CONSTRUCTION DESIGN RELEASE
State Form 41191 (R9/5-98)
Report Printed on: August 29, 2018
Project number Release date
402125 08/23/18
Construction type Occupancy classification
Scope of release
II-B, SPK S-1, M
Type of release
Project name
Street address
City County
ARCH ELEC MECH
PLUM STR
Standard
Belle Tire
9700 Michigan Rd
CARMEL HAMILTON
To: Owner / Architect / Engineer
Enright Architects
Christopher Vincent Enright AR11500011
628 E. Parent Ave
Royal Oak MI 48067
Note :(A1A & A1B): In accordance with the affidavit sworn under penalties of perjury in the application for construction design release the plans
and specifications filed in conjunction with this project shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety
Commission. Providing false information constitutes an act of perjury, which is a Class D felony punishable by a prison term and a fine up to $10,000.
The plans, specifications and application submitted for the above referenced project have been reviewed for compliance with the applicable rules of
the Fire Prevention and Building Safety Commission. The project is released for construction subject to, but not necessarily limited to, the conditions
listed below. THIS IS NOT A BUILDING PERMIT. All required local permits and licenses must be obtained prior to beginning construction work. All
construction work must be in full compliance with all applicable State rules. Any changes in the released plans and/or specifications must be filed with
and released by this Office before any work is altered. This release may be suspended or revoked if it is determined to be issued in error, in violation
of any rules of the Commission or if it is based on incorrect or insufficient information. This release shall expire by limitation, and become null and
void, if the work authorized is not commenced within one (1) year from the above date.
CONDITIONS:
14B
14B1600
9E6006
14W32067A
9E2108
9E11027B
4G0603AE
14M0303
14B11012
14B12032
14B11092
This project has been reviewed under the 2014 Indiana Building Code.
Buildings, or portions thereof, shall be designed and constructed to sustain all dead, live, and
environmental loads in accordance with Chapter 16, IBC (675 IAC 13-2.6).
Location of the disconnection means for a sign shall be within sight of the sign or outline lighting
system that it controls in accordance with Section 600.6, IEC (675 IAC 17-1.8).
Smoke and heat vents shall be provided in accordance with Section 3206.7 and Table 3206.2, IFC
(675 IAC 22-2.5).
Commercial bathrooms, kitchens, and rooftops shall be provided with GFCI protection in
accordance with Section 210.8, IEC (675 IAC 17-1.8).
Where electric equipment is likely to be exposed to physical damage, enclosures or guards shall be
installed to prevent damage in accordance with Section 110.27(B), IEC (675 IAC 17-1.8).
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm.
This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans.
Use Internet Browser to View this report, other browsers are not compatible to view this report
Page 2/2
14B1100HC
14B100815
14B10098
AREL
The current code for handicapped accessibility in use in the State of Indiana is Chapter 11 of the
Indiana Building Code (675 IAC 13-2.6) and ICC standard A117.1, 2009 edition (675 IAC 13-2.6).
There shall be a floor or landing on each side of a door in accordance with Section 1008.1.5, IBC
(675 IAC 13-2.6).
There shall be a floor or landing at the top and bottom of each stairway. The width of landings shall
not be less than the width of stairways they serve. Every landing shall have a minimum width
measured perpendicular to the direction of travel equal to the width of the stairway. Where the
stairway has a straight run, the depth need not exceed 48 inches, in accordance with Section
1009.8, IBC (675 IAC 13-2.6).
Pursuant to 675 IAC 12-6-21, the issuance of a design release does not relieve the owner from
compliance with all applicable rules of the commission, even if items contrary to those rules appear
in the plans and specifications that have been filed with the division. The owner is responsible for
correcting any and all areas of noncompliance even if they are discovered subsequent to the issuing
of this design release.
Please be advised that if an administrative review of this action is desired, a written petition for review must be filed at the above address with the
Fire Prevention and Building Safety Commission identifying the matter for which a review is sought no later than eighteen (18) days from the above -
stated date, unless the eighteenth day falls on a Saturday, a Sunday, a legal holiday under State statute, or a day in which the Department of Fire
and Building Services is closed during normal business hours. In the latter case, the filing deadline will be the first working day thereafter. If you
choose to petition, and the before-mentioned procedures are followed, your petition for review will be granted, and an administrative proceeding will
be conducted by an administrative law judge of the Fire Prevention and Building Safety Commission. If a petition for review is not filed, this Order will
be final, and you must comply with its requirements.
Code review official
Address (name,title of local official,street,city,state and ZIP code
MICHAEL ANDERSON
JIM BLANCHARD
ONE CIVIC SQUARE
CARMEL, IN 46032
DEPT OF COMMUNITY SERVICE
Fax & e-mail: 3175712499, jblanchard@carmel.in.gov
mianderson@dhs.in.gov Director, Division of Fire and Building Safety
Detailed plans and specifications of the fire suppression system shall be filed with the required
application and appropriate fees in accordance with 675 IAC 12-6-3(a), 675 IAC 12-6-7(g)(17), and
675 IAC 13-1-8. (N.F.P.A. 13)
Fuel-fired equipment and appliances shall be located and installed in accordance with Sections 303
and 304, IMC (675 IAC 18-1.6).
Buildings and facilities shall be designed and constructed to be accessible in accordance with
Section 1101.2, IBC (675 IAC 13-2.6) and ICC standard A117.1 2009 edition (675 IAC 13-2.6).
Attic ventilation shall be provided in accordance with Section 1203.2, IBC (675 IAC 13-2.6).
Each toilet room and bathing room shall be handicapped accessible in accordance with Section
1109.2, IBC (675 IAC 13-2.6). (Clear turning radius, Door Swing, Grab Bars, Fixture Clearances,
Fixture Mounting Heights, Shower/Bathtub seats)
Indiana Department of Homeland Security
DIVISION OF FIRE & BUILDING SAFETY
PLAN REVIEW DIVISION
402 W. Washington St., Room E245
Indianapolis, IN 46204
Fax & e-mail:
SUPPORT HOOSIER SAFETY
Available At Your Local Licence Branch
In accordance with Section 19 of the General Administrative Rules (675 IAC 12-6-19) a complete set of plans and specifications that conform
exactly to the design that was released by the office of the state building commissioner shall be maintained on the construction jobsite as well as a
copy of the design release.
2485483236, cenright@enrightarchitects.com