHITECT.
2. PROVIDE WELDED METAL FRAME WTH TYPED CIRCUIT DIRECTORY
FOR EACH PANEL
3. COMPLIANT TO THE FOLLOWING STANDARDS: UL 50, UL 67, VENA
PB -1, NAPA 70 AND FED. SPEC W -P -115C , UL 489, NOMA
AB -1, FED. SPEC. W-C-375B/CEN, IEC 157-1 AND BS 4752.
4. COMPLIANT TO ARTICLE 384 OF ME NEC: "UGHTNG AND
APPLIANCE PANELBOARD". MAXIMUM OF 42 POLES PER
PANELBOARD ASSEMBLY.
S PROVIDE PANELBOARDS WITH INTERRUPTING RATINGS AS SHOWN
ON ME PLANS.
6. PROVIDE 240 VOLT AC RATED PANELBOARDS FOR 208/120 AND
240 VOLT AC SYSTEMS.
7. PROVIDE TIN-PLATED COPPER BUS BARS OR TIN-PLATED
ALUMINUM BUS BARS.
8. PROVIDE PROPER LUGS (75' C. MINIMUM TEMPERATURE RATING)
AND GUTTER SPACE FOR CABLE SIZE INDICATED ON ME PUNS.
9. PROVIDE ALL PANELS BY ME SAME MANUFACTURER,
10. PROVIDE MOLDED CASE, NON-ADJUSTABLE, THERMAL-MAGNETC,
QUICK -MAKE, QUICK -BREAK, BOLT -ON TYPE CIRCUIT BREAKERS.
REFER TO ME SCHEDULES ON ME PUNS FOR SIZES AND
QUANTITIES.
11. PROVIDE MULTI -POLE BREAKERS WHERE INDICATED ON ME
SCHEDULES. HANDLE TIES ON SINGLE POLE BREAKERS ARE NOT
ACCEPTABLE.
12. SERIES RATING OF CIRCUIT BREAKERS IS NOT ALLOWED.
13. ACCEPTABLE MANUFACTURERS:
a. 240 VOLT: SQUARE D TYPE MOOD OF NF, SIEMENS TYPE St
SERIES, CUTLER HAMMER POW -R -LINE 1A SERIES. GENERAL
ELECTRIC M SERIES, OR PRE -APPROVED EQUAL
E. PROVIDE PANEL IDENTIFICATION LABEL FOR EACH PANEL INCLUDING
PANEL NAME, VOLTAGE AND FEEDER. FOR EXAMPLE: "L-1, 120/208 V.
30, 4 WRE, 2"C - 4 # 4/0 MOON".
F. MOUNT PANELBOARDS AND CABINETS TO BUILDING SMUCTURE OR
INTERIOR WALL CONSTRUCTION. MOUNT INDEPENDENT OF CONDUIT AND
RACEWAYS ENTERING BOXES.
G. MOUNT PANELBOARDS WTH CABINET TOP AT 78" ABOVE FINISHED
FLOOR.
H. PROVIDE 3/4 -EMPTY CONDUITS FROM EACH RUSH MOUNTED
PANELBOARD. WHEN ME FLOOR IS ON GRADE, PROVIDE THREE (3)
CONDUITS INTO ME CEIUNG CAVITY ABOVE. WHEN ME FLOOR HAS
ACCESSIBLE SPACE BELOW, PROVIDE TWO (2) CONDUITS INTO ME
CEILING SPACE ABOVE AND TWO (2) CONDUITS INTO ME ACCESSIBLE
SPACE BELOW ME FLOOR. ENDS SHALL BE CAPPED AND SHALL BE
TAGGED AT BOTH ENDS WITH PERMANENT TAGS.
I. EQUIPMENT GROUND - SOLIDLY GROUND ALL CONDUIT SYSTEMS,
SWITCH BOXES, CABINETS, MOTOR FRAMES, SWTCHGEAR,
TRANSFORMERS, AND ALL OTHER PERMANENTLY INSTALLED EQUIPMENT
IN ACCORDANCE WITH ME LATEST EDITION OF ME NATIONAL
ELECTRICAL CODE TO FORM A CONTINUOUS, PERMANENT AND EFFECTW
GROUNDING SYSTEM. BOND EXPANSION JOINTS AND METAL RACEWAY
SECTIONS. PROVIDE GROUND CONDUCTOR AS INDICATED ON ME
DRAWNGS OR SPECIFIED HEREIN.
J. DRY -TYPE TRANSFORMERS: REUSE EXISTING OR PROVIDE NEW PER
ME FOUOWNG. NEW NEMA ST20, 480V - 120/208Y CONNECTED, 115
DEGREE RISE, KVA RATING AS INDICATED. INSTALL USING MBRATION
ISOLATORS. FOR JURISDICTIONS WITH REQUIREMENTS FOR ENERGY
EFFICIENT TRANSFORMERS, PROVIDE NEMA TYPE Wt, 150 DEGREE RISE.
SECTION 16430 - MOTOR CONTROL
A. PROVIDE "W -OFF" TOGGLE TYPE MANUAL STARTER SWITCH WTH
THERMAL OVERLOAD PROTECTION FOR SINGLE PHASE MOTORS, WHERE
MANUAL CONTROL IS INDICATED. PROMOE EACH SWITCH WTH A RED
PILOT LIGHT INDICATING WHEN MOTOR IS ON.
B. PROVIDE FULL VOLTAGE TYPE STARTERS AND THERMAL OVERLOAD
PROTECTION AND EXTERNAL MANUAL RESET FOR ALL THREE-PHASE
MOTORS, UNLESS INDICATED OTHERWISE. EQUIP EACH STARTER WITH
120 VOLT COIL, CONTROL POWER TRANSFORMER, SECONDARY FUSE
BLOCK AND FUSES, AU%IUARY CONTACTS AS INDICATED, RED "ON"
PILOT LIGHT, AND "HAND -OFF -AUTO" CONTROL SWITCH. PROVIDE
COMBINATION STARTER/DISCONNECT WHEN INDICATED ON ME PLANS.
ACCEPTABLE MANUFACTURERS FOR MAGNETIC STARTERS:
ALLEN -BRADLEY BULL. 509 &512. SQUARE D CLASS 8536. CUTLER
HAMMER. GENERAL ELECTRIC. ITE/SIEMENS EQUIVALENT OR
PRE -APPROVED EQUAL.
C. PROVIDE MANUAL MOTOR STARTING SWITCH OR TYPE "SS" FUSED
DISCONNECT ADJACENT TO EACH 120 VAC SINCE PHASE MOTOR
LOCATED OUT OF SIGHT AND/OR IN EXCESS OF 501 FROM ME
CONTROLLER, OR AS INDICATED ON ME DRAWNGS.
SECTION 16500 - LIGHTING
A. COMPLY WITH NEC AS APPLICABLE TO ME INSTALLATION AND
CONSTRUCTION OF LIGHT FIXTURES.
B. PROVIDE LIGHT FIXTURES THAT ARE LISTED AND LABELED BY U.L OR
ANOTHER NATIONALLY RECOGNIZED TESTING LABORATORY FOR THE
APPLICATOR.
C. PROVIDE UMP BALLASTS THAT COMPLY WITH CERTIFIED BALLAST
MANUFACTURERS ASSOCIATION STANDARDS AND CARRY ME CBM
LABEL.
D. COMPLY WITH ALL LOCAL, STATE AND FEDERAL ENERGY CODES.
E. PROVIDE FIXTURES WITH LAMPS, FOR EACH OUTLET SHOWN ON ME
DRAWNGS AND AS SPECIFIED HEREIN. SEE FIXTURES UST W ME
PUN.
F. PROVIDE FLUORESCENT LAMP BALLASTS WITH ME FOLLOWING MINIMUM
SPECIFICATIONS
1. PROVIDE U.L. LISTED AND LABELED, C.B.M. APPROVED BALLASTS.
2. PROGRAMMED RAPID START TECHNOLOGY TO ENSURE LONGEST
LAMP UAE
3. TO ONLY: PARALLEL-WRED OPERATION TO ENSURE LIGHT
OUTPUT FROM ONE BALLAST EVEN WITH ONE OR TWO LAMPS
EXTINGUISHED.
4. COMPACT FLUORESCENT ONLY: SERIES WRED LAMPS FOR
MULTIPLE LAMP CONFIGURATIONS. AND PLUG-IN LEAD
CONNECTORS FOR ALL UMP LEADS
5. CUSS "P" RATED MW THERMALLY ACTIVATED AUTOMATIC
RESETTING PROTECTIVE DEVICES SEALED IN HOUSING.
6. CURRENT CREST FACTOR: 1.7 OR LESS ON 60 HZ MODULATED
CURRENT.
7. COMPLY WTH FCC RULES PART 18 REQUIREMENTS GOVERNING
ELECTROMAGNETIC AND RADIO FREQUENCY INTERFERENCE
8. COMPLIES WITH IEEE 587 FOR WTHSTANDING UNE TRANSIENTS,
VOLTAGE REGULATION + 10 PERCENT, LIGHT REGULATION + 10
PERCENT.
9. BALLAST FACTOR: 0.88 OR HIGHER.
10. POWER FACTOR: GREATER MAN 95 PERCENT
11. SOUND RATING: "A"
12. MINIMUM 5 YEAR WARRANTY INCLUDING S10/13ALLAST LABOR
13, TOTAL HARMONIC DISTORTION: Q07, BUT GREATER MAN 10%
14. END -OF -UAE LAMP SENSING FOR ALL COMPACT FLUORESCENT
BALLASTS.
G. APPROVED MANUFACTURERS - T8 ELECTRONIC BALLASTS
1. ADVANCE CENTUM PROGRAM RAPID START SERIES
2. UNIVERSAL LIGHTING TECHNOLOOES TRIAD ACCUSTART SERIES
H. APPROVED MANUFACTURERS - COMPACT FLUORESCENT
1. MOTOROLA GOD EDITION
2. ROBERTSON
3. OSRAM OUICKTRONIC SERIES
4. UNIVERSAL LIGHTING TECHNOLOGIES
I. PROVIDE LAMPS AS NOTED IN UGHT FIXTURE SCHEDULE
J. SCUD STATE TYPE TIME SWTCHES.
1. PROVIDE SOLD STATE, PROGRAMMABLE 24 HOUR OR 7 -DAY,
El ECMIC TIME SWITCH WITH FOUR (6) SPST CONTACT RATED 20A
AT 240 VOLTS. PROVIDE LONG LIFE LITHIUM BATTERY BACKUP
TO MAINTAIN TIME AND MEMORY SETTING DURING A POWER
OUTAGE.
2. ACCEPTABLE MANUFACTURERS
a. PARAGON EC7000 SERIES
b. TORK MODEL D100 SERIES
c. PRE -APPROVED EQUAL
K. NOT USED.
L PROVIDE ALL HANGERS, RODS. MOUNTING BRACKETS, SUPPORTS,
FRAMES, ETC. FOR PROPER AND SAFE FIXTURE INSTALLATION.
INSTALL ALL FIXTURES IN ACCORDANCE WTH MANUFACTURERS'
RECOMMENDATIONS AND INSTRUCTIONS.
M. PROVIDE FIXTURES COMPLETE WITH ALL AUXILIARIES REQUIRED FOR
PROPER, SAFE AND DISTORTION FREE INSTALLATION IN ME VARIOUS
CEIUNG CONSTRUCTONS IN WHICH THEY APPEAR. COORDINATE
CEIUNG TYPES WITH ME ARCHITECTURAL DRAWNGS AND PROVIDE
COMPATIBLE FIXTURES.
N. PROVIDE FELT OR FIBERGLASS GASKETS ON ALL INCANDESCENT
LIGHTING FIXTURES WHERE NECESSARY TO PREVENT LIGHT LEAKAGE
AT ME CEILING UNE.
0. SECURELY SUPPORT ALL LIGHT FIXTURES DIRECTLY FROM BUILDING
STRUCTURAL MEMBERS OR 1 1/2" OR LARGER STEEL CEILING
FRAMING CHANNELS. USE STEEL CHANNEL EQUIVALENT TO KINDORF
#6029 WERE IT IS NECESSARY TO SPAN ME BUILDING STRUCTURAL
MEMBERS FOR FIXTURE SUPPORT. WOOD SUPPORTING MEMBERS OR
WRES WILL NOT BE ACCEPTABIE. PROVIDE MINIMUM M" DIAMETER
LAG SCREWS WHEN ANCHORING INTO WOOD STRUCTURAL MEMBERS.
PENETRATE MOOD STRUCTURAL MEMBERS A MINIMUM OF 2" WITH ALL
SCREWS. PROVIDE STEM OR LEAD, EXPANDABLE TYPE, ANCHORS
WITH MINIMUM PENETRATION OF 1 1/2" WHEN ANCHORING TO
CONCRETE. WHEN INSTALLING LIGHT FIXTURES IN A SEISMIC ZONE,
SECURE TO MEET ALL REQUIREMENTS.
P. DO NOT SUSPEND ANY CONDUIT. LIGHT FIXTURES. OR BALLASTS
FROM METAL RIDGE DECK OR FROM ME CEILING SUSPENSION CURES.
SUPPORT ALL LAY -IN FIXTURES INDEPENDENT OF ME CEIUNG
SUPPORT SYSTEM. PROVIDE FASTENING CUPS ON EACH CORNER OF
EACH FIXTURE IN ACCORDANCE WM ME APPLICABLE BUILDING
CODES.
0. SUPPORT ALL SURFACE MOUNTED FLUORESCENT FIXTURES WITH A
MINIMUM OF ONE HANGER PER FIXTURE PLUS ONE PER ROW.
SUPPORT INDIVIDUAL FIXTURES WITH A MINIMUM OF TWO HANGERS.
ATTACH FIXTURE HANGERS TO ME CEIUNG GRID PER CODE.
R. SUPPORT ALL SUSPENDED FLUORESCENT FIXTURES WITH A MINIMUM
OF TWO FIXTURE HANGERS. ATTACH EACH HANGAR TO A DEDICATED
ANCHOR. LOCATE HANGARS DIRECTLY ABOVE ME CORNERS OF ME
LIGHT FIXTURES.
S. WRE ALL RECESSED UY-IN FIXTURES MW 6 FEET OF FLEXIBLE
METAL CONDUIT WTH TYPE "MHN/TUWN" WRE TO ME OUTLET BOX.
PROVIDE GROUNDING TYPE CONNECTORS FOR ALL CONDUIT AND
CABLE.
T. PROVIDE OUTLET BOXES ADJACENT TO EACH RECESSED FIXTURE
OUTLET IN SUSPENDED CEILINGS TO PERMIT EACH FIXTURE TO BE
ADJUSTED TO FIT CEILING PATTERN AND TO PERMIT "FEED THROUGH"
WRING.
U. AT THE TIME OF SUBSTANTIAL COMPLETION, ALL FIXTURES MUST BE
INSTALLED AND LAMPED WW NEW LAMPS. INSTALL ALL FIXTURES
COMPLETE WTH LENSES, DIFFUSERS, REFLECTORS, LWYERS AND
OTHER REQUIRED ACCESSORIES.
V. REPLACE ANY DAMAGED REFLECTORS. DIFFUSERS, LOUVERS OR
OTHER COMPONENTS AT NO EXPENSE TO THE OWNER.
W. CLEAN ALL FIXTURES FREE OF DUST, FINGER PRINTS, PAINT, ETC..
X. PERFORM AIMING AND ADJUSTMENT OF ALL LIGHTING FIXTURES IN
ACCORDANCE WTH INSTRUCTIONS ISSUED BY THE ENGINEER/TENANT.
ADJUST ALL DIRECTIONAL TYPE FIXTURES (INTERIOR AND EXTERIOR)
AFTER DARK UNDER ME DIRECTION OF THE ARCHITECT, ENGINEER,
AND/OR TENANT.
Y. REPLACE ALL DEFECTW BALLASTS WITHIN ME GUARANTEE PERIOD
AT NO COST TO ME TENANT.
Z. INSTALL TIME SWTCHES ADJACENT TO ME SOURCE LIGHTING PANEL,
UNLESS SPECIFICALLY LOCATED ELSEWHERE ON ME PUNS.
M. PROVIDE 'NAMEPLATES" AS SPECIFIED IN SECTION 16050 FOR ALL
CONTACTORS AND TIME SWTCHES. LABEL CONTACTORS AND TIME
SWTCHES TO INDICATE LOAD SERVED (E.G., CANOPY LIGHTS, STORE
SIGN, ETC.).
SECTION 16535- EMERGENCY LIGHTING
A PROVIDE AUTOMATIC BATTERY POWERED LIGHTING UNITS AS
INDICATED ON ME DRAWNGS.
B. PROVIDE EMERGENCY UGHTNG AS SHOWN ON ME PLANS TO
ILLUMINATE ME EGRESS CORRIDORS AND OTHER REQUIRED AREAS.
REFER TO ME LIGHT FIXTURE SCHEDULE ON ME DRAWNGS FOR
TYPES.
C. PROVIDE AN INTENSITY OF NOT LESS MAN 1.0 FOOTCANDLE AT ME
FLOOR LEVEL ALONG ME PAM OF EGRESS.
D. PROVIDE AN EXIT LIGHT AT EACH EXIT AND ALONG ME EGRESS
PATH AS REQUIRED.
E. CONNECT EMERGENCY UGHM TO ME UNSWTCHED BRANCH
CIRCUITS) IN ME AREA PROVIDE HANDLE -LOCK DEVICE FOR THAT
CIRCUIT.
SECTION 16700 - SYSTEM
A. DATA SYSTEM ROUGH -IN: PROVIDE DEDICATED CONTINUOUS 3/4"
MINIMUM EMT RACEWAY SYSTEM WITH CAT 5e CABLE FROM DATA
SYSTEM EQUIPMENT LOCATION TO ALL DATA SYSTEM OUTLETS FOR
NON -PLENUM ACCESSIBLE CEILING SPACES, AND WHERE APPROVED
BY TENANT. LANDLORD AND LOCAL AUTHORITY. BUSHED RACEWAY
STUBS FROM OUTLET BOXES TO CEILING SPACE ARE PERMITTED IN
LIEU OF CONTINUOUS SYSTEM OR AS NOTED. FOR WALL OUTLETS,
PROVIDE 4" SQUARE OUTLET BOX WW SINGLE GANG ADAPTER RING
AND DATA PLATE. FOR ROOK OUTLET, PROVIDE FLOOR BOX AS
ELSEWHERE SPECIFIED AND DATA PLATE. PROVIDE FINAL
TERMINATIONS UPON SUCCESSFUL CABLE CONTINUITY TEST.
B. TELEPHONE SYSTEM ROUGH -IN: PROVIDE DEDICATED CONTINUOUS
3/4" MINIMUM EMT RACEWAY SYSTEM WITH CAT 5e CABLE FROM
LANDLORD STUB -IN TO BACKBOARD AND FROM BACKBOARD TO ALL
TELEPHONE OUTLETS. FOR NON -PLENUM ACCESSIBLE CEIUNG
SPACES. AND WERE APPROVED BY TENANT. LANDLORD AND LOCAL
AUTHORITY, BUSHED RACEWAY STUBS FROM OUTLET BOXES TO
CEILING ARE PERMITTED IN LIEU OF CONTINUOUS SYSTEM OR AS
NOTED. FOR WALL OUTLETS, PROVIDE 4" SQUARE CUTLET BOX WITH
SINGLE BANG ADAPTER RING AND TELEPHONE PLATE. FOR FLOOR
OUTLET, PROVIDE FLOOR BOX AS ELSEWHERE SPECIFIED AND
TELEPHONE PLATE. PROVIDE 3/4" FIRE -TREATED PLYWOOD
BACKBOARD OF SIZE REQUIRED FOR TELEPHONE EQUIPMENT.
PROMPTLY NOTIFY TENANT WHEN ROUGH -IN INSTALLATION IS
COMPLETE. ME FOUOWNG REQUIREMENTS APPLY TO ME PHONE
AND DATA INSTALLATION AND CONSTRUCTION PROCESS. PROVIDE
FINAL TERMINATIONS UPON SUCCESSFUL CABLE CONTINUITY TEST.
C. CWOUIT MUST BE INSTALLED AND FIRE RATED CAULKING/SEAUNT
USED AT ME POINT WHERE ME UNE CROSSES ME DEMISING
PARTITION AND ENTERS INTO ME SERVE CORRIDOR (WHICH ARE
RATED FOR MPE SAFETY). THIS IS A REQUIREMENT OF ME FIRE
MARSHALL. FOR CONSISTENCY, CONDUIT CULL BE USED ABOVE ME
TENANT SPACE AND THROUGHOUT ME SPACE. CONDUIT IS LIMITED
TO 2" DIAMETER FOR PHONE/DATA LINES.
D. SECURITY SYSTEM ROUGH -IN: PROVIDE CONTINUOUS RACEWAY
SYSTEM WTH PULL WRE AS INDICATED FOR INSTALLATION OF
SECURITY SYSTEMS BY OTHERS.
E. SOUND SYSTEWINSTALL SPEAKERS PROVIDED BY RED WNG TO
BOTTOM OF ROOF DECK OR TRUSSES- COORDINATE LAYOUT IN
FIELD. INSTALL SPEAKER WRE NEATLY FROM SPEAKERS AND EXTEND
TO SHELF ABOVE WORK DESK AT 84" A.F.F. LEAVE APPROXIMATELY
10' COIL OF WRE AT END TO ALLOW FOR FINAL INSTALLATION INTO
ME AMP AND PLAYER BY OTHERS.
Alan J.Plutowski
ARCHITECT
4125 Lakeland Ave. N., Suite 200
Minneapolis, Minnesota 55422
763-533-7171 fax 763-533-7979
Consultants
01D p
!Mma
RED WING SHOES
s14 ION 7sr) so wHa w saW
M1pXE (SO) SFYIN
Certification
Project Information
RED WING SHOES
BUILD -OUT FOR
NEW DEALER
STORE
Red Wing Shoe Store
9893 N. Michigan Rd, ate 1204
Carmel, Indiana 46032
Revisions
Date: 04/06/18
Drawn By: SMB
Checked By: NMM
Job Number: 18RW-007
Sheet Information
ELECPRICAL SPECIFICATIONS
COPYRIGHT 2018 ALAN J. PLUTOWSKI
E4a0
6440.74