SECTION #
M001
SHT, # WHERE CONTROL PANEL SERVICE ACCESS
SECTION IS DRAWN INSTALL TO ENSURE REQUIRED
ELECTRICAL CLEARANCE TERMINAL UNIT
HOT WATER PROVIDE DAMPERS AT ALL BRANCHES TO SUPPLY DIFFUSERS.
REHEAT COIL
3'-0" MIN. STRAIGHT AT ROUND INTO RECTANGULAR DUCT
DUCT SECTION CONNECTIONS PROVIDE SPIN -IN TYPE FITTING
I�I� WITH DAMPER.
MED. VELOCITY ROUND
DUCT, INTERIOR DIM.,
00"0 EXTERNALLY INSULATED
MED. VELOCITY FLAT OVAL OR ROUND
SUPPLY DUCT, INTERIOR DIM.
1ST NUMBER WIDTH, 2ND NUMBER DEPTH
00"/00" OR 00" 0
FD
FIRE DAMPER
® � SUPPLY DUCT
UP -DOWN
PT RIQR
CITY T LINRNA� 0
dEL.� DUGE� DE Qo/
f+�E5IINS�JPPI,D�ATE
.�ATEOr �TPKE PEQUI
h(TYQGIP. T'� 5 AGI��QNN D
VE EDUGNRIAI, EQU
�IDEAR
TP?
UP UPCPP d�L
TA�AI,EGTR GIC T
RETURN OR EXHAUST
DUCT UP -DOWN
FLEX.
DUCT
1'-0"
MAX.
RECTANGULARPROVIDE
SIDE-WALL GRILLE TRANSSITI
VARIABLE AIR VOLUME
TERMINAL UNIT
rz:::� TU -XXX
INDICATES ROOM
SERVED BY UNIT
45 -LATERAL
,,,- PROVIDE MINIMUM OF TWO ELBOWS
BETWEEN TERMINAL UNIT AND DIFFUSER.
SUPPLY DIFFUSER
S_ SEE SCHEDULE
XXX -___CFM (TYP.)
PROVIDE FLEX DUCT TO ALL OUTLETS THOUGH
XXX NOT SHOWN IN PLAN VIEW (3'-0" MIN. LENGTH)
(6'-0" MAX. LENGTH) USE FORMFLEX ELBOW AS
MANUFACTURED BY THERMOFLEX TO ENSURE 1.5
RADIUS ELBOWS. REFER TO DETAILS.
"-PROVIDE TURNING VANES (SUPPLY DUCT ONLY)
IF RADIUSED ELBOW IS NOT POSSIBLE AND
MITERED ELBOW IS USED
TAKE-OFFI 61LOW VELOCITY RECTANGULAR SUPPLY DUCT.
SHEET METAL DIM., 1ST NUMBER WIDTH,
2ND NUMBER DEPTH. EXTERNALLY INSULATED.
/,LOW VELOCITY ROUND DUCT
EXTERNALLY INSULATED
RETURN OR EXHAUST GRILLE
SEE SCHEDULE
/f m
R- E_.
1XXX OR XXX
CFM (TYP.) PROVIDE VOLUME
DAMPER IN DUCT
AT ALL EXH. AND
RETURN BRANCHES
TO GRILLES
LOW VELOCITY RECTANGULAR EXHAUST
OR RETURN DUCT. SHEET METAL DIM.,
1ST NUMBER WIDTH, 2ND NUMBER DEPTH
HVAC DUCT LEGEND
SCALE: NONE
INS E UND A ED E PEI�ETA�I,PTE� ASI, �E�Tf� ,�IT,,,
PQINSU� SSUREET� INS AT GQG VAI
I.QGI AL�� wri
V PRET 000TTVN
I,Qw EXTERN ��� DUE�(TE TYPE
SUPP
•
0
0
DUGT S
ENGTf� TRAIGNT
PLC ;, �IA� Q,, 01NN IQN
if. -'o 3'' T SE
DUG
HVAC DUCT LEGEND DETAIL
SCALE: NONE
HVAC SYMBOLS AND ABBREVIATIOI
NOTE: NOT ALL SYMBOLS MAY BE USED.
NEW TO EXISTING CONNECTION A.F.F.
-j FD
PNEUMATIC THERMOSTAT FOR
TERMINAL UNITS
LINE VOLTAGE THERMOSTAT FOR
RADIANT CEILING PANELS
EQUIPMENT TO BE REMOVED
FIRE DAMPER
3
DN.
EX.
FD
MAX.
MIN.
PRESS
RM.
TU
TYP.
VAV
VD
CLG.
H TG.
MANUF
LE
.,-PHOTO OR ISOMETRIC
A VIEW MARK
M001
EQUIPED
SUPC cc
To 'SCApN
�L
IN CTRIG IN
CLC EG �,� U OIC INS SpUPP�(
ES
REH IN NESUPC
EXT. ING PRED�S. DUGT
,TUR O, Egg
SUREENGT�)
V� PRNIP��
(5'0 IUS
AD
now
ABOVE FINISHED FLOOR
DOWN
EXISTING
FIRE DAMPER
MAXIMUM
MINIMUM
PRESSURE
ROOM
TERMINAL UNIT
TYPICAL
VARIABLE AIR VOLUME
VOLUME DAMPER
COOLING
HEATING
MANUFACTURER
4
5
7
ROOM AIRFLOW SCHEDULE
ROOM
NUMBER
ROOM NAME
FLOOR AREA
SF
CEILING HEIGHT
(FT)
PRESSURIZATION
(+,-,_)
SUPPLY
CFM
RETURN
CFM
EXHAUST
CFM
ACH
200
LOBBY
208
8'-0"
-
0
150
0
5.4
200A
HALLWAY
117
8'-0"
+
175
0
0
11.2
201
CHECK-IN
91
8'-0"
=
75
75
0
6.2
202
FAMILY SLEEP RM
339
8'-0"
=
420
420
0
9.3
203
PATIENT RESTROOM
83
8'-0"
-
90
0
115
10.4
204
FAMILY BREAK RM
150
8'-0"
+
555
0
0
27.8
205
FAMILY LOUNGE
222
8'-0"
-
410
965
0
32.6
206
ON-CALL SUITE
221
8'-0"
+
18a
160
0
6.1
207
ON-CALL RESTROOM
75
8'-0"
-
85
0
105
10.5
208A
HALLWAY
126
8'-0"
+
280
0
0
16.7
208B
HALLWAY
706
8'-0"
-
470
660
0
7.0
208D
HALLWAY
299
8'-0"
+
160
0
0
4.0
209
SLEEP ROOM
202
8'-0"
=
165
165
0
6.1
210
PATIENT RESTROOM
100
8'-0"
-
110
0
135
10.1
211
SLEEP ROOM
208
8'-0"
=
345
345
0
12.4
212
NOURISHMENT
222
8'-0"
-
280
535
0
18.1
214
STAFF BREAK RM
95
8'-0"
+
380
0
0
30.0
215
STAFF RESTROOM
78
8'-0"
-
165
0
190
18.3
216
OBSERVATION
317
8'-0"
-
520
875
0
20.7
217
READING ROOM
157
8'-0"
=
355
355
0
16.9
218
STORAGE
38
8'-0"
+
25
0
0
4.9
219
SLEEP ROOM
196
8'-0"
=
160
160
0
6.1
220
SLEEP ROOM
204
8'-0"
=
165
165
0
6.1
221
SLEEP ROOM
232
8'-0"
=
190
190
0
6.1
222
SLEEP ROOM
197
8'-0"
=
160
160
0
6.1
223
BED STORAGE
135
8'-0"
=
310
310
0
17.2
224
SLEEP ROOM
211
8'-0"
=
355
355
0
12.6
225
SLEEP ROOM
220
8'-0"
=
440
440
0
15.0
226
PATIENT RESTROOM
83
8'-0"
-
90
0
115
10.4
227
PATIENT RESTROOM
88
8'-0"
-
95
0
120
10.2
228
SOILED UTILITY
87
8'-0"
-
110
0
135
11.6
229
CLEAN SUPPLY
66
8'-0"
+
65
0
0
7.4
230
VACUUM ROOM
150
8'-0"
-
870
870
0
43.5
231
MED GAS
27
8'-0"
-
0
0
96
26.7
SCHEDULE OF FAN POWERED TERMINAL UNITS
SYMBOL
MANUF.
MODEL
SIZE
INLET
SIZE
CLG.
MIN./H TG.
CFM
DESIGN
CFM
MAXIMUM
BOX CFM
AIR VALVE
PRESSURE
DROP (IN. WG)
ELECTRIC
REHEAT COIL
KW - STAGES
L.A.T .
(.F)
FAN CHARACTERISTICS
ACOUSTICS -
RADIATED FAN
AND VALVE (NC)
REMARKS
CFM
ESP
HP
VAV-202
TRANE
VSCF
08
8
0
420
900
0.053
S-2
70.00
420
0.25
0.125
30
ALL NOTES APPLY
VAV-204
TRANE
VSEF
10
10
290
965
1400
0.159
-
2.5 2
72.62
965
0.25
0.500
35
ALL NOTES APPLY
VAV-206
TRANE
VSCF
06
6
0
265
500
0.049
-
70.00
265
0.25
0.125
30
ALL NOTES APPLY
VAV-208B
TRANE
VSEF
12
12
365
1215
2000
0.024
3.0 - 2
72.24
1215
0.25
0.500
38
ALL NOTES APPLY
VAV-209
TRANE
VSCF
10
10
0
725
1400
0.179
-
70.00
725
0.25
0.333
33
ALL NOTES APPLY
VAV-210
TRANE
VSCF
08
8
0
450
900
0.062
-
70.00
450
0.25
0.125
31
ALL NOTES APPLY
VAV-211
TRANE
VSEF
06
6
105
345
500
0.086
1.5 - 1
78.08
345
0.25
0.125
29
ALL NOTES APPLY
VAV-216
TRANE
VSEF
10
10
320
1065
1400
0.071
2.5 - 2
71.86
1065
0.25
0.500
36
ALL NOTES APPLY
VAV-217
TRANE
VSEF
06
6
110
355
500
0.091
1.0 - 1
73.16
355
0.25
0.125
30
ALL NOTES APPLY
VAV-220
TRANE
VSCF
06
6
0
325
500
0.076
-
70.00
325
0.25
0.125
30
ALL NOTES APPLY
VAV-222
TRANE
VSCF
06
6
0
350
500
0.089
-
70.00
350
0.25
0.125
30
ALL NOTES APPLY
VAV-225
TRANE
VSEF
10
10
280
930
1400
0.144
2.5 - 2
73.94
930
0.25
0.500
35
ALL NOTES APPLY
VAV-230
TRANE
VSEF
10
10
295
870
1400
0.195
2.5 - 2
72.81
870
0.25 1
0.333
34
ALL NOTES APPLY
NOTES:
1. THE #'S AFTER THE "VAV-" CORRESPOND TO THE ROOM NUMBER IN WHICH THE THERMOSTAT IS LOCATED.
2. UNITS SHALL BE PRESSURE INDEPENDENT.
3. FAN MOTORS SHALL BE 277/60/1. AMP DRAW IS MAXIMUM ACCEPTABLE.
4. ELECTRIC HEATERS SHALL BE 460/60/3. AMP DRAW IS MAXIMUM ACCEPTABLE.
5. AIR VALVE PRESSURE DROP SHALL NOT EXCEED 0.2".
6. PROVIDE 24V CONTROL TRANSFORMER FOR EACH VAV TERMINAL UNIT.
7. PROVIDE FACTORY MOUNTED DDC CONTROLLER FOR EACH VAV TERMINAL UNIT. CONTRACTOR SHALL PROVIDE TITUS TERMINAL UNITS IN LIEU OF THE TRANE UNITS SPECIFIED.
SCHEDULE OF GRILLES & DIFFUSERS
SCHEDULE
OF
EXHAUST FANS
PANEL
SIZE
SYMBOL
AREA SERVED
MANUF.
TYPE
SIZE
WATTS
FRPM
MOUNTING
CFM
STATIC
TITUS
ELECTRICAL
FAN
REMARKS
6"0
98
3
0.044
<10
4
LAY -IN
ALL NOTES APPLY
S-2
PRESSURE
PAS
CHARACTERISTICS
MOUNTING
8"0
EF -3
MED GAS ROOM
GREENHECK
CSP
8110
80
950
S-3
96
0.5
24x24
115/1
IN-LINE
ALL NOTES APPLY
NOTES:
0.036
14
4
LAY -IN
1. FURNISH
WITH BACKDRAFT DAMPER, DISCONNECT.
TITUS
PAS
24x24
SCHEDULE OF GRILLES & DIFFUSERS
SYMBOL
MANUFACTURER
MODEL
PANEL
SIZE
CORE TYPE
INLET
DIMENSION
NOMINAL
CFM
THROW
®100 FPM
PRESSURE
DROP(IN.)
SOUND
N.C.
THROWS
MOUNTING
REMARKS
S-1
TITUS
PAS
24x24
PERFORATED
6"0
98
3
0.044
<10
4
LAY -IN
ALL NOTES APPLY
S-2
TITUS
PAS
24x24
PERFORATED
8"0
175
4
0.049
16
4
LAY -IN
ALL NOTES APPLY
S-3
TITUS
PAS
24x24
PERFORATED
10"o
218
4
0.036
14
4
LAY -IN
ALL NOTES APPLY
S-4
TITUS
PAS
24x24
PERFORATED
12"0
236
6
0.032
<10
4
LAY -IN
ALL NOTES APPLY
S-5
TITUS
PAS
24x24
PERFORATED
14"0
1 321
1 6
0.034
1 12
4
LAY -IN
ALL NOTES APPLY
SCHEDULES
R-1
TITUS
PAR
24x24
PERFORATED
22x22
1008
N/A
0.03
13
N/A
LAY -IN
ALL NOTES APPLY
E-1
TITUS
PAR
24x24
PERFORATED
22x22
1008
N/A
0.03
13N
/A
LAY -IN
ALL NOTES APPLY
E-2
TITUS
350R
8x8
LOUVER
6x6
57
N/A
0.018
<10
N/A
SIDEWALL
ALL NOTES APPLY
NOTES:
1. COLOR SHALL BE AS DIRECTED BY ARCHITECT.
2. ALL GRILLES AND DIFFUSERS SHALL BE PROVIDED WITH VOLUME DAMPERS.
j WA
rx
L
u
SCHEDULE OF ELECTRIC RADIANT
CEILING PANELS
SYMBOL
MANUFACTURER
MODEL
SIZE
ELECTRICAL
CHARACTERISTICS
WATTS
MOUNTING
REMARKS
CP -1
317 595.1000 main 317 572.1236 fax
MARLEY/QMARK
CP
12x24
277/1
155
LAY -IN
ALL NOTES APPLY
CP -2
CONSULTING ENGINEERS
MARLEY/QMARK
CP
12x36
277/1
235
LAY -IN
ALL NOTES APPLY
CP -3
Z
MARLEY/QMARK
CP
12x48
277/1
315
LAY -IN
ALL NOTES APPLY
NOTES:
d M
0
cri z "-
U Qz
1. FACE SHALL
BE SILKSCREENED TO MATCH ACOUSTICAL CEILING TILES.
W W
::F
2. PROVIDE
WITH LINE VOLTAGE THERMOSTAT.
W �
a. 0
z
3. PROVIDE
WITH FUSED DISCONNECT.
cli �
W
j WA
rx
L
u
STUDIO
THREE
DESIGN
architecture - interior design
wwwAtudio3design,net
317 595.1000 main 317 572.1236 fax
8604 Allisonville Road, Suite 330 Indianapolis, IN 46250
CONSULTANT
BIAGI, CHANCE, CUMMINS,
LONDON, TITZER, INC.
CONSULTING ENGINEERS
INDIANA - KENTUCKY - M1550URI - NEW )ER5EY
1060 Capitol Avenue Suite E240
Inciianapolis, IN 46204
www. BCC LT. co m
PHONE: 317-968-0239 FAX: 317-968-0235
v
Z
W
d 0
v -'
O
cli
� M �
d M
0
cri z "-
U Qz
�.....a .
W - J
�._.. W
W W
::F
W �
a. 0
z
0
cli �
W
z
PROJECT NO.
10977
DATE
REVISIONS
CERTIFICATION
S TeRde,
Z
No. 19441.
-o", STATE OF
�o • •�2
0'� •% ND
FssIAN �oN ..• ��
W
z-8-11
SHEET DESCRIPTION
HVAC LEGEND
AND
SCHEDULES
SHEET NUMBER
M001