GENERAL NOTES
A. NO PIPING OR DUCTWORK SHALL PASS THROUGH ELECTRICAL ROOMS,
ELEVATOR EQUIPMENT ROOMS, STAIR SHAFTS, ELEVATOR SHAFTS OR
SIMILAR SPACES UNLESS SYSTEM SERVES SPACE AND IS LIKEWISE SHOWN
ON PLAN.
B. WOMEN'S CENTER FALLS UNDER SECTION 9.4.1 OF THE 2001 AIA GUIDELINES
AS NO INVASIVE PROCEDURES ARE TO BE PERFORMED.
C. CONNECTOR FALLS UNDER SECTION 7.31 OF THE 2001 AIA GUIDELINES AS AN
EXTENSION OF THE EXISTING HOSPITAL.
D. SEISMIC RESTRAINT SHALL NOT BE REQUIRED FOR WOMEN'S CENTER.
E. SEISMIC RESTRAINT SHALL BE REQUIRED FOR CONNECTOR.
F. FAN POWERED BOX AND TERMINAL BOX DISCHARGE DUCTWORK SHALL BE
THE SAME SIZE AS UNIT DISCHARGE SIZE UNLESS NOTED OTHERWISE.
G. INSTALL RETURN GRILLE SOUND TRAPS SO THEY ARE NOT FACING ANY
NEARBY FAN POWERED TERMINAL BOXES OR OTHER SOUND TRAPS. IF
THERE ARE CONFLICTS IN A CONGESTED AREA, FACING THE SOUND TRAP
AWAY FROM FAN POWERED TERMINAL BOXES SHALL BE THE PRIORITY.
PLAN NOTES
1 42"X12" SUPPLY AIR DUCT UP.
2 42"X30" RETURN AIR DUCT UP.
3 24"X12" EXHAUST AIR DUCT UP,
4 28"X12" EXHAUST AIR DUCT UP.
5 14"X14" EXHAUST DUCT UP TO KEF-1. INSULATE DUCT IN 2 HOUR RATED FIRE WRAP
COMPLETE UP THROUGH ROOF.
6 14"X14" EXHAUST DUCT DOWN TO KITCHEN HOOD. INSULATE DUCT IN 2 HOUR RATED
FIRE WRAP COMPLETE WITHIN ROOM.
5.2
5.8
m
9365 Counselors Row
Indianapolis, IN 46240-1478
ph 317.819.7878 fx 317.819.7288
www.bsalifestructures.com
St, V ncen
Carmel Hovital
WOMEN'S CENTER
CARMEL, IN
BP #5 DESIGN
DOCUMENTS
WOMEN'S
POB 1�CENTER
'F -CONNECTOR
N
KEYPLAN
MARK DATE DESCRIPTION
FIRST FLOOR HVAC
PLAN
CLIENT NO.: 0461
PROJECT NO. 04610082
SCALE As indicated
DATE SEPTEMBER 12, 2014