HomeMy WebLinkAbout105HANGER ROD
PIPE HANGER
PRE-FINIHSED
OR PAINTED
\\ AS SPECIFIED
INSULATION
12" LONG, 180' GALVANIZED
STEEL SADDLE BETWEI-N
HANGER AND INSULA11ON
PIPE REFER TO
PLANS FOR
SIZE
STEEL CRADLE, WELD TO STEEL SERVICE PIPE,
CRADLE THICKNESS TO MATCH INSULATION THICKNESS
ENSURE VAPOR BARRIER COVERS CRADLE
ING ONLY
INSULATED ST E
PIPE REFER TO
PLANS FOR
SIZE
WOOD PIPE CHAULE
NO SCALE
AIR
PORT INSULATED ST
UNION FLOW
(TYPICAL) 11r -PIT GAUGE CONNEC11ON
BALANCING VALVE
—CHS I
COOLING COIL
�—�-- C H R
FAN -
SHUT-OFF VALVE
2 -WAY TEMPERATURE
CONTROL VALVE
FAN COIL UNIT PIPING
DETAIL E
NO SCALE
P/T GAUGE CONNECTION
UNION
(TYPICAL) AIR
FLOW
SHUT-OFF VALVE
f --10 HS I
COIL
f-4 H R
---
BALANCING VALVE
2 -WAY TEMPERATURE
CONTROL VALVE FAN
CABINET UNIT HEATER PIPING
INSULATION
DETAIL F
NO SCALE
UNION, VALVE, ETC.
TAPER (45') AND SEAL INSULATION ENDS
CLOSE TO UNION, VALVE, ETC.
HEATING WATER PIPE
TYPICAL INSULATION TERMINATION
DETAIL K
NO SCALE
SHUT-OFF VALVE—
U
STRAINER WITH BLOWDOWN
(BALL VALVE), HOSE END
AND CAP
T
THERMOMETE
SHUT-OFF
VALVE
(TYPICAL)
BALL VALVE WITH HOSE -
END AND CAP (TYPICAL)
GALVANIZED HANGER ROD
GALVANIZED PIPE HANGER
(TRAPEZE SIMILAR)
INSULATION
LONG, 180' GALVANIZED
_L SADDLE BETWEEN
GER AND INSULATION
NO SCALE
BALANCING VALVE
FLOW MEASURING STATION.
PROVIDE 3 PIPE DIAMETERS
= DOWNSTREAM & 5 PIPE
DIAMETERS UPSTREAM OF
STRAIGHT PIPE.
TEMPERATURE
SENSOR BY TCC
TWO-WAY TEMPERATURE
CONTROL VALVE. PROVIDE
REDUCERS AT CONTROL
VALVE AS REQUIRED
T
THERMOMETER
UNION MANUAL AIR VENT
F(BALL VALVE)
P/T PLUG (TYPICAL)
COOLING COILS
DETAIL G
NO SCALE
V//,—HANGER
f — HS/HR u HS/HR —�
12" MAX.
SHUT-OFF
VALVE FLEXIBLE BALANCING VALVE
CONNECTION
STRAINER E_� CHECK VALVE (NON -SLAM)
BLOWDOWNP INCREASER TYP. IF REQUIRED
BALL VALVE ( )
BASE MOUNTED
HOSE END--� END SUCTION PUMP
AND CAP
PRESSURE GAUGE VIBRATION
ISOLATORS
MIN. 5 PIPE DIAMETERS ^ FLOOR
OF STRAIGHT PIPE
3/4" COPPER PIPE REDUCER IF
TO NEAREST FLOOR
DRAIN REQUIRED INERTIA BASEEH-6
DRIP PAN FOR
COOLING PUMPS
END SUCTION PUM
NO SCALE
OR PAINTED AS SPECIFIED
OVERHEAD TRAPEZ
12" LONG, 180' GALVANIZED
STEEL SADDLE BETWEEN
U -BOLT AND INSULATION
1I/
1/2 BELOW NU 1.
MOUNT
v ■ i I.■ E.— v
NO SCALE
SHUT-OFF VALVE
BALANCING VALVEIF
STRAINER WITH BLOWDOW
FLOW MEASURING STATION.— (BALL VALVE), HOSE END
PROVIDE 3 PIPE DIAMETERS AND CAP
DOWNSTREAM AND 5 PIPE NOTE:
DIAMETERS UPSTREAM OF REFER TO THE COIL
STRAIGHT PIPE. SCHEDULE FOR THE I
PIPE SIZE.
TEMPERATURE
SENSOR BY TCC THERMOMETER
T T
TWO-WAY TEMPERATURE
CONTROL VALVE. PROVIDE MANUAL AIR VENT
REDUCERS AT CONTROL UNION (BALL VALVE)
VALVE OFF
VALVE AS REQUIRED SHUTC
(TYPICAL) ,� I•
BALANCING VALVE I P/T PLUG (TYPICAL)
(TYPICAL)��
AIR
�d
BALL VALVE WITH HOSE'
END AND CAP (TYPICAL)
HEATING COIL PIPING
DETAIL H
NO SCALE
NOTE:
P/T GAUGE CONNECTION
(TYPICAL OF 2)
%I LINE PUMP
n I I n
INCREASER TEE FLEXIBLE CONNECTOR
(TYPICAL OF 2)
CHECK VALVE
BALANCING VALVE
INLINE PUNT -
DETAIL M
NO SCALE
ADJUSTMENT BOLT
1/4" (6 mm) NON-SKID NEOPRENE '
ACOUSTICAL ISOLATION PAD
I
I
11
I
I
I
I
CONCRETE INFILL—J
Z1225 EQUIPMENT
BASE ANCHOR BOLT
CAP SCREW SECURES EQUIPMENT STEEL BUSHING
//—TO ADJUSTMENT BOLT
ALL -DIRECTIONAL
BRIDGE BEARING
QUALITY
DUCTILE HOLDERS NEOPRENE
TOP AND BOTTOM ® BUSHING
SNUBBER BOLT ® RESTRAINING
AND WASHER ANGLE
SLF SPRING MOUNT
21225 ALL DIRECTIONAL SEISMIC SNUBBER
OSHPD PRE -APPROVAL NO. 0196
BOLTED OR WELDED
STEEL CONCRETE FORM
I
I
I
I
I
— — I
I
1
® 3/4" WAFFLE PADS
SEISMIC SNUBBER
STEEL REINFORCEMENT
HEIGHT SAVING
BRACKET
ERTIA BASES FOR PUMPS
DETAIL D
NO SCALE
TEMPERATURE BALL VALVE VENT
CONTROL VALVE
/
PT GAUGE CONNECTION
BALANCING VALVE
A Ill.
f-- HR
P/T GAUGE CONNECTION
SHUT-OFF FF VALVE
S
�-- HS
STRAINER WITH HOSE UNION
END AND CAP
ARRANGE PIPING FOR
USE AS COIL DRAIN
NOTES:
1. VERIFY TEMPERATURE CONTROL VALVE CONNECTION SIZE WITH TEMPERATURE CONTROL CONTRACTOR,
PROVIDE REDUCERS AS REQUIRED.
2. STAINLESS STEEL HOSES (MAX 12" LENGTH) MAY BE SUBSTITUTED FOR UNIONS
AIR TERMINAL UNIT
HEATING COIL PIPING
DETAIL J
NO SCALE
AIR SEPARATOR PIPING
DETAIL N
NO SCALE
Owner:
CARMEL CITY CENTER
COMMUNITY DEVELOPMENT
CORPORATION
30 West Main Street, Suite 220
Carmel, Indiana 46032
317.571-2787
Architect:
PEDCOR DESIGN GROUP
Architecture / Project Management:
355 City Center Drive
Carmel, Indiana 46032
317.705.7979 (phone)
317.705.7980 (fax)
CIRCLE DESIGN GROUP, INC,
810 S EAST SIIEFT. WIE F . KWW USN 18!21.0111781 700
WAW. VMU,K le OMn3W. R1J-K FK PRDT M
,g11NG" Bxwx DES" TM%XTMM
����1111111fill///0
L
NO.
870242
STATE OF :
N
Project:
AUTOMATIC AIR VENT
UNION
PIPE TO FLOOR
— REDUCING TEE
DRAIN
SHUT-OFF VALVE
U
=
AIR SEPARATOR
TO PUMP
SHUT-OFF VALVE
0.
�
co
PIPE TO FLOOR DRAIN
W%
AIR SEPARATOR PIPING
DETAIL N
NO SCALE
Owner:
CARMEL CITY CENTER
COMMUNITY DEVELOPMENT
CORPORATION
30 West Main Street, Suite 220
Carmel, Indiana 46032
317.571-2787
Architect:
PEDCOR DESIGN GROUP
Architecture / Project Management:
355 City Center Drive
Carmel, Indiana 46032
317.705.7979 (phone)
317.705.7980 (fax)
CIRCLE DESIGN GROUP, INC,
810 S EAST SIIEFT. WIE F . KWW USN 18!21.0111781 700
WAW. VMU,K le OMn3W. R1J-K FK PRDT M
,g11NG" Bxwx DES" TM%XTMM
����1111111fill///0
L
NO.
870242
STATE OF :
N
Project:
1
U
W
J
Q
W
W
U
=
0.
�
co
N
W%
M
z
U
O
�
W
Q
W
J
m
--
Z
-
O
0,5
WT
(D
a�
E
1`
z
L
1
0
U
Z
J
O
W
00
V
Q
U
J
LL
J
O
COPYRIGHT & OWNERSHIP OF DOCUMENTS
THIS DOCUMENT IS AN INSTRUMENT OF SERVICES AND IS THE SOLE
PROPERTY OF THE ARCHITECT AND PEDCOR DESIGN GROUP, LLC. ALL
INFORMATION CONTAINED HEREIN IS CONFIDENTIAL. ITS SUBMISSION AND
DISTRIBUTION TO OTHER PARTIES IS NOT TO BE CONSTRUED AS
PUBLICATION IN DEROGATION OF COMMON LAW COPYRIGHT,
INTELLECTUAL PROPERTY RIGHTS OR OTHER RESERVED RIGHTS. ALL
INFORMATION CONTAINED HEREIN CONSTITUTES THE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT, JAMES R. STUTZMAN, AND
PEDCOR DESIGN GROUP, LLC. NO PART OR WHOLE OF THIS DESIGN,
THESE DRAWINGS, OR FHE RESULTING BUILDING OR BUILDINGS, OR
PORTIONS OF THE RESULTING BUILDING OR BUILDINGS MAY BE
DUPLICATED, COPIED, IDIHIBITED, PHOTOGRAPHED, PUBLISHED, MODIFIED
OR OTHERWISE DISTRIBUTED IN ANY WAY WITHOUT THE SPECIFIC AND
PRIOR WRITTEN CONSENT OF THE ARCHITECT, JAMES R. STUTZMAN AND
PEOCOR DESIGN GROUP, LLC. c COPYRIGHT 2006, 2007, 2008, 2009,
JAMES R. STUTZMAN, AIA, CARMEL, IN.
BID SET No.1
SHELL & CORE
Print Date Sheet Issue Date
9/14/09 9/15/09
Drawn By Checked By
Last Revision Date:
O
O
O
O
O
O
Project Number:
Sheet Title:
DETAILS - HVAC
Sheet Number:
H 602