HomeMy WebLinkAbout07 84 43 Fire-Resistant Joint SystemsTHE KENT 07 84 43 - THE KENT Issue Date 05.09.18 FIRE RESISTIVE JOINT SYSTEMS THE KENT SECTION 07 84 43 - FIRE-RESISTIVE JOINT SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes fire-resistive joint systems for the following: 1. Floor-to-floor joints. 2. Floor-to-wall joints. 3. Head-of-wall joints. 4. Wall-to-wall joints. 5. Perimeter fire-resistive joint systems consisting of floor-to-wall joints between perimeter edge of fire-resistance-rated floor assemblies and exterior curtain walls. 1.3 PERFORMANCE REQUIREMENTS A. General: Provide fire-resistive joint systems that are produced and installed to resist spread of fire according to requirements indicated, resist passage of smoke and other gases, and maintain original fire-resistance rating of assembly in which fire-resistive joint systems are installed. B. Joint Systems in and between Fire-Resistance-Rated Constructions: Provide systems with assembly ratings equaling or exceeding the fire-resistance ratings of construction that they join, and with movement capabilities and L-ratings indicated as determined by UL 2079. 1. Load-bearing capabilities as determined by evaluation during the time of test. C. Perimeter Fire-Resistive Joint Systems: For joints between edges of fire-resistance-rated floor assemblies and exterior curtain walls, provide systems of type as determined by NFPA 285 and UL 2079. 1. UL-Listed, Perimeter Fire-Containment Systems: Integrity ratings equaling or exceeding fire-resistance ratings of floor or floor/ceiling assembly forming one side of joint. D. For fire-resistive systems exposed to view, provide products with flame-spread and smoke- developed indexes of less than 25 and 450, respectively, as determined per ASTM E 84. 1.4 SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings. THE KENT 07 84 43 - THE KENT Issue Date 05.09.18 FIRE RESISTIVE JOINT SYSTEMS THE KENT C. Product Certificates: For each type of fire-resistive joint system, signed by product manufacturer. D. Qualification Data: For Installer. E. Field quality-control test reports. F. Evaluation Reports: Evidence of fire-resistive joint systems' compliance with ICBO ES AC30, from the ICBO Evaluation Service. G. Research/Evaluation Reports: For each type of fire-resistive joint system. 1.5 QUALITY ASSURANCE A. Installer Qualifications: A Specialty Contractor firm experienced and approved as a Factory Mutual FM-4991 Contractor, in installing fire-resistive joint systems similar in material, design, and extent to that indicated for this Project, whose work has resulted in construction with a record of successful performance. B. Installation Responsibility: Assign installation of fire-resistive joint systems in Project to a single qualified Specialty Contractor installer. C. Source Limitations: Obtain fire-resistive joint systems, for each kind of joint and construction condition indicated, through one source from a single manufacturer. D. Fire-Test-Response Characteristics: Provide fire-resistive joint systems that comply with the following requirements and those specified in Part 1 "Performance Requirements" Article: 1. Fire-resistance tests are performed by a qualified testing and inspecting agency. A qualified testing and inspecting agency is UL or another agency performing testing and follow-up inspection services for fire-resistive joint systems acceptable to authorities having jurisdiction. 2. Fire-resistive joint systems are identical to those tested per methods indicated in Part 1 "Performance Requirements" Article and comply with the following: a. Fire-resistive joint system products bear classification marking of qualified testing and inspecting agency. b. Fire-resistive joint systems correspond to those indicated by referencing system designations of the qualified testing and inspecting agency. 1.6 COORDINATION A. Coordinate construction of joints to ensure that fire-resistive joint systems are installed according to specified requirements. THE KENT 07 84 43 - THE KENT Issue Date 05.09.18 FIRE RESISTIVE JOINT SYSTEMS THE KENT PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Products: Subject to compliance with specified requirements, provide a fire-resistive joint system application for each required application. The system application shall be provided by one of the manufacturers from the list of Fire-Resistive Joint system manufacturers listed below: 1. Hilti, Inc. 2. RectorSeal Corporation (The). 3. Specified Technologies Inc. 2.2 FIRE-RESISTIVE JOINT SYSTEMS A. Compatibility: Provide fire-resistive joint systems that are compatible with joint substrates, under conditions of service and application, as demonstrated by fire-resistive joint system manufacturer based on testing and field experience. B. Accessories: Provide components of fire-resistive joint systems, including primers and forming materials, that are needed to install fill materials and to comply with Part 1 "Performance Requirements" Article. PART 3 - EXECUTION 3.1 PREPARATION A. Surface Cleaning: Clean joints immediately before installing fire-resistive joint systems to comply with fire-resistive joint system manufacturer's written instructions. B. Priming: Prime substrates where recommended in writing by fire-resistive joint system manufacturer using that manufacturer's recommended products and methods. 3.2 INSTALLATION A. General: Install fire-resistive joint systems to comply with Part 1 "Performance Requirements" Article and fire-resistive joint system manufacturer's written installation instructions for products and applications indicated. END OF SECTION 07 84 43