Loading...
HomeMy WebLinkAbout236200 SPLIT SYSTEM CONDENSING UNITSTHE KENT 23 62 00 - 1 THE KENT Issue Date 05.09.18 SPLIT SYSTEM CONDENSING UNITS THE KENT SECTION 23 62 00 - SPLIT SYSTEM CONDENSING UNITS PART 1 - GENERAL 1.01 RELATED SECTIONS: A. Drawings, general provisions of the Contract, including General and Supplementary Conditions, and Division-1 Specification Sections and Division 20 and 28 Specification Sections, apply to work of this Section. 1.02 DESCRIPTION OF WORK: A. The Contractor shall furnish all the labor, materials, equipment, appliances, services and drayage, and perform all the operations in connection with the construction and installation of the Work. All Work to be as herein specified and as denoted on the accompanying Drawings. B. This Section of the Work includes the furnishing and installation of the air-cooled condensing unit(s), supports, refrigerant piping, refrigerant system specialties, controls and control panel, and other such related items to provide a complete system where and as denoted on the Drawings and as herein specified. 1.03 SUBMITTALS: A. Product Data: Submit manufacturer's technical product data and installation instructions for split system condensing units. B. Shop Drawings: Submit layout drawings of split system condensing units showing layout of components. In addition, show details of installation and associated supporting structures. C. Piping roughing-in requirements: Submit roughing-in requirements prepared by the equipment manufacturer and submitted on factory letterhead, including all piping material and accessory sizes and locations. Submit piping isometric diagram which documents pipe routing including changes in elevation between interior and exterior equipment components. Isometric diagram shall indicate intermediate traps and/or double suction risers as required for project specific equipment application. D. Wiring Diagrams: Submit wiring diagrams for split system condensing units showing connection to electrical power feeders. Differentiate between portions of wiring that are manufacturer-installed and portions to be field-installed. E. Maintenance Data: Submit maintenance data and parts list for each split system condensing unit, control, and accessory; including "trouble-shooting" maintenance guide. Include this data, product data, shop drawings, and wiring diagrams in maintenance manual; in accordance with requirements of Division 1. F. Provide manufacturer's compressor warranty for five years from the date of acceptance by the Owner. 1.04 CODES: A. Capacity ratings for condensing units shall be in accordance with ARI Standard 360 "Standard for Commercial and Industrial Unitary Air-Conditioning Equipment". THE KENT 23 62 00 - 2 THE KENT Issue Date 05.09.18 SPLIT SYSTEM CONDENSING UNITS THE KENT B. Refrigeration system of condensing units shall be in accordance with ASHRAE Standard ASHRAE 15 "Safety Code for Mechanical Refrigeration". C. Condensing units shall meet or exceed the minimum COP/Efficiency levels as prescribed in ASHRAE 90A "Energy Conservation in New Building Design". D. Condensing units shall be listed by UL and have UL label affixed. 1.05 WARRANTY ON MOTOR/COMPRESSOR: A. Provide written warranty, signed by manufacturer, agreeing to replace/repair, within warranty period, motors/compressors with inadequate or defective materials and workmanship, including leakage, breakage, improper assembly, or failure to perform as required; provided manufacturer's instructions for handling, installing, protecting, and maintaining units have been adhered to during warranty period. Replacement is limited to component replacement only, and does not include labor for removal and reinstallation. B. Warranty Period: 5 years from date of start-up and owner acceptance. 1.06 ACCEPTABLE MANUFACTURERS: A. Condensing unit manufacturer to be the same as the manufacturer of the furnace. Subject to compliance with requirements, provide air-cooled condensing units of one of the following: 1. Lennox 2. Bryant 3. Trane 4. Goodman 5. Carrier 6. Guardian/York PART 2 - PRODUCTS 2.01 RESIDENTIAL AIR-COOLED CONDENSING UNITS: A. Factory-assembled and tested, consisting of compressor, condenser coil, fan, motor, refrigerant reservoir, and operating controls. Capacity and electrical characteristics shall be as scheduled. B. Casing: Galvanized steel casing finished with baked enamel. Casing shall have removable panel for access to controls, and weep holes for water drainage, base with mounting holes, and brass service valves, fittings, and gage ports on exterior of casing. C. Compressor: Hermetic compressors with built-in overloads and vibration isolation. Compressor motor shall have, thermal and current sensitive overload device, internal high-pressure protection, high and low pressure cutout switches, start capacitor and relay, 2-pole contactor, crankcase heater, and temperature actuated switch and timer to prevent compressor rapid cycle. D. Condenser: Coil shall have copper tubes and aluminum fins, or aluminum tubes and aluminum fins; provided with liquid accumulator and liquid subcooler. Aluminum propeller fan shall have direct drive, with permanently lubricated fan motor with thermal overload protection. THE KENT 23 62 00 - 3 THE KENT Issue Date 05.09.18 SPLIT SYSTEM CONDENSING UNITS THE KENT E. Accessories: 1. Low-voltage thermostat and sub base to control condensing unit and evaporator fan; includes fan-off-auto and heat/cool switches. 2. Hard start kit with start relay and start capacitor. 3. Head pressure control to modulate condenser fan motor speed for low ambient conditions (0 F). 4. Time delay relay (adjustable to 15 minutes). 5. Low voltage control transformer. 6. Filter drier-liquid line. 7. Furnish and install all necessary controls as to provide a properly functioning system. F. Efficiency: Minimum SEER (13.0) rated in accordance with ARI 210, or as noted on drawings. PART 3 - EXECUTION 3.01 INSTALLATION: A. Install condensing units in accordance with manufacturer’s installation instructions. Install units plumb and level, firmly anchored in locations indicated, and maintain manufacturer's recommended clearances. B. Install ground-mounted units on 4" thick reinforced concrete pad, 4" larger on each side than condensing unit. Anchor unit to pad using inserts or anchor bolts. C. Install roof-mounted units on mechanical equipment stand, constructed in accordance with NRCA Handbook. Anchor unit to structural frame with removable fasteners. D. Install electrical devices furnished by manufacturer but not specified to be factory-mounted. Furnish copy of manufacturer's wiring diagram submittal to Electrical Installer. 1. Verify that electrical wiring installation is in accordance with manufacturer's submittal and installation requirements of Division 26 sections. Do not proceed with equipment start-up until wiring installation is acceptable to equipment Installer. E. Start-up condensing units, in accordance with manufacturer's start-up instructions, and in presence of manufacturer's representative. 1. Test controls and demonstrate compliance with requirements. Replace damaged or malfunctioning controls and equipment. F. Provide services of manufacturer's technical representative to instruct Owner's personnel in operation and maintenance of condensing units. G. Schedule training with Owner, provide at least 7-day notice to Architect/Engineer of training date. END OF SECTION THE KENT 23 62 00 - 4 THE KENT Issue Date 05.09.18 SPLIT SYSTEM CONDENSING UNITS THE KENT THIS PAGE IS LEFT INTENTIONALLY BLANK