HomeMy WebLinkAbout14WHEEL j MOTOR MIN. T.S.P. DIA. FAN MAX. TAG LOCATION AREA SERVED CFM (IN. WG.) FAN TYPE ARRANGEMENT TYPE (IN.) RPM BHP HP RPM VOLTS PHASE CYCLE KEF 1 ROOF COMMUNITY ROOM 1375 0.75 UTILITY SET UPBLAST BI 13" 1430 0.35 1/2 1725 480 3 NOTES: 60 1. FAN SHALL BE UL 762 LISTED WITH A NON-STICK FAN WHEEL WITH CLEANOUT PORT, HEAT BAFFLE, GREASE TRAP, DRAIN AND WEATHER HOOD. FROM RTU TERMINAL BOX TB -1-114 BO -X 1175/350 BY ECC LOCATE SWITCH ON HOOD SEQUENCE OF OPERATION: \— FIRE SUPPRESSION SYSTEM 1. KEF-1 IS ACTIVATED FROM HOOD SWITCH OR WHENEVER HOOD TEMPERATURE IS 15'F (ADJ.) ABOVE ROOM TEMPERATURE. 2. WHEN KEF-1 IS ACTIVATED TERMINAL BOX INDEXES TO 1,175 CFM CONSTANT VOLUME THROUGH BMS. 3. WHEN KEF-1 SWITCH IS TURNED OFF, A 15 MINUTE (ADJ.) TIMER IS SET. WHEN THE TIMER REACHES ZERO, KEF-1 IS DEACTIVATED. 4. IF THE HOOD FIRE SUPPRESION SYSTEM IS ACTIVATED THE FOLLOWING SHALL OCCUR: A. KEF-1 SHALL BE ACTIVATED, B. TERMINAL BOX INDEXES TO 1,175 CFM CONSTANT VOLUME. C. THE COOKING EQUIPMENT SHALL BE SHUTDOWN. 5. WHEN HOOD IS ACTIVATED WHILE THE AIR HANDLING UNIT IS UNOCCUPIED MODE THE AIR HANDLING UNIT, RTU -1, SHALL BE RETURNED TO OCCUPIED MODE UNTIL THE NEXT UNOCCUPIED CYCLE. NOTE: 1. CONTROL POINTS TO BE INCORPORATED INTO CLOSEST DDC PANEL. 2. TERMINAL BOX HEATING CONTROL TO BE PER TERMINAL BOX CONTROL SCHEMATIC. PROVIDE ALL TERMINAL UNIT CONTROLS PER CONTROL SCHEMATIC FOR VAV TERMINAL BOX (DDC), WITH CAV CONTROL WHEN INDEXED TO HOOD OPERATION MODE. 3. HOOD MANUFACTURER TO PROVIDE CONTACTS FOR CONTROL. 4. CONTACTS ON SUPPRESSION SYSTEM TO START FAN WHEN FIRE SUPPRESSION SYSTEM IS ACTIVATED. 5. BI -X SHALL SEND ALARM TO LOCAL BUILDING ALARM PANEL. 6. ROOM AND EXHAUST TEMPERATURE SENSORS BY KITCHEN HOOD SUPPLIER. TEMPERATURE SENSOR CONTROLS INTEGRAL THROUGH HOOD CONTROLLER. A,,\ KITCHEN FAN CONTROL SCHEMATIC " NO SCALE FAN SCHEDULE SOUND POWER (MAX. DB) PER OCTAVE BAND (NOTE: INLET SOUND FOR RETURN AND EXHAUST FANS; OUTLET SOUND FOR SUPPLY FANS) 63Hz 125Hz 250Hz 500Hz 1000Hz I 2000Hz 1400OHz 8000Hz 83 79 71 71 63 1 60 1 56 52 WEATHERPROOF FLEX CONNECTION — VERIFY SIZE OF FAN INLET WITH FAN MANUFACTURER MAINTAIN 2 DUCT DIAMETERS - SEE PLAN FOR DUCT SIZE CONTINUOUS WELD STORM COLLAR SECURED TO DUCT - SECURE COUNTER FLASHING TO DUCT AND CAULK 2"X14" FRAME & NAILER " HOLE THRU ROOF 1" LARGER (BOTH WAYS) THAN DUCTS SEE PLAN FOR DUCT CONTINUATION WEATHER PROOF HOUSING \< 9365 Counselors Row \ Q Indianapolis, IN 46240-1478 \ ' w J W ph 317.819.7878 fX 317.819.7288 16"MIN. EQUIPMENT RAILS www.bsalifestructures.com ROOF 2-2'X10" MIN. " 2" WOOD DECK SEE PLAN FOR DUCT CONTINUATION AND TERMINATION LOCATION REQUIREMENTS 16 GA. WELDED STAINLESS STEEL DISCHARGE DUCT 16 GA. ZINC COATED SHEET METAL (TYPICAL) VERIFY ACTUAL ROOF CONSTRUCTION WITH ARCHITECTURAL DRAWINGS ELEVATION -A VERIFY ACTUAL ROOF CONSTRUCTION WITH ARCHITECTURAL DRAWINGS COVER OPENING WITH 1/2" MESH BIRD SCREEN VMINIMUM 72" ABOVE 450 ROOF EQUIPMENT RAILS CANT STRIP (TYPICAL) FLASHING (TYPICAL) INSULATION (TYPICAL) STRUCTURAL ROOF n KITCHEN EXHAUST FAN DETAIL NO SCALE vi m 0 ccnUj cs m l W 0 Z O V F- O v oc CC LU a a a U. .j w a WEIGHT oc 5 a CL 3 ccoo (LBS) No Yes No No Yes 200 DESIGN REFERENCE MANUFACTURER GREENHECK TERMINAL BOX SCHEDULE CFM DUCT I z MIN. MAX. MIN. UNIT RUNOUT TAG TB -1 114 cc 0 HEATING HEATING CFM CFM 1175 610 INLET SIZE (IN.) 10 1 SIZE TO UNIT (IN.) 12" MIN KW 7.5 LU 0.. a D J cr_Lucn Q 0 'z > Q cc m W Z M o v ,� U. a m 0 m m o o cs cccc > No Yes No Yes Yes Yes Yes No No yesi Yes ELEVATION -A VERIFY ACTUAL ROOF CONSTRUCTION WITH ARCHITECTURAL DRAWINGS COVER OPENING WITH 1/2" MESH BIRD SCREEN VMINIMUM 72" ABOVE 450 ROOF EQUIPMENT RAILS CANT STRIP (TYPICAL) FLASHING (TYPICAL) INSULATION (TYPICAL) STRUCTURAL ROOF n KITCHEN EXHAUST FAN DETAIL NO SCALE vi m 0 ccnUj cs m l W 0 Z O V F- O v oc CC LU a a a U. .j w a WEIGHT oc 5 a CL 3 ccoo (LBS) No Yes No No Yes 200 DESIGN REFERENCE MANUFACTURER GREENHECK TERMINAL BOX SCHEDULE CFM DUCT I MIN. MAX. MIN. UNIT RUNOUT TAG TB -1 114 MAX. 1175 COOLING CFM 1 350 HEATING HEATING CFM CFM 1175 610 INLET SIZE (IN.) 10 1 SIZE TO UNIT (IN.) 12" MIN KW 7.5 MODEL NOTES SWB-113 1 :LECTRICAL POWER VOLT I PHASE 480 7 3 NOTES: 1. PROVIDE DUCT TRANSITION AT UNIT WHERE UNIT INLET SIZE AND DUCT RUNOUT SIZE ARE DIFFERENT. REFER TO TERMINAL BOX DETAIL FOR REQUIRED STRAIGHT RUN INTO BOX. 2. UNIT MAXIMUM PRESSURE DROP INCLUDING REHEAT COIL IS 0.6". 3. PROVIDE LAT, BTU/H, AND AIR PRESSURE DROP IN SUBMITTAL INFORMATION BASED ON ENTERING CONDITIONS OF 55°F EAT AT SCHEDULED MIN CFM, MINIMUM LEAVING AIR TEMPERATURE SHALL BE 80°F. CYCLE NOTES _ 60 SIMILAR TO PRICE SDV . Vi 5tMAet Carmel,Hoz!�.�tal WOMEN'S CENTER Isla CARMEL, IN BP #5 DESIGN DOCUMENTS WOMEN'S CENTER CONNECTOR N KEYPLAN MARK DATE DESCRIPTION HVAC SCHEDULES, DETAILS AND SCHEMATICS CLIENT N0.: 0461 PROJECT N0. 04610082 SCALE As indicated DATE SEPTEMBER 12, 2014 CORD MKC 1 5 ■MIF& 0�