GENERAL PROVISIONS
A. THE TERMS DEFINED BELOW APPLY TO ALL WORK INCLUDED IN
THE CONTRACT DOCUMENTS.
1. THE TERM 'WORK' MEANS THE CONSTRUCTION AND SERVICES
REQUIRED BY THE CONTRACT DOCUMENTS AND INCLUDES ALL
OTHER LABOR, MATERIALS, EQUIPMENT AND SERVICES
PROVIDED OR TO BE PROVIDED BY THE CONTRACTOR TO
FULFILL THE MECHANICAL SUBCONTRACTOR'S OBUGARONS.
2. FURNISH — TO OBTAIN IN NEW CONDITION READY FOR
INSTALLATION INTO THE WORK.
3. INSTALL — TO STORE, SE IN PLACE, CONNECT AND PUCE
INTO OPERATION INTO THE WORK.
4. PROVIDE — TO FURNISH AND INSTALL
5. CONNECT — TO BRING SERVICE TO THE EQUIPMENT AND
MAKE FINAL ATTACHMENT INCLUDING NECESSARY SWITCHES,
OUTLETS, BOXES, TERMINATIONS, EC.
6. CONDUIT — INCLUDES IN ADDITION TO CONDUIT, ALL FITTINGS,
PULL BOXES, HANGERS AND OTHER SUPPORTS AND
ACCESSORIES RELATED TO SUCH CONDUIT.
7. CONCEALED — HIDDEN FROM SIGHT IN CHASES, FURRED
SPACES, SHAFTS, HUNG CEILINGS, EMBEDDED IN
CONSTRUCTION, IN CRAWL SPACES OR BURIED.
S. EXPOSED — NOT INSTALLED UNDERGROUND NOR CONCEALED
AS DEFINED ABOVE.
B. THE GENERAL CONDITIONS, SPECIAL CONDITIONS, SUPPLEMENTARY
CONDITIONS, AND MECHANICAL SPECIFICATIONS OF THE MAIN MALL
SPECIFICATIONS AND "GENERAL CONDITIONS OF THE CONTRACT",
CURRENT EDITION, ESTABLISHED IN STANDARD FORM BY THE
AMERICAN INSTITUTE OF ARCHITECTS SHALL APPLY TO ALL WORK
ON THIS PROJECT EXCEPT AS MODIFIED BELOW. COORDINATE THE
MECHANICAL WORK WITH OTHER TRADES AND TENANT PRIOR TO
INSTALLATION.
C. THE ARCHITECTURAL ELECTRICAL AND FIRE PROTECTION PIANS
AND SPECIFICATIONS ARE A PART OF THE CONTRACT DOCUMENTS.
THE MECHANICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME
FAMILLMIZED WITH ALL CONDITIONS SURROUNDING THE WORK. IF
ANY OF THE CONDRIONS REQUIRE A MODIFICATION OF THE
SYSTEMS INDICATED BY THESE PLANS AND SPECIFICATIONS, ADVISE
THE ENGINEER OF THE REQUIRED MODIFICATIONS AND IF
APPROVED BY THE ENGINEER, INCLUDE THE COST OF SUCH
MODIFICATIONS IN HIS BID.
D. THROUGHOUT THE COURSE OF THE WORK, MINOR CHANGES AND
ADJUSTMENTS TO THE PLIAS AND SPECIFICATIONS MAY BE
REQUESTED BY THE TENANT. MAKE SUCH ADJUSTMENTS WITHOUT
ADDITIONAL COST TO THE TENANT, WHERE SUCH ADJUSTMENTS
ME NECESSARY FOR THE PROPER INSTALLATION AND OPERATION
OF THE SYSTEMS, AND WITHIN THE INTENT OF THE CONTRACT
DOCUMENTS.
E. R IS THE INTENT OF THE PLANS AND SPECIFICATIONS TO PROVIDE
INFORMATION FOR A COMPLETE INSTALLATION. EVERYTHING
NECESSARY FOR THE COMPLETION AND SUCCESSFUL OPERATION
OF THE WORK, WHETHER OR NOT HEREIN DEFINITELY SPECIFIED
OR INDICATED ON THE DRAWINGS, SHALL BE FURNISHED AND
INSTALLED AS WELL AND AS FAITHFULLY AS IF SO SPECIFIED OR
INDICATED WITHOUT ADDITIONAL COST TO THE TENANT. THE
MECHANICAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND
LENGTHS PRIOR TO INSTALLATION.
F. NOTWTHSIANDING ANY OTHER PROVISIONS OF THE CONTRACT
DOCUMENTS. THE MECHANICAL CONTACTOR BEARS ULTIMATE
RESPONSIBILITY FOR COMPLIANCE OF THE INSTALLATION WITH THE
REQUIREMENTS OF THE LANDLORD AND OF THE LOCAL AUTHORITY
HAVING JURISDICTION.
G. IF ANY ERRORS, DISCREPANCIES OR OMISSIONS APPEAR IN THE
DRAWINGS, SPECIFICATIONS OR OTHER CONTRACT DOCUMENTS, THE
MECHANICAL CONTRACTOR SHALL NOTIFY THE ENGINEER IN
WRITING OF SUCH ERROR OR OMISSION. IN THE EVENT THIS
CONTRACTOR FAILS TO GIVE SUCH NOTICE BEFORE CONSTRUCTION
AND/OR FABRICATION OF THE WORK, HE WILL BE HELD
RESPONSIBLE FOR THE RESULTS OF ANY SUCH ERRORS,
DISCREPANCIES OR OMISSIONS AND THE COST OF RECTIFYING
SAME.
H. COMPLY WITH THE REQUIREMENTS OF ALL STATE AND LOCAL
CODES REGULATING THIS WORK.
I. PAY ALL FEES AND RELATED CHARGES FOR PERMITS. LICENSES,
ETC., REQUIRED FOR INSTALLATION OF THE MECHANICAL SYSTEM.
J. REIMBURSE THE ELEC70CAL CONTACTOR, WITHOUT ANY COST TO
TENANT OR LANDLORD, ANY ADDITIONAL EXPENSES THE
ELECTRICAL CONTRACTOR INCURS DUE TO THE MECHANICAL
CONTRACTOR'S SUBSTITUTION OF MECHANICAL EQUIPMENT HAVING
DIFFERENT ELECTRICAL SERVICE REQUIREMENTS THAN THE
SCHEDULED EQUIPMENT.
K. PROVIDE THE ARCHITECT AND/OR OWNER WITH A MINIMUM OF
FIVE CERTIFIED COPIES OF ALL SHOP AND EQUIPMENT DRAWINGS
FOR HIS APPROVAL, TWO OF WHICH SHAT BE RETAINED BY THE
ARCHITECT. AND THE REMAINING BEING RETURNED TO THE
GENERAL CONTRACTOR. DRAWINGS SHALL BE SUBMITTED BEFORE
START OF CONSTRUCTION. FAILURE OF COMPLIANCE WITH THIS
PARAGRAPH WILL RESULT IN WITHHOLDING OF FINAL PAYMENT.
L PROVIDE A WRITTEN WARRANTY THAT THE ENTRE INSTALLATION IS
FREE FROM DEFECTS IN MATERIALS AND WORKMANSHIP FOR A
PERIOD OF ONE YEAR, EXCEPT THAT AR CONDITIONING
COMPRESSORS SHALL BE WARRANTED FOR FIVE (5) YEARS AND
GAS FIRED HEAT EXCHANGERS SHALL BE WARRANTED FOR TEN
(10) YEARS.
M. ALL WORKMANSHIP AND MATERIALS SHALL MEET OR EXCEED THE
INDUSTRY FOR QUALITY IN EVERY RESPECT. ALL MATERIALS AND
EQUIPMENT SHALL BE NEW, OF THE LATEST DESIGN AND FREE OF
DEFECTS.
N. DESIGN ALL PIPING AND DUCTWORK TO PRESENT A NEAT AND
ORDERLY APPEARANCE. RUN ALL LINES PARALLEL WITH BUILDING
WALLS AND CONSTRUCTION. KEEP PIPING AND DUCTWORK FREE
FROM CONTACT WITH STRUCTURE OR EQUIPMENT TO PREVENT
NOISE TRANSMISSION. ALLOWING CLEARANCE FOR EXPANSION AND
CONTRACTION. PROVIDE ACCESS DOORS OR PANELS FOR ALL
VALVES, CLFANOUTS, DAMPERS, CONTROLS, DEVICES, ETC.
0. PROVIDE VIBRATION ISOLATION DEVICES FOR Al MOVING
MACHINERY. PROVIDE FLEXIBLE CONNECTIONS TO ALL MOVING
MACHINERY.
P. ALL WELDING SHALL BE PERFORMED IN ACCORDANCE WITH THE
NATIONAL CERTIFIED PIPE WELDING BUREAU, LOCAL CODES OR
OTHER APPROVED PROCEDURE CONFORMING TO THE ASME CODE
FOR PRESSURE PIPING.
O FURNISH Al MATERIALS AND LABOR FOR COMPLETE AND FULL
OPERATION OF THE ENCOMPASSED SYSTEMS.
R. BEFORE BIDS ME RECEIVED, INFORM THE OWNER OF PERCEIVED
OMISSIONS. ISSUES IN THE SPECIFICATIONS OR ISSUES ON THE
PLANS. OTHERWISE, THE ABOVE DOCUMENTS WILL BE CONSIDERED
SUFFICIENT NOTIFICATION TO PROVIDE MATERIAL AND LABOR FOR
A COMPLETE AND OPERATIONAL SYSTEM.
DUCTWORK
A THE AR DISTRIBUTION SYSTEM SHALL BE FABRICATED M
RECOMMENDED IN THE LATEST EDITION OF THE SMACNA LOW
VELOCITY DUCTWORK MANUAL AND INSTALLED WHERE SHOWN ON
HVAC PUN. FURNISH ALL REQUIRED DAMPERS, TRANSITIONS, AND
CONNECTIONS TO AR TERMINALS NECESSARY FOR A COMPLETE
OPERATING SYSTEM.
B. FABRICATE AND INSTALL AS RECOMMENDED IN LATEST
EDITION OF SMACNA HVAC DUCTWORK CONSTRUCTION STANDARDS
— MEM AND FLEXIBLE AND THE ASHRAE GUIDE AND DATA BOOK
FOR SHEET MEAL DUCTWORK SERVING SUPPLY, RETURN AND
EXHAUST SYSTEMS OPERATING BETWEEN —2.0 IN. W.G. AND +2.0
IN. W.G. MAXIMUM PRESSURE. INSTAL WHERE SHOWN ON THE
PLAINS. DUCT SIZES SHOWN ON THE PUNS ME INTERIOR CLEAR
DIMENSIONS. WHERE INTERNAL INSULATION IS PROVIDED, DUCT
SIZES SHALL BE INCREASED AS REQUIRED TO MAINTAIN THE
INDICATED INTERIOR CLEAR DIMENSIONS. PROVIDE DUCTWORK IN
ACCORDANCE WITH INDUSTRY STANDARDS FOR ACHIEVING AIR
TIGHT 5 PERCENT LEAKAGE AND NOISELESS (NO OBJECTIONABLE
NOISE) SYSTEMS, CAPABLE OF PERFORMING EACH INDICATED
SERVICE.
C. FABRICATE DUCTWORK FROM GALVANIZED SHEET STEEL COMPLYING
WITH ANSI/ASTM, SMACNk INDUSTRY STANDARDS AND LOCAL
CODE REQUIREMENTS. MINIMUM SHEET THICKNESS AND
REINFORCING SHALL BE AS FOLLOWS:
1. DUCTS UP TO 12" WIDEST DIMENSION (OR DIAMETER): 26
GAUGE
2. DUCTS 13" TO 30" WIDEST DIMENSION: 24 GAUGE
3. DUCTS 31" TO 54" WIDEST DIMENSION: 22 GAUGE
D. DUCT SEALANT: UNITED DUCT SEALER OR EQUAL PROVIDE A
NON—HARDENING, NON—MIGRATNG MASTIC OR UOUID ELASTIC
SEALANT OF A TYPE AS RECOMMENDED BY THE MANUFACTURER
SPECIFICALLY FOR SEANNG JOINTS AND SEAMS IN SHEET MEM
DUCTWORK. ALL DUCTWORK SHALL HAVE SEALED LONGITUDINAL
AND TRANSVERSE JOINTS. WHERE SUP AND DRIVE JOINTS ARE
WE. A SEALER SR41L BE APPLIED OVER THE ENTIRE JOINT
AFTER THE DRIVE IS IN PUCE APPLY A SECONDARY LAYER OF
SEALER AT THE CORNERS AFTER THE DRIVE ENDS ARE CRIMPED
IN PLACE. ALL LONGITUDINAL SEAMS SHALL BE COVERED WITH A
SEALING MASTIC. ALL SUP JOINTS SHALL BE MADE AND COATED,
THEN INSERTED INTO THE DUCT OR COLLAR AND SECURED WITH
SHEET METAL SCREWS. COVER THE ENTIRE OUTER JOIN" AND
SCREWS WITH MASTIC. COVER JOINTS AROUND ALL SPIN—IN
FITTINGS. INTERNALLY CLEAN DUCTWORK OF OUST AND DEBRIS.
E SUPPORT MATERIALS: EXCEPT AS OTHERWISE INDICATED, PROVIDE
HOT—DIPPED GALVANIZED SHEET FASTENERS, ANCHORS, RODS,
STOPS, TRIM, AND ANGLES FOR SUPPORT OF DUCTWORK.
F. ANY SUPPLY DUCTWORK AND PLENUMS THAT ARE DESIGNED TO
OPERATE AT STATIC PRESSURES GREATER THAN 0.25" WG BUT
LESS THAN 2" WG, WHICH ME LOCATED OUTSIDE OF THE
CONDITIONED SPACE OR IN RETURN PLENUMS, SHALL HAVE
JOINTS SEALED IN ACCORDANCE WITH SEM CUSS AS DEFINED IN
THE Sell HVAC DUCT LEAKAGE TEST MANUAL PRESSURE
SENSITIVE TAPE SHALL NOT BE USED AS THE PRIMARY SEALANT
WHERE SUCH DUCTS ME DESIGNED TO OPERATE AT STATIC
PRESSURES OVER 1" W.G.
DUCTWORK ACCESSORIES
A BALANCING DAMPERS: AR BALANCE, INC., LOUVERS @ DAMPERS,
INC., GREENHECK, RUSKIN, OR EQUAL PROVIDE MANUAL. SINGLE
OR MULTIBLADE DAMPERS, AS INDICATED AND AS CONSTRUCTED IN
ACCORDANCE WITH SMACNA STANDARDS.
B. DAMPERS SHALL HAVE RIGID 2" X 1/2" X10—GAUGE CHANNEL
FRAMES, HALL OR BRONZE SLEEVE BEARINGS, 1/2" POLISHED
STEEL AXLES, 16—GAUGE, REINFORCED, FELT—EDGED BLADES (NOT
OVER 8" WIDE) AND STOP FRAMES MOUND THE ENTIRE
PERIMETER. VOLUME DAMPERS IN DUCTS LARGER 12" X 6" SHALL
BE THE OPPOSED BLADE TYPE. DAMPERS IN ROUND DUCTS AND
DUCTS 12" X 6" AND SMALLER SHALL BE BUTTERFLY TYPE
ROUND BUTTERFLY TYPE VOLUME DAMPERS SHALL BE 26—GAUGE
STEEL THROUGH 12" DIAMETER, 24—GAUGE FOR ABOVE 120
.
C. PROVIDE VENTFMRICS. YOUNG REGULATOR, OR EQUAL DAMPERS.
ALL DAMPERS SHALL BE EQUIPPED WITH STANDARD OUMDR NTS
OF SUITABLE SIZE IN EQUIPMENT ROOMS/BACK OF HOUSE ARES.
PROVIDE YOUNG REGULATOR MODEL J 301A. OR EQUAL,
RECESSED—TYPE IN FINISHED MEAS. PROVIDE QUADRANT LOCKING
DEVICE FOR EACH DAMPER ON ONE END OF THE SHAFT AND AN
END BEARING EXTENDED QUADRANT LOCKED AND EXTENDED
BEARING PLATES FOR EXTERNALLY INSULATED DUCTWORK.
D. VOLUME DAMPERS SHALL BE PROVIDED IN ALL DUCTS TO PERMIT
ACCURATE BALANCING OF THE SYSTEM. THE DAMPERS SHALL BE
ADJUSTED TO SATISFY THE HEATING, COOLING AND VENTILATING
REQUIREMENTS OF THE CONDITIONED SPACE AND LOCKED IN
PLACE.
E. MOTORIZED DAMPERS: FURNISH AND INSTAL ALL MOTORIZED
DAMPERS SHOWN ON THE PUNS AND REQUIRED FOR SYSTEM
OPERATION AND AS DESCRIBED IN THIS SECRON AND NOT BEING
FURNISHED WITH EQUIPMENT. DAMPERS SHALL BE OPPOSED
BLADE WITH NEOPRENE EDGES AND SHALL NOT BE LESS THAN 13
GAUGE GALVANIZED STEEL FORMED FOR EXTRA STRENGTH WITH
MOUNTING HOLES FOR ENCLOSED DUCT MOUNTING.
GRILLES. REGISTERS AND DIFFUSERS
A FURNISH AND INSTALL TITUS, KRUEGER, PRICE, ANDAOSTAT OR
EQUAL AS SCHEDULED. OPPOSED BLADE VOLUME DAMPERS FOR
REGISTERS SHALL BE TINS SERIES AG -35, KRUEGER SERIES
OBC, OR EQUAL. FOR OPPOSED BLADE TYPES WITH VERITCAL
BLADES AND SCREWDRIVER SLOTS OR ALLEN WRENCH
ADJUSTMENT ACCESSIBLE THROUGH THE REGISTER. IT SHALL BE
THIS CONTRACTOR'S RESPONSIBILITY TO PROVIDE MISCELLANEOUS
ITEMS AS NECESSARY FOR A COMPLETE AND PROPER
INSTALUTON IN THE TYPES OF WALLS, AND CEILINGS USED ON
THIS PROJECT. THIS SHAT INCLUDE SUCH ITEMS AS FASTENERS,
PLASTER RINGS, AND SUPPORTS, EIC.
B. DUCT PLASTER RINGS AT ALL WALL PENETRATIONS SHALL BE
PRICE INDUSTRIES 0DIFF, OR OR PR IN AN APPROPRIATE SIZE
TO MATCH DUCT. FINISH TO MATCH WALL OR DUCT.
CONNECTIONS
A ALL SQUARE ELBOWS SHALL HAVE TINS, KRUEGER OR
STREAMLINED TURNING VANES.
B. ALL BRANCH TAKEOFF DUCTS SHALL BE OF THE PROPORTIONAL
TYPE UNLESS SPECIFICALLY SHOWN OTHERWISE. VOLUME DAMPERS
ME REQUIRE! ON ALL TAKE—OFFS.
C. ALL OPENINGS IN DUCT FOR GRILLES, REGISTERS, ETC, SHALL BE
CAPPED DUST TIGHT WITH G.I. MEAL CAPS DURING THE
CONSTRUCTION PERIOD.
D. ROUND BRANCH DUCT CONNECITONS TO RECTANGULAR MANS
SHALL BE MADE WITH SPIN—IN—CONICAL TAKEOFF WITH INTEGRAL
VOLUME DAMPER AND QUADRANT OPERATOR AND EXTRACTOR AIR
SCOOP.
E. WHERE DUCTS RUN THROUGH BAR JOISTS OR OTHER CEILING
SPACES AND STRUCTURAL, MECHANICAL OR ELECTRICAL
INTERFERENCE IS ENCOUNTERED, SHEET MEAL WORKER SHALL
MODIFY DUCTWORK TO MAINTAIN SAME CROSS—SECTOWL AREA AS
INDICATED ON THE PIANS WITH A MAXIMUM OF 5 TO 1 ASPECT
RATIO.
FIEXIBLE CONNECTIONS
A PROVIDE VENTFMRICS, INC., DURO DYNE. OR EQUAL PROVIDE
FLEXIBLE DUCT CONNECTIONS WHEREVER DUCTWORK CONNECTS
TO VIBRATION ISOLATED EQUIPMENT AND WHERE SHOWN OR
NOTED. MAKE AIRTIGHT JOINTS. PROVIDE ADEQUATE JOINTS.
ACCESS PANELS
A PROVIDE ACCESS PANELS AT ALL REHEAT COILS, FIRE DAMPERS,
MOTORIZED VOLUME DAMPERS, CONTROL EQUIPMENT, ELBOWS ON
DUCT MANS WITH TURNING VANES OR ORDER EQUIPMENT
REQUIRING MAINTENANCE TO PERMIT EASY ACCESS FOR
INSPECTIONS AND MANTDMCE PANELS SHALL BE LOCATED ON
BOTTOM OR SIDES OF DUCT SUCH THAT MAINTENANCE CAN BE
PERFORMED. PANELS SHALL BE SE IN RIGID FRAME WITH
CLOSED—CELL SOFT GASKET, DOUBLE WALL INSULATED AND
COMPLETE WITH TWO UTCHES FOR DOORS UP TO 18"X18" AND
FOUR LATCHES FOR LARGER DOORS.
INSTALLATION
A PROVIDE DUCTWORK IN CONFORMANCE TO LATEST ADDITION OF
SIAM STANDARDS.
B. ALL DUCTWORK SHALL BE RUN SUBSIANTALLY AS SHOWN
ON THE DRAWINGS WITH BENDS AND CURVES IN COMPLIANCE
WITH LATEST EDITION OF SMACNA STANDARDS. IN NO CASE SHALL
THE INSIDE RADIUS BE LESS THAN THE WIDTH OF THE DUO
EXCEPT WHERE DUCT TURNING VANES ME USED. CHANGES IN
SIZE OR CROSS SECTION SALOL BE MADE WITH LONG TAPERS.
THE ENGINEER RESERVES THE RIGHT TO SLIGHTLY CHANGE THE
RUN OF CERTAIN DUCTS WITHOUT EXTRA COST TO THE OWNER IF
NECESSARY TO AVOID UNFORESEEN STRUCTURAL OR OTHER
INTERFERENCES.
C. BEFORE FMRICATNG ANY DUCTWORK, TAKE ACCURATE
MEASUREMENTS ON THE JOBSTIE TO INSURE PROPER
CLEARANCES.
D. PROVIDE SPIN—IN FITTINGS WITH DAMPERS AT DUCT
TAKE—OFFS TO DIFFUSERS.
E. FLEXIBLE DUCT ON BRANCH ENDS SHALL BE A MAXIMUM OF
5'-0" IN LENGTH, WITH A VOLUME DAMPER MOUNTED AT THE
NECK OF THE DIFFUSER. THE VOLUME DAMPER LEVER SHALL
HAVE A RED TAG INSTALLED, CLEARLY VISIBLE FROM SIDES OF
DIFFUSERS ABOVE CEIUNG. THE FLEXIBLE DUCT SHALL BE
CONNECTED AT BOTH ENDS WITH STAINLESS SCREW TYPE HOSE
CLAMPS.
CONDENSATE PIPING
A CONDENSATE PIPING FROM COOLING GOIL AND MOISTURE FROM
FLUE GASES SHALL BE FURNISHED AND INSTALLED BY THE
MECHANICAL CONTRACTOR. PROVIDE WATER TRAP AT EACH GOIL
AND FLUE DRAIN. RUN BOTH SYSTEMS SEPARATELY TO NEAREST
FLOOR DRAIN OR RECEPTOR APPROVED BY AUTHORITY HAVING
JURISDICTION.
INSULATION
A INSULATION SHALL BE REQUIRED ON ALL SURFACES TO RETARD
UNDESIRABLE HEAT TRANSFER AND PREVENT CONDENSATION.
INSULATION SHALL BE APPLIED TO PIPE LINES, DUCTWORK AND
EQUIPMENT ONLY AFTER THEY HAVE BEEN TESTED, INSPECTED
AND ALL SURFACES THOROUGHLY CLEANED OF ALL MOISTURE,
FOREIGN MATERIAL, GREASE AND RUST. INSULATION SHALL BE
CONTINUOUS THROUGH WALLS, PARTITIONS, SLEEVES, EC., EXCEPT
WHERE OTHERWISE INDICATED OR SPECIFIED. ALL INSULATION
ADHESIVES, SEALERS AND COATINGS SHALL HAVE A FIRE HAZARD
RATING NOT TO EXCEED 25/50/50 FLAME SPREAD, FUEL
CONTRIBUTED AND SMOKE DEVELOPED IN ACCORDANCE WITH UL
723 AND ASIM—E84. PROVIDE INSULATION FOR HOT AND COLD
WATER PIPING, HORIZONTAL WASTE PIPING IN CEIUNG SPACE,
SUPPLY ALR, RETURN AR, EXHAUST AR AND OUTSIDE AR SHOE
MEAL DUCTWORK.
B. WHERE NOTED ON THE DRAWINGS, ALL NEW SUPPLY AND RETURN
DUCTWORK SHALL BE INSULATED WITH EXTERNA DUCT WWW.
DUCT WRAP SHALL BE FOIL REINFORCED KRAFT FACING. All
INSULATION SHALL MEET NAPA 90A FLUME SPREAD UNDER 25
AND SMOKE DEVELOPED UNER 50. THICKNESS, DENSITY AND "R"
VALUE SHALL BE PER LOCAL ENERGY CODE INSULATION SHALL
BE FASTENED TO DUCTWORK PER MANUFACTURER'S INSTALLATION
INSTRUCTIONS AND Sell STANDARDS. ROUND BRANCH
DUCTWORK SHALL BE INSULATED WITH MINIMUM 1" THICK
FIBERGLASS SLEEVE WITH FOIL JACKET AND ALL JOINTS AND
TERMINATIONS SEALED WITH FOIL DUCT TAPE EXPOSED DUCTWORK
IN THE CONDITIONED SPACE DOES NOT NEED TO BE INSULATED.
C. INSULATED FLEXIBLE DUCT SHALL BE GENERAL ENVIRONMENTAL
CORPORATION ME G30A. OR EQUAL FLEXIBLE DUCT RUNS
SHALL BE UMITED TO A MAXIMUM LENGTH OF 5'-0'.
D. RETURN DUCT IN ATTIC SPACES SHALL BE INSULATED PER THE
REQUIREMENTS OF SUPPLY DUCTWORK NOTED ABOVE.
E. ROUND BRANCH DUCTWORK SHALL BE INSULATED WITH MINIMUM
1- THICK FIBERGLASS SLEEVE WITH FOIL JACKET AND ALL JOINTS
AND TERMINATIONS SEALED WITH FOIL DUCT TME. EXPOSED
DUCTWORK IN THE CONDITIONED SPACE DOES NOT NEED TO BE
INSULATED.
F. EXCEPTION: IN ACCORDANCE WITH THE ENERGY CODE INSULATION
IS NOT REQUIRED WHERE THE DESIGN TEMPERATURE DIFFERENCE
BETWEEN THE INTERIOR AND THE EXTERIOR OF THE DUCT OR
PLENUM IS NOT GREATER THAN 15' F.
G. IF A SPLIT SYSTEM IS USED SUCTION UNFS SHALL BE
INSULATED WITH 1" THICK FOAM TYPE PIPE INSULATION, M
ARMAFLE(, OR APPROVED EQUAL. WHEREVER POSSIBLE,
INSULATION SHALL BE SUPPED OVER LENGTHS OF PIPING BEFORE
FINAL FABRICATION WITHOUT SUITING THE INSULATION.
FIRE/SMOKE DAMPERS
A GALVANIZED STEEL CURTAIN TYPE WITH INTERLOCKING BLADES,
STAINLESS STEEL CLOSURE SPRINGS AND LATCHES FOR
HORIZONTAL INSTALLATION, BLADES OUT OF AR STREAM, FUSIBLE
LINKS, UL LISTED 33.
B. ACCEPTABLE MANUFACTURERS: GREENHECK, LOWERS & DAMPERS,
RUSKIN OR EQUAL
EOUIPMENT — SCOPE
A UNLESS OTHERWISE NOTED, FURNISH ALL LABOR, MATERIALS AND
EQUIPMENT FOR THE INSTALLATION OF A COMPLETE AND TENANT
ACCEPTABLE OPERATING HEATING AND AIR CONDITIONING SYSTEM
HEREIN DESCRIBED, AND AS SHOWN ON PUNS. THE SPACE IN
GENERA SHALL BE HEATED AND COOLED BY MEANS OF AN
EXISTING PACKAGED ROOFTOP AR CONDITIONING UNIT.
SPACE TEMPERATURE CONTROL REQUIREMENTS
A PROVIDE UNLESS NOTED OTHERWISE, ALL ELECTRIC WIRING,
THERMOSTATS, SENSORS, CONTROLLERS, RELAYS, CONTACTORS,
DAMPERS, ACRM70RS AND ALL OTHER MATERIALS NECESSARY FOR
A COMPLETE AND PROPERLY INSTALLED OPERATING TEMPERATURE
CONTROL SYSTEM THAT IS COMPATIBLE WIRD THE INSTALLED
EQUIPMENT AND ALL LANDLORD REQUIREMENTS, INCLUDING
EMERGENCY SHUTDOWN OF HVAC EQUIPMENT, UNLESS OTHERWISE
NOTED.
B. PROVIDE NEW ELECTRONIC 7—DAY PROGRAMMABLE THERMOSTAT
OF COMPATIBLE MANUFACTURER AS THE HVAC UNIT AT LOCATIONS
SHOWN ON PUMA. VERIFY THAT ALL TEMPERATURE CONTROL
SEQUENCES ME OPERATING PROPERLY AND TO THE INSTALLATION
REQUIREMENTS OF THE HVAC UNIT MANUFACTURER. UNLESS
NOTED OTHERWISE, OR AS DIRECTED BY TENANT, PROGRAM TO
THE FOLLOWING SETPOINTS:
OCCUPIED HEAT — 70F
OCCUPIED COOL — 751
HEATING NIGHT SETBACK — 60F
COOLING NIGHT SET BACK — 85'F
SEQUENCE OF OPERATION
A OCCUPIED HOURS: SUPPLY FAN SHALL OPERATE CONTINUOUSLY,
AND THE OUTSIDE MR DAMPER SHALL OPEN TO THE MINIMUM
POSITION. COOLING OR HEATING SHALL CYCLE TO MAINTAIN SPACE
TEMPERATURE SE POINT.
B. UNOCCUPIED HOURS: OUTSIDE AR DAMPER SHALL BE CLOSED.
SUPPLY FAN AND CONDENSING UNIT/SECRON OR GAS HEATING
SHALL CYCLE TO MAINTAIN SPACE TEMPERATURE SEFPOINT.
C. ECONOMIZER MODE: DRY—BULB CONTROLLED ECONOMIZER SHAT
ACTIVATE WHENEVER THE OUTSIDE AR DRY—BULB IS LOWER THAN
THE DRY—BULB CONTROL SETING. ECONOMIZER DAMPERS SHALL
MODULATE TO FULL OPEN POSITION, AS REQUIRED, TO MAINTAIN
DISCHARGE AR TEMPERATURE BETWEEN 52 AND 58 DEGREES
FAHRENHEIT. MECHANICAL COOUNG/HEATING SHALL BE LOCKED
OUT OF ECONOMIZER MODE. WHEN THE SPACE TEMPERATURE
SETPOINT IS SATISFIED. THE DAMPER SHALL RETURN TO THE
MINIMUM OLUSIDE AR POSITION DURING OCCUPIED All AND
CLOSE COMPLETELY DURING UNOCCUPIED MODE.
D. SMOKE ALARM MODE UPON A SIGNAL FROM THE DUCT SMOKE
DEFECTOR AND THE HVAC UNIT SHALL SHUT DOWN, AND THE
OUTSIDE AR DAMPER SHALL CLOSE.
BAIANCING AIR AND WATER SYSTEMS
A. WHEN THE WORK HAS BEEN COMPLETED, WITTY THE GENERAL
CONTRACTOR, WHO SHALL HIRE A BALANCING CONTRACTOR. THE
SYSTEM BALANCING SHALL BE BY AN INDEPENDENT TRADE
LICENSED BY THE ASSOCIATED AIR BALANCING COUNCIL (AABC) OR
THE NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEED) TO
TEST. ADJUST AND BALANCE ALL SPACE CONDITIONING AND
VENTILATION SYSTEMS. Al BALANCING WORK SHALL BE
COMPLETED AND DONE IN ACCORDANCE WITH THE MOST RECENT
STANDARDS OF THEIR SOCIETY. ALL COSTS FOR TESTING AND
BOUNCING SHALL BE INCLUDED IN THE BID. THE MECHANICAL
CONTRACTOR SHALL PROVIDE FINAL OR AND WATER BALANCE
INSPECTION AND REPORT TO THE LANDLORD, TENANT, ENGINEER,
AND THE GENERAL CONTRACTOR.
START UP OF SYSTEMS. GUARANTEE AND INSrRUcnONS
A GUARANTEE AND MAINTAIN THE STABILITY OF ALL WORK AND
MATERIALS FOR A PERIOD OF ONE (1) YEAR AFTER THE FINAL
PAYMENT FOR COMPLETION OF THE WORK AS VERIFIED BY FINAL
INSPECTION OF TENANT'S ARCHITECT. DEFECTS OF ANY KIND DUE
TO FAULTY WORK OR MATERIALS APPEARING DURING THE
ABOVE—MENTIONED PERIOD MUST BE IMMEDIATELY CORRECTED BY
THIS MECHANICAL CONTRACTOR AT HIS OWN EXPENSE TO THE
ENTIRE SATISFACTION OF TENANTS ARCHITECT AND ENGINEERS.
SUCH REPAIRS AND RECONSTRUCTION SHALL INCLUDE AL1 DAMAGE
TO THE FINISH OR FURNISHINGS OF THE BUILDING RESULTING
FROM THE ORIGINAL DEFECT OR REPAIRS THERETO. OWNERS
DESIGNATED OPERATING PERSONNEL SHALL BE FULLY INSTRUCTED
BY THE MECHANICAL CONTRACTOR IN THE OPERATION OF EACH
MECHANICAL SYSTEM AT THE TIME R IS PUT INTO SERVICE.
ASSEMBLE AND DELIVER TO TENANT BEFORE FINAL PAYMENT IS
MADE FOUR (4) 3—RING BINDER COMBINED SETS OF SHOP
DRAWINGS. MANUFACTURER'S BULLETINS OR OTHER DATA AS
REQUIRED COVERING THE CARE, MANIENANCE, AND OPERATION OF
EACH PIECE OF EQUIPMENT FURNISHED AND/OR REFURBISHED,
AND DELIVER TWO (2) BINDERS TO THE GENERAL CONTRACTOR
AND TWO (2) BINDERS TO THE OWNER.
PLUMBING
A SUPPORT HORIZONTAL PIPING ADEQUATELY FROM SLABS OR
OTHER STRUCTURAL MEMBERS AT INTERVALS SPECIFIED BELOW.
USE GRINNELL /260 HANGERS, OR EOUA. HAVING ADJUSTABLE
WROUGHT CLEVS, SOUD RODS AND SOCKETS. PIPING INSTALLED
ALONG WALLS SHALL BE SUPPORTED BY GRINNELL /199, OR
APPROVED EQUAL STEL ANGLE BRACKETS. THE SPACING OF PIPE
SUPPORTS FOR STEEL PIPE 0" TO 2" SHALL BE 10'-0" FOR
COPPER PIPE SIZE UP TO 2" SHALL BE 6'-0". HANGERS IN
CONTACT WITH COPPER SHALL BE COPPER PLATED AND SHALL BE
GRINNELL FIG. CT -65 OR APPROVED EOUAL HANGERS RODS
SHALL BE 1" DIAMETER FOR PIPES UP TO 2" IN SIZE. PROVIDE
16 GAUGE, GALVANIZED STEEL PIPE SUPPORT SHIELDS, AT ALL
PIPE HANGERS.
B. CUT ALL OPENINGS IN FLOORS AND WALLS REQUIRED FOR
PENETRATION OF PIPING. COORDINATE OPENINGS WITH GENERAL
CONTRACTOR, WHO SHALL PERFORM ALL PATCHING AS REQUIRED
BY ARCHIE DURAL SPECIFICATIONS. ALL HORIZONTAL PIPING
WHICH PENETRATES WALLS SHALL BE ITTTED WITH PIPE SLEEVES
MADE UP OF STANDARD STEEL PIPE 1" GREATER IN DIAMETER
MAN OUTSIDE DIAMETER OF PIPE AND PIPE INSULATION.
C. THE VOID BETWEEN PIPE AND SLEEVE SHALL BE SEALED WITH
ROPE AND FILLED WITH EXPANDABLE (NON—SHRINKING) CEMENT.
SLEEVES SHALL BE OF SUCH LENGTH THAT THEY END FLUSH
WITH WALL FINISH ON BOTH SIDES OF WALL WHERE UNCOVERED
EXPOSED PIPES PASS THROUGH WALLS THE SHALL BE FITTED
WITH CRANE /10. OR EQUAL WALL PLATES.
D. ALL PENETRATIONS THROUGH FIRE RATED MATERIALS SHALL BE
SEALED AS NEEDED AND REQUIRED TO COMPLY WITH THE
APPROPRIATE U.L REQUIREMENTS.
E. ALL ABOVE GROUND WATER SUPPLY PIPE SHALL BE TYPE L HARD
TEMPER COPPER WATER TUBE COMPLYING WITH ASTM BOB AND
ANSV14SF STANDARD 61. ALL FITTINGS SHALL BE WROUGHT
COPPER COMPLYING WITH USASI 876..16 k B16.18a. DIELECTRIC
COUPLINGS SHALL BE USED BETWEEN STEEL AND COPPER
CONNECTIONS. ALL BELOW GROUND WATER SUPPLY PIPE SHALL
BE TYPE K SOFT TEMPER COPPER WATER TUBE. USE LEAD FREE
SOLDER ON ALL JOINTS IN POTABLE WATER PIPING.
F. IF PERMITTED BY LOCAL CODES AND THE LOCAL AUTHORITY
HAVING JURISDICTION, THE CONTRACTOR MAY PROVIDE ABS OR
BVC PIPING IN UEU OF CAST IRON FOR SANITARY WASTE AND
VENT PIPING OR IN UEU OF COPPER PIPING FOR DOMESTIC
WATER PIPING. CONTRACTOR SHALL VERIFY WITH OTHER TRADES
PRIOR TO SUBSTIMION THAT THERE IS NO PLENUM RETURN ON
THIS PROJECT.
G. All ABOVE GROUND SANITARY WASTE AND VENT PIPING SHALL BE
NO—HUB CAST IRON SANITARY SYSTEM COMPLYING WITH CISPI
#301-69T. ALL BELOW GROUND SANITARY AND WASTE PIPING
SR41L BE NO—HUB CAST IRON SANITARY SYSTEM COMPLYING WITH
CISPI If301-69T OR SERVICE WEIGHT CAST IRON HUB AND
SPIGOT WITH NEOPRENE GASKET COMPLYING WITH CISPI
MIFISN-68I OR SCHEDULE 40 PVC BELOW GRADE OR AS
REQUIRED FOR LANDLORD APPROVAL AND LOCAL CODE
H. FURNISH AND INSTALL VALVES WHERE INDICATED ON PUN AND
NECESSARY FOR PROPER SYSTEM OPERATION AND COMPONENT
ISOLATION. PROVIDE VALVES RATED FOR 125 PSI OR GREATER
WORKING PRESSURE IN WATER PIPING.
CHECK VALVE UP TO 3". CRANE NO. 37, OR EQUAL
GLOBE VALVE UP 70 3": CRANE NO. 1240, 1241, OR EQUAL
GATE VALVE UP TO 3": CRANE 428, 1334, OR EQUAL
BALL VALVE UP TO 3": APOLLO SERIES 70-100, OR EQUAL
PRESS. REUEF VALVE: WATTS 10L MOD. M4, OR EQUAL Y.nM X
Y."F
SHOCKSTOP: WADE 110 (HOT), WADE }5 (COLD)
BACKFLOW PREVENTER: WATTS NO. 009, OR EQUAL
VACUUM REE VALVE: WATTS NO. 36A — x", OR EQUAL
I. INSULATION SHALL BE REQUIRED ON ALL SURFACES TO REMD
UNDESIRABLE HEAT TRANSFER AND PREVENT CONDENSATION.
INSULATION SHALL BE APPLIED 70 PIPE LINES, AND EQUIPMENT
ONLY AFTER THAT HAVE BEEN TESTED, INSPECTED AND ALL
SURFACES THOROUGHLY CLEANED OF ALL MOISTURE. FOREIGN
MATERIAL GREASE AND RUST. INSULATION SHALL BE CONTINUOUS
THROUGH WALLS, FLOORS, PARTITIONS, SLEEVES, ETC., EXCEPT
WHERE OTHERWISE INDICATED OR SPECIFIED. ALL INSULATION
25/50/50 FLAME SPREAD, FUEL CONTRIBUTED AND SMOKE
DEVELOPED IN ACCORDANCE WITH UL 723 AND ASTM—E84.
PROVIDE INSULATION FOR HOT AND COLD WATER PIPING,
HORIZONTAL WASTE PIPING IN CEIUNG SPACE. PROVIDE PIPE
INSULATION BY MANVILLE, OWENS CORNING, OR EQUAL
J. PIPE INSULATION SHALL BE K INCH THICK FIBERGLASS WITH ALL
SERVICE JACKET, OR M REQUIRED IN ACCORDANCE WITH LOCM
ENERGY CODES.
K. ORDER ALL EQUIPMENT REQUIRED WITHIN TEN DAYS UPON
RECEIPT OF CONTRACT IN ORDER TO ENSURE TIMELY RECEIPT OF
MATERIAL SUBSTITUTIONS AFTER THIS DATE DUE TO LACK OF
PLACEMENT OF ORDER, WILL NOT BE APPROVED.
L CLEAN, DISINFECT AND TEST ALL PLUMBING AND PIPING SYSTEMS
AS REQUIRED BY LOCAL CODES AND LANDLORD'S CRnERM.
M. PROVIDE PLUMBING FIXTURES AS SCHEDULED ON PUNS.
SPRINKLER SPECIFICATION
A SUBMIT SHOP DRAWING(S) TO ARCHITECT WITH EXACT LOCATION
AND TYPE OF SPRINKLER HEADS. ARCHITECT TO REVIEW, DO NOT
PURCHASE OR INSTALL HEADS UNTIL ARCHITECT HAS APPROVED
LOCATIONS SHOWN ON SHOP DRAWING.
B. THIS WORK SHALL BE INSTALLED IN CONFORMITY WITH APPLICABLE
LOCAL ORDINANCES AND STATE STATUTES. ALL REQUIREMENTS OF
THE CURRENT PLUMBING CODES, HEATING AND VENTILATING
CODES, ENERGY OR CONSERVATION CODES, INSURANCE
UNDERWRITER REQUIREMENTS AND NFPA BULLETINS MUST BE ME.
C. STANDARDS AND SIZES WHICH MEET OR EXCEED THE ABOVE
MENTIONED REQUIREMENTS SHALL BE INSIALLED AS DRAWN OR
SPECIFIED. NOTHING IN THE SPECIFICATIONS OR DRAWINGS SHALL
BE CONSTRUED TO PERMIT DEVIATION FROM THE REQUIREMENTS
OF GOVERNING CODES.
D. ALL LICENSES REWIRED IN CONNECTION WITH THIS WORK SHALL
BE SECURED AND MAINTAINED BY THE PROPER RESPECTIVE
CONTRACTOR WITH THE PROPER LOCAL OR STATE AUTHORITY
HAVING JURISDICTION.
E UPON COMPLETION OF THE SPRINKLER SYSTEM, THE FIRE
PROTECTION CONTRACTOR SHALL HYDROSTATICALLY TEST ALL
PIPING AT 200 PSI FOR TWO HOURS. MATERIAL AND TEST
CERTIFICATES MUST BE PROPERLY FILLED OUT AND FURNISHED TO
THE LANDLORD'S PROJECT MANAGER AT THE JOB SITE.
F. PIPING IN FINISHED ROOMS SHALL BE CONCEALED IN PARITTONS.
FURRED SPACES, OR SUSPENDED CEILINGS. IN UNFINISHED
ROOMS, PIPING SHAT BE ARRANGED TO PROVIDE FOR A MAXIMUM
OF HEAD ROOM.
G. IT IS INTENDED THAT ALL APPARATUS BE LOCATED SYMMETRICAL
WITH ARCHITECTURAL ELEMENTS AND SHALL BE INSIAILED AT THE
HEIGHT AND LOCATIONS AS SHOWN ON THE ARCHITECTURAL
DRAWINGS WHEREVER POSSIBLE.
H. THE HANGERS SHALL BE SO LOCATED AS TO PROPERLY SUPPORT
THE PIPES, RELIEVE STAN ON PIPES AND FITTINGS, AND AT THE
SAME TIME ALLOW FOR AMPLE EXPANSION AND CONTRACTION.
PIPING SHALL NOT BE HUNG FROM MEAL DECKING. BRIDGING, OR
MECHANICAL EQUIPMENT SUCH AS PIPE OR DUCT. SPAN
STRUCTURAL MEMBERS AS NECESSARY WITH UNISTRUT.
I. ALL SPRINKLER PIPING IN THE BUILDING ABOVE GROUND SHALL
BE SCHEDULE 40 BUCK STEEL WITH THREADED CONNECTIONS
AND FITTINGS. Al PIPING SHALL BE INSTALLED IN CONFORMANCE
WITH NEPA 313 REGULATIONS.
J. THE FIRE SPRINKLER SYSTEM WILL BE COMPLETED BY THE
WJDLORD's CONTRACTOR. SPRINKLER HEADS: EXPOSED PENDANT
OR UPRIGHT — RELIABLE MODEL "G", 165 DEGREE, 8" ORIFICE,
BRASS FINISH. FINISH CBUNG — RELIABLE "GAL" CONCEALED, 165
DEGREE, F ORIFICE, WHITE FINISH.
K. PROVIDE BRASS PENDANT HEADS IN NON—VISIBLE MEAS WITH NO
CEILINGS.
L PROVIDE AUXILIARY DRAIN VALVE WHERE NECESSARY FOR PROPER
DRAINING OF THE SYSTEM AND INSTALL PROPER IDENTIFICATION
FOR EXPOSED OR CONCEALED VALVE.
M. Al SPRINKLER HEAD SPACING BASED ON 130 SQUARE FEE PER
HEAD IN SALES AREA AND 100 SQUARE FEE PER HEAD IN
STOCK MEA VERIFY LANDLORD'S REQUIREMENTS.
N. COORDINATE WORK SUCH THAT SYSTEM IS OPERATIONAL WHEN
FIRE PROTECTION CONTRACTOR IS NOT ON PREMISES.
0. COORDINATE FIRE PROTECTION SYSTEM CONSTRUCTION AND
OPERATION WITH LANDLORD'S INSURANCE PROVIDER.
Alan J.Plutowski
ARCHITECT
4125 Lakeland Ave. N., Suite 200
Minneapolis, Minnesota 55422
763-533-7171 fax: 763-533-7979
Consultants
oDD
RED WING SHOES
314 MW ST6E1 IBD MW', M UM 6
F boo) M -&b FY (Ni H
Certification
Project Information
RED WING SHOES
BUILD -OUT FOR
NEW DEALER
STORE
Red Ting Shoe Store
9699 N. Michigan Rd, ate 1207
Carmel, Indiana 46092
Revisions
Date: 04/06/18
Di By: MMS
Checked By: MEA
Job Number: 18RW-007
Sheet Information
MECHANICAL
SPECIFICATIONS
COPYRIGHT 2018
ALAN J.
PLUTOWSKI
M390