HomeMy WebLinkAbout39HEATING CABLE
THE CONTRACTOR SHALL PROVIDE HEAT TRACE CABLE FOR ENTIRE LENGTH
OF HOT WATER PIPING FROM THE POINT AT ITS CONNECTION TO WATER HEATER TO THE
RESPECTIVE FIXTURE. THIS IS FOR DOMESTIC HOT WATER TEMPERATURE
MAINTENANCE AND WILL BE CONTROLLED BY THE HEATING CABLE PANEL
LOCATED IN THE MECHANICAL ROOM AS SHOWN BELOW.
HEATING CABLE SYMBOL LEGEND
—HT— HEAT -TRACED HOT WATER SUPPLY PIPING
FP CIRCUIT NUMBER, POWER CONNECTION
OE CIRCUIT NUMBER, END SEAL
REFER TO SPECIFICATION SECTION 220533 FOR FURTHER INFORMATION ON
HEAT TRACE TAPE SYSTEM.
23 WH -1
E '
NOTE: CONTRACTOR SHALL PITCH ALL WATER PIPING ON THIS PROJECT TO
ALLOW POSITIVE DRAINAGEWHEN WINTERIZING THE BUILDING AND EXTERIOR
DUGOUT DRINKING FOUNTAINS. THIS INCLUDES HOSE BIBBS IN RESTROOM
CHASES AND ALL OTHER LOCA11ONS TO INSURE COMPLETE ELIMINATION
OF WATER IN THESE PIPES.
UNIT ■A■ FIRST FLOOR
PLAN — PLUMBING AND FIRE PROTECTION
1/4" = 1'-0"
PLAN NOTES
O 4" WASTE DOWN; 2" VENT.
20 2" WASTE DOWN; 1 1/2" VENT.
O3 3/4" HOT AND COLD WATER DOWN; 2" WASTE DOWN- 1 1/2" VENT.
O INCOMING 3" DOMESTIC WATER FROM BELOW.
O5 INCOMING 6" FIRE PROTECTION WATER SERVICE FROM BELOW. (BY FIRE PROTECTION CONTRACTOR).
0 4" FIRE DEPARTMENT CONNECTION SERVICE FROM BELOW (BY FIRE PROTECTION CONTRACTOR).
O7 1 1/2" COLD WATER UP.
O8 3" VENT UP; FIREMAIN UP.
O FIREMAIN- SIZE PIPING PER HYDRAULIC CALCULATIONS (BY FIRE PROTECTION CONTRACTOR)
10 2 1/2" COLD WATER DOWN. PROVIDE MAIN SHUT-OFF VALVE AND
WATER HAMMER ARRESTER V IN AN ACCESSIBLE LOCATION
JUST ABOVE THE CEILING.
11 2" COLD WATER DOWN. PROVIDE MAIN SHUT-OFF VALVE AND
WATER HAMMER ARRESTER V IN AN ACCESSIBLE LOCATION
JUST ABOVE THE CEILING.
12 WATER METER BY CARMEL WATER COMPANY. CONTRACTOR TO ROUGH IN FOR
METER PER THE UTILITY COMPANY INSTALLATION DEATAILS AND STANDARDS. THE
CONTRACTOR SHALL COORDINATE ALL DETAILS ASSOCIATED WITH THE INSTALLATION
OF METERS PRIOR TO START OF WORK TO CONFIRM FINAL SIZING OF METER
AND ROUGH IN REQUIREMENTS.
13 REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER (BFP-1). REFER TO THE
PLUMBING EQUIPMENT SCHEDULE ON DRAWING P3.1 FOR FURTHER INFORMATION.
14 DOUBLE CHECK VALVE ASSEMBLY (DCVA-1) REFER TO THE PLUMBING EQUIPMENT
SCHEDULE ON DRAWING P3.1 FOR FURTHER INFORMATION. (BY FIRE PROTECTION CONTRACTOR).
15 ELECTRIC DOMESTIC WATER HEATER (DWH-1). PROVIDE 1/4- THICK STEEL PLATE
WITH ANGLE CHANNEL SUPPORTS FOR A SECURE WALL MOUNT INSTALLATION. INSTALL
THE WALL SUPPORT AT +48" ABOVE FINISHED FLOOR.
16 MASTER THERMOSTATIC MIXING VALVE (TMV-A). REFER TO THE PLUMBING EQUIPMENT
SCHEDULE ON DRAWING P3.1 FOR FURTHER INFORMATION. INSTALL MIXING VALVE
AT +48" ABOVE FINISHED FLOOR.
17 DRY PIPE SYSTEM VALVE AND ASSOCIATED TRIM. REFER TO SPECIFICATION SECTION
211000 FOR FURTHER INFORMATION.
18 INSPECTORS TEST AND DRAIN ASSEMBLY. REFER TO DETAIL ON DRAWING P3.1
FOR FURTHER INFORMATION (BY FIRE PROTECTION CONTRACTOR).
19 FLOW SWITCH (BY FIRE PROTECTION CONTRACTOR)
20 SUPERVISED VALVE (BY FIRE PROTECTION CONTRACTOR).
21 SUPERVISED VALVE, FLOW SWITCH AND INPECTORS TEST AND DRAIN ASSEMBLY
SHALL BE INSTALLED NO HIGHER THAN +5'-0" ABOVE FINISHED FLOOR FOR
EASE OF MAINTENANCE.
0 3/4" COLD WATER DOWN.
23 NON FREEZE WALL HYDRANT. INSTALL AT +18" ABOVE FINISHED SURFACE. SEE
PLUMBING EQUIPMENT SCHEDULLE ON DRAWING P3.1 FOR FURTHER INFORMATION.
24 4" WASTE FROM ABOVE.
25 4" WASTE DOWN. CONNECT TO HORZONTAL WASTE PIPING IN CHASE.
26 3/4" HOT AND COLD WATER DOWN; 1 1/2" VENT FROM BELOW.
27 3/4" COLD WATER DOWN. CONNECT TO DRINKING FOUNTAINS.
28 PROVIDE ACCESS PANEL FOR SERVICE TO NON FREEZE VALVE WITH DRINKING FOUNTAIN.
REFER TO MANUFACTURES DATA SHEETS FOR EXACT INSTALLATION INFORMATION AND
PANEL LOCATION.
29 1" COLD WATER DOWN.
O 1/2" HOT AND COLD WATER UP; 2" WASTE FROM ABOVE.
31 RECESSED KNOX BOX: KNOX COMPANY 320OR SERIES. FIRE PROTECTION CONTRACTOR
TO CONTACT LOCAL FIRE CHIEF- BRUCE KNOTT ® 1-317-571-2619 TO OBTAIN
KNOX BOX ORDER FORM. INSTALL BOX AT +54" ABOVE FINISHED SURFACE TO CENTERLINE.
32 REFER TO DETAIL ON DRAWING P3.2 FOR FURTHER INFORMATION.
d
as
W
I-
0 O
co
W
t
0
s
Sam
aQo
O
v
, Zt
X y
W .1
JW =Z
wma U Q
�
�a Cf)D
�U, }z
�
J� V W
=Qa �2
U�z � a
LL It
O a
(n U
Z
O
H
V
W
H
Q C
O a.
J W
H m
Q G
r
Z_
H m
22
J
n.Z
s
J
IL
S
0
0 0
N
N
04
O N
Z
V C
N
■
N
0.
CHERRY TREE SOFTBALL COMPLEX RENOVATIONS
208032.00.00