HomeMy WebLinkAbout30N I a I 0 C 5 I PLUMBING GENERAL NOTES 1. ALL WASTE AND VENT PIPING SHALL BE SCHEDULE 40 PVC PER CHAPTERS 7, 8 & 9 OF THE U.P.C. WITH INDIANA AMENDMENTS TO INCLUDE CHAPTER 14. 2. ALL FITTINGS USED FOR THE DRAIN, WASTE AND VENT SYSTEMS MUST BE IN ACCORDANCE WITH CHAPTERS 7, 8 & 9 OF THE U.P.C. WITH INDIANA AMENDMENTS TO INCLUDE CHAPTER 14. 3. VENTS BELOW THE FLOOR & BELOW THE FLOOD LEVEL OF THE FIXTURE ARE NOT PERMITTED (EXCEPT AS SHOWN). THE MAXIMUM DISTANCE FROM FLOOR DRAIN TO VENT IS 5'-0" (EXCEPT WHERE SIZED AS A RUNNING VENT), AND MAXiMUM DISTANCE FROM WATER CLOSET TO VENT IS 6'-0". 4. VENTS SHALL TERMINATE A MINIMUM DISTANCE ABOVE THE ROOF AS PER SECTION 906.1 AND SHALL BE 10'-0" MINIMUM FROM ALL AIR INTAKES. 5. WHERE POSSIBLE, TIE VENTS TOGETHER TO AVOID EXCESSIVE ROOF PENETRATIONS 6. ALL HORIZONTAL WASTE AND DRAIN PIPING OF 3" IN DIAMETER OR LESS MUST BE INSTALLED WITH A GRADE OF AT LEAST 1/4" PER FOOT. PIPING 4" IN DIAMETER OR LARGER MUST BE INSTALLED WITH A GRADE OF AT LEAST 1/8" PER FOOT. 7. ALL UNDERGROUND WATER SUPPLY PIPING TO BE TYPE "K" BELOW CONCRETE SLAB. ALL HOT AND COLD WATER PIPING SHALL BE TYPE "L" HARD COPPER WITH COPPER OR WROUGHT BRASS FITTINGS OR CPVC PER CHAPTER 6 OF THE U.P.C. WITH INDIANA AMENDMENTS TO INCLUDE CHAPTER 14. 8. FLUX AND SOLDER FOR THE USE OF JOINING POTABLE WATER PIPING MUST BE LEAD FREE AS PER SECTION 316.1.3. 9. ALL HOT WATER PIPING SHALL BE COVERED WITH 1/2" ARMAFLEX PIPE INSULATION. 10. (NOT USED) 5 10 2 MECHANICAL GENERAL NOTES 1. MECHANICAL CONTRACTOR TO FURNISH ALL LABOR, MATERIAL & EQUIPMENT REQUIRED FOR THE COMPLETION & OPERATION ON ALL SYSTEMS IN THIS SECTION OF WORK. ALL MECHANICAL WORK SHALL BE IN STRICT ACCORDANCE WITH UNIFORM MECHANICAL CODE (U.M.C.), LATEST EDITION INCLUDING ADOPTED INDIANA AMENDMENTS. ALL INSTALLATIONS SHALL BE PERFORMED IN A GOOD WORKMANLIKE MANNER. 2. INSTALL ALL GAS FIRED H.V.A.C. UNITS IN STRICT ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND NFPA 54. 3. GAS PIPING SHALL BE OF BLACK STEEL PIPE, ASTM 53, A105 OR A120, AND SCHEDULE 40. GAS PIPING IN CONTACT WITH THE GROUND SHALL BE COATED WITH FACTORY INSTALLED POLYETHYLENE TAPE, 20 MILS. GAS COCKS, 2" AND SMALLER, SHALL BE 150 PSI W.O.G., BRONZE BODY. USE THREADED JOINTS AND FITTINGS FOR 2" AND SMALLER PIPE, UNIONS TO BE GROUND JOINT FITTINGS, WELDED JOINTS FOR LARGER PIPE. INSTALL GAS PIPING IN STRICT ACCORDANCE WITH NFPA-54, NATIONAL FUEL GAS CODE. DO NOT INSTALL GAS PIPING IN CONCEALED SPACES, WITHOUT APPROVAL OF GOVERNING AUTHORITY. INSTALL SHUTOFF COCKS, SEDIMENT TRAPS, AND UNIONS AT ALL EQUIPMENT ITEMS. BOND SYSTEM TO A GROUNDING ELECTRODE IN ACCORDANCE WITH NFPA-70. PIPING SIZED AS SHOWN, HANGERS SHALL BE MINIMUM OF 1/4" THREADED ROD WITH SADDLES @ 6'-0" APART. GAS METER LOCATION IS ASSUMED AND SHALL BE COORDINATED WITH LOCAL UTILITY. 4. ALL PIPING, DUCTS, VENTS, ETC., EXTENDING THROUGH WALLS & ROOF SHALL BE FLASHED AND COUNTER FLASHED IN A WATERPROOF MANNER. 5. ALL DUCTWORK INSULATION SHALL BE RUN CONTINUOUSLY THROUGH FLOORS, PARTITIONS, ROOF STRUCTURE AND DECKS. 6. ALL PIPING AND DUCTWORK LOCATIONS SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE. COORDINATE WITH ALL OTHER TRADES PRIOR TO PURCHASING OR INSTALLING EQUIPMENT AND MATERIALS. 7. METAL DUCTWORK SHALL COMPLY WITH SMACMA, "HVAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE." COMPLY WITH ASHRAE HANDBOOK FOR INSTALLATION OF METAL DUCTWORK. ALSO COMPLY WITH NFPA 90A. ALL TRUNK METAL DUCTWORK SHALL BE WRAPPED WITH 1 1/2" FOIL BACK INSULATION. ALL COVERING AND LINERS INCLUDING ADHESIVES, SHALL HAVE A FLAME SPREAD RATING NOT MORE THAN TWENTY-FIVE (25) AND SMOKE -DEVELOPED RATING NOT MORE THAN FIFTY (50) WHEN TESTED IN ACCORDANCE WITH ASTM -E-84. ALL SQUARE ELBOWS SHALL HAVE AIRFOIL TYPE TURNING VANES. PROVIDE VOLUME CONTROL DAMPERS AT ALL BRANCH DUCTS TO DIFFUSERS AND A MAXIMUM OF 5 FEET ABOVE THE CEILING. ALL DUCTWORK SHALL BE GALV. SHEET METAL & SHALL BE CONSTRUCTED & INSTALLED IN ACCORDANCE WITH SMACMA STANDARDS. DUCT SIZES SHOWN ARE NET FREE AREA. 8. MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 10'-0". ALL FLEXIBLE DUCT SHALL CONFORM TO THE REQUIREMENTS OF UL 181 FOR CLASS 1 FLEXIBLE AIR DUCTS. SUPPORT TO ELIMINATE SAGGING & KINKING. 9. SUPPORT DUCTS RIGIDLY AT INTERVALS NOT EXCEEDING TEN (10) FEET WITH SUITABLE GALVANIZED TIES AND FASTENERS FOR THE SIZE OF DUCT, AND RUN IN NEAT, STRAIGHT LINES, TIGHT TO STRUCTURES OR WALLS. DO NOT OBSTRUCT USABLE SPACE. WHERE DUCTS PASS THROUGH WALLS, FLOORS, CEILINGS, ETC., PROVIDE FLANGES AND APPROPRIATE SEALING METHODS TO MAINTAIN INTEGRITY OF SURFACE PENETRATED AND PROVIDE A FINISHED APPEARANCE. PROVIDE PROTECTION BARRIERS TO EXPOSED DUCTS THAT MAY BE SUBJECTED TO MECHANICAL DAMAGE BY VEHICLES, OR FROM OTHER CAUSES. PROVIDE FIRE STOPPING AS REQUIRED FOR FIRE RATED PENETRATIONS. 10. ALL HVAC EQUIPMENT TO BE INSTALLED PER MFG. REQUIREMENTS AS SHOWN. UTILIZE FACTORY FILTERS DURING CONSTRUCTION & REPLACE W/ REPLACEABLE MEDIA IN METAL FILTER FRAME JUST PRIOR TO TEST & BALANCE & AT TIME BUILDING IS TURNED OVER TO THE OWNER. COORDINATE WITH THE OWNER. 11. PROVIDE FLEXIBLE CONNECTIONS AT ALL EQUIPMENT FOR SOUND AND VIBRATION ISOLATION. 12. PROVIDE FIRE DAMPERS, READILY ACCESSIBLE FOR SERVICING AT ALL PENETRATIONS OF FIRE RATED CONSTRUCTION AS RECOMMENDED FOR APPLICATIONS AND POSITION OF INSTALLATION. PROVIDE TURNING VANES AND CONTROL DAMPERS INDICATED OR AS REQUIRED TO ACHIEVE DESIRED FLOWS. INSTALL CONTROL DAMPERS AT ACCESSIBLE LOCATIONS. INSTALL ACCESS PANELS FOR SERVICING DAMPERS. INSTALL AS CLOSE TO MAIN DUCT RUNS AS POSSIBLE. 13. MAINTAIN MIN. 10' BETWEEN OUTDOOR AIR INTAKES AND EXHAUST FAN DISCHARGE, PLUMBING, VENT, ETC. 14. INSTALL ACCESSORY ITEMS, SUCH AS THROUGH THE WALL UNITS, AIR CLEANERS, HUMIDIFIERS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER'S PRINTED INSTRUCTIONS. 15. PROVIDE AND INSTALL ALL CONDENSATE DRAIN LINES FROM HUMIDIFIERS AND COOLING COILS AS REQUIRED. TERMINATE ALL DRAIN LINES OVER OPEN SIGHT DRAINS, FLOOR DRAINS OR ROOF DRAINS. 16. PROVIDE ONE PART ELASTOMERIC SEALANT FORMULATED FOR USE IN A THROUGH -PENETRATION FIRE STOP FOR SYSTEM FILLING OPENINGS AROUND DUCT PENETRATIONS THROUGH WALLS AND FLOORS, HAVING FIRE RESISTANCE RATING INDICATED AS ESTABLISHED BY TESTING IDENTICAL ASSEMBLIES PER ASTM 814 BY UNDERWRITERS LABORATORIES OR OTHER TESTING AND INSPECTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PRODUCTS THAT MAY BE INCORPORATED IN THE WORK INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING: 1)"DOW CORNING FIRE STOP SEALANT", DOW CORNING CORP.; 2)"3M FIRE BARRIER CAULK CP -2 ELECTRICAL PRODUCTS DIV./3M; 3)"RTV 7403", GENERAL ELECTRIC CO.; AND 4)"FYRE PUTTY", STANDARD OIL MATERIALS CO. 17. THERMOSTAT WIRING AND LOCATION: THERMOSTAT MUST BE MOUNTED ON A VERTICAL VIBRATION -FREE SURFACE FREE FROM AIR CURRENTS AND IN ACCORDANCE WITH THE FURNISHED INSTRUCTION. MOUNT THE THERMOSTAT APPROXIMATELY 5 FEET (1.5M) ABOVE THE FLOOR AREA WHERE IT WILL BE EXPOSED TO A FREE CIRCULATION OF AVERAGE TEMPERATURE AIR, ALWAYS REFER TO THE THERMOSTAT INSTRUCTIONS AS WELL AS UNIT WIRING DIAGRAM AND WIRE ACCORDINGLY. AVOID MOUNTING THE THERMOSTAT IN THE FOLLOWING LOCATIONS: COLD AREAS - OUTSIDE WALLS OR AREAS WHERE DRAFTS MAY AFFECT THE OPERATION OF THE CONTROL. HOT AREAS - AREAS WHERE THE SUN'S RAYS, RADIATION OR WARM AIR CURRENTS MAY AFFECT CONTROL OPERATION. DEAD AREAS - AREAS WHERE AIR CANNOT CIRCULATE FREELY, SUCH AS BEHIND DOORS OR IN CORNERS. 18. CONTRACTOR SHALL VISIT THE JOB SITE AND BE FAMILIAR WITH ALL PROJECT CONDITIONS PRIOR TO FABRICATING ANY EQUIPMENT, DUCTWORK, ETC. NO ALLOWANCES WILL BE MADE FOR CONTRACTOR UNFAMILIARITY WITH PROJECT CONDITIONS. 19. ROOF CURBS SHALL HAVE A BASE THAT FITS SLOPE OF ROOF AS REQUIRED. TOP OF CURB SHALL BE LEVEL. CURB BY EQUIPMENT MFG. 20. MECHANICAL CONTRACTOR SHALL BALANCE SYSTEM TO WITHIN 10% OF AIR QUANTITIES INDICATED ON PLANS AND PROVIDE OWNERS REPRESENTATIVE WITH A COMPLETE BALANCE REPORT. 21. ALL EQUIPMENT SHALL HAVE 2 -YEAR WARRANTY & COMPRESSORS SHALL HAVE ADDITIONAL MINIMUM 5 -YEAR EXTENDED WARRANTY. 22. ALL CONTROL WIRING & CONDUIT SHALL COMPLY WITH NEC. 23. PIPE & DUCT ROUTING SHOWN IS SCHEMATIC. HVAC CONTRACTOR SHALL PROVIDE ANY ADDITIONAL OFFSETS AND FITTING, INCLUDING DIVIDED DUCTS, REQUIRED [OR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES AS ENCOUNTERED IN THE FIELD. 24. LIGHT FIXTURE LOCATIONS TAKE PRECEDENCE OVER DIFFUSER AND GRILLE LOCATIONS. LOCATE DIFFUSERS AND GRILLES TO ACCOMMODATE LIGHTING LAYOUT. 25. DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS & REFLECTED CEILING PLANS FOR EXACT LOCATION OF DOORS, WINDOWS, CEILING DIFFUSERS, ETC. 26. MECHANICAL CONTRACTOR SHALL COORDINATE THE WORK WITH ALL TRADES INVOLVED IN THE CEILING WORK TO INSURE CLEARANCES FOR FIXTURES, DUCTS, PIPING CEILING SUSPENSION SYSTEMS, ETC., NECESSARY TO MAINTAIN THE FINISHED CEILING HEIGHTS INDICATED ON ARCHITECTURAL DRAWINGS. 11. BACK FLOW PREVENTERS MUST BE IN ACCORDANCE WITH STANDARDS REFERENCED IN SECTIONS 204, 603, & 1002. 12. PLUMBING CONTRACTOR SHALL PROVIDE SHUT-OFF VALVES AT EACH FIXTURE. 13. PLUMBING CONTRACTOR SHALL COORDINATE WITH CARPENTER FOR LOCATIONS OF PLUMBING EQUIPMENT AND PIPING. 14. PLUMBING CONTRACTOR SHALL PROVIDE THEIR OWN EXCAVATION, BACKFILL & COMPACTION TESTING (WITH REPORT). 15. ALL TRADE CONTRACTORS SHALL COORDINATE WITH EACH OTHER THE LOCATIONS OF ALL PLUMBING LINES, DUCTWORK, AND ELECTRICAL SERVICES TO AVOID CONFLICTS WITH EACH OTHER. 16. ALL INSTALLATIONS SHALL BE COMPLETE, TESTED AND TOTALLY FUNCTIONAL, EVEN THOUGH EACH AND EVERY ITEM MAY NOT BE SHOWN OR SPECIFICALLY CALLED OUT. 17. ALL PLUMBING NOT SPECIFICALLY REFERENCED ABOVE SHALL BE ACCORDING TO THE CURRENT EDITION OF THE INDIANA PLUMBING CODE (WITH ALL INDIANA, LOCAL CODE AND ORDINANCES AMENDMENTS. 18. CONTRACTORS SHALL NOT CUT OPENINGS IN STRUCTURAL MEMBERS. 19. PLUMBING CONTRACTOR SHALL INSTALL DIELECTRIC UNIONS AT ALL CONNECTIONS OF DISSIMILAR METALS. 20. PLUMBING CONTRACTOR SHALL ROUGH -IN ALL. WASTE AND SUPPLY LINES TO FIXTURES / EQUIPMENT ACCORDING TO MANUFACTURER'S SHOP DRAWINGS AND MAKE FINAL CONNECTIONS. ALL SUPPLIES SHALL BE VALVED. 21. INSTALL ALL WATER HEATING EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE FACTORY AUTHORIZED STARTUP OF ALL EQUIPMENT - NO EXCEPTIONS. PLUMBING NOTES 1. ALL BRANCH SIZES SHOWN ON THE PLAN ARE INDIVIDUAL BRANCH SIZES TO VALVES, FAUCETS, BUBBLERS, ETC. 2. SEE SCHEDULE FOR WATER CLOSET TYPE. 3. CABINET SINKS WILL BE FURNISHED COMPLETE WITH TRIM BY THE PLUMBING CONTRACTOR AT THE JOB SITE. THE PLUMBING CONTRACTOR SHALL SET THE SINKS AND TRIM AND SHALL PROVIDE ALL LABOR AND MATERIAL TO ROUGH -IN AND HOOKUP COMPLETE. 4. ALL FIXTURES SHALL HAVE A SHUT OFF VALVE ACCESSIBLE AT THE FIXTURES. 5. HANDICAPPED WATER CLOSETS SHALL HAVE THE FLUSH TRIP LEVER LOCATED ON THE WIDE SIDE OF THE ROOM. 6. OTHER THAN FOR SHOWER UNITS, "OR EQUAL" FIXTURE SPECIFICATIONS WHICH MEET THE INTENT OF THE DESIGN MAY BE PROPOSED FOR ACCEPTANCE BY THE GENERAL CONTRACTOR. 7. PROVIDE (4) COPIES OF PROPOSED PLUMBING FIXTURE CUT SHEET FOR PRIOR REVIEW BY THE OWNER, GENERAL CONTRACTOR AND ENGINEER. 8. ALL A.D.A. DESIGNATED AREAS SHALL BE PROVIDED WITH FIXTURES WHICH COMPLY WITH APPLICABLE STANDARDS OF THE A.D.A. AND THE I.H.A.C. 9. INSTALL SERVICE, SHUTOFF & CHECK VALVES, COCKS, AIR CUSHIONS, VACUUM BREAKERS, AND SAFETY DEVICES WHERE REQUIRED BY CODE, DRAWINGS, OR AS REQUIRED TO FUNCTION PROPERLY. 10. EXPOSED P -TRAPS SHALL BE CHROME PLATED CAST BRASS "P" TRAP WITH CLEAN OUT AND ESCUTCHEON PLATE. 11. STOPS TO BE CHROME PLATED ANGLE VALVE WITH CHROME PLATED 12" LONG FLEXIBLE RISERS AND CHROME PLATED ESCUTCHEON PLATE. 12. ALL EXPOSED DRAINS AND WATER SUPPLY PIPING TO LAVATORIES SHALL BE INSTALLED WITH "HANDI LAV -GUARD" INSULATION KIT BY "TRUEBRO". 2 A M C 11 ........... BYRUM ARCHITECTS 8910 PURDUE ROAD, SUITE 680 INDIANAPOLIS, INDIANA 46268 317.471.1200 FAX.317.471-1224 © Copyright 2010 LClio C,ISTER�� �Q� v No. Z 16188 STATE OF OX F //VD I ANP �T10NAL S' W U FD Certified By Drawn By Checked By JB SH Date 6-25-10 Revisions: Use of Documents The Drawings, Specifications, and other documents prepared by the Architect for this Project are instruments of the Architect's service for use solely with respect to this Project and shall not be used on other projects or additions to this Project without written permission and due compensation to the Architect. Scope Drawings These drawings indicate the general scope of the project in terms of architectural design concept, the dimensions of building, the major architectural elements and, in some cases, the structural, mechanical, and/or electrical systems. The Drawings do not necessarily indicateor describe all work required for full performance and completion of the require- ments of the Contract. On the basis of the general scope indicated or described, the trade contractors shall furnish all items required for the proper execution and completion of the work. V J LJ O z d" T8W T&W Corporation 3841 W. Moms St. Indianapolis, Indiana 46241 ca V LClio z W U W U FD E� DCU CU -_ 86 U- cc 0 Q U 0 N LL 2- o U U L 06 42 06 .o QN L o Z C�� Co U U� E 0 L1J 0 ,1 io LL vJ♦ ) � a.Cn Sheet No. MP2001 Project No. 10004