Oclobet 25, 2001
Centex Homes
6602 E 7S' Street
Indianapolis, IN 46250
Attn: John Farley
Re Stone Haven Lot 4223
Floor Joist Evaluation
SC Project #01176
Dear John
As you requested, I visited the residence under construction on lot #223 in the Stone Haven
development in Carmcl, Indiana on October 24, 2001. The purpose of my visit was to evaluate a
Floor joist that had been notched to accommodate a second floor plumbing fixture. Based on my
cAiservations and analysis, it is my opinion that the floor joist is adequate.
The second floor framing is 2x10 joists spaced at 16-inch centers The floor joist in question
spans approximately l V-a" and supports the master bathr(mm flow. A notch roughly 2 inches
deep and 4 inches long had been cut in the trip of the joist to allow passage of the bathtub drain
The joist had been reinforced by nailing a 4-fool long W onto the side of the joist.
The joist was analyzed for floor loads specified in the 2000 International Residential Code with
Indiana amendments. Analysis indicated that the unreinforced joist with its reduced section at
the notch is adequate for strength and deflection requirements.
Please call if you have any questions or require additional assistance.