HomeMy WebLinkAbout39HEATING CABLE THE CONTRACTOR SHALL PROVIDE HEAT TRACE CABLE FOR ENTIRE LENGTH OF HOT WATER PIPING FROM THE POINT AT ITS CONNECTION TO WATER HEATER TO THE RESPECTIVE FIXTURE. THIS IS FOR DOMESTIC HOT WATER TEMPERATURE MAINTENANCE AND WILL BE CONTROLLED BY THE HEATING CABLE PANEL LOCATED IN THE MECHANICAL ROOM AS SHOWN BELOW. HEATING CABLE SYMBOL LEGEND —HT— HEAT -TRACED HOT WATER SUPPLY PIPING FP CIRCUIT NUMBER, POWER CONNECTION OE CIRCUIT NUMBER, END SEAL REFER TO SPECIFICATION SECTION 220533 FOR FURTHER INFORMATION ON HEAT TRACE TAPE SYSTEM. 23 WH -1 E ' NOTE: CONTRACTOR SHALL PITCH ALL WATER PIPING ON THIS PROJECT TO ALLOW POSITIVE DRAINAGEWHEN WINTERIZING THE BUILDING AND EXTERIOR DUGOUT DRINKING FOUNTAINS. THIS INCLUDES HOSE BIBBS IN RESTROOM CHASES AND ALL OTHER LOCA11ONS TO INSURE COMPLETE ELIMINATION OF WATER IN THESE PIPES. UNIT ■A■ FIRST FLOOR PLAN — PLUMBING AND FIRE PROTECTION 1/4" = 1'-0" PLAN NOTES O 4" WASTE DOWN; 2" VENT. 20 2" WASTE DOWN; 1 1/2" VENT. O3 3/4" HOT AND COLD WATER DOWN; 2" WASTE DOWN- 1 1/2" VENT. O INCOMING 3" DOMESTIC WATER FROM BELOW. O5 INCOMING 6" FIRE PROTECTION WATER SERVICE FROM BELOW. (BY FIRE PROTECTION CONTRACTOR). 0 4" FIRE DEPARTMENT CONNECTION SERVICE FROM BELOW (BY FIRE PROTECTION CONTRACTOR). O7 1 1/2" COLD WATER UP. O8 3" VENT UP; FIREMAIN UP. O FIREMAIN- SIZE PIPING PER HYDRAULIC CALCULATIONS (BY FIRE PROTECTION CONTRACTOR) 10 2 1/2" COLD WATER DOWN. PROVIDE MAIN SHUT-OFF VALVE AND WATER HAMMER ARRESTER V IN AN ACCESSIBLE LOCATION JUST ABOVE THE CEILING. 11 2" COLD WATER DOWN. PROVIDE MAIN SHUT-OFF VALVE AND WATER HAMMER ARRESTER V IN AN ACCESSIBLE LOCATION JUST ABOVE THE CEILING. 12 WATER METER BY CARMEL WATER COMPANY. CONTRACTOR TO ROUGH IN FOR METER PER THE UTILITY COMPANY INSTALLATION DEATAILS AND STANDARDS. THE CONTRACTOR SHALL COORDINATE ALL DETAILS ASSOCIATED WITH THE INSTALLATION OF METERS PRIOR TO START OF WORK TO CONFIRM FINAL SIZING OF METER AND ROUGH IN REQUIREMENTS. 13 REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER (BFP-1). REFER TO THE PLUMBING EQUIPMENT SCHEDULE ON DRAWING P3.1 FOR FURTHER INFORMATION. 14 DOUBLE CHECK VALVE ASSEMBLY (DCVA-1) REFER TO THE PLUMBING EQUIPMENT SCHEDULE ON DRAWING P3.1 FOR FURTHER INFORMATION. (BY FIRE PROTECTION CONTRACTOR). 15 ELECTRIC DOMESTIC WATER HEATER (DWH-1). PROVIDE 1/4- THICK STEEL PLATE WITH ANGLE CHANNEL SUPPORTS FOR A SECURE WALL MOUNT INSTALLATION. INSTALL THE WALL SUPPORT AT +48" ABOVE FINISHED FLOOR. 16 MASTER THERMOSTATIC MIXING VALVE (TMV-A). REFER TO THE PLUMBING EQUIPMENT SCHEDULE ON DRAWING P3.1 FOR FURTHER INFORMATION. INSTALL MIXING VALVE AT +48" ABOVE FINISHED FLOOR. 17 DRY PIPE SYSTEM VALVE AND ASSOCIATED TRIM. REFER TO SPECIFICATION SECTION 211000 FOR FURTHER INFORMATION. 18 INSPECTORS TEST AND DRAIN ASSEMBLY. REFER TO DETAIL ON DRAWING P3.1 FOR FURTHER INFORMATION (BY FIRE PROTECTION CONTRACTOR). 19 FLOW SWITCH (BY FIRE PROTECTION CONTRACTOR) 20 SUPERVISED VALVE (BY FIRE PROTECTION CONTRACTOR). 21 SUPERVISED VALVE, FLOW SWITCH AND INPECTORS TEST AND DRAIN ASSEMBLY SHALL BE INSTALLED NO HIGHER THAN +5'-0" ABOVE FINISHED FLOOR FOR EASE OF MAINTENANCE. 0 3/4" COLD WATER DOWN. 23 NON FREEZE WALL HYDRANT. INSTALL AT +18" ABOVE FINISHED SURFACE. SEE PLUMBING EQUIPMENT SCHEDULLE ON DRAWING P3.1 FOR FURTHER INFORMATION. 24 4" WASTE FROM ABOVE. 25 4" WASTE DOWN. CONNECT TO HORZONTAL WASTE PIPING IN CHASE. 26 3/4" HOT AND COLD WATER DOWN; 1 1/2" VENT FROM BELOW. 27 3/4" COLD WATER DOWN. CONNECT TO DRINKING FOUNTAINS. 28 PROVIDE ACCESS PANEL FOR SERVICE TO NON FREEZE VALVE WITH DRINKING FOUNTAIN. REFER TO MANUFACTURES DATA SHEETS FOR EXACT INSTALLATION INFORMATION AND PANEL LOCATION. 29 1" COLD WATER DOWN. O 1/2" HOT AND COLD WATER UP; 2" WASTE FROM ABOVE. 31 RECESSED KNOX BOX: KNOX COMPANY 320OR SERIES. FIRE PROTECTION CONTRACTOR TO CONTACT LOCAL FIRE CHIEF- BRUCE KNOTT ® 1-317-571-2619 TO OBTAIN KNOX BOX ORDER FORM. INSTALL BOX AT +54" ABOVE FINISHED SURFACE TO CENTERLINE. 32 REFER TO DETAIL ON DRAWING P3.2 FOR FURTHER INFORMATION. d as W I- 0 O co W t 0 s Sam aQo O v , Zt X y W .1 JW =Z wma U Q � �a Cf)D �U, }z � J� V W =Qa �2 U�z � a LL It O a (n U Z O H V W H Q C O a. J W H m Q G r Z_ H m 22 J n.Z s J IL S 0 0 0 N N 04 O N Z V C N ■ N 0. CHERRY TREE SOFTBALL COMPLEX RENOVATIONS 208032.00.00