EXISTING ROOF
NEW ROOF
EXISTING ROOF
RTU
NEN 3L 18 TON RID 4 16 TON
60 AMP W/P DISCONNECT �-_1 gfK\ 50 AMP WEE DISCONNECT �-_1 j /P \`
(H-2)-19.21,23 V (14-2)45.27,29 /
mi
3- p6 HOT \ 3- H6 HOT /
1- N8 GROUND A 1- 18 GROUND /
42.2 MRS 42.2 AMPS --/
30 AMP W/P DISCONNECT
(H-2)-7,9,11
/ - 3- 110 HOT
1- 112 GROUND
213 AMPS
glu 1O I
D
gb
30 AMP W/P DISCONNECT
(H-2)-13.15,17
/--�3 p10 HOT
1- #12 GROUND
23,3 AMPS
HBL2
____________________\T n 10 TM
_w,P@ JI
e 0
RN 6, 7-1/2 TON
R1U 8: 7-1/2 10N
0
30 AMP W/P DISCONNECT
(H-2)-37,39,41
3- 112 HOT
1- 112 GROUND 30 AMP WEE DISCONNECT / 9fi
18.7 AMPS (H-2)-8,10,12 /
3- 112 HOT
1- 112 GROUND /
RN S 6 TOM 187 MRS /
P
0 AMP W/P DISCONNECT _1 ge
( -2)-31,33,38
3-
.'- 12 30 AMP W/P DISCONNECT
# GROUND
1- 112 GROUND 3- #1 14,16,18
3-
163 AMPS p12 HOT
1- 112 GROUND
187 AMPS
gfi
30 FMR W/P DISCONNECT
(H-2)-2.4.6
3- f12 HOT a
1- p12 GROUND
13 AMPS
RTU
EXISTING ROOF
I II
I II
1 I�
RTU
O
EXISTING ROOF
_ RE-ROUTE WIRE FROM
- EXISTING FAN TO NEW
\ LOCATION OF EXISTING
OROOF FAN.
ROOF {12 WIRE
RN 11: 18 TON
60 AMP W/P DISCONNECT -\ 9
IP
\
(H-3)-7.9.1 \
3- 06 HOT
1- A8 GROUND \
42.2 AMPS
\
I
I
EF -7
K/
1 / /
/ RDI 11: 16 TON /
\ V (H-3)-1421,23 /
460V
PIP
/ 60 AMP W/P DISCONNECT gfl
(H-3)-8.10,12
3- 06 HOT
1- p8 GROUND
422 AMPS
O
-'-� 30 AMP WED DISCONNECT
(H-3)-8,10.12
3- #12 HOT
1- d12 GROUND
18A AMPS
.IEF
F--8
i
(H-3)-25,27,29
460V
LEGEND
110 MOLT WALL MOUNTED GENERAL PURPOSE
I OR MOUNTED OF ROOfmP UNIT
w/P /o: WTATER PROOF CO ER -WHILE IN USE
9fi aTi: GROUND FAULT INIE16iUP1E6
>= NIU 14 DISCONNECT EXILAPPED ON ROOF TOP UNIT
EXISTING ROOF
NEW ROOF
REVISION
VERSATILE
CONSTRUCTION
GROTTY, LLC.
\1 570 Eaet Tracy Road, Su1b 610
New Whiteland. Indiana 46184
Ph 317.535.3579 Fax: 317.335.3561
email: infoOvereatile-Ilaaem
THIS DRAWINGS THE PROPER[ 'L
VERSATILE CONSTRUCTION THE
GROUP uc
AND IS NOT TO BE USOTHER PURPOSE THAN ETOFOR
HE PROJECT
DESCRIBED HEREIN.
�UlOugy�i
�\``F,NS 15 B'S'T ����
tib. No. FP
==
�� js7ATE OF *cFEXISTING(B)Indianapolis
a' 6T 1E0PuW�
%�ALH E�`\ ��
1llhljlll\\\ y
/ 7L W)Pve.A,
L -
LNEW(A)
World Wide Motors
(� ♦ (� }77.� Street
3900 East 96411 Sl eet
IndianaT�02Subject
'
L
rL'1 J
RELEASED FOR CONSTRUCTION
to compliance with all regulations
of State and [Deal Codes
Ci of Camlel
City
NhW\D
�
Job N0.
102'
Date Stamped
°2252D18
Drawn By
Nat
Checked By
tab
Scale:
3/32"=1' 0"
�
7� Plan
Roof Top Power r lan
CAD FILE:
CERTIFIED BY:
G\I7OS\e2O3 roof Power Plonewg